York E'BD-F018, W036, E'BD-T, E'BD-F060, W060 User Manual

0 (0)

TECHNICAL

GUIDE

SPLIT-SYSTEM HEAT PUMPS

13 SEER – R-22

MODELS: E*BD-F018 THRU 060

(1.5 THRU 5 NOMINAL TONS, 1 PHASE)

E*BD-(T,W)036 THRU 060

(2.5 THRU 5 NOMINAL TONS, 3 PHASE)

ISO 9001

Certified Quality

Management System

LISTED

Due to continuous product improvement, specifications are subject to change without notice.

Visit us on the web at www.york.com

Additional rating information can be found at www.ahridirectory.org

246819-BTG-H-0208

DESCRIPTION

The 13 SEER series heat pumps are designed for use with a variety of UPG evaporator sections to suit any application need. A full line of matching Add-On Coils are available for use with upflow, downflow or horizontal furnaces. Matching Air Handlers are also available for upflow, downflow or horizontal installation to provide a complete system. Electric heat may be installed in air handlers. All units are factory charged to assure easy installation.

WARRANTY

Single Phase Units:

5-year limited parts warranty.

5-year limited compressor warranty.

Three Phase Units:

1-year limited parts warranty.

5-year limited compressor warranty.

FEATURES

DURABLE CONSTRUCTION - The outdoor unit is constructed of pre-painted steel that offers tough protection against corrosion and resists fading when exposed to sunlight. Drain holes are incorporated into the base pan to permit free drainage of moisture.

QUALITY COILS - The coil is constructed of enhanced copper tube and aluminum fins.

COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.

PROTECTED COMPRESSOR - The hermetic compressor is internally protected against high pressure and temperature by the simultaneous operation of a high pressure relief valve and temperature sensors which stop the compressor if operating temperatures go too high. Both protectors reset automatically. A discharge line solid core filter drier further protects the compressor.

Complete System Control – These heat pumps utilize the unique microprocessor defrost control system to provide optimal comfort and to monitor the overall system for reliable operation. The defrost control system continuously monitors the space environment to maintain optimum efficiency. It initiates defrost only when necessary to further reduce heating costs and improve reliability. In the event improper operating conditions occur, the control will automatically shut the system down to extend the life of the heat pump. Rapid cycling is prevented by use of an internal anti-recycle timer.

LOW OPERATING SOUND LEVEL - The compressor is mounted on rubber isolators to reduce operating sounds. The slow moving condenser fan keeps air turbulence and sound to a low level.

EASY ACCESS - Removable panel affords accessibility to the electrical box.

FULLY CHARGED AND FACTORY WIRED - to simply installation and reduce labor costs. Only power supply and control wiring and refrigerant lines must be connected. All models are sweat connect with reusable service valves.

Factory tested - to verify system operation and control functioning before shipment.

U.L. and C.U.L. listed - approved for outdoor application.

Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

York E'BD-F018, W036, E'BD-T, E'BD-F060, W060 User Manual

246819-BTG-H-0208

Physical and Electrical Data - 1 Phase

MODEL

 

EABD-F018S

EABD-F024S

EABD-F030S

EABD-F036S

EABD-F042S

EABD-F048S

EABD-F060S

Unit Supply Voltage

 

 

208-230V, 1φ, 60Hz

 

 

 

 

 

 

 

 

 

 

Normal Voltage Range 1

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

9.9

15.0

16.9

19.8

25.0

32.7

37.8

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

15

25

25

30

40

50

60

Min. Overcurrent Device Amps 3

15

20

20

20

30

35

40

Compressor Type 4

Recip

Recip

Recip

Recip

Recip

ScrollD

ScrollD

Compressor

Rated Load

7.5

10.7

12.4

14.6

18.8

25.0

29.1

Amps

Locked Rotor

41

44

60

78

78

115

150

 

 

 

 

 

 

 

 

 

Crankcase Heater

Yes

Yes

Yes

Yes

Yes

No

No

 

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

0.5

1.5

1.5

1.5

1.5

1.5

1.5

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

22

22

22

22

22

24

24

 

 

 

 

 

 

 

 

 

 

Rated HP

1/15

1/4

1/4

1/4

1/4

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

 

Nominal RPM

850

850

850

850

850

850

850

 

 

 

 

 

 

 

 

 

 

Nominal CFM

2,000

3,250

3,450

3,500

3,500

3,400

3,500

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

15.72

18.34

20.96

23.58

23.58

24.00

27.00

Coil

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

1

1

2

2

 

 

 

 

 

 

 

 

 

 

Fin / Inches

22

22

22

22

22

18

18

 

 

 

 

 

 

 

 

 

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

 

 

 

 

 

 

 

 

Vapor Line Set OD (Field Installed)

3/4

3/4

7/8

7/8

7/8

7/8

1-1/8

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 5

7 - 1

6 - 6

8 - 7

8 - 7

8 - 7

12 - 8

16 - 7

Charge Per Foot, Oz.

0.68

0.68

0.70

0.70

0.70

0.70

0.76

 

 

 

 

 

 

 

 

Operating Weight Lbs.

172

184

196

208

208

250

294

 

 

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.

5.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

 

All dimensions are in inches. They are subject to change

 

without notice. Certified dimensions will be provided upon

 

request.

 

 

 

 

 

 

C

 

Dimensions

 

Refrigerant

 

Unit

 

 

Connection

 

 

(Inches)

 

 

Model

 

 

 

Service Valve Size

 

 

A1

B

C

Liquid

Vapor

 

018

27

37

27

 

3/4”

 

024

31

37

27

 

A

 

 

030

35

37

27

 

 

 

 

 

 

036

39

37

27

3/8”

7/8”

 

042

39

37

27

 

 

 

 

 

048

34

43

32

 

 

 

060

38

43

32

 

7/8”*

B

1. Including Fan Guard.

 

 

 

* Adapter fitting required for 1-1/8” line set.

 

2

Unitary Products Group

246819-BTG-H-0208

Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase

Outdoor Unit

EABD-F018S

EABD-F024S

EABD-F030S

EABD-F036S

EABD-F042S

EABD-F048S

EABD-F060S

Required TXV

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2C1

1TVM2C1

1TVM2C1

Factory Charge, lbs-oz

7 - 1

6 - 9

8 - 9

8 - 7

8 - 7

12 - 8

16 - 7

 

 

 

 

 

 

 

 

Indoor Coil1,2

 

 

Additional Charge, Oz

 

 

FC/MC/PC/UC18A2A

0

FC/MC/PC/UC18B2A

0

FC/MC/PC/UC24A2A

0

FC/MC/PC/UC24B2A

0

FC/MC/PC/UC30A2A

0

FC/MC/PC/UC30B2A

0

FC/MC/PC35B2A

0

9

FC/MC/PC35C2C

0

9

FC/MC/PC/UC42B2C

0

9

FC/MC/PC/UC42C2C

0

9

FC/MC/PC/UC48C2C

9

14

FC/MC/PC/UC48D2C

9

14

FC/PC/UC60C2C

7

7

FC/MC/PC/UC60D2C

7

7

MC61D2C

7

7

HC18A2A

0

HC30A2A

0

HC36B2A

0

HC42C2C

9

HC60C2C

7

7

HD24A2A

0

HD36B2A

0

9

HD48C2C

14

HD60D2C

7

7

AHP18B2A

0

AHP24B2A

0

AHP30B2A

0

AHP36C2A

9

AHP42C2C

9

AHP/SHP48D2C

14

7

AHP/SHP60D2C

7

7

AV24B2A

0

0

AV36C2A

0

9

AV/SV48D2C

14

7

AV/SV60D2C

7

FC/MC/PC/UC18A3X

0

FC/MC/PC/UC18B3X

0

FC/MC/PC/UC24A3X

0

FC/MC/PC/UC24B3X

0

FC/MC/PC/UC30A3X

0

FC/MC/PC/UC30B3X

0

FC/MC/PC35B3X

0

9

FC/MC/PC35X3X

0

9

FC/MC/PC/UC42B3X

0

9

FC/MC/PC/UC42X3X

0

9

FC/MC/PC/UC48C3X

9

14

FC/MC/PC/UC48D3X

9

14

FC/PC/UC60C3X

7

7

FC/MC/PC/UC60D3X

7

7

MC61D3X

7

7

HC18A3X

0

HC30A3X

0

HC36B3X

0

HC42C3X

9

HC60C3X

7

7

For Notes See Page 4.

 

 

 

 

 

 

 

Unitary Products Group

3

246819-BTG-H-0208

Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)

Outdoor Unit

EABD-F018S

EABD-F024S

EABD-F030S

EABD-F036S

EABD-F042S

EABD-F048S

EABD-F060S

Required TXV

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2C1

1TVM2C1

1TVM2C1

Factory Charge, lbs-oz

7 - 1

6 - 9

8 - 9

8 - 7

8 - 7

12 - 8

16 - 7

 

 

 

 

 

 

 

 

Indoor Coil1,2

 

 

Additional Charge, Oz

 

 

HD24A3X

0

HD36B3X

0

9

HD48C3X

14

HD60D3X

7

7

AHP18B3X

0

AHP24B3X

0

AHP30B3X

0

AHP36C3X

9

AHP42C3X

9

AHP/SHP48D3X

14

7

AHP/SHP60D3X

7

7

AV24B3X

0

0

AV36C3X

0

9

AV/SV48D3X

14

7

AV/SV60D3X

14

7

7

F*FP024H06T2A

0

F*FP030H06T2A

0

F*FP040H06T2A

0

9

F*FP042H06T2A

9

F*FV060H06T2C

7

7

FOOTNOTES:

 

 

 

 

 

 

 

1.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

2.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

*This loose coil match does not achieve 13 SEER.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.

2.Verify the orifice size and the additional charge required for the specific evaporator coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base charge (as shipped) + adder for evaporator + adder for line set.

5.If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice/TXV size.

4

Unitary Products Group

246819-BTG-H-0208

Physical and Electrical Data - 3 Phase

MODEL

 

EABD-

EABD-

EABD-

 

EABD-

EABD-

EABD-

EABD-

EABD-

 

EABD-

EABD-

 

T030S

T036S

T042S

 

T048S

T060S

W030S

W036S

W042S

 

W048S

W060S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Supply Voltage

 

 

208-

230V, 3φ,

60Hz

 

 

460V, 3φ, 60Hz

 

Normal Voltage Range 1

 

 

187 to 252

 

 

 

 

432 to 532

 

 

Minimum Circuit Ampacity

12.1

14.3

14.4

 

20.2

23.1

5.6

6.9

7.2

 

9.5

11.2

Max. Overcurrent Device Amps 2

20

20

20

 

35

40

15

15

15

 

15

15

Min. Overcurrent Device Amps 3

15

15

15

 

25

25

15

15

15

 

15

15

Compressor Type

 

Recip

Recip

Recip

 

Scroll

Scroll

Recip

Recip

Recip

 

Scroll

Scroll

Compressor Amps

 

Rated Load

8.5

10.2

10.4

 

15.0

16

3.9

4.9

6.1

 

6.1

8

 

Locked Rotor

62

72

71

 

95

123

30

45

45

 

45

70

 

 

 

 

Crankcase Heater

 

 

Yes

Yes

Yes

 

No

No

Yes

Yes

Yes

 

No

No

Fan Motor Amps

 

Rated Load

1.5

1.5

1.5

 

1.5

1.5

0.7

0.7

0.7

 

0.7

0.7

Fan Diameter Inches

 

 

22

22

22

 

24

24

22

22

22

 

24

24

 

 

Rated HP

1/4

1/4

1/4

 

1/4

1/4

1/4

1/4

1/4

 

1/4

1/4

Fan Motor

 

Nominal RPM

850

850

850

 

850

850

850

850

850

 

850

850

 

 

Nominal CFM

3450

3500

3500

 

3400

3500

3450

3500

3500

 

3400

3500

 

 

Face Area Sq. Ft.

20.96

23.58

23.58

 

24.00

27.00

20.96

23.58

23.58

 

24.00

27.00

Coil

 

Rows Deep

1

1

1

 

2

2

1

1

1

 

2

2

 

 

Fin / Inches

22

22

22

 

18

18

22

22

22

 

18

18

Liquid Line Set OD

(Field Installed)

3/8

3/8

3/8

 

3/8

3/8

3/8

3/8

3/8

 

3/8

3/8

Vapor Line Set OD (Field Installed)

7/8

7/8

7/8

 

7/8

1-1/8

7/8

7/8

7/8

 

7/8

1-1/8

Unit Charge (Lbs. - Oz.) 4

8 - 7

8 - 7

8 - 7

 

12 - 8

16 - 7

8 - 7

8 - 7

8 - 7

 

12 - 8

16 - 7

Charge Per Foot, Oz.

0.70

0.70

0.70

 

0.70

0.76

0.70

0.70

0.70

 

0.70

0.78

Operating Weight Lbs.

196

208

208

 

250

294

196

208

208

 

250

294

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. If line exceeds 25 feet, you may refer to publications software 036-68001-001 for proper line sizing.

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

 

DIMENSIONS

 

 

 

 

C

Dimensions

Refrigerant Connection

 

Unit

 

 

(Inches)

 

Service Valve Size

 

Model

A1

B

C

Liquid

Vapor

 

 

 

030

35

37

27

 

 

A

036

39

37

27

 

7/8”

042

39

37

27

3/8”

 

 

 

048

34

43

32

 

 

 

060

38

43

32

 

7/8”*

 

1.

Including Fan Guard.

 

 

 

* Adapter fitting required for 1-1/8” line set.

 

B

Unitary Products Group

5

246819-BTG-H-0208

Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase

Outdoor Unit

EABD-(T,W)030S

EABD-(T,W)036S

 

EABD-(T,W)042S

 

EABD-(T,W)048S

EABD-(T,W)060S

Required TXV

1TVM2A1

1TVM2A1

 

1TVM2C1

 

1TVM2C1

1TVM2C1

Factory Charge, lbs-oz

8 - 9

8 - 7

 

8 - 7

 

12 - 8

16 - 9

 

 

 

 

 

 

 

 

Indoor Coil1

 

 

Additional Charge, Oz

 

 

FC/MC/PC/UC35B2C

0

9

 

 

FC/MC/PC/UC35C2C

0

9

 

 

FC/MC/PC/UC42B2C

0

9

 

 

FC/MC/PC/UC42C2C

0

9

 

 

FC/MC/PC/UC48C2C

9

 

14

 

FC/MC/PC/UC48D2C

9

 

14

 

FC/PC/UC60C2C

 

 

7

5

FC/MC/PC/UC60D2C

 

 

7

5

MC61D2C

 

 

7

5

HC36B2A

0

 

 

HC42C2C

9

 

 

HC60C2C

 

 

7

5

HD36B2A

0

9

 

 

HD48C2C

 

14

 

HD60D2C

 

 

7

5

AHP30B2A

0

 

 

AHP36C2A

9

 

 

AHP42C2C

9

 

 

AHP/SHP48D2C

 

14

 

7

AHP/SHP60D2C

 

 

7

5

FC/MC/PC/UC42B3X

0

9

 

 

FC/MC/PC/UC42X3X

0

9

 

 

FC/MC/PC/UC48C3X

9

 

14

 

FC/MC/PC/UC48D3X

9

 

14

 

FC/PC/UC60C3X

 

 

7

5

FC/MC/PC/UC60D3X

 

 

7

5

MC61D3X

 

 

7

5

HC36B3X

0

 

 

HC42C3X

9

 

 

HC60C3X

 

 

7

5

HD36B3X

0

9

 

 

HD48C3X

 

14

 

HD60D3X

 

 

7

5

AHP30B3X

0

 

 

AHP36C3X

9

 

 

AHP42C3X

9

 

 

AHP/SHP48D3X

 

14

 

7

AHP/SHP60D3X

 

 

7

5

F*FP040H06T2A

0

9

 

 

F*FP042H06T2A

9

 

 

FOOTNOTES:

 

 

 

 

 

 

 

1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-con- necting line tubing.

2.Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.

6

Unitary Products Group

246819-BTG-H-0208

COOLING CAPACITY - With Air Handler Coils

UNIT

AIR HANDLER

 

 

 

 

COOLING

 

 

 

 

 

COIL MODEL1

 

 

 

 

 

 

 

 

RATED

NET MBH

 

 

MODEL

MODEL

W

 

SEER

EER

 

 

CFM

TOTAL

SENS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

& 3 PH 13 SEER HP

WITH MA

 

 

 

 

EABD-F018S

MA08B

17

 

FC/MC18B

600

18.0

12.4

13.00

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F024S

MA08B

17

 

FC/MC24B

800

23.2

16.8

13.00

11.00

 

 

 

 

 

 

 

 

 

MA08B

17

 

FC/MC30B

800

23.2

16.8

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-F030S

MA12B

17

 

FC/MC35B

1000

28.4

20.3

13.00

11.00

 

 

 

 

 

 

 

 

 

MA12B

17

 

FC/MC42B

1000

28.4

20.3

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-(T,W)030S

MA12B

17

 

FC/MC35B

1000

28.0

20.0

13.00

11.00

 

 

 

 

 

 

 

 

 

MA12B

17

 

FC/MC42B

1000

28.0

20.0

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

MA12B

17

 

FC/MC35B

1200

34.6

25.3

13.00

11.00

EABD-F036S

 

 

 

 

 

 

 

 

 

MA12B

17

 

FC/MC42B

1200

34.6

25.3

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

MA14D

24

 

FC/MC48D

1200

35.0

25.6

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

MA12B

17

 

FC/MC35B

1200

34.0

24.8

13.00

11.00

EABD-(T,W)036S

 

 

 

 

 

 

 

 

 

MA12B

17

 

FC/MC42B

1200

34.0

24.8

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

MA14D

24

 

FC/MC48D

1200

34.4

25.1

13.00

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F042S

MA16C

21

 

FC/MC48C

1400

41.0

30.8

13.00

11.00

 

 

 

 

 

 

 

 

 

MA14D

24

 

FC/MC48D

1400

41.0

30.8

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-(T,W)042S

MA16C

21

 

FC/MC48C

1400

40.0

30.0

13.00

11.00

 

 

 

 

 

 

 

 

 

MA14D

24

 

FC/MC48D

1400

40.0

30.0

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

MA16C

21

 

FC60C

1600

46.0

35.4

13.00

11.00

EABD-F048S

 

 

 

 

 

 

 

 

 

MA20D

21

 

FC/MC60D

1600

46.0

35.4

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

MA20D

24

 

MC61D

1600

46.0

35.5

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

MA16C

21

 

FC60C

1600

45.0

34.6

13.00

11.00

EABD-(T,W)048S

 

 

 

 

 

 

 

 

 

MA20D

21

 

FC/MC60D

1600

45.0

34.6

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

MA20D

24

 

MC61D

1600

45.0

34.7

13.00

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F060S

MA20D

24

 

FC/MC60D

1800

55.0

40.7

13.00

11.00

 

 

 

 

 

 

 

 

 

MA20D

24

 

MC61D

1800

55.5

41.0

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-(T,W)060S

MA20D

24

 

FC/MC60D

1800

54.5

40.3

13.00

11.00

 

 

 

 

 

 

 

 

 

MA20D

24

 

MC61D

1800

55.0

40.6

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

1 PH 13 SEER HP WITH MV - VARIABLE SPEED

 

 

 

EABD-F018S

MV12B

17

 

FC/MC18B

600

18.0

12.6

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F024S

MV12B

17

 

FC/MC24B

800

23.6

16.7

14.00

12.00

 

 

 

 

 

 

 

 

 

MV12B

17

 

FC/MC30B

800

23.6

16.7

14.00

12.00

 

 

 

 

 

 

 

 

 

 

 

 

 

MV12B

17

 

FC/MC35B

1000

29.0

20.1

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F030S

MV16C

21

 

FC/MC35C

1000

29.0

20.1

14.00

12.00

 

 

 

 

 

 

 

 

 

MV12B

17

 

FC/MC42B

1000

29.0

20.1

14.00

12.00

 

 

 

 

 

 

 

 

 

 

 

 

 

MV16C

21

 

FC/MC42C

1000

29.0

20.1

14.00

12.00

 

 

 

 

 

 

 

 

 

 

 

MV12B

21

 

FC/MC35C

1200

35.2

25.0

13.50

11.00

 

 

 

 

 

 

 

 

 

 

 

MV16C

21

 

FC/MC35C

1200

35.2

25.0

14.00

12.00

EABD-F036S

 

 

 

 

 

 

 

 

 

MV16C

21

 

FC/MC42C

1200

35.4

25.2

14.00

12.00

 

 

 

 

 

 

 

 

 

 

 

MV16C

21

 

FC/MC48C

1200

35.4

25.2

14.00

12.00

 

 

 

 

 

 

 

 

 

 

 

MV20D

24

 

FC/MC48D

1200

35.4

25.2

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F042S

MV16C

21

 

FC/MC48C

1400

41.0

30.3

13.75

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F048S

MV20D

24

 

FC/MC60D

1600

46.0

34.6

13.50

11.00

 

 

 

 

 

 

 

 

 

MV20D

24

 

MC61D

1600

46.5

34.8

13.75

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-F060S

MV20D

24

 

FC/MC60D

1800

54.0

39.7

13.25

11.00

 

 

 

 

 

 

 

 

 

MV20D

24

 

MC61D

1800

55.0

39.9

13.25

11.00

 

 

 

 

 

 

 

 

 

 

 

 

For Notes See Page 8

Unitary Products Group

7

246819-BTG-H-0208

COOLING CAPACITY - With Air Handler Coils (Continued)

UNIT

AIR HANDLER

 

 

 

COOLING

 

 

 

 

 

COIL MODEL1

 

 

 

 

 

 

 

 

RATED

NET MBH

 

 

MODEL

MODEL

 

W

SEER

EER

 

 

CFM

TOTAL

SENS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 PH 13 SEER AC WITH AV / SV - VARIABLE SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

EABD-F018S

AV24

 

17

600

18.0

12.6

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F024S

AV24

 

17

800

23.8

16.7

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F030S

AV36

 

17

1000

29.2

20.1

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F036S

AV36

 

21

1200

35.0

25.2

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F042S

AV/SV48

 

21

1400

41.5

30.3

14.00

12.00

 

 

 

 

 

 

 

 

 

 

EABD-F048S

AV/SV48

 

24

1600

46.5

34.8

13.75

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F060S

AV/SV60

 

24

1800

55.0

39.9

13.25

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

1 & 3 PH

13 SEER HP WITH AHP / F*FP / F*FV

 

 

 

EABD-F018S

F*FP024

 

17

600

18.0

11.4

13.00

11.00

 

 

 

 

 

 

 

 

 

AHP18

 

17

600

18.0

11.4

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-F024S

F*FP030

 

17

800

23.2

16.4

13.00

11.00

 

 

 

 

 

 

 

 

 

AHP24

 

17

800

23.0

16.4

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-F030S

F*FP040

 

21

1000

28.0

19.5

13.00

11.00

 

 

 

 

 

 

 

 

 

AHP30

 

17

1000

28.4

19.5

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

F*FP040

 

21

1000

27.6

19.2

13.00

11.00

EABD-(T,W)030S

 

 

 

 

 

 

 

 

 

AHP30

 

17

1000

28.0

19.2

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

AHP30

 

17

1000

28.0

19.2

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

F*FP040

 

21

1200

34.6

25.4

13.00

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F036S

F*FP042

 

21

1200

34.6

25.4

13.00

11.00

 

 

 

 

 

 

 

 

 

AHP36

 

21

1200

34.4

25.4

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

AHP42

 

21

1200

34.6

25.3

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

F*FP040

 

21

1200

34.0

24.9

13.00

11.00

 

 

 

 

 

 

 

 

 

 

EABD-(T,W)036S

F*FP042

 

21

1200

34.0

24.9

13.00

11.00

 

 

 

 

 

 

 

 

 

AHP36

 

21

1200

33.8

24.9

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

AHP42

 

21

1200

34.0

24.8

13.00

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F042S

AHP/SHP48

 

24

1400

41.0

30.7

13.00

11.00

 

 

 

 

 

 

 

 

 

 

EABD-(T,W)042S

AHP/SHP48

 

24

1400

40.0

29.9

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

F*FV060

 

24

1600

46.0

34.6

13.50

11.00

EABD-F048S

 

 

 

 

 

 

 

 

 

AHP/SHP48

 

24

1600

46.0

35.3

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

AHP/SHP60

 

24

1600

46.0

34.6

13.25

11.00

 

 

 

 

 

 

 

 

 

 

 

F*FV060

 

24

1600

45.0

33.8

13.50

11.00

EABD-(T,W)048S

 

 

 

 

 

 

 

 

 

AHP/SHP48

 

24

1600

45.0

34.5

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

AHP/SHP60

 

24

1600

45.0

33.8

13.25

11.00

 

 

 

 

 

 

 

 

 

 

EABD-F060S

F*FV060

 

24

1800

54.0

39.7

13.25

11.00

 

 

 

 

 

 

 

 

 

AHP/SHP60

 

24

1800

55.0

39.7

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

EABD-(T,W)060S

F*FV060

 

24

1800

53.5

39.3

13.25

11.00

 

 

 

 

 

 

 

 

 

AHP/SHP60

 

24

1800

54.5

39.3

13.00

11.00

 

 

 

 

 

 

 

 

 

 

 

 

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.

= Not Applicable.

Go to www.ari.org/aridirectory for the latest additional matches.

8

Unitary Products Group

246819-BTG-H-0208

COOLING CAPACITY - Upflow, Downflow, and Horizontal Furnaces and Coils

 

FURNACE**

 

COIL

 

 

COOLING

 

 

UNIT MODEL

CFM RANGE

 

 

RATED

NET MBH

 

 

 

W

MODEL

SEER1

EER

 

(MIN.-MAX.)

 

CFM

 

 

 

 

TOTAL

SENS.

 

 

 

 

 

 

EABD-F018S

450

 

14,17

FC/MC/PC/UC18

600

18.0

12.4

13.00

11.00

750

 

 

 

 

 

 

 

 

 

14

HC18

600

17.8

12.1

13.00

11.00

 

 

 

 

 

14,17

FC/MC/PC/UC24

800

23.2

16.7

13.00

11.00

 

600

 

14,17

FC/MC/PC/UC30

800

23.2

16.7

13.00

11.00

EABD-F024S

 

14

HC30

760

23.4

16.6

13.00

11.00

1000

 

 

 

HD24

800

23.2

16.7

13.00

11.00

 

 

 

 

 

 

17,21

FC/MC/PC35

1000

28.4

20.3

13.00

11.00

 

800

 

17,21

FC/MC/PC/UC42

1000

28.4

20.3

13.00

11.00

EABD-F030S

 

17

HC36

950

28.0

19.6

13.00

11.00

1200

 

 

 

HD36

1000

28.6

20.3

13.00

11.00

 

 

 

 

 

 

17,21

FC/MC/PC35

1000

28.0

20.0

13.00

11.00

EABD-(T,W)030S

800

 

17,21

FC/MC/PC/UC42

1000

28.0

20.0

13.00

11.00

1200

 

 

 

 

 

 

 

 

 

17

HC36

950

27.6

19.3

13.00

11.00

 

 

 

 

 

HD36

1000

28.2

20.0

13.00

11.00

 

 

 

17,21

FC/MC/PC35

1200

34.6

25.3

13.00

11.00

 

 

 

17,21

FC/MC/PC/UC42

1200

34.6

25.3

13.00

11.00

EABD-F036S

1000

 

21,24

FC/MC/PC/UC48

1200

35.0

25.6

13.00

11.00

1400

 

 

 

 

 

 

 

 

 

21

HC42

1140

34.4

24.5

13.00

11.00

 

 

 

 

 

HD36

1200

34.4

25.2

13.00

11.00

 

 

 

17,21

FC/MC/PC35

1200

34.0

24.8

13.00

11.00

 

1000

 

17,21

FC/MC/PC/UC42

1200

34.0

24.8

13.00

11.00

EABD-(T,W)036S

 

 

 

 

 

 

 

 

 

21,24

FC/MC/PC/UC48

1200

34.4

25.1

13.00

11.00

1400

 

 

 

21

HC42

1140

33.8

24.0

13.00

11.00

 

 

 

 

 

 

HD36

1200

33.8

24.7

13.00

11.00

EABD-F042S

1200

 

21,24

FC/MC/PC/UC48

1400

41.0

30.8

13.00

11.00

1000

 

 

 

 

 

 

 

 

 

HD48

1400

40.5

30.3

13.00

11.00

 

 

EABD-(T,W)042S

1200

 

21,24

FC/MC/PC/UC48

1400

40.0

30.0

13.00

11.00

1600

 

 

 

 

 

 

 

 

 

HD48

1400

39.5

29.5

13.00

11.00

 

 

 

 

 

21,24

FC/MC/PC/UC60

1600

45.0

35.4

13.00

11.00

EABD-F048S

1400

 

24

MC61

1600

46.0

35.5

13.00

11.00

1800

 

 

 

 

 

 

 

 

 

24

HC60

1520

45.5

34.3

13.00

11.00

 

 

 

 

 

HD60

1600

45.0

34.7

13.00

11.00

 

 

 

21,24

FC/MC/PC/UC60

1600

44.0

34.6

13.00

11.00

EABD-(T,W)048S

1400

 

24

MC61

1600

45.0

34.7

13.00

11.00

1800

 

 

 

 

 

 

 

 

 

24

HC60

1520

44.5

33.5

13.00

11.00

 

 

 

 

 

HD60

1600

44.0

33.9

13.00

11.00

 

 

 

21,24

FC/MC/PC/UC60

1800

55.0

40.7

13.00

11.00

EABD-F060S

1600

 

24

MC61

1800

55.5

41.0

13.00

11.00

2000

 

 

 

 

 

 

 

 

 

24

HC60

1710

54.5

39.7

13.00

11.00

 

 

 

 

 

HD60

1800

54.0

39.9

13.00

11.00

 

 

 

21,24

FC/MC/PC/UC60

1800

54.5

40.3

13.00

11.00

EABD-(T,W)060S

1600

 

24

MC61

1800

55.0

40.6

13.00

11.00

2000

 

 

 

 

 

 

 

 

 

24

HC60

1710

54.0

39.3

13.00

11.00

 

 

 

 

 

HD60

1800

53.5

39.5

13.00

11.00

1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up.

Unitary Products Group

9

246819-BTG-H-0208

COOLING CAPACITY - With Variable Speed Furnaces

 

VARIABLE SPEED

COIL

 

 

 

COOLING

 

 

UNIT MODEL

FURNACE MODEL

MODEL1

W

RATED

NET MBH

SEER

EER

 

 

 

 

CFM

TOTAL

SENS.

 

 

 

1 PH 13 SEER HP WITH VARIABLE SPEED FURNACES2

 

 

 

 

(F,L)L8VA12

FC/MC/PC18A

14

600

18.0

12.5

14.00

12.00

 

FL9VA12

FC/MC/PC18A

14

600

18.0

12.5

14.00

12.00

EABD-F018S

 

 

 

 

 

 

 

 

FL9(C,V)B12

FC/MC/PC18B

17

600

18.0

12.6

14.00

12.00

 

(F,L)L8VA12

HC18

14

600

18.0

12.5

14.00

12.00

 

FL9VA12

HC18

14

600

18.0

12.5

14.00

12.00

 

(F,L)L8VA12

FC/MC/PC24A

14

800

23.2

16.7

14.00

12.00

 

FL9VA12

FC/MC/PC24A

14

800

23.2

16.7

14.00

12.00

 

FL9(C,V)B12

FC/MC/PC24B

17

800

23.2

16.6

14.00

12.00

 

(F,L)L8VA12

FC/MC/PC30A

14

800

23.2

16.7

14.00

12.00

EABD-F024S

FL9VA12

FC/MC/PC30A

14

800

23.2

16.7

14.00

12.00

FL9(C,V)B12

FC/MC/PC30B

17

800

23.2

17.2

14.00

12.00

 

 

(F,L)L8VA12

HC30

14

800

23.2

17.2

14.00

12.00

 

FL9VA12

HC30

14

800

23.2

16.9

14.00

12.00

 

(F,L)L8VA12

HD30

800

23.2

16.9

14.00

12.00

 

FL9VA12

HD30

800

23.2

16.9

14.00

12.00

 

(F,L)L8VB16

FC/MC/PC35B

17

1000

29.0

20.4

14.00

12.00

 

FL9(C,V)B12

FC/MC/PC35B

17

1000

29.0

20.4

14.00

12.00

 

(F,L)L8VC16

FC/MC/PC35C

21

1000

29.0

20.3

14.00

12.00

 

FL9(C,V)C16

FC/MC/PC35C

21

1000

29.0

20.4

14.00

12.00

 

(F,L)L8VB16

FC/MC/PC42B

17

1000

29.0

20.4

14.00

12.00

EABD-F030S

FL9(C,V)B12

FC/MC/PC42B

17

1000

29.0

20.4

14.00

12.00

(F,L)L8VC16

FC/MC/PC42C

21

1000

29.0

20.3

14.00

12.00

 

 

FL9(C,V)C16

FC/MC/PC42C

21

1000

29.0

20.4

14.00

12.00

 

(F,L)L8VB16

HC36

17

1000

29.0

20.4

14.00

12.00

 

FL9(C,V)B12

HC36

17

1000

29.0

20.4

14.00

12.00

 

(F,L)L8VB16

HD36

1000

29.0

20.4

14.00

12.00

 

FL9(C,V)B12

HD36

1000

29.0

20.4

14.00

12.00

 

(F,L)L8VB16

FC/MC/PC42B

17

1200

35.2

25.7

13.50

11.00

 

FL9(C,V)B12

FC/MC/PC42B

17

1200

35.2

25.7

13.25

11.00

 

(F,L)L8VC16

FC/MC/PC42C

21

1200

35.2

25.6

13.75

11.00

 

(F,L)L8VC20

FC/MC/PC42C

21

1200

35.2

25.6

14.00

12.00

 

FL9(C,V)C16

FC/MC/PC42C

21

1200

35.0

25.5

13.25

11.00

 

FL9(C,V)C20

FC/MC/PC42C

21

1200

35.0

25.4

13.50

11.00

 

(F,L)L8VC20

FC/MC/PC48C

21

1200

35.4

25.7

14.00

12.00

EABD-F036S

FL9(C,V)C16

FC/MC/PC48C

21

1200

35.4

25.7

14.00

12.00

FL9(C,V)C20

FC/MC/PC48C

21

1200

35.4

25.4

14.00

12.00

 

 

FL9(C,V)D20

FC/MC/PC48D

24

1200

35.4

25.6

14.00

12.00

 

(F,L)L8VC20

HC42

21

1200

35.2

25.4

14.00

12.00

 

FL9(C,V)C16

HC42

21

1200

35.0

25.6

13.25

11.00

 

FL9(C,V)C20

HC42

21

1200

35.0

25.6

13.50

11.00

 

(F,L)L8VC20

HD36

1200

35.2

25.8

14.00

12.00

 

FL9(C,V)C16

HD36

1200

35.0

25.5

13.25

11.00

 

FL9(C,V)C20

HD36

1200

35.0

25.6

13.50

11.00

 

(F,L)L8VC20

FC/MC/PC48C

21

1400

41.0

30.9

13.50

11.00

 

FL9(C,V)C16

FC/MC/PC48C

21

1400

41.0

30.9

13.50

11.00

 

FL9(C,V)C20

FC/MC/PC48C

21

1400

41.0

30.9

13.50

11.00

EABD-F042S

 

 

 

 

 

 

 

 

FL9(C,V)D20

FC/MC/PC48D

24

1400

41.0

30.9

13.50

11.00

 

(F,L)L8VC20

HD48

1400

40.0

30.2

13.50

11.00

 

FL9(C,V)C16

HD48

1400

40.5

30.6

13.25

11.00

 

FL9(C,V)C20

HD48

1400

40.0

30.1

13.25

11.00

For Notes See Page 11

10

Unitary Products Group