York 1-1-2, D1EB018, 060 User Manual

0 (0)
York 1-1-2, D1EB018, 060 User Manual

J

CHAMPION® SERIES

 

 

SINGLE PACKAGE AIR CONDITIONERS

 

ELECTRIC/ELECTRIC, AIR-COOLED

INSTALLATION INSTRUCTION Supersedes: 035-16703-000-A-0701

035-16703-001-A-0202

MODELS D1EB018 THRU 060

1-1/2 THRU 5 TON

(10 SEER)

GENERAL

Model D1EB units are factory assembled cooling only air conditioners designed for outdoor installation on a rooftop or a slab. Field-installed electric heater accessories are available to provide electric heat combined with electric cooling. All units and heaters are certified by AGA and CGA.

The units are completely assembled on rigid, but easily removable base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require only electric power and duct connections at the point of installation.

The electric heaters have nickel-chrome resistance wire elements and utilize single point power connection.

INSPECTION

As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Refer to Form 50.15-NM for additional information.

REFERENCE

Additional information on the design, installation, operation and service of this equipment is available in the following reference forms:

55.70-N1 -General Installation

55.70-N2 -Pre-start & Post-start Check List

511.26-N1.1V -Electric Heater Accessory

REPLACEMENT PARTS

Refer to Replacement Parts Manual for complete listing of replacement parts on this equipment.

All forms referenced in this instruction may be ordered from:

Standard Register

Norman, OK 73069

Toll Free: Tel. 877-318-9675/Fax. 877-379-7920

Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.

CAUTION

THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH

THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE

LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED

TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.

WARNING

INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY O R PRO PERT Y DAM AG E.

035-16703-001-A-0202

PRODUCT NOMENCLATURE

 

 

 

 

D

 

1

 

E

B

 

0

2

4

 

A

 

0

 

6

 

 

 

 

 

 

PRODUCT CATEGORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE CODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D = Single Package Air Conditioner

 

 

 

 

 

 

 

 

 

 

 

NOMINAL COOLING

 

 

 

 

 

 

06 = 208/230-1-60

 

(Air Cooled)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 = 208/230-3-60

 

 

 

 

 

 

 

 

 

 

 

CAPACITY (MBH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46 = 460-3-60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018 = 18,000 BTUH

 

 

 

 

PRODUCT GENERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58 = 575-3-60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024 = 24,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = NEW or Current Design

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

030 = 30,000 BTUH

 

 

 

 

 

 

FACTORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036 = 36,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLED ELECTRIC HEAT

 

PRODUCT IDENTIFIER

 

 

 

 

 

 

 

 

 

 

 

 

042 = 42,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A = No Electric Heat Installed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EB = 10 SEER Cooling Models

 

 

 

 

 

 

 

 

 

 

 

 

048 = 48,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060 = 60,000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION

 

 

 

 

 

 

 

 

LIMITATIONS

These units must be installed in accordance with the following national and local safety codes.

1.National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions).

2.Local plumbing and waste water codes and other applicable local codes.

Refer to Table 1 for unit application data and to Table 5 for electric heat application data.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense.

Size of unit for proposed installation should be based on heat loss/heat gain calculations made in accordance with industry recognized procedures identified by the Air Conditioning Contractors of America.

TABLE 1 - UNIT APPLICATION DATA

Voltage Variation

 

208/230V3

187 / 2533

 

460V

414

/ 504

Min. / Max.1

 

 

575V

518

/ 630

 

 

Wet Bulb Temperature (° F) of Air on

57

/ 72

Evaporator Coil,

Min. / Max.

 

 

Dry Bulb Temperature (° F) of Air on

45 / 120

Condenser Coil,

Min.2 / Max.

1 Rated in accordance with ARI Standard 110, utilization range “A”. 2 A low ambient accessory is available for operation down to 0° F

3“T1" transformer primary tap must be moved from the 230 volt connection to the 208 volt connection for low voltage applications of 208 volt and below.

LOCATION

Use the following guidelines to select a suitable location for these units.

1.Unit is designed for outdoor installation only.

2.Condenser must have an unlimited supply of air. Where a choice of location is possible, position unit on either north or east side of building.

3.For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.

4.For roof top installation, be sure the structure will support the weight of the unit plus any field installed components. Unit must be installed on a level roof curb or appropriate an-

gle iron frame providing adequate support under the compressor/condenser section.

5. Maintain level tolerance of unit to 1/8" maximum.

RIGGING OR HANDLING

Care must be exercised when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig unit with slings placed under the unit. Spreader bars of sufficient length should be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift. Slotted openings in the skid are provided for this purpose. Forks must pass completely through the base.

Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity.

TABLE 2 - UNITS WEIGHTS

 

SHIPPING

OPERAT-

CORNER WEIGHTS

 

UNIT

ING

 

(location, lbs.)

 

SIZE

WEIGHT

WEIGHT

 

 

 

 

(lbs.)

“A”

“B”

“C”

“D”

 

(lbs.)

 

 

018

318

313

86

76

73

83

024

324

319

88

77

75

85

030

333

328

85

81

82

86

036

338

333

91

80

78

88

042

347

342

94

83

80

91

048

368

363

92

88

92

97

060

376

371

105

100

84

87

 

 

“D”

CENTER OF GRAVITY

 

 

 

 

FRONT

 

“A”

 

“C”

 

 

OF

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

“B”

 

 

 

 

 

 

 

 

 

 

49 1

26

 

47

1

 

 

 

 

4

 

 

 

8

 

 

 

 

FIG. 1 - CENTER OF GRAVITY

2

Unitary Products Group

CLEARANCES

All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for combustion, construction, servicing and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps:

1.Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws securing each duct cover (save these screws to use later).

2.Install the duct covers, removed in step one, to the rear supply and return air duct openings. Secure with the four (4) screws used in step one.

3.Seal the duct covers with silicone caulking.

Downflow units must have an L-shaped supply duct without any outlets or registers located directly below the supply outlet of the unit.

Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to minimize the transmission of noise.

CAUTION: When fastening duct work to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 3 for information concerning rear and bottom supply and return air duct openings.

TABLE 3 - PHYSICAL DATA

035-16703-001-A-0202

FILTERS

Single phase units are shipped without a filter and is the responsibility of the installer to secure a filter in the return air ductwork or install a Filter/Frame Kit (1FF0114).

A filter rack and a filters are standard on three phase units.

Filters must always be used and must be kept clean. When filters become dirt laden, insufficient air will be delivered by the blower, decreasing your units efficiency and increasing operating costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit may be used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate drain. The plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install the condensate drain line (34“ NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the following removable panels:

Blower service access

Electrical/filter access

Compressor service access

Refer to Figure 3 for location of these access panels and minimum clearance.

THERMOSTAT

The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with the thermostat for general installation procedure. Four or five color coded insulated wires (minimum #18 AWG) should be used to connect thermostat to unit. See Figure 2.

 

MODELS

 

 

 

DEB

 

 

 

 

018

024

030

036

042

048

060

 

 

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

9 X 6

10 X 8

10 X 8

10 x 8

11 X 10

11 x 10

11 x 10

BLOWER

FAN MOTOR HP (Three Speed)

12

12

12

34

34

34

1

EVAPORATOR

ROWS DEEP

2

2

2

2

2

2

3

FINS PER INCH

13

15

15

15

15

13

16

COIL

FACE AREA (Sq. Ft.)

2.19

2.81

4.38

4.38

4.38

5.62

5.26

 

CONDENSER

PROPELLER DIA. (in.)

22

22

22

22

22

22

22

FAN MOTOR HP

14

14

14

14

14

14

14

FAN

NOM. CFM TOTAL

1,800

2,200

2,400

2,400

2,400

2,800

2,800

 

CONDENSER

ROWS DEEP

1

1

1

1

1

1

1

FINS PER INCH

18

16

20

18

16

13

20

COIL

FACE AREA (Sq. Ft.)

8.3

8.3

8.3

8.3

11.7

16.4

16.4

 

CHARGE

REFRIGERANT 22 (lbs./oz.)

3 / 4

3 / 5

3 / 13

3 / 10

4 / 7

5 / 15

5 / 15

FILTER

FACE AREA (Sq. Ft. / Qty. / Size)

 

 

2.14 / 2 / 14" x 22"

 

 

COMPRESSOR

HERMETIC Type, (Qty. = 1)

Recip

Recip

Recip

Recip

Recip

Scroll

Scroll

Unitary Products Group

3

035-16703-001-A-0202

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 3.

The wiring entering the cabinet must be provided with mechanical strain relief.

A fused or HACR breaker disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.

Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted for shipping. CAUTION: Loosen compressor mounting bolts half turn before operating unit.

 

 

CONTROL WIRING

THERMOSTAT

UNIT TERMINAL STRIP

** = Minimum wire size of 18 AWG

R

**

R

 

 

 

wire should be used for all field

 

 

 

installed 24 volt wire.

G

 

G

NOTE:

HEAT ANTICIPATOR SHOULD BE SET AT 0.25 AMPS FOR ALL MODELS.

PROGRAMMABLE

THERMOSTAT ONLY

* = Only required on units with supplemental electric heat.

YY

W * W

CC

24 VOLT TRANSFORMER

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

POWER WIRING

REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, WIRING & OVERCURRENT PROTECTION.

REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, WIRING & OVERCURRENT PROTECTION.

FIG. 2 - TYPICAL FIELD WIRING DIAGRAM

4

Unitary Products Group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

035-16703-001-A-0202

TABLE 4 - ELECTRICAL DATA (BASIC UNIT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

COND.

SUPPLY

 

 

 

MAX.

 

MAX.

 

 

 

 

MODEL

POWER SUP-

LIMITATIONS

COMPRESSOR

 

AIR

 

MINIMUM

FUSE

 

HACR

UNIT

 

TRANSFORMER

 

FAN

 

 

 

 

1

 

 

 

BLOWER

 

CIRCUIT

 

SIZE,

BREAKER

POWER

 

DEB

PLY

 

 

 

 

 

 

MOTOR,

 

 

 

 

SIZE (VA)

MIN.

 

MAX.

RLA

LRA

 

MOTOR,

 

AMPACITY

 

AMPS

 

SIZE,

FACTOR

 

 

 

 

 

 

FLA

FLA

 

 

2

 

AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

208/230-1-60

187

 

253

9.0

48.0

 

1.1

2.6

 

 

14.9

20

 

20

 

.96

 

40

024

208/230-1-60

187

 

253

11.5

60.0

 

1.1

2.6

 

 

18.1

25

 

25

 

.96

 

40

030

208/230-1-60

187

 

253

14.7

73.0

 

1.1

2.6

 

 

22.1

30

 

30

 

.96

 

40

036

208/230-1-60

187

 

253

17.3

94.0

 

1.1

3.5

 

 

26.2

35

 

35

 

.96

 

40

042

208/230-1-60

187

 

253

20.5

120.0

 

1.1

3.5

 

 

30.2

40

 

40

 

.96

 

40

048

208/230-1-60

187

 

253

24.4

140.0

 

1.3

4.0

 

 

35.8

45

 

45

 

.96

 

40

060

208/230-1-60

187

 

253

28.9

165.0

 

1.3

4.0

 

 

44.4

60

 

60

 

.96

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

208/230-3-60

187

 

253

10.9

78.0

 

1.1

3.5

 

 

18.2

25

 

25

 

.96

 

75

042

208/230-3-60

187

 

253

14.1

110.0

 

1.1

3.5

 

 

22.2

30

 

30

 

.96

 

75

048

208/230-3-60

187

 

253

14.1

105.0

 

0.7

4.0

 

 

22.3

30

 

30

 

.96

 

75

060

208/230-3-60

187

 

253

16.0

125.0

 

1.3

7.0

 

 

28.3

40

 

40

 

.96

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

460-3-60

414

 

504

5.8

40.0

 

0.6

1.8

 

 

9.6

15

 

15

 

.96

 

75

042

460-3-60

414

 

504

7.1

54.0

 

0.6

1.8

 

 

11.2

15

 

15

 

.96

 

75

048

460-3-60

414

 

504

7.1

55.0

 

0.6

2.0

 

 

11.5

15

 

15

 

.96

 

75

060

460-3-60

414

 

504

8.0

67.0

 

0.7

3.5

 

 

14.2

20

 

20

 

.96

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

575-3-60

518

 

630

4.5

32.0

 

0.4

1.5

 

 

7.6

15

 

15

 

.96

 

75

042

575-3-60

518

 

630

5.8

44.0

 

0.4

1.5

 

 

9.1

15

 

15

 

.96

 

75

048

575-3-60

518

 

630

5.6

44.0

 

0.6

1.6

 

 

9.3

15

 

15

 

.96

 

75

060

575-3-60

518

 

630

6.4

50.0

 

0.6

2.8

 

 

11.4

15

 

15

 

.96

 

75

1 = Rated in accordance with ARI Standard 110, utilization range “A”.

2 = Dual element, time delay type.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* = KW listed is for 240 volts, use this table for 208 or 230 volts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL VOLTAGE

 

VOLTAGE

 

KW CAP. MULTI-

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEAT

 

 

 

PLIER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208

 

 

.75

 

 

 

 

 

 

 

 

 

 

 

CORRECTION

 

 

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

 

 

.92

 

 

 

 

 

 

 

 

 

 

 

 

FACTORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

 

460

 

 

.92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

575

 

 

.92

Unitary Products Group

5

035-16703-001-A-0202

TABLE 5 - ELECTRICAL DATA (COOLING / ELECTRIC HEAT)

DEB

 

COMPRESSOR

COND.

SUPPLY

ELECTRIC HEAT ACCESSORY

 

MAX.

MAX.

 

 

 

 

 

 

 

 

MINIMUM

 

POWER

 

 

FAN

AIR

 

 

 

 

 

FUSE

HACR2

MODEL

SUPPLY

 

 

MOTOR

BLOWER

 

STAGE

 

 

 

CIRCUIT

SIZE,1

BREAKER

 

 

 

FLA

MOTOR,

 

 

 

TOTAL

AMPACITY

AMPS

SIZE

 

 

RLA

LRA

FLA

MODEL NO.

 

KW

 

 

 

 

 

 

 

AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

208/230-1-60

9.0

48.0

1.1

2.6

2NH04500506

1

3.8/5.0

*

18.1/20.8

25.8/29.3

30/30

30/30

2NH04500706

2

5.6/7.5

*

27.1/31.3

37.1/42.3

40/45

40/45

 

 

 

 

 

 

 

 

 

 

 

 

2NH04500506

1

3.8/5.0

*

18.1/20.8

25.8/29.3

30/30

30/30

024

208/230-1-60

11.2

60.0

1.1

2.6

2NH04500706

2

5.6/7.5

*

27.1/31.3

37.1/42.3

40/45

40/45

 

 

 

 

 

 

2NH04501006

2

7.5/10.0

*

36.1/41.7

48.4/55.3

50/60

50/60

 

 

 

 

 

 

2NH04500506

1

3.8/5.0

*

18.1/20.8

25.8/29.3

30/30

30/30

030

208/230-1-60

12.0

73.0

1.1

2.6

2NH04500706

2

5.6/7.5

*

27.3/31.3

37.1/42.3

40/45

40/45

2NH04501006

2

7.5/10.0

*

36.1/41.7

48.4/55.3

50/60

50/60

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501506

2

11.3/15.0

*

54.2/62.5

71.0/81.4

80/90

80/90

036

208/230-1-60

17.3

94.0

1.1

3.5

2NH04501006

2

7.5/10.0

*

36.1/41.7

49.5/56.5

50/60

50/60

2NH04501506

2

11.3/15.0

*

54.2/62.5

72.1/82.5

80/90

80/90

 

 

 

 

 

 

 

 

 

 

 

 

2NH04500506

1

3.8/5.0

*

18.1/20.8

30.2/30.4

40/40

40/40

042

208/230-1-60

20.5

120.0

1.1

3.5

2NH04500706

2

5.6/7.5

*

27.1/31.3

38.2/43.4

50/50

50/50

2NH04501006

2

7.5/10.0

*

36.1/41.7

49.5/56.5

50/60

50/60

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501506

2

11.3/15.0

*

54.2/62.5

72.1/82.5

80/90

80/90

 

 

 

 

 

 

2NH04501006

2

7.5/10.0

*

36.1/41.7

50.1/57.1

60/60

60/60

048

208/230-1-60

24.4

140.0

1.3

4.0

2NH04501506

2

11.3/15.0

*

54.2/62.5

72.1/83.1

80/90

80/90

2NH04502006

2

15.0/20.0

*

72.2/83.3

95.3/109.2

100/110

100/110

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502506

2

18.8/25.0

*

90.3/104.2

117.8/135.2

125/150

125/150

 

 

 

 

 

 

2NH04501006

2

7.5/10.0

*

36.1/41.7

53.9/60.8

70/70

70/70

060

208/230-1-60

28.9

165.0

1.3

7.0

2NH04501506

2

11.3/15.0

*

54.2/62.5

76.5/86.9

80/90

80/90

2NH04502006

2

15.0/20.0

*

72.2/83.3

99.0/112.9

100/125

100/125

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502506

2

18.8/25.0

*

90.3/104.2

121.6/139.0

125/150

125/150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

208/230-3-60

10.9

78.0

1.1

3.5

2NH04501025

1

7.5/10.0

*

20.8/24.1

30.4/34.4

35/35

35/35

2NH04501525

1

11.3/15.0

*

31.3/36.1

43.5/49.5

45/50

45/50

 

 

 

 

 

 

042

208/230-3-60

14.1

110.0

1.1

3.5

2NH04501025

1

7.5/10.0

*

20.8/24.1

30.4/34.4

35/35

35/35

2NH04501525

1

11.3/15.0

*

31.3/36.1

43.5/49.5

45/50

45/50

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501025

1

7.5/10.0

*

20.8/24.1

31.1/35.1

35/40

35/40

048

208/230-3-60

14.1

105.0

0.7

4.0

2NH04501525

1

11.3/15.0

*

31.3/36.1

44.1/50.1

45/60

45/60

2NH04502025

2

15.0/20.0

*

41.7/48.1

57.1/65.1

60/70

60/70

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502525

2

18.8/25.0

*

52.1/60.1

70.2/80.2

80/90

80/90

 

 

 

 

 

 

2NH04501025

1

7.5/10.0

*

20.8/24.1

34.8/38.8

40/40

40/40

060

208/230-3-60

16.0

125.0

1.3

7.0

2NH04501525

1

11.3/15.0

*

31.3/36.1

47.8/53.9

50/60

50/60

2NH04502025

2

15.0/20.0

*

41.7/48.1

60.9/68.9

70/70

70/70

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502525

2

18.8/25.0

*

52.1/60.1

73.9/83.9

80/90

80/90

036

460-3-60

5.8

40.0

0.6

1.8

2NH04501046

1

10.0 **

12.0

17.3

20

20

2NH04501546

1

15.0 **

18.0

24.8

25

25

 

 

 

 

 

 

042

460-3-60

7.1

54.0

0.6

1.8

2NH04501046

1

10.0 **

12.0

17.3

20

20

2NH04501546

1

15.0 **

18.0

24.8

25

25

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501046

1

10.0 **

12.0

17.5

20

20

048

460-3-60

7.1

55.0

0.6

2.0

2NH04501546

1

15.0 **

18.0

25.1

30

30

2NH04502046

2

20.0 **

24.1

32.6

35

35

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502546

2

25.0 **

30.1

40.1

45

45

 

 

 

 

 

 

2NH04501046

1

10.0 **

12.0

19.4

20

20

060

460-3-60

8.0

67.0

0.7

3.5

2NH04501546

1

15.0 **

18.0

26.9

30

30

2NH04502046

2

20.0 **

24.1

34.4

35

35

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502546

2

25.0 **

30.1

42.0

45

45

 

 

 

 

 

 

 

 

 

 

 

 

 

036

575-3-60

4.5

32.0

0.4

1.5

2NH04501058

1

10.0 ***

9.6

13.9

15

15

2NH04501558

1

15.0 ***

14.4

19.9

20

20

 

 

 

 

 

 

042

575-3-60

5.8

44.0

0.4

1.5

2NH04501058

1

10.0 ***

9.6

13.9

15

15

2NH04501558

1

15.0 ***

14.4

19.9

20

20

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501058

1

10.0 ***

9.6

14.0

15

15

048

575-3-60

5.6

44.0

0.6

1.6

2NH04501558

1

15.0 ***

14.4

20.0

25

25

2NH04502058

2

20.0 ***

19.2

26.1

30

30

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502558

2

25.0 ***

24.1

32.1

35

35

 

 

 

 

 

 

2NH04501058

1

10.0 ***

9.6

15.5

20

20

060

575-3-60

6.4

50.0

0.6

2.8

2NH04501558

1

15.0 ***

14.4

21.5

25

25

2NH04502058

2

20.0 ***

19.2

27.6

30

30

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502558

2

25.0 ***

24.1

33.6

35

35

1= Dual element, time delay type.

2= Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.

**= KW listed is for 480 volts, use table on previous page for 460 volts.

***= KW listed is for 600 volts, use table on previous page for 575 volts.

6

Unitary Products Group

Loading...
+ 11 hidden pages