York 036-048, 90, 60 User Manual

0 (0)
York 036-048, 90, 60 User Manual

TECHNICAL GUIDE SPLIT-SYSTEM HEAT PUMPS 10 SEER – R-22

MODELS:

E*RA036 THRU 060

(3 THRU 5 NOMINAL TONS, 3 PH)

MODELS: 036-048 (3 PH)

MODELS: 060, 090 (3 PH)

 

ISO 9001

LISTED

Certified Quality

Management System

Due to continuous product improvement, specifications are subject to change without notice.

Visit us on the web at www.york.com

Additional rating information can be found at www.ari.org/aridirectory.

279104-YTG-B-0307

DESCRIPTION

The 10 SEER Series heat pumps is the outdoor part of a versatile system of heat pumps. It is designed to be custommatched with one of UPG’s complete line of evaporator sections, with each serving a specific function. Matching Air Handlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are available, if required. Add-On coils are available for use with upflow, downflow, or horizontal furnaces and air handlers.

WARRANTY

1-year limited parts warranty.

5-year limited compressor warranty.

FEATURES

QUALITY COILS - The coil is constructed of copper tube and aluminum fins.

COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard.

PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the compressor.

DURABLE FINISH - Cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.

LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof.

TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.

LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds.

LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.

EASY SERVICE ACCESS - Fully exposed refrigerant connections, a single panel covering the electrical controls, and the molex plug in the control box connecting the condenser fan make for easy servicing of the unit.

SECURED SERVICE VALVES - Secured re-usable service valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.

U.L. and C.U.L. listed - approved for outdoor application.

Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

279104-YTG-B-0307

Physical and Electrical Data

 

MODEL

E1RA036S25

E2RA048S25

E1RA060S25

E1RA036S46

E2RA048S46

E1RA060S46

Unit Supply Voltage

 

 

208/230-3-60

 

 

460 - 3 - 60

 

Normal Voltage Range 1

 

187 to 252

 

 

432 to 504

 

Minimum Circuit Ampacity

15.0

18.9

24.5

8.0

10.1

12.0

Max. Qvercurrent Device Amps 2

25

30

40

15

15

20

Compressor Type3

 

Inertia

ScrollD

ScrollC

Inertia

ScrollD

ScrollC

Compressor Amps

 

Rated Load

10.9

14.1

18.6

5.8

7.0

9.0

 

 

 

Locked Rotor

78

125

128

40

55

63

Crankcase Heater

 

 

Yes

No

No

Yes

No

No

Fan Motor Amps

 

Rated Load

1.4

1.3

1.3

.8

.7

.8

Fan Diameter Inches

 

 

18

22

24

18

22

24

Fan Motor

 

 

Rated HP

1/4

1/4

1/4

1/4

1/5

1/4

 

 

 

Nominal RPM

1,100

850

850

1,100

825

850

 

 

 

Nominal CFM

2,750

3,500

3,100

2,750

3,500

3,100

Coil

Face Area Sq. Ft.

12.58

19.65

18.00

12.58

19.65

18.00

 

Rows Deep

1

1

2

1

1

2

 

Fin / Inches

14

13

14

14

13

14

Liquid Line

Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

7/8

7/8

3/4

7/8

7/8

Unit Charge (Lbs. - Oz.) 4

5 - 12

8 - 3

11 - 3

5 - 12

8 - 3

11 - 3

Charge Per Foot, Oz.

 

.68

.70

.70

.68

.70

.70

Operating Weight Lbs.

178

232

243

178

232

243

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker.

3.All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon

Crequest.

 

 

DIMENSIONS

 

 

 

 

 

 

Unit

Dimensions

 

Refrigerant

A

 

 

Connection

 

Model

(Inches)

 

 

 

 

Service Valve Size

 

 

 

 

 

 

 

 

 

A1

B

C

Liquid

Vapor

 

 

036

25

35

23

 

3/4”

 

 

048

33

37

27

3/8”

7/8”

 

B

060

26

43

32

 

7/8”

 

 

1.

Including fan guard.

 

 

 

2

Unitary Products Group

 

 

 

 

 

279104-YTG-B-0307

Additional R-22 Charge / Orifice Size for Various Matched Systems

 

 

 

 

 

 

 

 

 

Outdoor Unit

E1RA036S(25,46)

 

E1RA048S(25,46)

 

E1RA060S(25,46)

 

Unit Orifice (s) 1

71, 81

 

81, 84, 87

 

99

 

Factory R-22 Charge, lbs-oz

5 - 12

 

8 - 3

 

11 - 3

 

 

 

 

 

 

Indoor Coil

 

System Orifice = Additional Charge, Oz

 

 

FC/MC/PC35(B,C)3X

81 + 8

 

 

 

FC/MC/PC/UC36(A,B,C)3X

71 + 7

 

 

 

FC/MC/PC/UC42(B,C)3X

81 + 8

 

 

 

FC/MC/PC/UC48C3X

 

87 + 6

 

 

FC/MC/PC/UC48D3X

 

87 + 6

 

 

FC/MC/PC/UC60C3X

 

84 + 4

 

99 + 0

 

FC/MC/PC/UC60D3X

 

84 + 4

 

99 + 0

 

AHP36C3X

81 + 13

 

84 + 3

 

 

AHP42C3X

81 + 13

 

84 + 3

 

 

AHP/SHP48D3X

 

84 + 4

 

99 + 0

 

AHP60D3X

 

84 + 4

 

99 + 0

 

G1NA036S17L

71 + 7

 

 

 

G1NA048S21D

71 + 7

 

81 + 8

 

 

G1NA048S24P

 

81 + 8

 

 

G1UA048S21/24

81 + 13

 

84 + 3

 

 

G1UA060S24

 

84 + 4

 

99 + 0

 

G1FA048S21/24

81 + 13

 

84 + 3

 

 

G1FA060S24

 

84 + 4

 

99 + 0

 

G2FD042S21

81 + 8

 

 

 

G2FD048S21/24

 

87 + 6

 

 

G2FD060S24

 

84 + 4

 

99 + 0

 

FOOTNOTES:

 

 

 

 

 

 

1. These orifices are packed in the instruction/warranty packet of each outdoor unit.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.

2.Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaportor + adder for line set.

5.If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.

Unitary Products Group

3

279104-YTG-B-0307

COOLING CAPACITY - With Air Handler Coils

 

AIR HANDLER

 

COIL1

 

 

COOLING

 

 

 

 

 

 

 

 

 

 

 

 

UNIT MODEL

 

ELECTRIC 2

 

RATED

NET MBH

SEER

SEER

 

MODEL

W

MODEL

EER

 

HEAT KW

CFM

 

 

W/O TXV

WITH TXV3

 

TOTAL

SENS.

 

 

 

 

 

 

 

3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD

 

 

 

 

 

MA12BN2,4

10

17

FC/MC35B3X

1250

34.4

25.3

10

8.95

 

 

 

 

 

 

 

 

 

 

 

E1RA036S(25,46)

MA12BN2,4

10

17

FC/MC36B3X

1250

34.4

25.3

10

8.95

 

 

 

 

 

 

 

 

 

 

MA12BN2,4

10

17

FC/MC42B3X

1250

34.4

25.3

10

8.95

 

 

 

 

 

 

 

 

 

 

 

 

 

N1AHC1646

10, 15

21

G2FD042(S,H)21

1250

34.2

25.3

10

8.95

 

 

 

 

 

 

 

 

 

 

 

 

MA16CN4

10, 15

21

FC/MC48C3X

1600

45.5

33.7

10

9.45

 

 

 

 

 

 

 

 

 

 

 

 

MA20DN2

10, 15, 25

24

FC/MC48D3X

1725

45.5

33.7

10

9.45

E2RA048S(25,46

 

 

 

 

 

 

 

 

 

 

MA20DN4

10, 15, 29

24

FC/MC48D3X

1725

45.5

33.7

10

9.45

 

 

 

 

 

 

 

 

 

 

 

 

N1AHC1646

10, 15

21

G2FD048(S,H)21

1600

45.5

33.7

10

9.45

 

 

 

 

 

 

 

 

 

 

 

 

N1AHD2046

10, 15, 29

24

G2FD048(S,H)24

1600

45.5

33.7

10

9.45

 

 

 

 

 

 

 

 

 

 

 

E1RA060S(25,46)

MA20DN4

10, 15, 29

24

FC/MC60D3X

2000

57.0

41.0

10

9.80

 

 

 

 

 

 

 

 

 

 

N1AHD2046

10, 15, 29

24

G2FD048(S,H)24

1700

57.0

41.0

10

9.80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 PH 10 SEER HP WITH AHP / SHP / F2RP / RC / FP / FC4,5

 

 

 

 

 

F2RP/FP036

5, 8, 10, 15, 19

21

1250

34.0

24.9

10

9.00

 

 

 

 

 

 

 

 

 

 

 

E1RA036S25

F2RD/FP042

5, 8, 10, 15

21

1250

34.0

25.6

10

9.00

 

 

 

 

 

 

 

 

 

 

AHP36C3X

10, 15

21

1250

34.0

25.6

10

9.00

 

 

 

 

 

 

 

 

 

 

 

 

 

AHP42C3X

10, 15, 18

21

1250

34.0

25.6

10

9.00

 

 

 

 

 

 

 

 

 

 

 

 

F2FP048

5, 8, 10, 15, 20, 25

24

1600

45.0

33.5

10

9.40

E2RA048S25

 

 

 

 

 

 

 

 

 

 

F2FP060

5, 8, 10, 15, 20, 25

24

1600

46.5

34.4

10

9.60

 

 

 

 

 

 

 

 

 

 

 

 

AHP/SHP48D3X

10, 15, 18

24

1600

46.5

34.4

10

9.60

 

 

 

 

 

 

 

 

 

 

 

E1RA060S25

F2FP060

5, 8, 10, 15, 20, 25

24

1700

56.0

40.0

10

9.40

 

 

 

 

 

 

 

 

 

 

AHP/SHP60D3X

10, 15

24

1700

56.0

40.0

10

9.40

 

 

 

 

 

 

 

 

 

 

 

 

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.

KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

1.G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.

2.Single phase units require single phase 2HK heaters.

3.TXV = Use 1TV700 Series Kit.

4.To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC. models. All ratings remain the same.

5.FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D. standard.

-= Not applicable

4

Unitary Products Group

279104-YTG-B-0307

COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils

 

FURNACE**

COIL

 

 

 

COOLING

 

 

 

 

 

 

 

 

 

 

 

 

UNIT MODEL

CFM RANGE

 

RATED

NET MBH

 

SEER

SEER + TXV1

 

W

MODEL

 

EER

 

(MIN.-MAX.)

 

 

CFM

TOTAL

SENS.

 

W/O TXV

+ TDR*

 

 

 

21,24

G1FA048S21

1250

34.4

24.7

 

10

9.05

 

 

 

 

 

 

 

 

 

 

 

 

 

17

G1NA036S17L

1250

35.0

26.2

 

10

9.00

 

 

 

 

 

 

 

 

 

 

 

 

 

21

G1NA048S21D

1250

35.0

26.2

 

10

8.95

 

1100

 

 

 

 

 

 

 

 

 

E1RA036S(25,46

21,24

G1UA048S21

1250

34.4

24.7

 

10

9.05

1400

 

 

 

 

 

 

 

 

 

21

G2FD042S21

1250

34.2

25.3

 

10

8.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17,21

FC/MC/PC35*3X

1250

34.4

24.7

 

10

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

14,17,21

FC/MC/PC/UC36*3X

1250

34.4

24.7

 

10

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

17,21

FC/MC/PC/UC42*3X

1250

34.4

24.7

 

10

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

21,24

G1FA048S21

1600

45.5

32.7

 

10

9.30

 

 

 

 

 

 

 

 

 

 

 

 

 

21

G1NA048S21D

1600

45.0

31.2

 

10

9.50

 

1400

 

 

 

 

 

 

 

 

 

E2RA048S(25,46

21,24

G1UA048S21

1600

45.5

32.7

 

10

9.30

1800

 

 

 

 

 

 

 

 

 

21,24

G2FD048(S,H)21,24

1600

45.5

33.7

 

10

9.40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

FC/MC/PC/UC48C3X

1600

45.5

32.7

 

10

9.30

 

 

 

 

 

 

 

 

 

 

 

 

 

24

FC/MC/PC/UC48D3X

1600

45.5

32.7

 

10

9.30

 

 

 

 

 

 

 

 

 

 

 

 

 

21,24

G1FA060S21,24

1700

57.0

41.0

 

10

9.80

 

 

 

 

 

 

 

 

 

 

 

 

1600

21,24

G1UA060S21,24

1700

57.0

41.0

 

10

9.80

 

 

 

 

 

 

 

 

 

 

E1RA060S(25,46)

24

G2FD060(S,H)24

1700

57.0

41.0

 

10

9.80

2100

 

 

 

 

 

 

 

 

 

 

 

 

21

FC/MC/PC/UC60C3X

1725

57.0

41.0

 

10

9.80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

FC/MC/PC/UC60D3X

2000

57.0

41.0

 

10

9.80

 

 

 

 

 

 

 

 

 

 

 

1. TXV = Use 1TV700 Series Kit.

 

 

 

 

 

 

 

 

*Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one.

**Refer to Quick Selection Chart for specific furnace match-up.

Unitary Products Group

5

Loading...