TECHNICAL GUIDE

J

SINGLE PACKAGE

AIR-TO-AIR

HEAT PUMPS

B3CH 036, 048 & 060 (208/230, 460V) B5CH 036 & 060 (575V), B6CH 048 3, 4 AND 5 NOMINAL TONS

(10 SEER)

SUNLINE 2000

DESCRIPTION

YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential and light commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.

All units are self--contained and assembled on rigid full perimeter base rails allowing for 3--way fork lift access and overhead rigging. Every unit is completely charged, wired, piped and tested at the factory to provide for a quick and easy field installation.

The units are available with supplemental electric heaters as field--installed accessories.

Both down and side discharge airflows are available without having to swap panels. The installer simply removes the duct covers for the desired configuration. Economizers may be used on either side or down discharge applications with no modifications required.

All models include a 1--year limited warranty on the complete unit. Compressors and electric heater elements each carry an additional 4--year warranty.

FEATURES

CONTROLS -- These heat pumps utilize a unique time-- temperature defrost circuit which adjusts the time between defrost cycles based on the outdoor temperature to provide optimal comfort control and ensure reliable operation. The ambient--modified, time--temperature defrost control extends the time below 35°F and shortens the time above 35°F. The nominal defrost times are field adjustable to 50, 80 and 110 minutes. The defrost time is initiated and terminated by a liquid line control with a 10 minute override limit built into the defrost control.

COMMON FOOTPRINT/COMMON CABINET -- The 3, 4 and 5 ton units all share the exact same cabinet -- and therefore the same roof curb. You now have the flexibility of setting one curb and, after the internal load has been determined, placing the proper tonnage unit on that curb.

HIGH EFFICIENCY -- All units have a minimum SEER of 10, a COP of 3.0 (high) and 2.0 (low) and an HSPF as high as 7.3. These efficiencies exceed all legislated minimum levels and provide low operating costs.

CONVERTIBLE AIRFLOW DESIGN -- Both the side and bottom duct openings are covered when they leave the factory. If a side supply/side return is desired, you simply remove the two side duct covers from the outside of the unit and discard them. If a bottom supply/return is desired, you simply remove the two bottom duct covers and discard them. No panel cutting or swapping is required! Convertible airflow design allows maximum field flexibility and minimum inventory.

FACTORY--INSTALLED OPTIONS -- Economizers can be installed at the factory. They are shipped installed and wired. The outdoor air hood needs only to be field assembled and installed.

Adjustable belt--drive blowers are available on most models from the factory for complete air flow flexibility.

FIELD--INSTALLED ACCESSORIES -- Accessories were designed for quick and easy installation. The motorized damper and economizers simply slide in and electrical connections are made by modular plugs. Electric heaters mount easily and knockouts are provided in the internal partitions to connect the elements to the control box single point kit.

The motorized air damper includes a slid--in/plug--in damper assembly with a rainhood and filters. The outdoor air dampers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.

The manual outdoor damper provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.

The 14" high roof curb is shipped knocked down. A roof curb deck is not required because the bottom of the unit is insulated.

WIDE RANGE OF INDOOR AIRFLOWS -- All models operate over a wide range of design conditions with a 3--speed direct-- drive fan motor. Belt--drive blowers are also available on all models.

FULL PERIMETER BASE RAILS -- The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails provide fork lift access from 3 sides and rigging holes are also provided so that an overhead crane can be used to place the units on a roof.

FEATURES - CONT'D.

SYSTEM PROTECTION -- Crankcase heaters and internal compressor protection are standard on all compressors. Every unit has a liquid line filter--drier, low pressure switch, high pressure switch and high temperature switch to protect all system components. A suction line freezestat is supplied on all three--phase units to protect against loss of charge and coil frosting due to low economizer outdoor air temperature while the compressor is running. All units will provide cooling at ambient temperatures down to 45°F.

UTILITY CONNECTIONS MADE EASY -- Electric utility knockouts are provided in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a

036-21564-002-A-0404

field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.

SIMPLE CONTROL CIRCUIT -- Mate--n--lock plug connectors are used where line and low voltage wires pass thru internal bulkheads. This allows for easier troubleshooting and component replacement. The electrical control box is not located in the compressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures.

AIR FILTERS -- Units come standard with 1" throwaway filters. The unit filter racks can accommodate 1" or 2" filters without any modifications.

SUNLINE 2000 Heat Pump

DIRECT DRIVE BLOWER MOTOR (Belt-Drive Option also available on some models)

(Direct Drive Models)

TABLE OF CONTENTS

Description ..........................................................................

1

Features ..............................................................................

1

Ratings ................................................................................

3

Physical Data.......................................................................

3

Cooling Capacities - 3 Ton...................................................

4

Cooling Capacities - 4 Ton...................................................

5

Cooling Capacities - 5 Ton...................................................

6

Heating Capacities ..............................................................

7

Supply Air Blower Perf. - 3 & 4 Ton w/Belt-Drive.................

8

Supply Air Blower Perf. - 5 Ton w/Belt-Drive .......................

9

Supply Air Blower Perf. - 3, 4 & 5 Ton w/Direct-Drive..........

9

Motor and Drive Data ..........................................................

9

Static Resistances .............................................................

10

Heater / CFM Limitations...................................................

10

Field Wiring .......................................................................

10

Electrical Data - Basic Units (Direct-Drive) ........................

11

Elec. Data-Ht. Pump/Elec.Ht. 3 Ton (Direct-Drive) ............

11

Elec. Data-Ht. Pump/Elec.Ht. 4 & 5 Ton (Direct-Drive)......

12

Electrical Data - Basic Units (Belt-Drive) ...........................

13

Elec. Data-Ht. Pump/Elec.Ht. 3 Ton (Belt-Drive) ...............

13

Elec. Data-Ht. Pump/Elec.Ht. 4 & 5 Ton (Belt-Drive).........

14

Unit Dimensions ................................................................

15

Roof Curb Dimensions ......................................................

17

Factory Installed Options / Field-Installed Accessories .....

18

Typical Applications...........................................................

19

2

Unitary Products Group

036-21564-002-A-0404

RATINGS

CAPACITY RATINGS

 

 

 

 

 

 

ARI RATINGS (SEE NOTE 1)

 

 

 

 

 

 

NOMINAL

 

MODEL

 

COOLING

 

 

SOUND

 

HEATING CAPACITY

ELECTRIC HEAT CAPACITY

 

 

 

RATING

 

 

 

 

 

 

 

(SEE NOTE 3)

 

BCH

PERFORMANCE

 

HSPF

47

°

F

17

°

F

 

 

(SEE NOTE 2)

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

MBH

 

SEER

 

EER

 

bels

 

MBH

 

COP

MBH

 

COP

240V

480V

600V

036

39

 

10.00

 

9.20

 

8.6

7.3

39.0

 

3.0

23.0

 

2.1

5, 7, 10, 15 & 20

7,10,15 & 20

10, 15 & 20

048

48

 

10.20

 

9.25

 

8.6

6.7

48.0

 

3.0

26.4

 

2.0

5, 7, 10, 15 & 20

7,10,15 & 20

10, 15 & 20

060

59

 

10.00

 

9.20

 

8.4

7.0

59.0

 

3.0

36.0

 

2.1

5,7,10,15,20 & 30

7,10,15,20 & 30

10,15,20 & 30

NOTE: 1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2.Rated in accordance with ARI Standard 270.

3.Heaters available as accessories - all with single point power supply.

SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

EER = Energy Efficiency Ratio-the cooling capacity in BTU's per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).

COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary resistance (BTU's per hour) divided by the total electric input (watts) x 3.412.

SOUND POWER RATINGS

 

 

ESP

Blower

 

 

 

 

Sound Power (dB 10-12 Watts)

 

 

 

Unit

CFM

 

 

Octave Band Centerline Frequency (Hz)

 

 

SWL

dB(A)

 

 

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IWG

Speed

KW

63

125

 

250

500

1000

2000

 

4000

8000

dB(A)

@ 10 ft*

 

 

 

 

 

 

038

1200

0.60

LOW

0.60

84

84

 

74

67

69

62

 

57

52

74

41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

1600

0.55

HIGH

0.80

85

85

 

75

68

70

63

 

58

53

75

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

2000

0.45

HIGH

1.00

86

86

 

76

69

71

64

 

59

54

76

43

*At a distance of 10 ft from the blower

NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are to be used for reference only. Calculation of dBAvalues cover matters of system design and the fan manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

PHYSICAL DATA

BASIC UNITS

 

MODELS

 

BCH

 

 

036

048

060

 

 

SUPPLY AIR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

12 x 10

12 x 10

12 x 10

FAN MOTOR HP (DIRECT-DRIVE)

12

3 4

1

BLOWER

FAN MOTOR HP (BELT-DRIVE)

1.5

1.5

1.5

 

INDOOR

ROWS DEEP

4

3

3

FINS PER INCH

16

15

15

COIL

FACE AREA (Sq. Ft.)

4.3

5.1

5.1

 

OUTDOOR

PROPELLER DIA. (in.)

22

22

24

FAN MOTOR HP

13

12

12

FAN

NOM. CFM TOTAL

4300

4200

4500

 

OUTDOOR

ROWS DEEP

1

1

1

FINS PER INCH

20

20

20

COIL

FACE AREA (Sq. Ft.)

17.1

17.1

17.1

 

AIR

QUANTITY PER UNIT (15" x 20" x 1")

2

2

2

FILTERS

QUANTITY PER UNIT (14" X 25" X 1")

1

1

1

(SEE NOTE)

TOTAL FACE AREA (sq. ft.)

6.6

6.6

6.6

CHARGE

REFRIGERANT 22 (lbs./oz.)

7/12

9/2

8/4

COMPRESSOR

HERMETIC, RECIPROCATING (Qty)

1

1

1

NOTE: Filter racks can accommodate 1" or 2" thick filters.

Unitary Products Group

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036-21564-002-A-0404

COOLING CAPACITIES - 3 TON (BCH036)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

85 °F

 

 

 

 

 

 

 

 

 

 

95 °F

 

 

 

 

 

 

 

Coil

 

Total

Power

 

Sensible Capacity1, MBH

 

Total

Power

 

 

Sensible Capacity1, MBH

 

 

 

 

CFM

 

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

 

 

 

°F

MBH

KW

86

83

80

77

 

74

71

 

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

72

51

3.4

37

32

28

24

 

19

-

 

-

47

3.7

 

34

29

25

22

17

-

-

 

1750

 

67

46

3.4

40

40

36

31

 

26

21

 

16

44

3.7

 

38

38

34

29

24

20

15

 

 

62

42

3.3

42

42

41

39

 

34

29

 

24

38

3.6

 

38

38

37

35

30

26

21

 

 

 

 

 

 

 

 

 

 

 

 

 

57

42

3.3

42

42

42

40

 

35

30

 

25

37

3.6

 

37

37

37

35

30

26

22

 

 

 

 

 

72

49

3.4

35

30

26

22

 

18

-

 

-

46

3.7

 

32

28

24

20

16

-

-

 

1500

 

67

45

3.4

39

37

33

29

 

24

20

 

15

42

3.7

 

36

34

30

27

22

18

14

 

 

62

41

3.3

41

41

40

37

 

32

28

 

24

37

3.6

 

37

37

36

33

28

25

21

 

 

 

 

 

 

 

 

 

 

 

 

 

57

41

3.3

41

41

41

38

 

34

29

 

25

36

3.6

 

36

36

36

33

29

25

21

 

 

 

 

 

72

48

3.4

33

29

24

20

 

16

-

 

-

45

3.7

 

30

27

22

18

15

-

-

 

1400

 

67

44

3.3

39

36

32

28

 

23

20

 

15

41

3.7

 

36

33

29

26

21

18

13

 

 

62

40

3.3

40

39

38

34

 

30

26

 

22

36

3.6

 

36

35

34

30

27

23

19

 

 

 

 

 

 

 

 

 

 

 

 

 

57

40

3.3

40

40

39

35

 

31

27

 

23

36

3.5

 

36

36

35

31

27

24

20

 

 

 

 

 

72

47

3.4

31

27

24

20

 

16

-

 

-

44

3.7

 

29

25

22

18

14

-

-

 

 

1200

 

67

41

3.3

36

32

29

25

 

22

18

 

14

39

3.6

 

34

30

27

23

20

17

13

 

 

 

62

38

3.3

38

37

36

32

 

29

25

 

21

35

3.6

 

35

34

33

29

26

23

19

 

 

 

 

 

 

 

 

 

 

 

 

 

57

37

3.3

37

37

36

33

 

30

26

 

22

35

3.5

 

35

35

34

31

28

24

20

 

 

 

 

 

72

45

3.3

28

25

22

19

 

16

-

 

-

42

3.6

 

26

23

20

17

14

-

-

 

1050

 

67

41

3.3

34

30

27

24

 

20

17

 

14

38

3.6

 

31

27

25

22

18

15

12

 

 

62

36

3.3

36

35

33

30

 

27

24

 

21

34

3.5

 

34

33

31

28

25

22

19

 

 

 

 

 

 

 

 

 

 

 

 

 

57

36

3.3

36

36

34

31

 

28

25

 

22

33

3.5

 

33

33

31

28

25

22

20

 

 

 

 

 

72

45

3.3

26

24

20

17

 

15

-

 

-

40

3.6

 

23

21

17

15

13

-

-

 

900

 

67

39

3.3

31

28

25

22

 

19

17

 

14

35

3.6

 

27

25

22

19

17

15

12

 

 

62

35

3.2

35

34

32

29

 

25

23

 

20

32

3.5

 

32

30

28

25

22

20

17

 

 

 

 

 

 

 

 

 

 

 

 

 

57

35

3.2

35

35

32

30

 

26

24

 

21

31

3.5

 

31

31

28

26

23

21

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

105 °F

 

 

 

 

 

 

 

 

 

 

115 °F

 

 

 

 

 

 

 

Coil

 

Total

Power

 

Sensible Capacity1, MBH

 

Total

Power

 

 

Sensible Capacity1, MBH

 

 

 

 

CFM

 

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

 

 

 

°F

MBH

KW

86

83

80

77

 

74

71

 

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

72

44

4.0

31

27

24

20

 

16

-

 

-

42

4.2

 

30

26

23

19

15

-

-

 

1750

 

67

40

4.0

34

34

31

26

 

22

18

 

13

36

4.1

 

31

31

28

24

20

16

12

 

 

62

35

3.9

35

35

34

32

 

28

24

 

20

34

4.1

 

34

34

33

31

27

23

19

 

 

 

 

 

 

 

 

 

 

 

 

 

57

35

3.9

35

35

35

33

 

29

25

 

20

33

4.1

 

33

33

33

31

27

23

19

 

 

 

 

 

72

43

4.0

30

26

22

19

 

15

-

 

-

41

4.2

 

29

25

21

18

15

-

-

 

1500

 

67

38

4.0

32

31

27

24

 

20

16

 

12

35

4.1

 

30

28

25

22

18

15

11

 

 

62

34

3.9

34

34

33

30

 

26

23

 

19

33

4.1

 

33

33

32

29

25

22

19

 

 

 

 

 

 

 

 

 

 

 

 

 

57

34

3.9

34

34

34

31

 

28

24

 

20

32

4.1

 

32

32

32

29

26

22

19

 

 

 

 

 

72

42

4.0

28

25

21

17

 

14

-

 

-

39

4.2

 

26

23

19

16

13

-

-

 

1400

 

67

37

4.0

32

30

26

23

 

19

16

 

12

34

4.1

 

30

27

24

21

17

15

11

 

 

62

33

3.9

33

32

31

28

 

24

21

 

18

32

4.1

 

32

31

30

27

24

20

17

 

 

 

 

 

 

 

 

 

 

 

 

 

57

32

3.8

32

32

31

28

 

24

21

 

18

32

4.0

 

32

32

31

28

24

21

18

 

 

 

 

 

72

41

4.0

27

23

20

17

 

13

-

 

-

37

4.2

 

24

21

18

15

12

-

-

 

1200

 

67

35

3.9

30

27

24

21

 

18

15

 

11

32

4.1

 

28

24

22

19

17

14

10

 

 

62

32

3.9

32

31

30

26

 

24

21

 

17

30

4.1

 

30

29

28

25

22

19

16

 

 

 

 

 

 

 

 

 

 

 

 

 

57

31

3.8

31

31

31

27

 

25

21

 

18

29

4.0

 

29

29

29

25

23

20

17

 

 

 

 

 

72

40

3.9

24

22

19

16

 

14

-

 

-

35

4.1

 

21

19

17

14

12

-

-

 

1050

 

67

34

3.9

28

24

22

19

 

16

14

 

11

31

4.0

 

25

22

20

18

15

12

10

 

 

62

30

3.8

30

29

27

25

 

22

20

 

17

29

4.0

 

29

28

26

24

21

19

16

 

 

 

 

 

 

 

 

 

 

 

 

 

57

30

3.8

30

30

28

25

 

23

20

 

18

28

4.0

 

28

28

26

24

21

19

17

 

 

 

 

 

72

38

3.9

21

20

16

14

 

12

-

 

-

34

4.1

 

19

18

15

12

11

-

-

 

900

 

67

32

3.9

25

22

20

18

 

15

13

 

11

29

4.0

 

23

20

18

16

14

12

10

 

 

62

29

3.8

29

27

25

23

 

20

18

 

16

27

4.0

 

27

25

24

21

18

17

15

 

 

 

 

 

 

 

 

 

 

 

 

 

57

29

3.8

29

29

26

24

 

21

19

 

17

26

4.0

 

26

26

23

22

19

17

15

 

 

1These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by

 

3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

 

 

 

 

 

 

 

 

 

2These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.

 

 

 

Refer to the Blower Performance Table for the KW of the supply air blower motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL RATING

 

 

 

 

 

 

 

 

ALL SENSIBLE CAPACITY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Unitary Products Group

036-21564-002-A-0404

COOLING CAPACITIES - 4 TON (BCH048)

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

Indoor

 

 

 

85 °F

 

 

 

 

 

 

 

 

 

95 °F

 

 

 

 

Coil

 

Total

Power

 

Sensible Capacity1, MBH

 

Total

Power

 

 

Sensible Capacity1, MBH

 

CFM

 

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

°F

MBH

KW

86

83

80

77

 

74

71

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

72

56

4.1

42

36

31

26

 

-

-

-

53

4.5

 

40

35

29

24

-

-

-

2000

 

67

53

4.0

48

47

41

36

 

30

25

-

51

4.4

 

46

45

41

35

30

24

-

 

62

49

4.0

49

49

48

44

 

38

33

28

46

4.3

 

46

46

45

41

35

30

24

 

 

 

 

 

 

57

49

3.9

49

49

49

44

 

38

33

28

46

4.3

 

46

46

46

41

35

30

24

 

 

72

55

4.0

40

35

30

25

 

-

-

-

53

4.4

 

38

33

28

23

-

-

-

1800

 

67

52

4.0

47

44

39

34

 

29

24

-

51

4.4

 

44

44

39

34

29

24

-

 

62

48

3.9

48

48

47

43

 

38

33

28

47

4.3

 

47

47

45

40

36

31

26

 

 

 

 

 

 

57

48

3.9

48

48

48

43

 

38

33

28

45

4.2

 

45

45

45

40

35

30

25

 

 

72

53

4.0

37

33

28

24

 

-

-

-

52

4.4

 

36

32

27

23

-

-

-

1600

 

67

51

4.0

46

42

37

33

 

28

24

-

50

4.3

 

44

43

38

34

29

25

-

 

62

47

3.9

47

47

46

41

 

37

32

28

45

4.2

 

45

45

44

40

36

31

27

 

 

 

 

 

 

57

47

3.9

47

47

47

42

 

38

33

29

44

4.1

 

44

44

44

40

36

31

27

 

 

72

52

4.0

34

30

26

22

 

-

-

-

49

4.3

 

33

29

25

21

-

-

-

1400

 

67

49

3.9

42

38

34

30

 

26

22

-

47

4.2

 

42

38

34

30

26

22

-

 

62

46

3.8

46

45

42

38

 

34

30

26

43

4.1

 

43

42

40

36

32

28

24

 

 

 

 

 

 

57

45

3.8

45

45

43

39

 

35

31

27

42

4.1

 

42

42

40

36

32

28

24

 

 

72

50

3.9

31

27

24

20

 

-

-

-

47

4.2

 

29

25

22

18

-

-

-

1200

 

67

47

3.9

38

35

31

28

 

24

21

-

45

4.2

 

37

34

30

27

23

20

-

 

62

44

3.8

44

42

39

35

 

32

28

25

40

4.1

 

40

39

36

32

29

25

22

 

 

 

 

 

 

57

44

3.7

44

43

39

36

 

32

29

25

40

4.0

 

40

39

36

32

29

25

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

Indoor

 

 

 

105 °F

 

 

 

 

 

 

 

 

 

115 °F

 

 

 

 

Coil

 

Total

Power

 

Sensible Capacity1, MBH

 

Total

Power

 

 

Sensible Capacity1, MBH

 

CFM

 

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

°F

MBH

KW

86

83

80

77

 

74

71

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

72

51

4.9

40

35

29

24

 

-

-

-

49

5.2

 

39

34

29

23

-

-

-

2000

 

67

46

4.7

42

42

39

34

 

28

23

-

41

5.0

 

40

40

37

32

26

21

-

 

62

43

4.6

43

43

42

37

 

32

27

21

40

4.9

 

40

40

39

34

29

23

18

 

 

 

 

 

 

57

43

4.6

43

43

43

38

 

32

28

22

40

4.8

 

40

40

40

34

30

24

19

 

 

72

50

4.8

38

33

28

23

 

-

-

-

47

5.1

 

37

32

27

22

-

-

-

1800

 

67

45

4.7

41

41

37

32

 

27

22

-

40

4.9

 

37

36

35

30

25

20

-

 

62

42

4.6

42

42

41

37

 

32

27

22

39

4.8

 

39

39

37

34

29

24

19

 

 

 

 

 

 

57

42

4.5

42

42

42

37

 

33

27

23

38

4.7

 

38

38

38

33

30

25

20

 

 

72

49

4.8

35

31

26

22

 

-

-

-

46

5.1

 

34

29

25

20

-

-

-

1600

 

67

44

4.6

40

40

35

31

 

26

22

-

39

4.9

 

36

36

32

28

23

19

-

 

62

41

4.5

41

41

40

35

 

32

27

23

37

4.7

 

37

37

36

33

28

24

19

 

 

 

 

 

 

57

41

4.4

41

41

41

36

 

32

28

23

37

4.7

 

37

37

37

34

28

25

20

 

 

72

47

4.7

32

28

24

20

 

-

-

-

44

5.0

 

31

27

23

19

-

-

-

1400

 

67

42

4.5

38

36

32

28

 

24

20

-

37

4.8

 

36

34

30

26

21

17

-

 

62

39

4.4

39

38

37

33

 

28

25

20

36

4.7

 

36

35

34

30

26

22

18

 

 

 

 

 

 

57

39

4.4

39

39

37

33

 

29

25

21

36

4.6

 

36

36

34

31

26

23

19

 

 

72

44

4.6

28

25

21

18

 

-

-

-

42

4.9

 

28

24

21

17

-

-

-

1200

 

67

40

4.5

36

32

29

25

 

22

18

-

36

4.7

 

34

31

27

24

20

17

-

 

62

38

4.4

38

36

34

29

 

27

22

20

35

4.6

 

35

34

30

28

24

20

17

 

 

 

 

 

 

57

37

4.3

37

37

34

30

 

27

23

20

35

4.6

 

35

35

31

29

24

21

18

1These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW. Refer to the Blower Performance Table for the KW of the supply air blower motor.

 

NOMINAL RATING

 

ALL SENSIBLE CAPACITY

Unitary Products Group

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036-21564-002-A-0404

COOLING CAPACITIES - 5 TON (BCH060)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

85 °F

 

 

 

 

 

 

 

 

 

 

 

95 °F

 

 

 

 

 

 

 

Coil

 

Total

Power

 

Sensible Capacity1, MBH

 

Total

Power

 

 

Sensible Capacity1, MBH

 

 

 

 

CFM

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

 

 

°F

MBH

KW

86

83

80

77

 

74

71

 

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

 

 

 

 

 

72

68

5.7

51

44

38

31

 

-

-

 

-

67

6.0

 

51

45

38

31

-

-

-

 

2500

67

65

5.6

58

56

50

43

 

37

30

 

-

64

5.9

 

56

56

50

43

37

30

-

 

62

61

5.6

61

61

59

53

 

46

39

 

33

59

5.9

 

59

59

57

50

44

38

31

 

 

 

 

 

 

 

 

 

 

 

57

60

5.5

60

60

59

53

 

47

40

 

33

58

5.8

 

58

58

57

51

44

39

32

 

 

 

 

72

67

5.6

48

42

36

30

 

-

-

 

-

66

5.9

 

48

42

36

30

-

-

-

 

2250

67

64

5.6

57

54

48

42

 

36

30

 

-

63

5.9

 

55

54

48

42

35

29

-

 

62

60

5.5

60

60

57

51

 

45

39

 

33

57

5.8

 

57

57

55

50

44

38

32

 

 

 

 

 

 

 

 

 

 

 

57

59

5.5

59

59

58

52

 

46

40

 

34

57

5.8

 

57

57

56

50

45

39

33

 

 

 

 

72

66

5.6

45

40

34

29

 

-

-

 

-

65

5.9

 

45

40

34

29

-

-

-

 

 

2000

67

63

5.5

56

51

45

40

 

35

29

 

-

61

5.9

 

55

51

45

40

34

29

-

 

 

62

59

5.4

59

59

55

50

 

44

39

 

33

56

5.8

 

56

56

54

49

44

38

33

 

 

 

 

 

 

 

 

 

 

 

57

58

5.4

58

58

57

52

 

46

41

 

36

56

5.7

 

56

56

55

50

44

39

34

 

 

 

 

72

64

5.5

42

37

32

27

 

-

-

 

-

62

5.9

 

43

38

33

28

-

-

-

 

1750

67

61

5.5

52

47

42

37

 

33

28

 

-

59

5.8

 

53

48

44

39

34

29

-

 

62

57

5.4

57

56

51

46

 

41

37

 

32

54

5.7

 

54

54

52

48

43

38

33

 

 

 

 

 

 

 

 

 

 

 

57

57

5.4

57

57

53

48

 

44

39

 

34

54

5.7

 

54

54

53

49

43

39

34

 

 

 

 

72

62

5.5

38

34

30

25

 

-

-

 

-

60

5.8

 

41

36

32

28

-

-

-

 

1500

67

59

5.5

48

43

39

35

 

31

26

 

-

57

5.8

 

51

46

42

38

34

29

-

 

62

55

5.4

55

52

47

43

 

39

35

 

30

52

5.7

 

52

52

50

46

42

38

34

 

 

 

 

 

 

 

 

 

 

 

57

55

5.3

55

54

49

45

 

41

37

 

32

52

5.6

 

52

52

51

47

42

39

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

105 °F

 

 

 

 

 

 

 

 

 

 

 

115 °F

 

 

 

 

 

 

 

Coil

 

Total

Power

 

Sensible Capacity1, MBH

 

Total

Power

 

 

Sensible Capacity1, MBH

 

 

 

 

CFM

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

 

 

°F

MBH

KW

86

83

80

77

 

74

71

 

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

 

 

 

 

 

72

64

6.0

51

44

38

31

 

-

-

 

-

60

6.9

 

50

43

37

30

-

-

-

 

2500

67

59

5.9

51

51

49

42

 

36

29

 

-

54

6.6

 

54

53

47

41

34

27

-

 

62

54

5.9

54

54

51

46

 

40

33

 

26

49

6.5

 

49

49

48

42

35

28

22

 

 

 

 

 

 

 

 

 

 

 

57

54

5.8

54

54

52

46

 

41

33

 

26

49

6.5

 

49

49

49

43

35

28

23

 

 

 

 

72

63

5.9

48

42

36

30

 

-

-

 

-

60

6.8

 

47

41

35

29

-

-

-

 

2250

67

58

5.9

51

51

46

40

 

34

28

 

-

54

6.6

 

47

47

45

39

32

26

-

 

62

53

5.8

53

53

52

46

 

40

34

 

28

49

6.5

 

49

49

47

42

36

30

24

 

 

 

 

 

 

 

 

 

 

 

57

53

5.8

53

53

52

46

 

41

35

 

27

49

6.4

 

49

49

48

43

37

31

25

 

 

 

 

72

62

5.9

45

39

34

28

 

-

-

 

-

59

6.8

 

44

38

33

27

-

-

-

 

2000

67

57

5.9

51

49

44

38

 

33

27

 

-

53

6.5

 

45

45

42

36

31

26

-

 

62

52

5.8

52

52

51

46

 

40

35

 

30

48

6.4

 

48

48

46

42

36

31

25

 

 

 

 

 

 

 

 

 

 

 

57

52

5.7

52

52

51

46

 

40

36

 

31

47

6.4

 

47

47

46

43

36

32

25

 

 

 

 

72

60

5.9

41

37

32

27

 

-

-

 

-

56

6.7

 

40

35

30

25

-

-

-

 

1750

67

55

5.8

48

46

41

36

 

31

26

 

-

51

6.5

 

43

43

38

33

29

24

-

 

62

50

5.7

50

50

48

43

 

39

34

 

29

46

6.4

 

46

46

43

38

33

28

24

 

 

 

 

 

 

 

 

 

 

 

57

50

5.7

50

50

48

43

 

39

34

 

30

45

6.3

 

45

45

43

38

33

28

25

 

 

 

 

72

57

5.8

38

34

30

25

 

-

-

 

-

53

6.6

 

36

31

27

23

-

-

-

 

1500

67

53

5.8

47

43

38

34

 

30

26

 

-

48

6.4

 

41

39

35

30

26

22

-

 

62

48

5.7

48

48

45

41

 

37

32

 

28

44

6.3

 

44

44

39

35

30

26

22

 

 

 

 

 

 

 

 

 

 

 

57

48

5.6

48

48

45

41

 

38

32

 

28

43

6.2

 

43

43

40

36

30

26

23

 

 

1These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by

 

3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

 

 

 

 

 

 

 

 

 

2These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.

 

 

 

Refer to the Blower Performance Table for the KW of the supply air blower motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL RATING

 

 

 

 

 

 

 

 

 

ALL SENSIBLE CAPACITY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Unitary Products Group

036-21564-002-A-0404

HEATING CAPACITIES

 

 

 

 

 

BCH036

 

 

 

 

 

CFM

RET. AIR

CAP

 

 

OUTDOOR AIR TEMPERATURE, °F (72% RH)

 

 

°F

& KW

-10

0

10

20

30

40

50

60

 

 

55

MBH

13.1

16.4

23.5

29.1

30.2

41.7

47.0

48.2

 

KW

2.9

3.0

3.2

3.3

3.5

3.7

3.8

3.9

 

 

1750

70

MBH

11.9

15.0

21.5

26.7

27.7

38.2

43.1

44.1

KW

3.0

3.1

3.4

3.4

3.6

3.8

3.9

4.1

 

 

 

80

MBH

10.9

13.6

19.6

24.3

25.2

34.8

39.3

40.2

 

KW

3.1

3.2

3.4

3.5

3.8

3.9

4.1

4.2

 

 

 

55

MBH

12.4

15.5

22.5

27.7

28.7

39.6

44.7

45.8

 

KW

2.7

2.9

3.0

3.1

3.3

3.5

3.6

3.7

 

 

1400

70

MBH

11.4

14.1

20.3

25.2

26.1

36.1

40.7

41.6

KW

2.9

3.0

3.2

3.3

3.5

3.7

3.8

3.9

 

 

 

80

MBH

10.4

13.1

18.0

23.2

24.2

33.3

37.6

38.5

 

KW

3.0

3.1

3.2

3.4

3.6

3.8

3.9

4.0

 

 

 

55

MBH

11.8

14.8

21.3

26.5

27.5

37.8

42.7

43.7

 

KW

2.7

2.8

3.0

3.1

3.3

3.4

3.5

3.6

 

 

1200

70

MBH

10.8

13.5

19.4

24.0

24.9

34.4

38.8

39.7

KW

2.9

3.0

3.1

3.3

3.4

3.6

3.7

3.8

 

 

 

80

MBH

9.9

12.4

17.8

22.0

22.9

31.5

35.6

36.5

 

KW

2.9

3.1

3.2

3.4

3.5

3.7

3.8

3.9

 

 

 

55

MBH

11.2

14.1

20.3

25.2

26.1

35.9

40.6

41.6

 

KW

2.6

2.7

2.9

3.0

3.3

3.3

3.5

3.5

 

 

1050

70

MBH

10.2

12.8

18.5

22.8

23.6

32.7

36.9

37.8

KW

2.8

2.9

3.0

3.2

3.3

3.5

3.6

3.7

 

 

 

80

MBH

9.3

11.7

16.7

20.7

21.5

29.8

33.6

34.4

 

KW

2.8

3.0

3.1

3.3

3.4

3.6

3.7

3.8

 

 

 

 

 

 

 

BCH048

 

 

 

 

 

 

55

MBH

12.3

17.3

22.5

28.2

36.3

44.5

53.8

61.6

 

KW

3.4

3.5

3.6

3.6

3.8

4.0

4.6

5.2

 

 

2000

70

MBH

11.8

16.6

21.6

27.1

34.9

42.8

51.7

59.2

KW

3.5

3.6

3.8

3.8

4.0

4.2

4.8

5.4

 

 

 

80

MBH

10.9

15.3

19.9

24.9

32.1

39.4

47.6

54.5

 

KW

3.6

3.7

4.0

4.0

4.1

4.4

5.0

5.7

 

 

 

55

MBH

12.1

17.0

22.0

27.7

34.5

42.3

51.2

58.6

 

KW

3.3

3.4

3.5

3.6

3.6

3.8

4.4

5.0

 

 

1600

70

MBH

11.6

16.3

21.2

26.6

33.2

40.7

49.2

56.3

KW

3.4

3.5

3.6

3.7

3.8

4.0

4.6

5.2

 

 

 

80

MBH

10.7

15.0

19.5

24.5

30.5

37.4

45.3

51.8

 

KW

3.5

3.6

3.8

3.9

4.0

4.2

4.8

5.4

 

 

 

55

MBH

10.9

15.3

19.9

24.9

31.7

38.9

47.0

53.8

 

KW

3.1

3.2

3.3

3.4

3.5

3.7

4.2

4.8

 

 

1200

70

MBH

10.5

14.7

19.1

24.0

30.5

37.4

45.2

51.7

KW

3.2

3.3

3.4

3.5

3.6

3.8

4.4

5.0

 

 

 

80

MBH

9.6

13.5

17.6

22.0

28.1

34.4

41.6

47.6

 

KW

3.3

3.4

3.5

3.6

3.8

4.0

4.6

5.2

 

 

 

 

 

 

 

BCH060

 

 

 

 

 

 

55

MBH

18.2

24.7

31.1

38.4

45.6

55.4

64.7

75.6

 

KW

5.0

5.1

5.2

5.3

5.3

5.6

5.9

6.5

 

 

2500

70

MBH

17.5

23.7

29.9

37.0

43.9

53.3

62.2

72.7

KW

5.2

5.3

5.4

5.5

5.6

5.9

6.2

6.8

 

 

 

80

MBH

16.1

21.8

27.5

34.0

40.4

49.0

57.2

66.9

 

KW

5.4

5.6

5.7

5.8

5.9

6.0

6.5

7.2

 

 

 

55

MBH

18.0

24.4

30.8

38.1

45.0

54.7

63.9

74.7

 

KW

4.7

4.8

4.9

5.0

5.3

5.5

5.8

6.4

 

 

2000

70

MBH

17.3

23.5

29.6

36.6

43.3

52.6

61.4

71.8

KW

4.9

5.0

5.1

5.2

5.5

5.8

6.1

6.7

 

 

 

80

MBH

15.9

21.6

27.2

33.7

39.8

48.4

56.5

66.1

 

KW

5.1

5.3

5.4

5.5

5.8

6.1

6.4

7.0

 

 

 

55

MBH

16.2

22.0

27.8

34.3

41.4

50.2

58.7

68.6

 

KW

4.5

4.6

4.7

4.8

5.0

5.3

5.5

6.1

 

 

1500

70

MBH

15.6

21.2

26.7

33.0

39.8

48.3

56.4

66.0

KW

4.7

4.8

4.9

5.0

5.2

5.5

5.8

6.4

 

 

 

80

MBH

14.4

19.5

24.6

30.4

36.6

44.5

51.9

60.7

 

KW

4.9

5.0

5.1

5.2

5.5

5.8

6.1

6.7

 

 

Unitary Products Group

7

036-21564-002-A-0404

SUPPLY AIR BLOWER PERFORMANCE - BCH036 & 048 with Belt-Drive

BCH036 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

0.20

0.30

0.40

0.50

0.60

0.70

0.80

BCH

CFM

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

 

 

2000

843

860

880

925

919

1005

956

1065

993

1145

1030

1195

1067

1235

 

1900

817

775

854

850

893

920

930

995

970

1065

1008

1125

1046

1170

 

1800

790

700

828

760

867

840

906

905

944

980

985

1040

1025

1100

 

1700

-

-

802

670

840

745

881

815

920

900

961

970

1001

1030

036

1600

-

-

-

-

818

665

858

740

898

820

940

890

980

950

 

1500

-

-

-

-

-

-

842

695

882

755

922

835

962

895

 

1400

-

-

-

-

-

-

833

650

867

705

904

765

942

820

 

1300

-

-

-

-

-

-

-

-

858

665

893

725

932

785

 

1200

-

-

-

-

-

-

-

-

847

640

880

680

916

730

 

 

 

 

 

 

 

 

 

 

 

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

0.90

1.00

1.10

1.20

1.30

1.40

1.50

BCH

CFM

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

 

 

2000

1103

1270

-

-

-

-

-

-

-

-

-

-

-

-

 

1900

1085

1210

-

-

-

-

-

-

-

-

-

-

-

-

 

1800

1064

1145

1102

1180

-

-

-

-

-

-

-

-

-

-

 

1700

1040

1075

1081

1115

1121

1140

-

-

-

-

-

-

-

-

036

1600

1020

1005

1060

1050

1100

1085

-

-

-

-

-

-

-

-

 

1500

1003

945

1044

995

1086

1035

-

-

-

-

-

-

-

-

 

1400

982

880

1024

920

1067

965

1107

1000

-

-

-

-

-

-

 

1300

970

835

1010

870

1053

920

1099

960

-

-

-

-

-

-

 

1200

953

780

992

815

1034

855

1080

905

-

-

-

-

-

-

NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.

BCH048 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

0.20

0.30

0.40

0.50

0.60

0.70

0.80

BCH

CFM

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

 

 

2000

843

860

880

925

919

1005

956

1065

993

1145

1030

1195

1067

1235

 

1900

817

775

854

850

893

920

930

995

970

1065

1008

1125

1046

1170

 

1800

790

700

828

760

867

840

906

905

944

980

985

1040

1025

1100

 

1700

-

-

802

670

840

745

881

815

920

900

961

970

1001

1030

048

1600

-

-

-

-

818

665

858

740

898

820

940

890

980

950

 

1500

-

-

-

-

-

-

842

695

882

755

922

835

962

895

 

1400

-

-

-

-

-

-

833

650

867

705

904

765

942

820

 

1300

-

-

-

-

-

-

-

-

858

665

893

725

932

785

 

1200

-

-

-

-

-

-

-

-

847

640

880

680

916

730

 

 

 

 

 

 

 

 

 

 

 

MODEL

AIR FLOW

 

 

 

 

Available External Static Pressure - IWG*

 

 

 

 

0.90

1.00

1.10

1.20

1.30

1.40

1.50

BCH

CFM

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

 

 

 

2000

1103

1270

-

-

-

-

-

-

-

-

-

-

-

-

 

1900

1085

1210

-

-

-

-

-

-

-

-

-

-

-

-

 

1800

1064

1145

1102

1180

-

-

-

-

-

-

-

-

-

-

 

1700

1040

1075

1081

1115

1121

1140

-

-

-

-

-

-

-

-

048

1600

1020

1005

1060

1050

1100

1085

-

-

-

-

-

-

-

-

 

1500

1003

945

1044

995

1086

1035

-

-

-

-

-

-

-

-

 

1400

982

880

1024

920

1067

965

1107

1000

-

-

-

-

-

-

 

1300

970

835

1010

870

1053

920

1099

960

-

-

-

-

-

-

 

1200

953

780

992

815

1034

855

1080

905

-

-

-

-

-

-

NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.