York B1HH018, THRU 060 User Manual

0 (0)
York B1HH018, THRU 060 User Manual

J

CHAMPION® SERIES

 

 

 

 

SINGLE PACKAGE HEAT PUMPS

INSTALLATION INSTRUCTION Supersedes: 66297-YIM-B-1004

66297-YIM-C-0205

 

MODELS B1HH018 THRU 060

 

 

1.5 THRU 5 TON

 

 

(12 SEER)

 

GENERAL

YORK Model B1HH units are factory assembled heat pumps designed for outdoor installation on a roof top or a slab. Fieldinstalled electric heater accessories are available to provide supplemental electric heat combined with electric cooling and heating.

The units are completely assembled on rigid, removable base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require only electric power and duct connections at the point of installation.

The electric heaters have nickel-chrome resistance wire elements and utilize single point power connection.

INSPECTION

As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Refer to Form 50.15-NM for additional information.

REFERENCE

Additional information on the design, installation, operation and service of this equipment is available in the following reference forms:

55.70-N1 — General Installation

55.70-N2 — Pre-start & Post-start Check List

511.26-N1.1V — Electric Heater Accessory

REPLACEMENT PARTS

Refer to Replacement Parts Manual for complete listing of replacement parts on this equipment.

Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.

CAUTION

THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES

WARNING

INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY, PROPERTY DAMAGE AND/OR DEATH.

WARNING

DE-ENERGIZE THE ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING TO INSPECT, REPAIR OR PERFORM MAINTENANCE TO THE UNIT.

PRODUCT NOMENCLATURE

66297-YIM-C-0205

 

 

 

 

 

 

 

B

 

1

 

H

H

 

0

 

2

4

 

A

 

0

6

 

 

 

 

 

 

 

PRODUCT CATEGORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE CODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B = Single Package Heat Pumps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06 = 208/230-1-60

 

 

(Air Cooled)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 = 208/230-3-60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46 = 460-3-60

 

 

PRODUCT GENERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58 = 575-3-60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = NEW or Current Design

 

 

 

 

 

 

 

 

 

 

NOMINAL COOLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FACTORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY (MBH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLED ELECTRIC HEAT

 

 

PRODUCT IDENTIFIER

 

 

 

 

 

 

018 = 18,000 BTUH

 

042 = 42,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HH = Heat Pump (12 SEER)

 

 

 

 

 

 

024 = 24,000 BTUH

 

048 = 48,000 BTUH

 

 

A = No Electric Heat Installed

 

 

 

 

 

 

 

 

 

030 = 30,000 BTUH 060 = 60,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036 = 36,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the following national and local safety codes.

1.National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions).

2.Local plumbing and waste water codes and other applicable local codes.

Refer to Table 1 for unit application data and to Table 5 for electric heat application data.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense.

Size of unit for proposed installation should be based on heat loss/heat gain calculations made in accordance with industry recognized procedures identified by the Air Conditioning Contractors of America.

TABLE 1 - UNIT APPLICATION DATA

Voltage Variation

 

208/230V3

187 / 2533

 

460V

414

/ 504

Min. / Max.1

 

 

575V

518

/ 630

 

 

Wet Bulb Temperature (°F) of Air on

57

/ 72

Evaporator Coil,

Min. / Max.

 

 

Dry Bulb Temperature (°F) of Air on

45 / 120

Condenser Coil,

Min.2 / Max.

1Rated in accordance with ARI Standard 110, utilization range “A”.

2A low ambient accessory is available for operation down to 0°F

3“T1" transformer primary tap must be moved from the 230 volt connection to the 208 volt connection for low voltage applications of 208 volt and below.

LOCATION

Use the following guidelines to select a suitable location for these units.

1.Unit is designed for outdoor installation only.

2.Condenser must have an unlimited supply of air. Where a choice of location is possible, position unit on either north or east side of building.

3.For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.

4.For roof top installation, be sure the structure can support the weight of the unit plus any field installed components. Unit must be installed on a level roof curb or appropriate angle iron frame providing adequate support under the compressor/condenser section.

5. Maintain level tolerance of unit to 1/8" maximum.

RIGGING OR HANDLING

Care must be exercised when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig unit with slings placed under the unit. Spreader bars of sufficient length should be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift. Slotted openings in the skid are provided for this purpose. Forks must pass completely through the base.

Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity.

TABLE 2 - UNITS WEIGHTS

 

SHIPPING

OPERAT-

CORNER WEIGHTS

UNIT

ING

 

(location, lbs.)

 

SIZE

WEIGHT

WEIGHT

 

 

 

 

(lbs.)

“A”

“B”

“C”

“D”

 

(lbs.)

 

 

018

351

346

103

92

73

83

024

356

351

97

93

81

84

030

353

348

96

93

81

84

036

388

383

106

102

89

92

042

440

435

120

115

101

104

048

485

480

132

127

111

115

060

495

490

135

130

113

117

 

 

“D”

 

 

 

 

 

 

 

 

CENTER OF GRAVITY

FRONT

 

“A”

 

“C”

 

 

OF

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

“B”

 

 

 

 

 

 

 

23½

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

FIG. 1 - CENTER OF GRAVITY

2

Unitary Products Group

66297-YIM-C-0205

CLEARANCES

All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for combustion, construction, servicing and proper unit operation.

WARNING:Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps:

1.Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws securing each duct cover (save these screws to use later).

2.Install the duct covers, removed in step one, to the rear supply and return air duct openings. Secure with the four (4) screws used in step one.

3.Seal duct covers with silicone caulk.

Downflow units must have an “L”-shaped supply duct without any outlets or registers located below the outlet of the unit.

Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to minimize the transmission of noise.

CAUTION: When fastening duct work to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 4 for information concerning rear and bottom supply and return air duct openings.

FILTERS

Single phase units are shipped without a filter and is the responsibility of the installer to secure a filter in the return air ductwork or install a Filter/Frame Kit (1FF0114).

A filter rack and a high velocity filters are standard on three phase units.

Filters must always be used and must be kept clean. When filters become dirt laden, insufficient air is delivered by the blower, decreasing your unit's efficiency and increasing operating costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit is used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate drain. The plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install the condensate drain line ( " NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the following removable panels:

Blower service access

Electrical/Filter access

Compressor service access

Refer to Figure 3 for location of these access panels and minimum clearances.

THERMOSTAT

The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with the thermostat for general installation procedure. Six color coded insulated wires (minimum #18 AWG) should be used to connect thermostat to unit. See Figure 2.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 3.

The wiring entering the cabinet must be provided with mechanical strain relief.

A fused disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.

Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.

COMPRESSORS

Units are shipped with compressor mountings factoryadjusted and ready for operation.

CAUTION: Do Not loosen compressor mounting bolts.

Unitary Products Group

3

66297-YIM-C-0205

CONTROL WIRING

THERMOSTAT

** = Minimum wire size of 18 AWG

R

wire should be used for all field

G

installed 24 volt wire.

 

 

Y

PROGRAMMABLE

W

 

THERMOSTAT ONLY

 

UNIT TERMINAL STRIP

NOTE:

** R HEAT ANTICIPATOR

SHOULD BE SET AT 0.25

G

AMPS FOR ALL MODELS.

 

Y

 

*

W2

24 VOLT TRANSFORMER

 

 

W1

 

OO

* = Only required on units with supplemental electric heat.

CC

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

POWER WIRING

REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, WIRING & OVERCURRENT PROTECTION.

REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, WIRING & OVERCURRENT PROTECTION.

FIG. 2 - TYPICAL FIELD WIRING DIAGRAM

TABLE 3 - PHYSICAL DATA

 

MODELS

 

 

 

BHH

 

 

 

 

018

024

030

036

042

048

060

 

 

INDOOR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

9 X 6

10 X 8

10 X 8

10 x 8

11 x 10

11 x 10

11 x 10

BLOWER

FAN MOTOR HP (Three Speed)

 

 

 

 

 

 

1

INDOOR

ROWS DEEP

2

2

3

3

3

3

3

FINS PER INCH

15

15

13

15

16

16

16

COIL

FACE AREA (Sq. Ft.)

4.38

4.38

4.38

4.38

5.63

5.63

5.63

 

OUTDOOR

PROPELLER DIA. (in.)

22

22

22

22

22

22

22

FAN MOTOR HP

 

 

 

 

 

 

 

FAN

NOM. CFM TOTAL

1,800

1.800

1,800

2,400

2,400

3,000

3,000

 

OUTDOOR

ROWS DEEP

1

1

1

2

2

2

2

FINS PER INCH

20

20

20

20

20

20

20

COIL

FACE AREA (Sq. Ft.)

8.3

11.7

11.7

11.7

16.4

16.4

16.4

 

CHARGE

REFRIGERANT 22 (lbs./oz.)

5 / 6

5 / 5

6 / 5

8 / 12

11 / 8

12 / 0

9 / 0

FILTER

FACE AREA (Sq. Ft. / Qty. / Size)

 

 

4.28 / 2 / 14" x 22"

 

 

COMPRESSOR

HERMETIC Type, (Qty. = 1)

Reciprocating

Reciprocating

Scroll

Scroll

Scroll

Scroll

Scroll

4

Unitary Products Group

66297-YIM-C-0205

TABLE 4 - ELECTRICAL DATA (BASIC UNIT)

 

 

VOLTAGE

 

 

 

OUTDOOR

SUPPLY

 

MAX.

MAX.

 

 

 

 

 

LIMITATIONS

COMPRESSOR

 

AIR

MINIMUM

FUSE

HACR

UNIT

TRANSFORMER

MODEL

POWER SUP-

 

1

 

 

 

FAN

BLOWER

CIRCUIT

SIZE,

BREAKER

POWER

BHH

PLY

 

 

 

 

 

 

MOTOR,

MOTOR,

AMPACITY

AMPS

SIZE,

FACTOR

 

SIZE (VA)

 

 

MIN.

 

MAX.

RLA

LRA

 

FLA

 

 

 

 

 

 

FLA

 

2

AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

208/230-1-60

187

 

253

7.1

48.0

 

1.1

2.6

 

12.5

15

15

 

0.96

40

024

208/230-1-60

187

 

253

9.3

57.0

 

1.1

2.6

 

15.3

20

20

 

0.96

40

 

208/230-1-60

187

 

253

15.0

72.5

 

1.1

2.6

 

22.5

30

30

 

0.96

40

030

208/230-3-60

187

 

253

10.0

63.0

 

1.1

2.6

 

16.2

25

25

 

0.96

75

 

460-3-60

414

 

504

5.0

31.0

 

0.6

1.4

 

8.3

15

15

 

0.96

75

 

208/230-1-60

187

 

253

17.2

94.0

 

1.1

3.5

 

26.1

35

35

 

0.96

40

036

208/230-3-60

187

 

253

11.4

78.0

 

1.1

3.5

 

18.9

25

25

 

0.96

75

460-3-60

414

 

504

5.7

40.0

 

0.6

1.8

 

9.5

15

15

 

0.96

75

 

 

 

 

 

 

575-3-60

518

 

630

4.7

32.0

 

0.4

1.5

 

7.8

15

15

 

0.96

75

 

208/230-1-60

187

 

253

20.0

104.0

 

1.1

3.5

 

29.6

40

40

 

0.96

40

042

208/230-3-60

187

 

253

13.9

88.0

 

1.1

3.5

 

22.0

30

30

 

0.96

75

460-3-60

414

 

504

6.4

44.0

 

0.6

1.8

 

10.4

15

15

 

0.96

75

 

 

 

 

 

 

575-3-60

518

 

630

5.4

34.0

 

0.4

1.5

 

8.7

15

15

 

0.96

75

 

208/230-1-60

187

 

253

23.4

126.0

 

1.5

4.0

 

34.7

45

45

 

0.96

40

048

208/230-3-60

187

 

253

13.0

93.0

 

1.5

4.0

 

21.8

30

30

 

0.96

75

460-3-60

414

 

504

6.4

46.5

 

0.8

2.0

 

10.8

15

15

 

0.96

75

 

 

 

 

 

 

575-3-60

518

 

630

5.1

37.2

 

0.6

1.6

 

8.6

15

15

 

0.96

75

 

208/230-1-60

187

 

253

28.8

148.0

 

1.5

5.6

 

43.1

60

60

 

0.96

40

060

208/230-3-60

187

 

253

17.2

123.0

 

1.5

5.6

 

28.7

40

40

 

0.96

75

460-3-60

414

 

504

8.2

62.0

 

0.8

5.6

 

16.7

20

20

 

0.96

75

 

 

 

 

 

 

575-3-60

518

 

630

7.0

50.0

 

0.6

2.8

 

12.2

15

15

 

0.96

75

1 = Rated in accordance with ARI Standard 110, utilization range “A”.

2 = Dual element, time delay type.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL VOLTAGE

 

VOLTAGE

 

KW CAP. MULTI-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLIER

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208

 

.75

 

 

 

 

 

 

 

 

 

 

CORRECTION

240

 

 

 

 

 

 

 

 

 

 

 

 

 

230

 

.92

 

 

 

 

 

 

 

 

 

 

 

FACTORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

 

460

 

.92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

575

 

.92

Unitary Products Group

5

66297-YIM-C-0205

TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT)

MODEL BHH

 

COMPRESSOR

COND.

SUPPLY

ELECTRIC HEAT ACCESSORY

 

MAX.

MAX.

 

 

 

 

 

 

 

MINIMUM

POWER

 

 

FAN

AIR

 

 

 

TOTAL

FUSE

HACR2

SUPPLY

RLA

LRA

MOTOR

BLOWER

MODEL NO.

KW

 

CIRCUIT

SIZE,

1

BREAKER

MOTOR,

 

AMPS

AMPACITY

 

 

 

 

 

FLA

FLA

 

 

 

 

 

AMPS

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

208/230-1-60

7.1

48.0

1.1

2.6

2NH04500506

3.8 / 5.0

*

18.1 / 20.8

35.1 / 38.6

40 / 40

40 / 40

2NH04500706

5.6 / 7.5

*

27.1 / 31.3

46.4 / 51.6

50 / 60

50 / 60

 

 

 

 

 

 

 

 

 

 

 

 

2NH04500506

3.8 / 5.0

*

18.1 / 20.8

37.9 / 41.4

40 / 45

40 / 45

024

208/230-1-60

9.3

57.0

1.1

2.6

2NH04500706

5.6 / 7.5

*

27.1 / 31.3

49.2 / 54.4

50 / 60

50 / 60

 

 

 

 

 

 

2NH04501006

7.5 / 10.0

*

36.1 / 41.7

60.5 / 67.4

70 / 70

70 / 70

 

 

 

 

 

 

2NH04500506

3.8 / 5.0

*

18.1 / 20.8

45.0 / 48.5

50 / 50

50 / 50

 

 

15.0

72.5

1.1

2.6

2NH04500706

5.6 / 7.5

*

27.3 / 31.3

56.3 / 61.5

60 / 70

60 / 70

 

 

2NH04501006

7.5 / 10.0

*

36.1 / 41.7

67.6 / 74.5

70 / 80

70 / 80

030

208/230-1-60

 

 

 

 

 

 

 

 

2NH04501506

11.3 / 15.0

*

54.2 / 62.5

90.2 / 100.6

100 / 110

100 / 110

 

 

15.0

72.5

1.1

2.6

2ND04501506

3.8/5.0

 

18.1/20.8

45.0/48.5

50/50

50/50

 

 

0.0

0.0

0.0

0.0

7.5/10.0

 

36.1/41.7

45.1/52.1

50/60

50/60

 

 

 

 

 

 

 

 

 

 

2NH04500506

3.8 / 5.0

*

18.1 / 20.8

48.7 / 52.1

60 / 60

60 / 60

 

 

17.2

94.0

1.1

3.5

2NH04500706

5.6 / 7.5

*

27.1 / 31.3

60.0 / 65.2

70 / 70

70 / 70

 

 

2NH04501006

7.5 / 10.0

*

36.1 / 41.7

71.2 / 78.2

80 / 80

80 / 80

036

208/230-1-60

 

 

 

 

 

 

 

 

2NH04501506

11.3 / 15.0

*

54.2 / 62.5

93.8 / 104.2

100 / 110

100 / 110

 

 

17.2

94.0

1.1

3.5

2ND04501506

3.8/5.0

 

18.1/20.8

48.7/52.1

60/60

60/60

 

 

0.0

0.0

0.0

0.0

7.5/10.0

 

36.1/41.7

45.1/52.1

50/60

50/60

 

 

 

 

 

 

20.0

104.0

1.1

3.5

2NP04501006

7.5 / 10.0

*

36.1 / 41.7

74.7 / 81.7

80 / 90

80 / 90

 

 

2NP04501506

11.3 / 15.0

*

54.2 / 62.5

97.3 / 107.7

100 / 110

100 / 110

042

208/230-1-60

 

 

 

 

20.0

104.0

1.1

3.5

2ND04501506

3.8/5.0

 

18.1/20.8

52.2/55.6

60/70

60/70

 

 

 

 

 

0.0

0.0

0.0

0.0

7.5/10.0

 

36.1/41.7

45.1/52.1

50/60

50/60

 

 

 

 

 

 

 

 

 

 

2NP04501006

7.5 / 10.0

*

36.1 / 41.7

79.9/86.8

90/90

90/90

048

208/230-1-60

23.4

126.0

1.5

4.0

2NP04501506

11.3 / 15.0

*

54.2 / 62.5

102.5/112.9

110/125

110/125

2NP04502006

15.0 / 20.0

*

72.2 / 83.3

125.0/138.9

150/150

150/150

 

 

 

 

 

 

 

 

 

 

 

 

2NX04502506

18.8 / 25.0

*

90.3 / 104.2

147.6/165.0

150/175

150/175

 

 

 

 

 

 

2NP04501006

7.5 / 10.0

*

36.1 / 41.7

88.2/95.2

100/110

100/110

060

208/230-1-60

28.8

148.0

1.5

5.6

2NP04501506

11.3 / 15.0

*

54.2 / 62.5

110.8/121.2

125/125

125/125

2NH04502006

15.0 / 20.0

*

72.2 / 83.3

133.4/147.3

150/150

150/150

 

 

 

 

 

 

 

 

 

 

 

 

2NP04502506

18.8 / 25.0

*

90.3 / 104.2

155.9/173.3

175/175

175/175

030

208/230-3-60

10.0

63.0

1.1

3.5

2NH04501025

7.5 / 10.0

*

20.8 / 24.1

42.3/46.3

45/50

45/50

2NH04501525

11.3 / 15.0

*

31.3 / 36.1

55.3/61.3

60/70

60/70

 

 

 

 

 

 

036

208/230-3-60

11.4

78.0

1.1

3.5

2NH04501025

7.5 / 10.0

*

20.8 / 24.1

44.9 / 48.9

50/50

50/50

2NH04501525

11.3 / 15.0

*

31.3 / 36.1

57.9 / 64.0

60/70

60/70

 

 

 

 

 

 

042

208/230-3-60

13.9

88.0

1.1

3.5

2NP04501025

7.5 / 10.0

*

20.8 / 24.1

48.0 / 52.0

50/60

50/60

2NP04501525

11.3 / 15.0

*

31.3 / 36.1

61.1 / 67.1

70/70

70/70

 

 

 

 

 

 

 

 

 

 

 

 

2NP04501025

7.5 / 10.0

*

20.8 / 24.1

47.8/51.8

50/60

50/60

048

208/230-3-60

13.0

93.0

1.5

4.0

2NP04501525

11.3 / 15.0

*

31.3 / 36.1

60.8/66.9

70/70

70/70

2NP04502025

15.0 / 20.0

*

41.7 / 48.1

73.9/81.9

80/90

80/90

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502525

18.8 / 25.0

*

52.1 / 60.1

86.9/96.9

90/100

90/100

 

 

 

 

 

 

2NH04501025

7.5 / 10.0

*

20.8 / 24.1

54.8/58.8

60/70

60/70

060

208/230-3-60

17.2

123.0

1.5

5.6

2NH04501525

11.3 / 15.0

*

31.3 / 36.1

67.8/73.8

70/80

70/80

2NH04502025

15.0 / 20.0

*

41.7 / 48.1

80.8/88.8

90/90

90/90

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502525

18.8 / 25.0

*

52.1 / 60.1

93.9/103.9

100/110

100/110

030

460-3-60

5.0

31.0

0.6

1.8

2NH04501046

10.0**

 

12.0

23.3

25

 

25

2NH04501546

15.0**

 

18.0

30.8

35

 

35

 

 

 

 

 

 

 

 

036

460-3-60

5.7

40.0

0.6

1.8

2NH04501046

10.0**

 

12.0

24.5

25

 

25

2NH04501546

15.0**

 

18.0

32.0

35

 

35

 

 

 

 

 

 

 

 

042

460-3-60

6.4

44.0

0.6

1.8

2NH04501046

10.0**

 

12.0

25.4

30

 

30

2NH04501546

15.0**

 

18.0

33.0

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2NP04501046

10.0**

 

12.0

25.8

30

 

30

048

460-3-60

6.4

46.5

0.8

2.0

2NH04501546

15.0**

 

18.0

33.4

35

 

35

2NH04502046

20.0**

 

24.1

40.9

45

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502546

25.0**

 

30.1

48.4

50

 

50

 

 

 

 

 

 

2NP04501046

10.0**

 

12.0

28.9

30

 

30

060

460-3-60

8.2

62.0

0.8

5.6

2NH04501546

15.0**

 

18.0

36.4

40

 

40

2NH04502046

20.0**

 

24.1

43.9

45

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2NP04502546

25.0**

 

30.1

51.4

60

 

60

1= Dual element, time delay type.

2= Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.

**= KW listed is for 480 volts, use table on previous page for 460 volts.

***= KW listed is for 600 volts, use table on previous page for 575 volts.

6

Unitary Products Group

66297-YIM-C-0205

TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) (Continued)

MODEL BHH

 

COMPRESSOR

COND.

SUPPLY

ELECTRIC HEAT ACCESSORY

 

MAX.

MAX.

 

 

 

 

 

 

 

 

RLA

LRA

MOTOR,

 

KW

 

AMPACITY

 

POWER

 

 

FAN

AIR

 

 

 

MINIMUM

FUSE

HACR2

 

SUPPLY

 

 

MOTOR

BLOWER

MODEL

 

TOTAL

CIRCUIT

SIZE,1

BREAKER

 

 

 

 

FLA

FLA

NO.

 

AMPS

 

AMPS

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

575-3-60

4.7

32.0

0.4

1.5

2NH04501058

10.0***

9.6

19.8

20

20

2NH04501558

15.0***

14.4

25.8

30

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

575-3-60

5.4

34.0

0.4

1.5

2NH04501058

10.0***

9.6

20.7

25

25

2NH04501558

15.0***

14.4

26.7

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501058

10.0***

9.6

20.6

25

25

048

575-3-60

5.1

37.2

0.6

1.6

2NH04501558

15.0***

14.4

26.7

30

30

2NH04502058

20.0***

19.2

32.7

35

35

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502558

25.0***

24.1

38.7

40

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501058

10.0***

9.6

24.2

25

25

060

575-3-60

7.0

50.0

0.6

2.8

2NH04501558

15.0***

14.4

30.2

35

35

2NP04502058

20.0***

19.2

36.3

40

40

 

 

 

 

 

 

 

 

 

 

 

 

2NP04502558

25.0***

24.1

42.3

45

45

 

 

 

 

 

 

 

 

 

 

 

 

1= Dual element, time delay type.

2= Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

*= KW listed is for 240 volts, use table on previous page for 208 or 230 volts.

**= KW listed is for 480 volts, use table on previous page for 460 volts.

***= KW listed is for 600 volts, use table on previous page for 575 volts.

Unitary Products Group

7

66297-YIM-C-0205

TABLE 6 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 600 CFM (B1HH018)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

65

5.5

5.8

6.1

6.4

 

6.7

7.0

7.3

 

13.0

18.7

24.5

30.2

70

5.1

5.5

5.9

 

6.3

6.7

7.1

 

12.4

17.8

23.1

28.5

75

5.4

 

5.8

6.3

6.8

 

11.8

16.8

21.8

26.8

80

 

5.4

6.0

6.6

 

11.2

15.8

20.5

25.1

85

 

5.6

6.3

 

10.6

14.9

19.1

23.4

90

 

5.3

6.1

 

10.0

13.9

17.8

21.7

95

 

5.8

 

9.4

12.9

16.5

20.0

100

 

 

7.9

11.0

14.1

17.2

105

 

 

6.5

9.1

11.8

14.4

110

 

 

5.0

7.2

9.4

11.6

115

 

 

5.3

7.1

8.8

TABLE 7 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 600 CFM (B1HH018)

INDOOR DB

 

 

 

OUTDOOR TEMPERATURE, °F

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

-10

0

10

 

20

30

 

40

50

60

°F

 

 

55

3.1

3.5

4.0

 

4.7

5.8

 

7.3

9.4

12.4

70

 

3.5

 

5.0

7.1

10.1

80

 

 

3.6

5.7

8.7

TABLE 8 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 800 CFM (B1HH024)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

18.8

20.7

22.6

24.5

 

26.4

28.3

30.2

 

30.6

31.0

31.4

31.8

70

15.7

17.5

19.3

21.1

 

22.9

24.7

26.5

 

27.5

28.6

29.7

30.8

75

12.5

14.2

15.9

17.6

 

19.3

21.0

22.7

 

24.5

26.2

28.0

29.7

80

9.4

11.0

12.6

14.2

 

15.8

17.4

19.0

 

21.4

23.8

26.3

28.7

85

6.2

7.7

9.2

10.7

 

12.2

13.7

15.2

 

18.3

21.4

24.6

27.7

90

5.9

7.2

 

8.7

10.1

11.5

 

15.3

19.1

22.9

26.7

95

 

5.1

6.4

7.7

 

12.2

16.7

21.1

25.6

100

 

5.3

6.2

 

10.0

13.9

17.7

21.5

105

 

 

7.9

11.1

14.2

17.4

110

 

 

5.8

8.3

10.8

13.3

115

 

 

5.5

7.3

9.2

TABLE 9 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 800 CFM (B1HH024)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

4.4

4.4

4.6

4.9

5.6

7.1

10.2

16.6

70

5.9

12.3

80

9.3

8

Unitary Products Group

66297-YIM-C-0205

TABLE 10 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

5.8

10.8

15.8

 

20.8

25.8

30.8

 

31.7

32.6

33.4

34.3

70

5.1

9.3

13.6

 

17.8

22.1

26.3

 

28.0

29.6

31.3

32.9

75

7.9

11.4

 

14.8

18.3

21.8

 

24.2

26.7

29.1

31.6

80

6.4

9.1

 

11.9

14.6

17.3

 

20.5

23.7

27.0

30.2

85

6.9

 

8.9

10.8

12.8

 

16.8

20.8

24.8

28.8

90

 

5.9

7.1

8.3

 

13.1

17.9

22.6

27.4

95

 

 

9.4

14.9

20.5

26.0

100

 

 

7.6

12.0

16.3

20.7

105

 

 

5.9

9.0

12.2

15.3

110

 

 

6.1

8.0

9.9

115

 

 

TABLE 11 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

5.8

7.9

9.6

13.4

19.1

26.9

36.6

70

5.4

11.2

18.9

28.7

80

8.1

15.9

25.6

TABLE 12 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

5.2

7.3

9.4

 

11.6

13.7

15.8

 

20.0

24.2

28.4

32.6

70

6.4

8.2

 

10.0

11.8

13.6

 

17.9

22.2

26.5

30.8

75

5.5

6.9

 

8.4

9.8

11.3

 

15.7

20.2

24.6

29.1

80

5.7

 

6.8

7.9

9.1

 

13.6

18.2

22.7

27.3

85

 

5.2

6.0

6.8

 

11.5

16.2

20.8

25.5

90

 

 

9.3

14.2

19.0

23.8

95

 

 

7.2

12.1

17.1

22.0

100

 

 

5.9

9.9

14.0

18.0

105

 

 

7.7

10.9

14.0

110

 

 

5.5

7.8

10.1

115

 

 

6.1

TABLE 13 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

3.3

4.1

5.3

7.0

9.5

13.2

70

3.8

5.5

8.0

11.7

80

4.5

8.2

Unitary Products Group

9