York DM150 User Manual

4 (1)
York DM150 User Manual

TECHNICAL

GUIDE 50Hz

TM

SINGLE PACKAGE AIR CONDITIONERS AND SINGLE PACKAGE GAS/ELECTRIC UNITS

DM090, 120, 150

7-1/2, 10, 12-1/2 NOMINAL TONS

9.0 - 10.0 EER 380/415-3-50

036-21044-003-A-0304

®

DESCRIPTION

YORK® Predator® units are convertible single packages with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, roof jack, or frame.

All Predator® units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.

All units are convertible between side and down airflow. A single economizer design is used on side and down discharge applications, as well as all tonnage sizes.

Predator® units are available in the following configurations: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options or as field-installed accessories.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21044-003-A-0304

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 1

FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 3

FACTORY INSTALLED OPTIONS . . . . . . . . . . . .

. . 5

FIELD INSTALLED ACCESSORIES . . . . . . . . . .

. . 6

NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . .

. . 8

 

LIST OF FIGURES

 

Fig. #

Pg. #

1

PREDATOR® COMPONENT LOCATION . . . . . . . .

. . . 3

2

UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . .

. . 31

3

UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . .

. . 31

4

UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . .

. . 31

5

UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . .

. . 32

6

PREDATOR® ROOF CURB DIMENSIONS . . . . . . .

. . 33

7

SUNLINE™ TO PREDATOR® TRANSITION

 

 

ROOF CURB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 33

8

BOTTOM DUCT OPENINGS (FROM ABOVE) . . . .

. . 34

9

REAR DUCT DIMENSIONS . . . . . . . . . . . . . . . . . . .

. . 34

10

COOLING UNIT WITH GAS HEAT WIRING

 

 

DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 35

11

COOLING UNIT WITH/WITHOUT ELECTRIC HEAT

 

WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . .

. . 36

 

LIST OF TABLES

 

Tbl. #

Pg. #

1

PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 12

2

CAPACITY RATINGS IMPERIAL . . . . . . . . . . . . . . .

. . 13

3

CAPACITY RATINGS METRIC . . . . . . . . . . . . . . . .

. . 13

4

COOLING CAPACITY 7-1/2 TON UNIT - IMPERIAL

. . 14

5

COOLING CAPACITY 26.4 KW UNIT - METRIC . . .

. . 15

6

COOLING CAPACITY 10 TON UNIT - IMPERIAL . .

. . 16

7

COOLING CAPACITY 35.1 KW UNIT - METRIC . . .

. . 17

8

COOLING CAPACITY 12-1/2 TON UNIT - IMPERIAL . 18

9

COOLING CAPACITY 43.9 KW UNIT - METRIC . . .

. . 19

10

ELECTRICAL DATA 7-1/2 TON . . . . . . . . . . . . . . . .

. . 20

11

ELECTRICAL DATA 10 TON . . . . . . . . . . . . . . . . . .

. . 20

12

ELECTRICAL DATA 12-1/2 TON . . . . . . . . . . . . . .

. . 20

13

BLOWER PERFORMANCE 7-1/2 TON STANDARD

 

MOTOR - SIDE DUCT (IMPERIAL) . . . . . . . . . . . . .

. . 21

14

BLOWER PERFORMANCE 7-1/2 TON STANDARD

 

MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . .

. . 21

15

BLOWER PERFORMANCE 7-1/2 TON OPTIONAL

 

 

MOTOR - SIDE DUCT (IMPERIAL) . . . . . . . . . . . .

. . 21

Tbl. #

Pg. #

16

BLOWER PERFORMANCE 7-1/2 TON OPTIONAL

 

 

MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . .

. . 22

17

BLOWER PERFORMANCE 10 TON STANDARD

 

 

MOTOR - SIDE DUCT (IMPERIAL) . . . . . . . . . . . . .

. . 22

18

BLOWER PERFORMANCE 10 TON STANDARD

 

 

MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . .

. . 22

19

BLOWER PERFORMANCE 10 TON OPTIONAL

 

 

MOTOR - SIDE DUCT (IMPERIAL) . . . . . . . . . . . .

. . 23

20

BLOWER PERFORMANCE 10 TON OPTIONAL

 

 

MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . .

. . 23

21

BLOWER PERFORMANCE 12-1/2 TON - SIDE

 

 

DUCT (IMPERIAL) . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 24

22

BLOWER PERFORMANCE 12-1/2 TON - SIDE

 

 

DUCT (METRIC) . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 24

23

BLOWER PERFORMANCE 7-1/2 TON STANDARD

 

MOTOR - DOWNSHOT (IMPERIAL) . . . . . . . . . . . .

. . 25

24

BLOWER PERFORMANCE 7-1/2 TON STANDARD

 

MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . .

. . 25

25

BLOWER PERFORMANCE 7-1/2 TON OPTIONAL

 

 

MOTOR - DOWNSHOT (IMPERIAL) . . . . . . . . . . . .

. . 25

26

BLOWER PERFORMANCE 7-1/2 TON OPTIONAL

 

 

MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . .

. . 26

27

BLOWER PERFORMANCE 10 TON STANDARD

 

 

MOTOR - DOWNSHOT (IMPERIAL) . . . . . . . . . . . .

. . 26

28

BLOWER PERFORMANCE 10 TON STANDARD

 

 

MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . .

. . 26

29

BLOWER PERFORMANCE 10 TON OPTIONAL

 

 

MOTOR - DOWNSHOT (IMPERIAL) . . . . . . . . . . . .

. . 27

30

BLOWER PERFORMANCE 10 TON OPTIONAL

 

 

MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . .

. . 27

31

BLOWER PERFORMANCE 12-1/2 TON - DOWNSHOT

 

(IMPERIAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 28

32

BLOWER PERFORMANCE 12-1/2 TON - DOWNSHOT

 

(METRIC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 28

33

ADDITIONAL STATIC RESISTANCE (IMPERIAL) .

. . 29

34ADDITIONAL STATIC RESISTANCE (METRIC) . . . . 30

35ELECTRIC HEAT MINIMUM SUPPLY AIR

- IMPERIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

36 ELECTRIC HEAT MINIMUM SUPPLY AIR

 

- METRIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30

37 INDOOR BLOWER SPECIFICATIONS . . . . . . . . . . . . 31 38 4 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . . 31 39 6 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . . 31 40 UNIT WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

41 UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . .

32

2

Unitary Products

036-21044-003-A-0304

 

™ Control Board w/

 

 

 

Terminal Block

Screw Connector for T-stat

Disconnect Location

Filter Access

Filter-Drier (Solid Core)

for Hi-Voltage

Wiring and Network Connection (Optional Disconnect Switch)

(2” Filters)

 

Connection

 

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

Section

 

Second model

 

 

 

 

 

 

 

 

Slide-out motor

 

nameplate inside

 

 

 

 

 

 

 

 

and blower

 

hinged access

 

 

 

 

 

 

 

 

assembly for

 

panel

 

 

 

 

 

 

 

 

easy adjustment

 

 

 

 

 

 

 

 

 

 

and service

 

Dual stage

 

 

 

 

 

 

 

 

 

 

 

 

cooling for

 

 

 

 

 

 

 

 

Belt-Drive

 

maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor

 

comfort

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Ventor Motor

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

#2 Access

 

 

 

 

 

 

 

 

 

 

 

 

(High-Eff

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

w/ crankcase

 

 

 

 

 

 

 

 

20-gauge aluminized

 

heater)

 

 

 

 

 

 

 

steel tubular heat

 

Base Rails w/ Fork-

 

 

 

 

 

 

 

exchanger for long life

 

 

 

 

 

 

 

 

(stainless steel option)

 

lift Slots (3 Sides) &

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lifting Holes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two-stage gas heat-

 

 

Roof curbs in eightand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slide-Out Drain

 

 

ing to maintain

 

 

fourteen-inch heights.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

warm, comfortable

 

 

 

 

 

 

 

Pan w/ Steel 3/4”

 

 

 

 

Roof curbs for transitioning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

NPT Connection

 

 

 

 

from York Sunline™ foot-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tool-less

 

 

 

 

 

 

 

 

 

 

 

print to the DM Series foot-

 

 

 

 

 

Intelligent control board for

 

door latch

 

Side entry power

Compressor #1 Access (High-Eff

 

print are also available

 

 

and control wiring

safe and efficient operation

 

 

 

Compressor w/ crankcase heater)

 

(field-installed accessory)

 

 

knockouts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 1 - PREDATOR® COMPONENT LOCATION

 

 

 

 

 

 

 

FEATURES

 

 

 

 

 

Service windows have been placed in both condenser

 

 

 

 

 

 

 

section walls. Rotation of the cover allows easy access

Standard Efficiency– All standard efficiency units have

 

to the condenser coils for cleaning or inspection.

 

 

 

 

 

 

 

 

a minimum EER of 9.0 (2.64 CoP).

Gas/electric units

 

Both the unit control board and ignition control board uti-

 

have electronic spark ignition and power vented combus-

 

lize flash codes to aid in diagnosis of unit malfunctions.

 

tion with steady state efficiencies of 80%.

 

Unique alarm codes quickly identify the source of the

Service Friendly – The Predator® incorporates a num-

 

unit alarm.

 

 

 

 

 

 

ber of enhancements which improve serviceability.

 

All units use the same standard filter size.

This stan-

 

The motor and blower slide out of the unit as a common

 

dardization removes any confusion on which filter sizes

 

 

are needed for replacement.

 

 

 

 

 

 

assembly. This facilitates greater access to all the indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

airflow components, thus simplifying maintenance and

 

The non-corrosive drain pan slides out of the unit to per-

 

adjustment.

 

 

 

 

 

mit easy cleaning. The drain pan is accessed by remov-

 

Service time is reduced through the use of hinged, tool-

 

ing the drain pan cover plate on the rear of the unit.

 

 

Once the plate is removed, the

drain pan

slides out

 

less panels. Such panels provide access to frequently

 

 

 

through the rear of the unit.

 

 

 

 

 

 

inspected components and areas, including the control

 

 

 

 

 

 

 

 

All Predator® units have a second model nameplate

 

box, compressors, filters, indoor motor & blower, and the

 

 

heating section. The panels are screwed in place at the

 

located inside the control access door. This is to prevent

 

factory to prevent access by children or other unautho-

 

deterioration of the nameplate through weathering.

 

rized persons. It is recommended that the panels be

Environmentally Aware – For

improved

Indoor Air

 

secured with screws once service is complete.

 

 

Quality, foil faced insulation is used exclusively through-

 

 

 

 

 

 

 

out the units.

Unitary Products

3

Balanced Heating – The Predator® offers “Ultimate Heating Comfort” with a balance between 1st and 2nd stage gas heating. The 1st stage of a gas heat Predator® unit provides 60% of the heating capacity. Balanced heating allows the unit to better maintain desired temperatures.

Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side supply/return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.

System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low-pressure switches. Internal compressor protection is standard on all compressors. Crankcase heaters are standard on reciprocating compressors. Scroll compressors do not require crankcase heaters. Phase Monitors are standard on units with scroll compressors. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.

Advanced Controls - 3FJMIF@FQV™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.

Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0°F (-17.8°C) outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.

Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

036-21044-003-A-0304

Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.

On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

Reliable – From the beginning – All units undergo computer automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit

amperage, and 100% functionality. For the long term – All Predator® units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 750 hour salt spray test.

Flexible Placement – All models and configurations share the same cabinet/footprint and thus the same roof curb. You have the flexibility to set one curb and choose the correct tonnage size and heating option after the internal loads have been determined.

To further simplify planning and installation, Predator® cabinets are designed to fit your roof. With the optional roof curb, the unit ductwork is designed to fit around 24” (610 mm) on-center joists or between 48” (1219 mm) oncenter joists.

The drain pan can be rotated to drain to either the front or the rear of the unit. Additionally, the drain pan can be piped to drain through the roof curb. As it is sometimes difficult to have a level installation, the drain pan features a generous slope to ensure proper drainage.

Full Perimeter Base Rails – The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer forklift access from 3 sides, and rigging holes are available so that an overhead crane can be used to place the units on a roof.

Easy Installation – Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.

All units are shipped with 2” (51 mm) filters installed.

4

Unitary Products

036-21044-003-A-0304

Wide Range of Indoor Airflows – All indoor fan motors are belt-drive type providing maximum flexibility to handle most airflow requirements. For high static applications, factory installed alternate indoor fan motors are available. With the optional indoor fan motor, all units can supply nominal airflow at a minimum of 1.5” (375 Pa) ESP.

FACTORY INSTALLED OPTIONS

YORK® offers several equipment options factory installed, for the Predator® line.

Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The installer needs only to assemble and mount the outdoor air hood (Provided). The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards,

the economizer control accepts an optional CO2 input for demand ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air.

With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.

Horizontal Economizer - (Without barometric relief) - All features as the downflow economizer exist except you must order the barometric relief separately. You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.

BAS Ready Economizer -(With barometric relief) - The economizer is provided with a Belimo actuator that requires a 0-10V DC input from an external source (i.e., field installed building automation system controller).

Power exhaust options are available. The economizer is 2% low leakage type with spring return and fully modulating dampers capable of introducing up to 100% outside air. Also include 2” (51 mm) pleated filters.

Power Exhaust (Downflow only) - This accessory installs in the unit with a down flow economizer.

Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.

Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.

Aluminized Steel Gas Heat Exchanger - For applications in non-corrosive environments.

Stainless Steel Gas Heat Exchanger - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

Electric Heaters - The electric heaters range from 9kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All heaters are intended for single point power supply.

Disconnect Switch - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.

Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. Available for both the supply and/or return air.

Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on units with Scroll Compressors.)

Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.

Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

Technicoat Condenser Coils - The condenser coils are coated with a phenolic coating for protection against corrosion due to harsh environments.

Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against corrosion due to harsh environments.

Novar® BAS Control - The Novar® ETC-3 building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

Unitary Products

5

CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

FIELD INSTALLED ACCESSORIES

YORK® offers several equipment accessories for field installation, for the Predator® line.

Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the econo-

mizer control accepts an optional CO2 input for demand ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible

Horizontal Economizer - (Without barometric relief) - All features as the downflow economizer exist except you must order the barometric relief separately. You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizer.

Dual Enthalpy Control, Accessory - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed slab economizers.

Power Exhaust - This accessory installs in the unit with a down flow economizer. Power exhaust plugs into the connector in the unit bulkhead. You must purchase

1EH0408 barometric relief/power exhaust hood when applying to a horizontal flow application.

Manual Outdoor Air Damper - Like the motorized outdoor air damper, each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.

036-21044-003-A-0304

Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.

Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

CO2 Sensor - Senses CO2 levels and automatically overrides the economizer when levels rise above the preset limits.

Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters.

Coil Guard - Field installed decorative wire coil guard.

Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.

Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

-60°F Gas Heat Kit - For installations which require gas heat units to perform in low ambient temperatures, a gas section heating kit is available. This kit provides electric heat in the gas heat controls section to ensure the gas valve and controls will continue to function properly at extremely low temperatures.

Gas Heat High Altitude Kit - This kit converts a gas heat unit to operate at high altitudes, 2,000 to 6,000 feet. Conversion kits are available for natural gas and propane.

Gas Heat Propane Conversion Kit - This kit converts a gas-fired heater from natural gas to propane. It contains the main burner orifices and gas valve replacement springs.

Gas Piping Kit - Contains pipe nipples, fittings and gas cock required for gas supply connection with external shut off.

Electric Heaters - The electric heaters range from 9 kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. Cooling units include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.

6

Unitary Products

036-21044-003-A-0304

Low Limit / Compressor Lockout Kit

1.Compressor Lockout (CLO): To prevent mechanical (compressorized) operation of the unit during cold outdoor conditions where there is a risk of returning liquid refrigerant back to the compressors.

2.Low Limit Control (LLC): To prevent the supply air from dropping below a specified setpoint by utilizing the units first stage heating means when there is a demand for cooling during cold outside conditions.

Metal Frame Filter Kit - Metal frame with polyester filter medium.

Permanent Filters - Permanent filters are available.

Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available

in 8” (203 mm) and 14” (356 mm) heights. For applications with security concerns, burglar bars are available for the duct openings of the roof curbs.

Roof Curb Transition - Single Piece Adapter (10” (254

mm) High) - Roof curbs for transitioning from Sunline™ units to Predator® Magnum. Fits 7.5 to 12.5 Sunline™ roof curbs only.

Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.

Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only thermostats, depending upon unit configuration.

Unitary Products

7

036-21044-003-A-0304

NOMENCLATURE

7½ - 12½ Ton Predator Model Number Nomenclature

 

 

 

D

M

090

 

N10

A

 

7

A

AA

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Product Generation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Product Category

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = Third Generation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D = Air Cond., Single Package

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

Installation Options

 

Additional Options

 

Product Identifier

 

 

 

 

 

 

 

 

 

 

7 = 380/415-3-50

 

 

 

A = No Options Installed

 

(See Next Page)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M = R-22 Standard Efficiency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B = Option 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C = Option 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D = Options 1 & 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E = Option 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F = Option 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G = Options 1 & 3

 

 

 

 

 

Nominal Cooling Capacity - MBH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H = Options 1 & 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J = Options 1, 2 & 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K = Options 1, 2 & 4

 

 

 

 

 

090 = 7-½ Ton

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L = Options 1, 3 & 4

 

 

 

 

 

120 = 10 Ton

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M = Options 1, 2, 3 & 4

 

 

 

 

 

150 = 12-½ Ton

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N = Options 2 & 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P = Options 2 & 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q = Options 2, 3 & 4

 

 

 

 

 

Heat Type & Nominal Heat Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

R = Options 3 & 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C00 = Cooling Only. Suitable for field installed electric heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Heat Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

N10 = 100 MBH Output Aluminized Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = Disconnect

 

 

 

 

 

N15 = 150 MBH Output Aluminized Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 = Non-Pwr’d Conv Outlet

 

 

 

 

 

S10 = 100 MBH Output Stainless Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = Smoke Detector S. A.

 

 

 

 

 

S15 = 150 MBH Output Stainless Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 = Smoke Detector R. A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric Heat Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E09 = 9 kW Electric Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E18 = 18 kW Electric Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E24 = 24 kW Electric Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E36 = 36 kW Electric Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E54 = 54 kW Electric Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

A = Standard Motor

B = Standard Motor/Economizer/Barometric Relief (Downflow only)

C = Standard Motor/Economizer/Power Exhaust (Downflow only)

D = Standard Motor/Motorized Damper (Downflow only)

E = Standard Motor/Horizontal Economizer (No Barometric Relief)

L = Standard Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)

M = Standard Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)

N = High Static Motor

P = High Static Motor/Economizer/Barometric Relief (Downflow only)

Q = High Static Motor/Economizer/Power Exhaust (Downflow only)

R = High Static Motor/Motorized Damper (Downflow only)

S = High Static Motor/Horizontal Economizer (No Barometric Relief)

Y = High Static Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)

Z = High Static Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)

8

Unitary Products

036-21044-003-A-0304

NOMENCLATURE ADDITIONAL OPTIONS:ì

AA

None

 

 

AB

Phase Monitor

 

 

AC

Coil Guard

 

 

AD

Dirty Filter Switch

 

 

AE

Phase Monitor & Coil Guard

 

 

AF

Phase Monitor & Dirty Filter Switch

 

 

AG

Coil Guard & Dirty Filter Switch

 

 

AH

Phase Monitor, Coil Guard, & Dirty Filter Switch

 

 

CA

CPC Controller with Dirty Filter Switch & Air Proving Switch

 

 

CB

CPC Controller, DFS, APS & Phase Monitor

 

 

CC

CPC Controller, DFS, APS & Coil Guard

 

 

CD

CPC Controller, DFS, APS, Phase Monitor, & Coil Guard

 

 

CE

CPC Controller, DFS, APS & Technicoat Cond. Coil

 

 

CF

CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

 

 

CG

CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

 

 

CH

CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

 

 

CJ

CPC Controller, DFS, APS & Technicoat Evap. Coil

 

 

CK

CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

 

 

CL

CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

 

 

CM

CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

 

 

CN

CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils

 

 

CP

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

 

 

CQ

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

 

 

CR

CPC Controller, DFS, APS, Technicoat Cond Coils, Phase Monitor, & 2” Pleated Filters

 

 

CV

CPC Controller, DFS, APS, & 2” Pleated Filters

 

 

CX

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, Coil Guard

 

 

HA

Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch

 

 

HB

Honeywell Excel 10 Controller, DFS, APS & Phase Monitor

 

 

HC

Honeywell Excel 10 Controller, DFS, APS & Coil Guard

 

 

HD

Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard

 

 

HE

Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil

 

 

HF

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

 

 

HG

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

 

 

HH

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

 

 

HJ

Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil

 

 

HK

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

 

 

HL

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

 

 

HM

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

 

 

HN

Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils

 

 

Unitary Products

9

036-21044-003-A-0304

HP

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

 

 

HQ

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

 

 

HR

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

 

 

JA

Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch

 

 

JB

Johnson UNT Controller, DFS, APS & Phase Monitor

 

 

JC

Johnson UNT Controller, DFS, APS & Coil Guard

 

 

JD

Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard

 

 

JE

Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil

 

 

JF

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

 

 

JG

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

 

 

JH

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

 

 

JJ

Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil

 

 

JK

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

 

 

JL

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

 

 

JM

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

 

 

JN

Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils

 

 

JP

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

 

 

JQ

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

 

 

JR

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

 

 

NA

Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch

 

 

NB

Novar ETC-3 Controller, DFS, APS & Phase Monitor

 

 

NC

Novar ETC-3 Controller, DFS, APS & Coil Guard

 

 

ND

Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard

 

 

NE

Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil

 

 

NF

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

 

 

NG

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

 

 

NH

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

 

 

NJ

Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil

 

 

NK

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

 

 

NL

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

 

 

NM

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

 

 

NN

Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils

 

 

NP

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

 

 

NQ

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

 

 

NR

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

 

 

TA

Technicoat Condenser Coil

 

 

TB

Technicoat Condenser Coil & Phase Monitor

 

 

TC

Technicoat Condenser Coil & Coil Guard

 

 

TD

Technicoat Condenser Coil & Dirty Filter Switch

 

 

TE

Technicoat Condenser Coil, Phase Monitor, & Coil Guard

 

 

TF

Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch

 

 

10

Unitary Products

036-21044-003-A-0304

TG

Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch

 

 

TH

Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch

 

 

TJ

Technicoat Evaporator Coil

 

 

TK

Technicoat Evaporator Coil & Phase Monitor

 

 

TL

Technicoat Evaporator Coil & Coil Guard

 

 

TM

Technicoat Evaporator Coil & Dirty Filter Switch

 

 

TN

Technicoat Evaporator Coil, Phase Monitor, & Coil Guard

 

 

TP

Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch

 

 

TQ

Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch

 

 

TR

Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch

 

 

TS

Technicoat Evaporator & Condenser Coils

 

 

TT

Technicoat Evaporator & Condenser Coils & Phase Monitor

 

 

TU

Technicoat Evaporator & Condenser Coils & Coil Guard

 

 

TV

Technicoat Evaporator & Condenser Coils & Dirty Filter Switch

 

 

TW

Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard

 

 

TX

Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch

 

 

TY

Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch

 

 

TZ

Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch

 

 

RC

Coil Guard, Heavy Mil Clear Shipping Bag, Made in U.S.A. Flag Decal

 

 

Unitary Products

11