530.26-TG3YI (1294)
®
DCG
Shown
DESCRIPTION
Sunline 2000 units are highly efficient, convertible rooftops. All models have dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
These units are designed and manufactured under ISO 9002 Quality System Certification.
Cooling only, cooling with gas heat and cooling with supplemental electric heat units are available with a wide variety of field-installed accessories to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails. The base rails have holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. Powder paint cabinets provide an exceptionally durable finish with the 750 hour salt spray process per ASTM-B117 test standard.
All models are available with three different outdoor air damper accessosries:
∙Single enthalpy economizer
∙Differential enthalpy economizer
∙Motorized outdoor air intake damper
All models (including those with an economizer ) are suitable for either downflow or sideflow duct connections. For downflow duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For sideflow duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
A fixed outdoor air intake assembly is shipped in the return air compartment of all units. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel.
SINGLE PACKAGE
GAS / ELECTRIC UNITS AND
SINGLE PACKAGE AIR CONDITIONERS
D3CE / D3CG 180 & 240 (WORLD 50 HZ)
SUNLINE 2000ä
With horizontal ductwork, it should be mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.
All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls.
All gas heat models are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
530.26-TG3YI
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS
Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide “free” cooling.
The rain hood is painted to match the basic unit and must be field-assembled before installing.
On units built prior to January 1995 an accessory field harness must be installed.
Power exhaust is not available as a field installed option.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS
Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
This enthalpy system contains one sensor that monitors the outdoor air and one sensor that monitors the return air. The logic module compares the two values and modulates the dampers, providing the maximum efficiency of the economizer system.
The rain hood is painted to match the basic unit and must be field-assembled before installing.
On units built prior to January 1995 an accessory field harness must be installed.
Power exhaust is not available as a field installed option.
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper with a 2-position, spring-return motor actuator which opens to a pre-set position whenever the supply air blower is operating and drives fully closed when the blower shuts down.
On units built prior to January 1995 an accessory field harness must be installled.
Power exhaust is not available as a field installed option.
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal air pressure on units with an economizer. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
ROOF CURBS - Roof curbs, 356mm (14 in.) high, provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. They’re designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
SIDE DUCT FLANGES - Twenty-five millimeter (1 in.) flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/horizontal return or horizontal supply/bottom return.
HIGH SPEED DRIVE - A smaller blower pulley, a larger motor pulley (including a replacement belt) increase the speed of the supply air blower for applications with a higher airflow and/or static pressure requirement.
ANTI-RECYCLE TIMERS - Two solid state timers prevent the compressors from short-cycling. Once a compressor is de-energized, it remains de-energized for approximately five minutes.
LOW AMBIENT CONTROLS TO 18°C (0°F) - An autotransformer and a thermostat maintain stable system operation by reducing the speed of the #1 condenser fan motor at low oudoor temperatures. The kit also includes a 1-phase motor to replace the unit’s standard 3-phase condenser fan motor. Standard units can operate down to 4 °C (25 °F).
TABLE OF CONTENTS
Description ........................................................................... |
1 |
Electrical Data - Cooling and Gas Heat ............................. |
13 |
|
Field-Installed Accessories................................................... |
2 |
Electrical Data - Units with Electric Heat............................ |
14 |
|
Ratings ................................................................................. |
3 |
Physical Data |
14 |
|
Cooling Capacities |
4 |
|||
Unit Dimensions |
15 |
|||
Blower Performance |
8 |
|||
Roof Curb Dimensions |
18 |
|||
Blower Motor and Drive Data |
12 |
|||
Typical Applications |
18 |
|||
Static Resistances.............................................................. |
10 |
|||
Field Wiring ........................................................................ |
13 |
|
|
2 |
Unitary Products Group |
530.26-TG3YI
®
SUNLINE 2000ä
(OPTION / ACCESS.) DCE UNITS
ALUMINIZED STEEL
THROWAWAY
D*CG UNITS
(OPTION / ACCESSORY)
FEMALE
MODEL DCG
(Gas Heating)
RATINGS
CAPACITY RATINGS - Cooling / Electric Heating
|
Rating |
1 |
Total Output, |
Total Input, |
COP2 |
EER3 |
Sensible Output, |
Latent Output, |
Electric Heat4 |
|
Model |
|
Nominal Capacity, |
||||||||
|
Point |
|
Mbh / kW |
kW |
|
|
Mbh / kW |
Mbh / kW |
kW |
|
|
T1 |
|
159 / 46.6 |
18.2 |
2.60 |
8.80 |
132 / 38.7 |
26.9 / 7.9 |
|
|
D3CE180 |
T2 |
|
142 / 41.7 |
20.0 |
2.10 |
7.15 |
141 / 41.2 |
1.6 |
/ 0.5 |
18, 36, 54, 72 |
|
T3 |
|
152 / 44.6 |
16.4 |
2.75 |
9.40 |
119 / 34.9 |
33.2 / 9.7 |
|
|
|
T1 |
|
210 / 61.5 |
24.8 |
2.50 |
8.50 |
176 / 51.5 |
34.0 |
/ 10.0 |
|
D3CE240 |
T2 |
|
182 / 53.3 |
27.1 |
2.00 |
6.75 |
182 / 53.3 |
0.0 |
/ 0.0 |
18, 36, 54, 72 |
|
T3 |
|
196 / 57.5 |
22.2 |
2.60 |
8.80 |
152 / 44.6 |
42.6 |
/ 12.5 |
|
1T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
2COP = Coefficient of Performance - total output kW divided by the total input kW.
3EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
4Heaters available as factory-installed options or field-installed accessories - all with single point power supply.
CAPACITY RATINGS - Gas Heating
|
|
|
|
Gas Heat Capacity |
|
|
|
Model |
Cooling Capacity, |
Input (Net) |
Output |
Gas Rate* |
Temp. Rise (°F / °C) |
||
Mbh / kW |
|
At Full Input |
|||||
|
Mbh / kW |
Mbh / kW |
cfh / m3/h |
|
|||
|
|
Min. |
|
Max. |
|||
|
|
|
|
|
|
||
D3CG180N320 |
180 / 52.7 |
291 / 85.2 |
258 / 75.6 |
302 / 8.5 |
30 / 17 |
|
60 / 33 |
D3CG240N320 |
240 / 70.3 |
|
|||||
|
|
|
|
|
|
NOTE: Gas Heaters are shipped available for natural gas, but can be converted to L.P. / propane gas with a field-installed conversion accessory. All gas units are two-stage heating. First stage is 50% of total.
*Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m3).
Unitary Products Group |
3 |
530.26-TG3YI
COOLING CAPACITIES (m3/s Air Flow) - 180 UNITS
|
Air On |
Total |
Power |
|
|
|
Sensible Capacity1, kW |
|
|
|||
Evaporator Coil |
1 |
2 |
|
|
Entering Dry Bulb Temp., |
° |
C |
|
||||
|
|
|
Cap. |
Input |
|
|
|
|
||||
m3/s |
|
WB °C |
kW |
kW |
32 |
30 |
|
28 |
26 |
|
24 |
22 |
|
|
|
|
@27°C Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
23 |
66.4 |
14.7 |
51 |
44 |
|
37 |
30 |
|
23 |
- |
|
|
21 |
62.3 |
14.4 |
59 |
52 |
|
44 |
37 |
|
30 |
23 |
3.40 |
|
19 |
58.2 |
14.0 |
58 |
58 |
|
52 |
45 |
|
38 |
31 |
|
|
17 |
56.7 |
14.0 |
57 |
57 |
|
56 |
49 |
|
41 |
34 |
|
|
15 |
55.2 |
13.9 |
55 |
55 |
|
55 |
52 |
|
45 |
37 |
|
|
23 |
61.5 |
14.5 |
46 |
40 |
|
34 |
27 |
|
21 |
- |
|
|
21 |
57.7 |
14.2 |
53 |
46 |
|
40 |
34 |
|
28 |
22 |
2.80 |
|
19 |
53.9 |
13.9 |
54 |
53 |
|
47 |
41 |
|
35 |
28 |
|
|
17 |
52.5 |
13.8 |
52 |
52 |
|
51 |
44 |
|
38 |
32 |
|
|
15 |
51.1 |
13.7 |
51 |
51 |
|
51 |
48 |
|
42 |
35 |
|
|
23 |
57.1 |
14.3 |
37 |
32 |
|
28 |
23 |
|
19 |
- |
|
|
21 |
53.6 |
14.0 |
43 |
38 |
|
33 |
29 |
|
24 |
19 |
2.10 |
|
19 |
50.1 |
13.6 |
48 |
44 |
|
39 |
34 |
|
30 |
25 |
|
|
17 |
48.7 |
13.6 |
49 |
47 |
|
42 |
37 |
|
33 |
28 |
|
|
15 |
47.4 |
13.5 |
47 |
47 |
|
45 |
40 |
|
36 |
31 |
|
|
|
|
@35°C Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
23 |
60.7 |
15.9 |
50 |
43 |
|
36 |
29 |
|
22 |
- |
|
|
21 |
57.2 |
15.5 |
57 |
50 |
|
43 |
36 |
|
29 |
22 |
3.40 |
|
19 |
53.7 |
15.2 |
54 |
54 |
|
51 |
43 |
|
36 |
29 |
|
|
17 |
52.3 |
15.1 |
52 |
52 |
|
52 |
47 |
|
40 |
32 |
|
|
15 |
51.0 |
15.0 |
51 |
51 |
|
51 |
47 |
|
40 |
33 |
|
|
23 |
56.3 |
15.9 |
44 |
38 |
|
32 |
25 |
|
19 |
- |
|
|
21 |
53.1 |
15.6 |
51 |
44 |
|
38 |
32 |
|
26 |
20 |
2.80 |
|
19 |
49.8 |
15.2 |
50 |
50 |
|
45 |
39 |
|
32 |
26 |
|
|
17 |
48.6 |
15.1 |
49 |
49 |
|
48 |
41 |
|
35 |
29 |
|
|
15 |
47.3 |
15.0 |
47 |
47 |
|
47 |
44 |
|
38 |
32 |
|
|
23 |
51.9 |
15.6 |
36 |
31 |
|
27 |
22 |
|
17 |
- |
|
|
21 |
48.9 |
15.3 |
41 |
37 |
|
32 |
27 |
|
23 |
18 |
2.10 |
|
19 |
45.9 |
14.9 |
46 |
42 |
|
38 |
33 |
|
28 |
24 |
|
|
17 |
44.7 |
14.8 |
45 |
45 |
|
40 |
35 |
|
31 |
26 |
|
|
15 |
43.6 |
14.7 |
44 |
44 |
|
43 |
38 |
|
33 |
29 |
|
|
|
|
@46°C Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
23 |
49.6 |
18.2 |
46 |
39 |
|
32 |
25 |
|
18 |
- |
|
|
21 |
47.3 |
17.6 |
47 |
46 |
|
39 |
32 |
|
25 |
18 |
3.40 |
|
19 |
45.0 |
17.1 |
45 |
45 |
|
45 |
39 |
|
32 |
25 |
|
|
17 |
43.6 |
17.1 |
44 |
44 |
|
44 |
40 |
|
33 |
26 |
|
|
15 |
42.1 |
17.1 |
42 |
42 |
|
42 |
39 |
|
31 |
24 |
|
|
23 |
49.4 |
17.8 |
41 |
35 |
|
29 |
23 |
|
17 |
- |
|
|
21 |
47.2 |
17.2 |
47 |
42 |
|
36 |
29 |
|
23 |
17 |
2.80 |
|
19 |
44.9 |
16.6 |
45 |
45 |
|
42 |
36 |
|
30 |
24 |
|
|
17 |
43.4 |
16.6 |
43 |
43 |
|
43 |
37 |
|
31 |
25 |
|
|
15 |
42.0 |
16.6 |
42 |
42 |
|
42 |
39 |
|
33 |
27 |
|
|
23 |
46.5 |
17.5 |
33 |
29 |
|
24 |
19 |
|
15 |
- |
|
|
21 |
44.4 |
17.0 |
39 |
34 |
|
30 |
25 |
|
20 |
16 |
2.10 |
|
19 |
42.3 |
16.4 |
42 |
40 |
|
35 |
31 |
|
26 |
21 |
|
|
17 |
40.9 |
16.4 |
41 |
41 |
|
36 |
32 |
|
27 |
22 |
|
|
15 |
39.5 |
16.4 |
40 |
40 |
|
38 |
33 |
|
28 |
24 |
1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
4 |
Unitary Products Group |
530.26-TG3YI
COOLING CAPACITIES (CFM Air Flow) - 180 UNITS
|
Air On |
Total |
Power |
|
|
Sensible Capacity1, MBH |
|
|||||
Evaporator Coil |
1 |
2 |
|
|
Entering Dry Bulb Temp., |
° |
|
|||||
|
|
|
Cap. |
Input |
|
|
|
F |
|
|||
CFM |
|
WB °F |
MBH |
kW |
90 |
86 |
|
82 |
79 |
|
75 |
72 |
|
|
|
|
@80°F Air Temperature on Condenser Coil1 |
|
|
|
|
||||
|
|
73 |
227 |
14.7 |
175 |
151 |
|
126 |
102 |
|
78 |
- |
|
|
70 |
213 |
14.4 |
200 |
176 |
|
152 |
127 |
|
103 |
79 |
7200 |
|
66 |
199 |
14.0 |
199 |
199 |
|
177 |
153 |
|
128 |
104 |
|
|
63 |
193 |
14.0 |
193 |
193 |
|
190 |
166 |
|
142 |
117 |
|
|
59 |
188 |
13.9 |
188 |
188 |
|
188 |
176 |
|
152 |
128 |
|
|
73 |
210 |
14.5 |
157 |
136 |
|
115 |
93 |
|
72 |
- |
|
|
70 |
197 |
14.2 |
180 |
159 |
|
138 |
116 |
|
95 |
74 |
5930 |
|
66 |
184 |
13.9 |
184 |
182 |
|
160 |
139 |
|
118 |
97 |
|
|
63 |
179 |
13.8 |
179 |
179 |
|
172 |
151 |
|
130 |
109 |
|
|
59 |
174 |
13.7 |
174 |
174 |
|
174 |
163 |
|
142 |
121 |
|
|
73 |
195 |
14.3 |
127 |
111 |
|
95 |
79 |
|
63 |
- |
|
|
70 |
183 |
14.0 |
146 |
130 |
|
114 |
98 |
|
82 |
66 |
4450 |
|
66 |
171 |
13.6 |
165 |
149 |
|
133 |
117 |
|
101 |
86 |
|
|
63 |
166 |
13.6 |
166 |
159 |
|
143 |
127 |
|
111 |
96 |
|
|
59 |
162 |
13.5 |
162 |
162 |
|
153 |
137 |
|
121 |
105 |
|
|
|
|
@95°F Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
73 |
207 |
15.9 |
170 |
146 |
|
122 |
98 |
|
74 |
- |
|
|
70 |
195 |
15.5 |
195 |
171 |
|
147 |
123 |
|
99 |
75 |
7200 |
|
66 |
183 |
15.2 |
183 |
183 |
|
172 |
148 |
|
124 |
100 |
|
|
63 |
179 |
15.1 |
179 |
179 |
|
179 |
159 |
|
135 |
111 |
|
|
59 |
174 |
15.0 |
174 |
174 |
|
174 |
162 |
|
138 |
113 |
|
|
73 |
192 |
15.9 |
150 |
129 |
|
108 |
87 |
|
66 |
- |
|
|
70 |
181 |
15.6 |
172 |
151 |
|
130 |
109 |
|
88 |
67 |
5930 |
|
66 |
170 |
15.2 |
170 |
170 |
|
153 |
132 |
|
110 |
89 |
|
|
63 |
166 |
15.1 |
166 |
166 |
|
162 |
141 |
|
120 |
99 |
|
|
59 |
161 |
15.0 |
161 |
161 |
|
161 |
151 |
|
130 |
109 |
|
|
73 |
177 |
15.6 |
123 |
107 |
|
91 |
75 |
|
59 |
- |
|
|
70 |
167 |
15.3 |
142 |
126 |
|
110 |
94 |
|
78 |
62 |
4450 |
|
66 |
157 |
14.9 |
157 |
145 |
|
129 |
113 |
|
97 |
81 |
|
|
63 |
153 |
14.8 |
153 |
153 |
|
137 |
121 |
|
105 |
89 |
|
|
59 |
149 |
14.7 |
149 |
149 |
|
145 |
129 |
|
113 |
97 |
|
|
|
|
@115°F Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
73 |
169 |
18.2 |
157 |
133 |
|
109 |
85 |
|
61 |
- |
|
|
70 |
161 |
17.6 |
161 |
158 |
|
134 |
110 |
|
85 |
61 |
7200 |
|
66 |
154 |
17.1 |
154 |
154 |
|
154 |
135 |
|
110 |
86 |
|
|
63 |
149 |
17.1 |
149 |
149 |
|
149 |
137 |
|
112 |
88 |
|
|
59 |
144 |
17.1 |
144 |
144 |
|
144 |
132 |
|
107 |
83 |
|
|
73 |
169 |
17.8 |
141 |
120 |
|
99 |
78 |
|
57 |
- |
|
|
70 |
161 |
17.2 |
161 |
142 |
|
121 |
100 |
|
79 |
58 |
5930 |
|
66 |
153 |
16.6 |
153 |
153 |
|
144 |
123 |
|
102 |
81 |
|
|
63 |
148 |
16.6 |
148 |
148 |
|
148 |
128 |
|
107 |
86 |
|
|
59 |
143 |
16.6 |
143 |
143 |
|
143 |
133 |
|
112 |
90 |
|
|
73 |
159 |
17.5 |
114 |
98 |
|
82 |
66 |
|
50 |
- |
|
|
70 |
151 |
17.0 |
133 |
117 |
|
101 |
85 |
|
69 |
53 |
4450 |
|
66 |
144 |
16.4 |
144 |
136 |
|
120 |
104 |
|
88 |
72 |
|
|
63 |
139 |
16.4 |
139 |
139 |
|
124 |
108 |
|
92 |
76 |
|
|
59 |
135 |
16.4 |
135 |
135 |
|
128 |
112 |
|
96 |
80 |
1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group |
5 |
530.26-TG3YI
COOLING CAPACITIES (m3/s Air Flow) - 240 UNITS
|
Air On |
Total |
Power |
|
|
|
Sensible Capacity1, kW |
|
|
|||
Evaporator Coil |
1 |
2 |
|
|
Entering Dry Bulb Temp., |
° |
C |
|
||||
|
|
|
Cap. |
Input |
|
|
|
|
||||
m3/s |
|
WB °C |
kW |
kW |
32 |
30 |
|
28 |
26 |
|
24 |
22 |
|
|
|
|
@27°C Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
23 |
80.4 |
19.0 |
74 |
65 |
|
55 |
46 |
|
37 |
- |
|
|
21 |
77.6 |
18.8 |
78 |
70 |
|
61 |
52 |
|
43 |
33 |
4.40 |
|
19 |
74.8 |
18.6 |
75 |
75 |
|
67 |
57 |
|
48 |
39 |
|
|
17 |
72.4 |
18.4 |
72 |
72 |
|
71 |
62 |
|
53 |
44 |
|
|
15 |
70.0 |
18.1 |
70 |
70 |
|
70 |
65 |
|
56 |
47 |
|
|
23 |
76.9 |
18.8 |
68 |
60 |
|
52 |
44 |
|
36 |
- |
|
|
21 |
74.3 |
18.6 |
73 |
65 |
|
57 |
49 |
|
41 |
33 |
3.80 |
|
19 |
71.6 |
18.4 |
72 |
70 |
|
62 |
54 |
|
46 |
38 |
|
|
17 |
69.3 |
18.2 |
69 |
69 |
|
67 |
59 |
|
51 |
43 |
|
|
15 |
67.0 |
17.9 |
67 |
67 |
|
67 |
63 |
|
55 |
47 |
|
|
23 |
71.2 |
18.5 |
56 |
50 |
|
44 |
37 |
|
31 |
- |
|
|
21 |
68.7 |
18.3 |
60 |
54 |
|
48 |
42 |
|
36 |
30 |
2.80 |
|
19 |
66.3 |
18.1 |
65 |
59 |
|
52 |
46 |
|
40 |
34 |
|
|
17 |
64.1 |
17.9 |
64 |
62 |
|
56 |
50 |
|
44 |
38 |
|
|
15 |
62.0 |
17.6 |
62 |
62 |
|
60 |
54 |
|
47 |
41 |
|
|
|
|
@35°C Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
23 |
74.9 |
21.0 |
71 |
61 |
|
52 |
43 |
|
34 |
- |
|
|
21 |
72.3 |
20.7 |
72 |
68 |
|
58 |
49 |
|
40 |
31 |
4.40 |
|
19 |
69.8 |
20.4 |
70 |
70 |
|
65 |
55 |
|
46 |
37 |
|
|
17 |
67.4 |
20.1 |
67 |
67 |
|
67 |
58 |
|
49 |
40 |
|
|
15 |
65.0 |
19.9 |
65 |
65 |
|
65 |
60 |
|
51 |
42 |
|
|
23 |
71.3 |
20.7 |
65 |
57 |
|
49 |
41 |
|
33 |
- |
|
|
21 |
68.9 |
20.5 |
69 |
62 |
|
54 |
46 |
|
38 |
30 |
3.80 |
|
19 |
66.4 |
20.2 |
66 |
66 |
|
60 |
52 |
|
44 |
36 |
|
|
17 |
64.2 |
19.9 |
64 |
64 |
|
63 |
55 |
|
47 |
39 |
|
|
15 |
61.9 |
19.7 |
62 |
62 |
|
62 |
58 |
|
50 |
42 |
|
|
23 |
65.4 |
20.4 |
52 |
46 |
|
40 |
34 |
|
28 |
- |
|
|
21 |
63.1 |
20.1 |
57 |
51 |
|
45 |
39 |
|
33 |
27 |
2.80 |
|
19 |
60.9 |
19.8 |
61 |
56 |
|
50 |
44 |
|
38 |
31 |
|
|
17 |
58.8 |
19.6 |
59 |
58 |
|
52 |
46 |
|
40 |
34 |
|
|
15 |
56.7 |
19.3 |
57 |
57 |
|
54 |
48 |
|
42 |
36 |
|
|
|
|
@46°C Air Temperature on Condenser Coil |
|
|
|
|
||||
|
|
23 |
66.4 |
23.4 |
65 |
56 |
|
47 |
38 |
|
29 |
- |
|
|
21 |
63.3 |
22.9 |
63 |
62 |
|
53 |
44 |
|
35 |
26 |
4.40 |
|
19 |
60.2 |
22.3 |
60 |
60 |
|
60 |
51 |
|
41 |
32 |
|
|
17 |
59.0 |
22.3 |
59 |
59 |
|
59 |
53 |
|
43 |
34 |
|
|
15 |
57.8 |
22.2 |
58 |
58 |
|
58 |
53 |
|
44 |
35 |
|
|
23 |
63.8 |
23.3 |
60 |
52 |
|
44 |
36 |
|
28 |
- |
|
|
21 |
60.8 |
22.7 |
61 |
58 |
|
50 |
42 |
|
34 |
26 |
3.80 |
|
19 |
57.8 |
22.2 |
58 |
58 |
|
56 |
48 |
|
40 |
32 |
|
|
17 |
56.7 |
22.1 |
57 |
57 |
|
57 |
50 |
|
42 |
34 |
|
|
15 |
55.5 |
22.1 |
56 |
56 |
|
56 |
52 |
|
44 |
35 |
|
|
23 |
59.4 |
23.1 |
49 |
42 |
|
36 |
30 |
|
24 |
- |
|
|
21 |
56.6 |
22.5 |
54 |
47 |
|
41 |
35 |
|
29 |
23 |
2.80 |
|
19 |
53.8 |
22.0 |
54 |
53 |
|
46 |
40 |
|
34 |
28 |
|
|
17 |
52.8 |
21.9 |
53 |
53 |
|
48 |
42 |
|
36 |
30 |
|
|
15 |
51.7 |
21.9 |
52 |
52 |
|
49 |
43 |
|
37 |
31 |
1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
6 |