York GFA, GHA, GHD, GFD, GNA User Manual

...
5 (1)
York GFA, GHA, GHD, GFD, GNA User Manual

R

Heating Air Conditioning

TECHNICAL GUIDE

ADD - ON COILS

FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS

MODELS: GHD, GFD, GFA, GNA,

GUA & GHA

600 - 2000 CFM 2 - 5 TON COILS

HORIZONTAL

G1HD FULL CASED

MULTI-POSITION

G2FD

UPFLOW UNCASED

G1NA

UPFLOW CASED

G1FA

HORIZONTAL CASED

UPFLOW

G1HA

G1UA

Due to continuous product improvement, specifications are subject to change without notice.

Visit us on the web at www.york.com for the most up-to-date technical information.

Additional rating information can be found at www.ariprimenet.org.

036-21145-003 Rev. A (0403)

DESCRIPTION

These cooling and heat pump coils are designed to be installed with UPG furnaces and to be matched with UPG cooling and heat pump outdoor units. All coils are available as sweat-connect models for your convenience and ease of matching.

Upflow Coils - Available in high-capacity models to match any system and upflow furnace. Models available with factory installed TXV or orifice metering system.

Multi-Position Coils - Available in high-capacity models to match any system and any multi-position furnace and air handler. Models available with factory installed TXV or orifice metering system.

Horizontal Duct Coils - Available to match any cooling or heat pump system and horizontal furnace. Field transition may be required.

Dedicated Horizontal Cased Coils - Available to match most cooling or heat pump systems and any horizontal gas furnace or modular air handler. For horizontal application only. Models available with factory installed TXV or orifice metering system.

FEATURES

Insulated Cabinet - All evaporator coil cabinets are thermally insulated to prevent sweating.

Internally Clean - All evaporator coils are factory leaktested, dehydrated, sealed and shipped with a holding charge.

Durable Finish - Coil casings are made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep.

Optimum Heat Transfer - Using the latest in heat transfer technology, staggered rows of rifled copper tubes are mechanically expanded into aluminum fins to provide optimum air to surface contact for ample moisture removal as well as high performance ratings.

Optional Factory Installed Thermal Expansion Valve -

Provides flexibility to match high efficiency applications at a lower installed cost.

Yorkmate Refrigerant Control - Provides optimum system performance and the flexibility to match coils with any efficiency level cooling or heat pump system.

ACCESSORIES

Refer to Price Manual for specific model numbers.

TXV Kits - Thermal expansion valve kits are available for indoor coils to obtain specific system performance.

Horizontal Drain Pan Kits - A field installed horizontal drain pan kit (1HP0623BK or 1HP0628BK) is available for horizontal applications on the multi-position coil. The full cased multiposition coil is also available with a factory installed horizontal drain pan option.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21145-003 Rev. A (0403)

COOLING CAPACITY - Coil Only*

 

RATED

ENTERING

MBH @ EVAPORATOR TEMPERATURE AND CORRESPONDING

MODEL

AIR ° F

 

 

PRESSURE °F / PSIG

 

 

CFM

(WET BULB)

 

 

 

 

 

 

35 / 61.5

 

40 / 68.5

45 / 76.0

50 / 84.0

 

 

 

 

 

 

UPFLOW "A" TYPE

 

 

 

 

 

 

72

35.6

 

32.5

29.0

25.2

G1FA024S14(T)

675

67

32.9

 

29.7

26.3

22.7

G1UA024S14

 

 

 

 

 

 

62

27.0

 

23.9

20.7

17.4

 

 

 

 

57

21.9

 

19.0

15.9

12.4

 

 

72

35.6

 

32.5

29.0

25.2

G1FA024S17(T)

850

67

32.9

 

29.7

26.3

22.7

G1UA024S17

 

 

 

 

 

 

62

27.0

 

23.9

20.7

17.4

 

 

 

 

57

21.9

 

19.0

15.9

12.4

 

 

72

38.9

 

35.4

31.6

27.6

G1FA030S14(T)

1025

67

33.9

 

30.3

26.8

23.0

G1UA030S14

 

 

 

 

 

 

62

27.3

 

23.7

22.5

18.0

 

 

 

 

57

22.6

 

20.1

17.5

14.8

G1FA036S14(T)

 

72

51.1

 

46.5

41.5

36.6

G1FA036S17(T)

1250

67

40.9

 

36.1

31.7

26.9

G1UA036S14

 

 

 

 

 

 

62

32.0

 

26.8

29.3

21.8

 

 

G1UA036S17

 

 

 

 

 

 

 

 

57

27.4

 

25.4

23.4

21.8

 

 

72

51.1

 

46.5

41.5

36.6

G1FA036S21(T)

1250

67

40.9

 

36.1

31.7

26.9

G1UA036S21

 

 

 

 

 

 

62

32.0

 

26.8

29.3

21.8

 

 

 

 

57

27.4

 

25.4

23.4

21.8

G1FA048S17(T)

 

72

99.4

 

85.5

71.2

56.2

G1FA048S21(T)

1620

67

79.6

 

66.8

54.4

41.6

G1UA048S17

 

 

 

 

 

 

62

62.1

 

49.4

40.2

33.7

 

 

G1FUA048S21

 

 

 

 

 

 

 

 

57

53.3

 

46.7

40.2

33.7

G1FA060S21(T)

 

72

118.7

 

100.0

81.1

61.5

G1FA060S24(T)

1850

67

95.0

 

78.4

61.9

45.4

G1UA060S21

 

 

 

 

 

 

62

74.0

 

58.0

45.7

36.7

 

 

G1UA060S24

 

 

 

 

 

 

 

 

57

63.6

 

54.8

45.7

36.7

* - See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

 

 

(T) indicates models with factory installed thermal expansion valve.

 

 

 

Coil Only*

 

RATED

ENTERING

MBH @ EVAPORATOR TEMPERATURE AND CORRESPONDING PRESSURE

MODEL

AIR ° F

 

 

 

°F/ PSIG

 

 

CFM

(WET BULB)

 

 

 

 

 

 

 

35 / 61.5

 

40 / 68.5

 

45 / 76.0

50 / 84.0

 

 

 

 

 

 

HORIZONTAL DUCT TYPE

 

 

 

 

 

 

72

35.3

 

32.4

 

28.7

24.9

G1HD024

815

67

32.6

 

29.4

 

26.0

22.5

62

26.7

 

23.7

 

20.5

17.2

 

 

 

 

 

 

57

21.7

 

18.8

 

15.7

12.3

 

 

72

57.9

 

52.7

 

47.1

41.5

G1HD036

1192

67

46.4

 

41.1

 

35.9

30.4

62

36.2

 

30.4

 

26.5

24.7

 

 

 

 

 

 

57

31.1

 

28.7

 

26.5

24.7

 

 

72

83.4

 

71.7

 

59.7

47.1

G1HD048

1610

67

66.8

 

56.1

 

45.6

34.9

62

52.1

 

41.5

 

33.7

28.3

 

 

 

 

 

 

57

44.7

 

39.2

 

33.7

28.3

 

 

72

133.0

 

112.4

 

90.9

69.2

G1HD060

2100

67

106.5

 

87.9

 

69.4

50.0

62

83.0

 

65.0

 

51.3

41.1

 

 

 

 

 

 

57

71.2

 

61.4

 

51.3

41.1

*See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

2

Unitary Products Group

036-21145-003 Rev. A (0403)

COOLING CAPACITY - COIL ONLY*

Model Coil

Rated CFM

Entering Air °F

MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG

(Wet Bulb)

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

 

 

 

 

FULL-CASED “A” TYPE MULTI-POSITION

 

 

G2FD024(S,H)14(T)

 

72

36.3

33.0

29.5

25.6

850

67

33.4

30.2

26.7

23.1

G2FD024(S,H)17(T)

62

27.4

24.3

21.0

17.7

 

 

 

57

22.2

19.3

16.2

12.6

G2FD030(S,H)17(T)

 

72

41.5

37.8

33.7

29.5

1025

67

36.2

32.4

28.6

24.5

G2FD035(S,H)14(T)

62

29.1

25.3

24.0

19.2

 

 

 

57

24.1

21.5

18.7

15.8

 

 

72

52.0

47.3

42.3

37.3

G2FD036(S,H)17(T)

1250

67

41.7

36.8

32.3

27.4

62

32.5

27.3

29.8

22.2

 

 

 

 

57

27.9

25.8

23.8

22.2

 

 

72

53.4

48.6

43.4

38.3

G2FD036(S,H)21(T)

1200

67

42.8

37.8

33.1

28.2

62

33.4

28.1

30.6

22.8

 

 

 

 

57

28.7

26.5

24.5

22.8

G2FD046(S,H)17(T)

 

72

88.4

76.0

63.3

50.0

1400

67

70.8

59.4

48.4

37.0

G2FD042(S,H)21(T)

62

55.2

43.9

35.8

29.9

 

 

 

57

47.4

41.5

35.8

29.9

G2FD048(S,H)21(T)

 

72

100.5

86.4

72.0

56.8

1650

67

80.4

67.5

55.0

42.1

G2FD048(S,H)24(T)

62

62.7

49.9

40.7

34.0

 

 

 

57

53.9

47.2

40.7

34.0

 

 

72

119.9

101.0

80.0

62.2

G2FD060(S,H)24(T)

1825

67

96.0

79.2

62.6

45.8

62

74.8

58.6

46.2

37.0

 

 

 

 

57

64.3

55.4

46.2

37.0

 

 

72

124.8

105.2

85.3

64.7

G2FD061(S,H)24(T)

2000

67

99.9

82.5

65.2

47.7

62

77.9

61.1

48.1

38.6

 

 

 

 

57

66.9

57.7

48.1

38.6

*See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

(T) indicates models with factory installed thermal expansion valve. Only available on coils with factory installed horizontal drain pan (H).

Notes:

G2FD coils available with a factory installed horizontal drain pan option (H).

G2FD061H24 is only available with a factory mounted horizontal pan.

COOLING CAPACITY - COIL ONLY*

 

RATED

ENTERING AIR

 

MBH @ EVAPORATOR TEMPERATURE AND

 

MODEL

°F

 

 

CORRESPONDING PRESSURE °F / PSIG

 

CFM

 

 

 

 

(WET BULB)

 

 

 

 

 

 

 

35/61.5

 

40/68.5

45/76.0

 

50/84.0

 

 

 

 

 

 

72

35.2

 

32.0

28.6

 

24.8

G1HA024H14(T)

800

67

32.4

 

29.3

25.9

 

22.4

62

26.6

 

23.6

20.4

 

17.2

 

 

 

 

 

 

57

21.5

 

18.7

15.7

 

12.2

 

 

72

49.1

 

44.7

39.9

 

35.2

G1HA036H14(T)

1150

67

39.4

 

34.8

30.5

 

25.9

62

30.7

 

25.9

28.2

 

22.8

 

 

 

 

 

 

57

26.4

 

24.4

22.5

 

21.0

 

 

72

73.4

 

63.1

52.5

 

41.5

G1HA036H17(T)

1200

67

58.8

 

49.3

40.2

 

30.7

62

45.8

 

36.4

29.7

 

24.8

 

 

 

 

 

 

57

39.3

 

34.4

28.1

 

23.2

 

 

72

94.4

 

81.2

67.6

 

53.4

G1HA048H21(T)

1550

67

75.6

 

65.4

51.7

 

39.5

62

59.0

 

46.9

38.2

 

32.0

 

 

 

 

 

 

57

50.6

 

44.4

35.6

 

29.7

 

 

72

112.8

 

95.0

77.0

 

58.4

G1HA060H24(T)

1800

67

90.3

 

74.5

58.8

 

43.1

62

70.3

 

55.1

43.4

 

34.9

 

 

 

 

 

 

57

60.4

 

52.1

40.4

 

31.9

* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

(T) indicates models with factory installed thermal expansion valve.

Unitary Products Group

3

036-21145-003 Rev. A (0403)

COOLING CAPACITY - COIL ONLY*

MODEL COIL

RATED CFM

ENTERING AIR °F (WET BULB)

MBH@ EVAPORATOR TEMPERATURE AND CORRESPONDING PRESSURE °F / PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

 

 

 

 

 

 

UNCASED UPFLOW

 

 

 

 

 

72

27.4

25.0

22.3

19.4

G1NA024S17G

800

67

25.3

22.9

20.3

17.5

62

20.8

18.4

15.9

13.4

 

 

 

 

57

16.9

14.6

12.2

9.4

 

 

72

35.2

32.0

28.6

24.8

G1NA030S17H

1000

67

32.4

28.6

25.3

21.9

62

26.6

23.6

21.5

18.7

 

 

 

 

57

25.2

22.7

20.2

17.6

 

 

72

39.6

36.0

32.1

27.9

G1NA030S17K

1000

67

36.4

33.2

29.5

25.7

62

29.9

27.2

24.2

21.0

 

 

 

 

57

28.1

25.6

22.7

19.8

 

 

72

49.3

44.9

39.9

34.7

G1NA036S17J

1200

67

45.4

41.3

36.7

32.0

62

37.2

33.8

30.1

26.2

 

 

 

 

57

35.0

28.3

28.3

24.6

 

 

72

59.9

54.5

48.5

42.6

G1NA036S17L

1200

67

55.1

51.1

44.6

38.9

62

45.2

41.1

36.6

31.9

 

 

 

 

57

42.5

38.7

34.4

30.0

 

 

72

49.3

44.9

39.9

34.7

G1NA036S21C

1200

67

45.4

41.3

36.7

32.0

62

37.2

33.8

30.1

26.2

 

 

 

 

57

35.0

31.8

28.3

24.6

 

 

72

86.7

73.0

59.2

44.9

G1NA042S24W

1400

67

69.4

57.2

45.2

33.1

62

54.0

42.3

33.4

26.8

 

 

 

 

57

46.4

40.0

33.4

26.8

 

 

72

62.4

56.8

50.5

44.4

G1NA048S21D

1400

67

57.4

53.2

46.5

40.5

62

47.1

42.8

38.1

33.2

 

 

 

 

57

44.3

40.3

35.8

31.2

 

 

72

95.4

82.1

68.4

54.0

G1NA060S24T

1800

67

76.4

64.1

52.2

39.9

62

59.6

47.4

38.6

32.4

 

 

 

 

57

51.2

44.8

38.6

32.4

*See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

APPLICATION FACTOR-RATED

CFM VS. ACTUAL CFM

% OF RATED AIR FLOW

80%

90%

RATED CFM

110%

120%

 

 

 

 

 

 

CAPACITY FACTOR

0.96

0.98

1.00

1.02

1.03

 

 

 

 

 

 

NOTE: Do not exceed minimum/maximum CFM limits shown under Air Flow Data.

APPLICATION LIMITATIONS

These units must be installed in accordance with all national and local safety codes.

Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.

ENTERING AIR TEMPERATURE LIMITS

WET BULB TEMP. ºF

DRY BULB TEMP. ºF

Min.

Max.

Min.

Max.

57

72

65

95

4