YOKOGAWA F3SP21-0N, F3SP25-2N, F3SP35-5N, F3SP28-3N, F3SP38-6N Manual

...
0 (0)

User’s

Manual

Hardware Manual

IM 34M6C11-01E

IM 34M6C11-01E

6th Edition

Yokogawa Electric Corporation

i

Applicable Product:

Range-free Multi-controller FA-M3

The document number and document model code for this manual are given below.

Refer to the document number in all communications; also refer to the document number or the document model code when purchasing additional copies of this manual.

Document No.

:

IM 34M6C11-01E

Document Model Code

:

DOCIM

Media No. IM 34M6C11-01E (FD)

6th Edition : May. 2001 (CR)

IM 34M6C11-01E 6th Edition : May 10, 2001-00

All Rights Reserved Copyright 1992, Yokogawa Electric Corporation

ii

Important

About This Manual

-This Manual should be passed on to the end user.

-Before using the controller, read this manual thoroughly to have a clear understanding of the controller.

-This manual explains the functions of this product, but there is no guarantee that they will suit the particular purpose of the user.

-Under absolutely no circumstances may the contents of this manual be transcribed or copied, in part or in whole, without permission.

-The contents of this manual are subject to change without prior notice.

-Every effort has been made to ensure accuracy in the preparation of this manual. However, should any errors or omissions come to the attention of the user, please contact the nearest Yokogawa Electric representative or sales office.

Safety Precautions when Using/Maintaining the Product

-The following safety symbols are used on the product as well as in this manual.

Danger. This symbol on the product indicates that the operator must follow the instructions laid out in this instruction manual to avoid the risk of personnel injuries, fatalities, or damage to the instrument. The manual describes what special care the operator must exercise to prevent electrical shock or other dangers that may result in injury or the loss of life.

Protective Ground Terminal. Before using the instrument, be sure to ground this terminal.

Function Ground Terminal. Before using the instrument, be sure to ground this terminal.

Alternating current. Indicates alternating current.

Direct current. Indicates direct current.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

iii

The following symbols are used only in the instruction manual.

WARNING

Indicates a “Warning”.

Draws attention to information essential to prevent hardware damage, software damage or system failure.

CAUTION

Indicates a “Caution”

Draws attention to information essential to the understanding of operation and functions.

TIP

Indicates a “TIP”

Gives information that complements the present topic.

SEE ALSO

Indicates a “SEE ALSO” reference.

Identifies a source to which to refer.

-For the protection and safe use of the product and the system controlled by it, be sure to follow the instructions and precautions on safety stated in this manual whenever handling the product. Take special note that if you handle the product in a manner other than prescribed in these instructions, the protection feature of the product may be damaged or impaired. In such cases, Yokogawa cannot guarantee the quality, performance, function and safety of the product.

-When installing protection and/or safety circuits such as lightning protection devices and equipment for the product and control system as well as designing or installing separate protection and/or safety circuits for fool-proof design and fail-safe design of processes and lines using the product and the system controlled by it, the user should implement it using devices and equipment, additional to this product.

-If component parts or consumable are to be replaced, be sure to use parts specified by the company.

-This product is not designed or manufactured to be used in critical applications which directly affect or threaten human lives and safety — such as nuclear power equipment, devices using radioactivity, railway facilities, aviation equipment, air navigation facilities, aviation facilities or medical equipment. If so used, it is the user’s responsibility to include in the system additional equipment and devices that ensure personnel safety.

-Do not attempt to modify the product.

Exemption from Responsibility

-Yokogawa Electric Corporation (hereinafter simply referred to as Yokogawa Electric) makes no warranties regarding the product except those stated in the WARRANTY that is provided separately.

-Yokogawa Electric assumes no liability to any party for any loss or damage, direct or indirect, caused by the user or any unpredictable defect of the product.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

iv

Software Supplied by the Company

-Yokogawa Electric makes no other warranties expressed or implied except as provided in its warranty clause for software supplied by the company.

-Use the software with one computer only. You must purchase another copy of the software for use with each additional computer.

-Copying the software for any purposes other than backup is strictly prohibited.

-Store the original media, such as floppy disks, that contain the software in a safe place.

-Reverse engineering, such as decompiling of the software, is strictly prohibited.

-No portion of the software supplied by Yokogawa Electric may be transferred, exchanged, or sublet or leased for use by any third party without prior permission by Yokogawa Electric.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

v

General Requirements for Using the FA-M3 Controller

Avoid installing the FA-M3 controller in the following locations:

-Where the instrument will be exposed to direct sunlight, or where the operating temperature exceeds the range 0°C to 55°C (0°F to 131°F).

-Where the relative humidity is outside the range 10 to 90%, or where sudden temperature changes may occur and cause condensation.

-Where corrosive or flammable gases are present.

-Where the instrument will be exposed to direct mechanical vibration or shock.

-Where the instrument may be exposed to extreme levels of radioactivity.

Use the correct types of wire for external wiring:

-Use copper wire with temperature ratings greater than 75°C.

Securely tighten screws:

-Securely tighten module mounting screws and terminal screws to avoid problems such as faulty operation.

-Tighten terminal block screws with the correct tightening torque as given in this manual.

Securely lock connecting cables:

-Securely lock the connectors of cables, and check them thoroughly before turning on the power.

Interlock with emergency-stop circuitry using external relays:

-Equipment incorporating the FA-M3 controller must be furnished with emergency-stop circuitry that uses external relays. This circuitry should be set up to interlock correctly with controller status (stop/run).

Ground for low impedance:

-For safety reasons, connect the [FG] grounding terminal to a Japanese Industrial Standards (JIS) Class 3 Ground. For compliance to CE Marking, use cables such as twisted cables which can ensure low impedance even at high frequencies for grounding.

Configure and route cables with noise control considerations:

-Perform installation and wiring that segregates system parts that may likely become noise sources and system parts that are susceptible to noise. Segregation can be achieved by measures such as segregating by distance, installing a filter or segregating the grounding system.

Configure for CE Marking Conformance:

-For compliance to CE Marking, perform installation and cable routing according to the description on compliance to CE Marking in the “Hardware Manual” (IM34M6C11-01E).

Keep spare parts on hand:

-Stock up on maintenance parts including spare modules, in advance.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

vi

Discharge static electricity before operating the system:

-Because static charge can accumulate in dry conditions, first touch grounded metal to discharge any static electricity before touching the system.

Never use solvents such as paint thinner for cleaning:

-Gently clean the surfaces of the FA-M3 controller with a cloth that has been soaked in water or a neutral detergent and wringed.

-Do not use volatile solvents such as benzine or paint thinner or chemicals for cleaning, as they may cause deformity, discoloration, or malfunctioning.

Avoid storing the FA-M3 controller in places with high temperature or humidity:

-Since the CPU module has a built-in battery, avoid storage in places with high temperature or humidity.

-Since the service life of the battery is drastically reduced by exposure to high temperatures, take special care (storage temperature should be from –20 °C to 75°C).

-There is a built-in lithium battery in a CPU module and temperature control module which serves as backup power supply for programs, device information and configuration information. The service life of this battery is more than 10 years in standby mode at room temperature. Take note that the service life of the battery may be shortened when installed or stored at locations of extreme low or high temperatures. Therefore, we recommend that modules with built-in batteries be stored at room temperature.

Always turn off the power before installing or removing modules:

-Failing to turn off the power supply when installing or removing modules, may result in damage.

Do not touch components in the module:

-In some modules you can remove the right-side cover and install ROM packs or change switch settings. While doing this, do not touch any components on the printed-circuit board, otherwise components may be damaged and modules may fail to work.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

vii

Introduction

„ Overview of the Manual

This manual explains the configuration, specifications and installation of the Range-Free Multi-controller FA-M3. It also discusses the individual specifications of power supply modules, base modules, I/O modules, cables and terminal block units.

„ Configuration of the Manual

This manual consists of two parts.

z Part A Standard Version

The main part of this manual explains all the details of the FA-M3 system except for those of the FA-M3 Value version.

z Part B FA-M3 Value (F3SC21-1N) Version

The second part of the manual discusses the details specific to the FA-M3 Value (F3SC21-1N).

Chapters A3 (Installation and Wiring), A4 (Test Runs and Troubleshooting) and A5 (Maintenance and Inspection) are common to both the standard FA-M3 and the FA-M3 Value. Be sure to read these chapters before using the FA-M3 Value.

Other Instruction Manuals

-For products other than the power supply module, base module, I/O module, cable and terminal block unit, refer to their respective manuals.

Trademarks

-Microsoft Windows, Windows 95, Windows 98 and Windows NT are registered trademarks of Microsoft Corporation, USA.

-Ethernet is a registered trademark of XEROX Corporation.

-The trade and company names that are referred to in this document are either trademarks or registered trademarks of their respective companies.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

Blank Page

TOC-1

FA-M3

Hardware Manual

IM 34M6C11-02E 6th Edition

CONTENTS

Applicable Product:...................................................................................

i

Important

...................................................................................................

ii

Introduction.............................................................................................

vii

A1.

System ...............................................................Configuration

A1-1

 

A1.1 ...........................................................................

System Configuration

A1-1

 

A1.2 ......................................................

Restrictions on Installing Modules

A1-3

 

A1.3

Peripheral Tools Supporting the Program Development of

 

 

......................................................................................................

FA - M3

A1-7

A2.

Specifications .............................................and Configuration

A2-1

 

A2.1 ........................................................................................

Specifications

A2-1

 

A2.2 ..........................................................

FA - M3 Controller Configuration

A2-2

 

A2.3 .........................................................................

Power Supply Modules

A2-9

 

A2.4 ......................................................................................

Base Modules

A2-13

 

A2.5 ..........................................................................................

I/O Modules

A2-14

(1)

F3XH04-3N High-speed Input Module.......................................

A2-16

(2)

F3XA08-1N/F3XA08-2N AC Input Modules...............................

A2-21

(3)

F3XC08-0N No-voltage Contact Input Module ..........................

A2-23

(4)

F3XD08-6F DC Input Module ....................................................

A2-24

(5)

F3XD16-3F/F3XD16-4F/F3XD16-3H DC Input Modules...........

A2-25

(6)

F3XD32-3F/F3XD32-4F/F3XD32-5F DC Input Modules ...........

A2-27

(7)

F3XD64-3F/F3XD64-4F DC Input Modules...............................

A2-29

(8)

F3XD08-6N DC Input Module ....................................................

A2-31

(9)

F3XD16-3N/F3XD16-4N DC-Input Modules..............................

A2-33

(10)

F3XD32-3N/F3XD32-4N/F3XD32-5N DC Input Modules..........

A2-35

(11)

F3XD64-3N/F3XD64-4N DC Input Modules ..............................

A2-37

(12)

F3XD64-6M DC Input Module....................................................

A2-39

(13)

F3YD04-7N Transistor Output Module ......................................

A2-40

(14)

F3YA08-2N Triac Output Module ...............................................

A2-42

(15)

F3YC08-0C/F3YC08-0N Relay Output Module ........................

A2-44

(16)

F3YD08-6A/F3YD08-6B Transistor Output Modules .................

A2-46

(17)

F3YD14-5A/F3YD14-5B Transistor Output Modules .................

A2-48

(18)

F3YC16-0N Relay Output Module .............................................

A2-50

(19)

F3YD32-1A/F3YD32-1B Transistor Output Modules .................

A2-52

(20)

F3YD32-1T TTL Output Module.................................................

A2-54

IM 34M6C11-01E 6th Edition : May 10, 2001-00

 

 

 

 

TOC-2

 

 

(21) F3YD64-1F Transistor Output Module.......................................

A2-56

 

 

(22)

F3YD64-1A Transistor Output Module.......................................

A2-58

 

 

(23) F3YD64-1M Transistor Output Module ......................................

A2-60

 

 

(24)

F3WD64-3F/F3WD64-4F Input/Output Modules .......................

A2-62

 

 

(25)

F3WD64-3N/F3WD64-4N Input/output Modules .......................

A2-66

 

A2.6

ROM Packs ..........................................................................................

A2-70

 

A2.7

Cables...................................................................................................

A2-72

 

 

(1) Cables for Programming Tool ....................................................

A2-72

 

 

(2) CPU Port/9-pin D-sub Adapter Cable ........................................

A2-73

 

 

(3) Cables for Connector Terminal Blocks.......................................

A2-74

 

 

(4)

Fiber-Optic Cord ........................................................................

A2-75

 

 

(5)

Fiber-optic Cables......................................................................

A2-76

 

A2.8

Terminal Block Unit and Connector Terminal Block ......................

A2-78

 

 

(1)

TA40-0N Terminal Block Unit .....................................................

A2-78

 

 

(2) TA50-0N/TA50-1N Connector Terminal Block............................

A2-81

 

 

(3)

TA60-0N ....................................................................................

A2-83

 

A2.9

Module Current Consumption Tables ...............................................

A2-85

 

A2.10

External Power Supply .......................................................................

A2-88

 

A2.11

External Dimensions...........................................................................

A2-89

A3.

Installation and Wiring...............................................................

A3-1

 

A3.1

Environmental Conditions for Installation within a

 

 

 

Panel Enclosure ....................................................................................

A3-1

 

A3.2

Methods for Mounting the FA-M3 within a Panel Enclosure ...........

A3-3

 

A3.3

System Design Considerations .........................................................

A3-10

 

A3.4

Noise Control Considerations ...........................................................

A3-19

 

A3.5

Wiring the Power Supply Module ......................................................

A3-21

 

A3.6

Wiring I/O Modules..............................................................................

A3-24

 

A3.7

External Cable Routing Requirements..............................................

A3-32

 

A3.8

Calculating Power Consumption.......................................................

A3-33

 

A3.9

CE Marking Conformance ..................................................................

A3-34

A4

Test Runs and Troubleshooting................................................

A4-1

 

A4.1

Test Run Procedure ..............................................................................

A4-1

 

A4.2

Test Run Precautions ...........................................................................

A4-2

 

A4.3

Self-diagnostic Functions ....................................................................

A4-3

 

A4.4

Troubleshooting Procedure .................................................................

A4-9

 

A4.5

CPU Module Reset and Memory Clearance........................................

A4-9

A5

Maintenance and Inspection .....................................................

A5-1

 

A5.1

Replacing I/O Modules..........................................................................

A5-1

 

A5.2

Routine Inspection................................................................................

A5-2

IM 34M6C11-01E 6th Edition : May 10, 2001-00

 

 

TOC-3

Appendix A1 System-wide Restrictions on

 

Module Installation............................................

Appx.A1-1

Appendix A1.1 Checking Compliance with Restrictions on

 

 

Module Installation........................................................

Appx.A1-1

Appendix A1.2

Restrictions due to the Number of Slots....................

Appx.A1-4

Appendix A1.3

Restrictions due to the Size of Data Area ..................

Appx.A1-5

Appendix A1.4

Restrictions due to the Type of CPU Module .............

Appx.A1-7

FA-M3 Value (F3SC21-1N)

B1.

System Configuration................................................................

B1-1

 

B1.1

System Configuration...........................................................................

B1-1

 

B1.2

Restrictions on Module Installation ....................................................

B1-2

 

B1.3

Peripheral Tools Supporting the Program Development of

 

 

 

FA-M3......................................................................................................

B1-3

B2.

Specifications and Configuration .............................................

B2-1

 

B2.1

Specifications........................................................................................

B2-1

 

B2.2

System Configuration...........................................................................

B2-2

 

B2.3

Sequence CPU Module.........................................................................

B2-3

Revision Information.................................................................................

i

IM 34M6C11-01E 6th Edition : May 10, 2001-00

Blank Page

A1-1

A1. System Configuration

A1.1 System Configuration

„ Basic Configuration

Figure A1.1 shows the location of slots for installing CPU and I/O modules. A slot number consists of three digits of which the third digit is the unit number.

module

001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016

P

 

 

C

 

Main unit

U

I/O modules

Powersupply

 

 

 

 

FA010101.VSD

Figure A1.1 Slot Numbering

„ Concept of Unit

z Main Unit

A unit in which a CPU module is installed is referred to as a main unit. Thus a main unit is comprised of only one unit.

z Subunit

Subunits are used to increase the number of I/O ports. A maximum of seven subunits can be added to the system to deal with up to 8192 (depending on the CPU module model) I/O points.

Unit

I/O modules

Main

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13

 

Power

CPU

Add-on CPU module

 

 

 

 

Fiber-optic

500m

supply

module

With a maximum of three slots

 

 

 

FA-bus 2

module

 

 

 

 

 

 

 

 

 

 

 

modules

max.

 

 

 

 

 

 

 

 

 

 

 

 

 

Subunit

 

 

 

I/O modules

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13

 

 

 

 

 

 

 

 

 

 

 

 

FA010102.VSD

Figure A1.2 Main Unit and Subunit

IM 34M6C11-01E 6th Edition : May 10, 2001-00

YOKOGAWA F3SP21-0N, F3SP25-2N, F3SP35-5N, F3SP28-3N, F3SP38-6N Manual

A1-2

Example of Increasing the Number of I/O Points Using Fiber-optic FA-bus 2 Modules

You can install fiber-optic FA-bus 2 modules in both main and subunits and connect them with optical fiber cables. This enables distributed arrangement of remote I/O points, increase in the number of I/O points, and control of I/O modules via high-speed, noise-immune communication.

CPU module

Fiber-optic FA-bus 2 module

FA-M3 main unit

Power supply module

add-on sequence CPU modules (up to three)

Subunit 1

Power supply module

Subunit 2

Power supply module

Subunit 3

Power supply module

Subunit 4

Power supply module

Subunit 5

Power supply module

Subunit 6

Power supply module

Subunit 7

Power supply module

Example of I/O configuration (32 points)

224 points

(384 points without expansion module)

* denotes a fiber-optic FA-bus 2 module.

The maximum length of each optical fiber cable between units is 500m.

FA010103.VSD

Figure A1.3 I/O Expansion Using Fiber-optic FA-bus 2 Modules

-The maximum number of subunits that can be connected is 7.

Subunit numbers are determined depending on the setting of the rotary switch on the fiber-optic FA-bus 2 module mounted to a subunit.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A1-3

A1.2 Restrictions on Installing Modules

A1.2.1 Restrictions on Module Location

-A CPU module installed in slot 1 serves as the main CPU module.

-CPU modules installed in slots 2 to 4 serve as the add-on CPU modules.

-I/O modules may also be installed in slots 2 to 4. No add-on sequence CPU module or add-on BASIC CPU module can be installed in a slot with a slot number greater than those of the I/O modules.

-In an application where two or more CPU modules are installed, no I/O module can be installed between any two CPU modules.

Slot

1

2

3

4

5

6

Slot

1

2

3

4

5

6

 

 

 

 

 

 

 

No

No

 

1

2

3

4

5

6

Power supply module

Main CPU module

Add-on CPU module

I/O module

I/O module

 

 

Power supply module

Main CPU module

I/O module

Add-on CPU module

I/O module

 

 

Power supply module

Main CPU module

Unused

Add-on CPU module

I/O module

 

 

FA010201.VSD

' × '

Figure A1.4 Restrictions on Module Location

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A1-4

A1.2.2 Restrictions on CPU Module Installation

A maximum of four CPU modules can be installed in slots 1 to 4.

Table A1.1 Combinations of Main CPU Modules with Add-on CPU Modules

 

 

 

 

 

 

Add-on CPU Module

 

 

 

 

 

Qty.

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

F3SP21-0N

F3SP25-2N

F3SP35-5N

 

F3SP28-3N

F3SP38-6N

F3SP53-4H

F3SP58-6H

 

F3BP20-0N

F3BP30-0N

F3FP36-3N

 

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3SP21-0N

4

'

'

'

 

'

'

'

'

 

'

'

'

 

F3SP25-2N

4

'

'

'

 

'

'

'

'

 

'

'

'

Module

F3SP35-5N

4

'

'

'

 

'

'

'

'

 

'

'

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3SP28-3N

4

'

'

'

 

'

'

'

'

 

'

'

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU

F3SP38-6N

4

'

'

'

 

'

'

'

'

 

'

'

'

F3SP53-4H

4

'

'

'

 

'

'

'

'

 

'

'

'

 

 

 

Main

F3SP58-6H

4

'

'

'

 

'

'

'

'

 

'

'

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3BP20-0N

1

'

'

'

 

'

'

'

'

 

'

 

F3BP30-0N

1

'

'

'

 

'

'

'

'

 

'

 

F3FP36-3N

1

'

'

'

 

'

'

'

'

 

'

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1.2.3 Restrictions on I/O Module Installation

Table A1.2 shows the types of modules that each CPU module can access directly, as well as the maximum number of modules of each type that can be installed at the same time. The maximum number referred to here means a limit to the quantity of modules when a multiple of the same I/O module is installed.

-'’’ identifies an I/O module that can be installed without limitation on its quantity.

-’’ identifies an I/O module to which the CPU module in question cannot have direct access.

-Each numeral means the maximum number of I/O modules that can be installed, provided that they are of the same type.

In addition to the restrictions on the quantity of each I/O module, there are system-wide limitations to the quantity of I/O modules that can be installed. For more information, see Appendix A1, “System-wide Restrictions on Module Installation.”

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A1-5

Table A1.2 Modules that Each CPU can Access Directly and the Maximum Number that can be Installed (1 of 4)

 

 

 

 

 

 

 

 

 

 

 

Sequence CPU

 

 

 

 

 

 

 

 

 

BASIC CPU

Module Name

Model

 

F3SP21-0N

 

 

F3SP25-2N

 

 

F3SP35-5N

 

 

F3SP28-3N

 

 

F3SP38-6N

 

 

F3SP53-4H

 

 

F3SP58-6H

 

 

F3FP36-3N

 

 

F3BP20-0N

 

 

 

F3BP30-0N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3XA08-VN

'

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XH04-3N

16

 

16

 

16

 

16

 

16

 

16

 

16

 

16

 

16*2

16*2

 

F3XC08-0N

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XD08-6F

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XD08-6N

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

Input module

F3XD16-VF

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XD16-3H

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XD32-VF

64

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XD16-VN

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XD32-VN

64

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3XD64-VV

32

64

 

'

 

64

 

'

 

64

 

'

 

64

 

'

 

'

 

 

F3YA08-2N

'

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3YC08-0C

'

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3YC08-0N

'

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3YC16-0N

'

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

Output module

F3YD04-7N

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3YD08-6V

'

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3YD14-5V

'

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3YD32-1V

64

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

'

 

 

F3YD64-1V

32

64

 

'

 

64

 

'

 

64

 

'

 

64

 

'

 

'

 

I/O module

F3WD64-VF

32

64

 

'

 

64

 

'

 

64

 

'

 

64

 

'

 

'

 

F3WD64-VN

32

 

64

 

'

 

64

 

'

 

64

 

'

 

64

 

'

 

'

 

 

 

 

 

 

 

 

 

 

 

 

Analog input module

F3AD04-0N

36

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

F3AD08-1N

36

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

 

 

 

 

 

 

 

 

 

 

F3DA02-0N

36

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

Analog output module

F3DA04-1N

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

F3DA08-5N

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

Temperature control and monitoring

F3CT04-VN

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

module

V

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

 

F3CR04- N

 

 

 

 

 

 

 

 

 

 

PID control module

F3CV04-1N

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

28

 

Discontinuity detection module

F3HB08-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

F3LC11-1F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Personal computer link module

F3LC11-1N

2*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

F3LC11-2N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3LC12-1F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UT link module *9

F3LC51-2N

4

 

4

 

4

 

4

 

4

 

4

 

4

 

4

 

4

 

4

 

DeviceNet interface module

F3LD01-0N

16

 

16

 

16

 

16

 

16

 

16

 

16

 

16

 

16

 

16

 

Ethernet interface module

F3LE01-5T

2*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

6*1

 

GP-IB communication module

F3GB01-0N*7

8

 

 

8

 

 

8

 

 

8

 

 

8

 

 

8

 

 

8

 

 

8

 

 

8

 

 

8

 

 

 

RS-232-C communication module

F3RS22-0N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

36

 

RS-422-A communication module

F3RS41-0N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

36

 

Ladder communication module

F3RZ81-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

 

F3RZ91-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A1-6

Table A1.2 Modules That Each CPU Can Access Directly and the Maximum Number of Them That Can Be Installed (1 of 4)

 

 

 

 

 

 

 

Sequence CPU

 

 

 

 

BASIC CPU

 

 

Module Name

Model

F3SP21-0N

 

F3SP25-2N

 

F3SP35-5N

 

F3SP28-3N

 

F3SP38-6N

 

F3SP53-4H

 

F3SP58-6H

 

F3FP36-3N

 

 

F3BP20-0N

 

 

F3BP30-0N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FA link H module

F3LP02-0N

*3

*3

 

*3

 

*3

 

*3

 

*3

 

*3

 

*3

 

 

 

 

 

 

 

 

2*6

8*6

 

8*6

 

8*10

8*10

8*10

8*10

8*4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fiber-optic FA link H module

F3LP12-0N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*6

 

 

 

 

 

Fiber-optic FA-bus module

F3LR01-0N

*5

 

*5

 

*5

 

*5

 

*5

 

*5

 

*5

 

*5

 

*5

 

*5

 

 

 

 

 

7*6

 

7*6

 

7*6

 

7

 

7

 

7

 

7

 

7*6

 

7

 

7

 

 

Fiber-optic FA-bus 2 module

F3LR02-0N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High-speed counter module

F3XP01-0H

32

 

64

 

'

 

64

 

'

 

64

 

'

 

64

 

'

 

'

 

 

F3XP02-0H

32

 

64

 

'

 

64

 

'

 

64

 

'

 

64

 

'

 

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse input module

F3XS04-VN

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

Positioning module

F3YP04-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

(Model with multichannel pulse

F3YP08-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

output)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Positioning module

F3NC11-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

(Advanced model with positioning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3NC12-0N

32

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

pulse output)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Positioning module

F3NC51-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

(Model with speed-control voltage

F3NC52-0N

32

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

36

 

 

output)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Install modules whose module names and models are shaded in main units.

 

 

 

 

 

 

 

 

 

 

 

*1:

Each numeral means the total sum of personal computer link modules, Ethernet interface modules and GP-IB

 

communication modules (when in slave mode) that can be installed in combination. If two or more CPU modules

 

having different total sums of modules are installed, the smallest total sum takes precedence over the others.

*2:

The pulse-capture feature is disabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*3:

Each numeral means the total sum of FA link H modules and fiber-optic FA link H modules that can be installed in

 

combination. If two or more CPU modules having different total sums of modules are installed, the smallest total sum

 

takes precedence over the others.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*4:

Configure the module using the WideField or Ladder Diagram Support Program M3.

 

 

 

 

 

 

 

*5:

Each numeral means the total sum of the fiber-optic FA-bus and fiber-optic FA-bus 2 modules that can be installed in

 

the main unit. If two or more CPU modules having different total sums of modules are installed, the smallest total

 

sum takes precedence over the others. If subunits are divided into groups using fiber-optic FA-bus 2 modules, the

 

total sum may become larger than this depending on the mode of such division. For more information, see the Fiber-

 

optic FA-bus Module and Fiber-optic FA-bus Type 2 Module instruction manual (IM 34M6H45-01E).

*6:

FA link H, fiber-optic FA link H, and fiber-optic FA-bus 2 modules can be used with a sequence CPU module with

 

version 8 or later. For information on the version of a sequence CPU module, refer to the indication on its side.

*7:

The maximum number that can be installed differs depending on the operating mode. The left number in each field

 

is when the module is in the master mode, while the right number (or symbol) is when the module is in the slave

 

mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1.2.4 Restrictions due to Current Consumption

Design your system making sure that the total sum of current consumed by modules in each unit does not exceed the capacity of the power supply module.

For more information, see Section A2.8, “Tables of Modules’ Current Consumption.”

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A1-7

A1.3 Peripheral Tools Supporting the Program

Development of the FA-M3

You can conveniently create and debug your programs on your personal computer.

-FA-M3 Programming Tool WideField

-Ladder Diagram Support Program M3

-BASIC Programming Tool M3 for Windows

-Sequence Programming Tool for Windows POPMUSCAT

FA-M3

CD-ROM

Floppy disk

Personal

Enternet or cable for programming tools

 

 

 

 

computer

(RS-232-C)

 

 

 

Printer

FA010301.VSD

Figure A1.5 Support Tools for the FA-M3

IM 34M6C11-01E 6th Edition : May 10, 2001-00

Blank Page

A2-1

A2. Specifications and Configuration

A2.1 Specifications

„Common Specifications

Item

 

 

 

Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3PU10-0N

 

F3PU20-0N

F3PU16-0N

 

F3PU26-0N

 

Supply voltage range

 

 

 

100 to 240 V AC, single phase 50/60 Hz

24 V DC

 

Range of supply voltage change

 

85 to 264 V AC

50/60Hz±3Hz

15.6 to 31.2 V DC

 

Power consumption

 

 

 

35 VA

 

85 VA

15.4 W

 

 

33.1 W

 

 

 

 

5 MΩ min. when tested between a group of external

5 MΩ min. when tested across a group of external DC

 

Insulation resistance

 

 

AC terminals and the FG terminal using a 500 VDC

terminals and the FG terminal using a 500 VDC

 

 

 

 

insulation resistance tester

 

insulation resistance tester

 

Withstanding voltage

 

 

1500 V AC for one minute between a group of external

1500 V AC for one minute between a group of

 

 

 

AC terminals and the FG terminal

external DC terminals and the FG terminal

 

 

 

 

 

FAIL-signal contact output

Located on the front terminal block of power supply module; contact ratings: 24 V DC, 0.3 A (Equipped with both

 

normally-open and normally-closed terminals)

 

 

 

 

 

 

 

 

 

 

 

 

 

Allowable common mode voltage of FAIL-

120 V AC or DC max.

 

 

 

 

 

 

signal contact

 

 

(between the COM terminal of FAIL OUTPUT and the FG terminal)

 

 

 

 

Leakage current

 

 

 

3.5 mA max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allowable momentary power failure time

 

 

 

20 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tested using a noise simulator with a noise voltage of 1500 Vp-p, pulse width of 1 µ s, rise time of 1 ns, and

 

Noise immunity

 

 

repetition frequency of 25 to 60 Hz.

 

 

 

 

 

 

 

 

For CE Marking-compliant modules, compliant to EN61326-1 and EN61000-6-2

 

 

 

 

 

 

 

Tested in compliance with JIS C0911 under the following conditions:

 

 

 

 

 

 

 

- Frequency ranges:

10 to 55 Hz with an amplitude of 0.15 mm

 

 

 

 

Vibration resistance

 

 

 

 

 

55 to 150 Hz with an acceleration of 9.8 m/s2

(1 G)

 

 

 

 

- Direction and frequency of sweep: 10 times each in the X, Y, and Z directions

 

 

 

 

 

 

 

(one octave for one minute)

 

 

 

 

 

 

Shock resistance

 

 

Tested in compliance with JIS C0912 under the following conditions:

 

 

 

 

 

 

- Direction and frequency of sweep: 3 times each in the X, Y, and Z directions with an acceleration of 98 m/s2 (10 G)

 

 

 

 

 

Operating ambient temperature range

 

 

 

0˚C to 55˚C

 

 

 

 

Operating ambient humidity range

 

 

 

10 to 90% RH (non-condensing)

 

 

 

 

Operating environment

 

Must be free of corrosive gases, flammable gases or heavy dust.

 

Storge ambient temperature range

 

 

 

-20˚C to 75˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storage ambient humidity range

 

 

 

10 to 90% RH (non-condensing)

 

 

 

 

Grounding

 

 

 

 

 

JIS Class 3 grounding

 

 

 

 

Cooling method

 

 

 

 

 

Natural-air cooled

 

 

 

 

 

 

 

 

 

 

 

 

Mounting

 

 

 

Direct mounting with M4-size setscrews *1 or DIN-rail mounting (except for F3BU16-0N module)

 

Structure

 

 

 

 

 

Designed for mounting inside a panel enclosure

 

 

 

 

Altitude of installation

 

 

 

 

 

Max. of 2000 m above sea level

 

 

 

 

 

 

 

UL508-approved (File No. E188707)

 

 

 

 

 

 

 

Safety

Compliant to IEC1010-1 and EN61010-1

 

 

 

 

 

Compliance with safety

 

(Category II Installation *3 and Pollution Degree*4 2)

 

 

 

 

 

and EMC

 

 

EMI

: Compliant to EN61326 and EN55011, Group 1, Class A

 

 

 

 

standards *2

 

EMC

EMS

: Compliant to EN 61326 and EN 61000-6-2

 

 

 

 

 

 

 

Power supply harmonic wave: Compliant to EN 61000-3-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flicker

: Compliant to EN 61000-3-3

 

 

 

 

 

Finish color

 

 

Light cobalt blue, equivalent to Munsell 6.2PB 4.6/8.8;

 

 

 

 

 

 

 

Lampblack, equivalent to Munsell 0.8Y 2.5/0.4

 

 

 

 

 

 

 

 

 

 

 

 

 

External dimensions

 

 

See the dimensional figures in Section A2.10, “External Dimensions.”

 

 

 

 

*1:

For details on the number of mounting screws, see subsection A3.2.1.

 

 

 

 

 

*2:

For details on conforming modules, see “UL-certified and CE Mark-compliant Modules” (GS 34M6C11-21E) general

 

specification brochure.

 

 

 

 

 

 

 

 

*3:

The term installation category involves prescriptions on resistance to surge voltage reduction due to lightning and has four

 

categories. Installation category II applies to systems with rated voltage of 220/230/260V and applies to electrical

 

appliances, portable devices, etc.

 

 

 

 

 

 

*4:

The term pollution degree is related to the degree of contamination with solid, liquid or gaseous substance that may produce a

 

reduction of dielectric strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 normally

 

refers to environment contaminated only with dry, non-conductive electrical substance. However, when condensation

sometimes occurs, temporary conduction may occur. An environment which is contaminated only with electrical substance which are normally dry and non-conductive, but which may become temporarily conductive under occasional conditions of condensation.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-2

A2.2 FA-M3 Controller Configuration

A2.2.1 Components

„Module Names

Base module

Power supply module

CPU module

I/O modules and special modules

FA020201.VSD

Figure A2.1 FA-M3 Controller

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-3

„ FA-M3 Components

z Base Modules

 

Module Description

Model

 

Specifications

 

 

 

 

 

 

F3BU04-0N

Slot for F3PU10/16 power supply module plus 4

 

 

slots

(for CPU and I/O modules)

 

 

 

 

 

F3BU06-0N

Slot for F3PU10/16 power supply module plus 6

 

 

slots

(for CPU and I/O modules)

 

 

 

 

Base module

F3BU09-0N

Slot for F3PU20/26 power supply module plus 9

 

slots

(for CPU and I/O modules)

 

 

 

 

 

F3BU13-0N

Slot for F3PU20/26 power supply module plus 13

 

 

slots

(for CPU and I/O modules)

 

 

 

 

 

F3BU16-0N

Slot for F3PU20/26 power supply module plus 16

 

 

slots

(for CPU and I/O modules)

 

 

 

z Power Supply Modules

 

 

Module Description

Model

Specifications

 

 

 

 

 

 

F3PU10-0N

100 to 240 V AC, for F3BU04 and F3BU06

 

 

 

 

NEW

Power supply module

F3PU16-0N

24 V DC, for F3BU04 and F3BU06

 

 

 

F3PU20-0N

100-240 V AC, for F3BU09, F3BU13 and F3BU16

 

 

 

 

 

 

 

 

F3PU26-0N

24 V DC, for F3BU09, F3BU13 and F3BU16

 

 

 

 

 

z CPU Modules

Module Description

Model

Specifications

 

 

 

 

 

 

F3SP21-0N

10K ladder steps, with 0.18 to 0.36 s execution

 

 

time for basic instructions

 

 

 

 

 

F3SP25-2N

20K ladder steps, with 0.12 to 0.24 s execution

 

 

time for basic instructions

 

 

 

 

 

F3SP35-5N

100K ladder steps, with 0.09 to 0.18 s execution

 

 

time for basic instructions

 

 

 

 

 

F3SP28-3N

30K ladder steps, with 0.045 to 0.18 s execution

NEW

Sequence CPU module

time for basic instructions

 

 

(with memory)

F3SP38-6N

120K ladder steps, with 0.045 to 0.18 s

NEW

 

execution time for basic instructions

 

 

 

 

F3SP53-4H

56K ladder steps, with 0.0175 to 0.07 s

NEW

 

execution time for basic instructions

 

 

 

 

F3SP58-6H

120K ladder steps, with 0.0175 to 0.07 s

NEW

 

 

execution time for basic instructions

 

 

F3FP36-3N

For SFC/ladder language; 40K ladder steps

 

 

Contact coil 0.09 s per instruction

 

 

 

 

BASIC CPU module

F3BP20-0N

120 KB for BASIC

 

 

 

 

F3BP30-0N

510 KB for BASIC

 

 

 

 

 

 

 

z ROM Packs

Module Description

Model

Specifications

 

 

 

 

 

 

RK10-0N

5K ladder steps (F3SP21/30)

 

 

 

 

 

 

RK30-0N

20K ladder steps; 120KB for BASIC

 

 

(F3SP21/25/30/35, F3BP20)

 

 

 

 

 

RK50-0N

100K ladder steps; 510KB for BASIC

 

ROM pack

(F3SP21/25/35, F3BP30)

 

 

 

RK33-0N

56K ladder steps (F3SP21/25/28/35/38/53/58)

NEW

 

 

 

 

 

 

RK53-0N

100K ladder steps; 510KB for BASIC

NEW

 

F3SP21/25/35, F3BP30)

 

 

 

 

RK73-0N

120K ladder steps, (F3SP28/38/53/58)

NEW

 

 

 

 

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-4

z I/O Modules

Module Description

Model

 

Specifications

 

 

 

 

 

High-speed input module

F3XH04-3N

24 V DC high-speed input points with pulse-capture feature, 4 points

 

 

 

 

 

AC input module

F3XA08-1N

100 to 120 V AC, 8 points

 

 

 

 

 

F3XA08-2N

200 to 240 V AC, 8 points

 

 

 

 

 

 

 

 

F3XD08-6F

DC Input sink/source, 12 to 24 V DC, 8 points *1

NEW

 

 

 

 

 

F3XD16-3F

DC Input sink/source, 24 V DC, 16 points *1

NEW

 

 

 

 

 

F3XD16-4F

DC Input sink/source, 12 V DC, 16 points *1

NEW

 

F3XD16-3H

DC Input sink (positive common), 24 V DC, 16 points

NEW

 

(High speed input)

 

 

 

 

F3XD32-3F

DC Input sink/source, 24 V DC, 32 points *1

NEW

 

 

 

 

 

F3XD32-4F

DC Input sink/source, 12 V DC, 32 points *1

NEW

 

F3XD32-5F

DC Input sink/source, 5 V DC, 32 points *1

NEW

 

 

 

 

 

F3XD64-3F

DC Input sink/source, 24 V DC, 64 points *1

NEW

 

 

 

 

DC input module

F3XD64-4F

DC Input sink/source, 12 V DC, 64 points *1

NEW

 

F3XD08-6N

DC input sink/ source, 12 to 24 V DC, 8 points

 

 

 

 

 

 

F3XD16-3N

DC Input sink/source, 24 V DC, 16 points

 

 

 

 

 

 

F3XD16-4N

DC Input sink/source, 12 V DC, 16 points

 

 

 

 

 

 

F3XD32-3N

DC Input sink/source, 24 V DC, 32 points

 

 

 

 

 

 

F3XD32-4N

DC Input sink/source, 12 V DC, 32 points

 

 

 

 

 

 

F3XD32-5N

DC Input sink/source, 5 V DC, 32 points

 

 

 

 

 

 

F3XD64-3N

DC Input sink/source, 24 V DC, 64 points

 

 

 

 

 

 

F3XD64-4N

DC Input sink/source, 12 V DC, 64 points

 

 

 

 

 

 

F3XD64-6M

DC Input matrix scan, 12 to 24 V DC, 64 points

 

 

 

 

 

 

Voltage-free contact input

F3XC08-0N

No-voltage contact input, 8 points

 

module

 

 

 

 

 

Triac output module

F3YA08-2N

Triac output

(100 to 240 V AC), 2 A, 8 points

 

 

 

 

 

 

 

F3YC08-0C

Relay output

(24 V DC, 100 to 240 V AC), 2 A, 8 points, all

NEW

 

independent

 

Relay output module

 

 

 

F3YC08-0N

Relay output

(24 V DC, 100 to 240 V AC), 2 A, 8 points

 

 

 

 

 

 

F3YC16-0N

Relay output (24 V DC, 100 to 240 V AC), 2 A, 16 points

 

 

 

 

 

 

F3YD04-7N

TR output, 24 V DC, 2 A, all independent, 4 points

 

 

 

 

 

 

F3YD08-6A

TR output sink type, 12 to 24 V DC, 1 A, 8 points

 

 

 

 

 

 

F3YD08-6B

TR output source type, 12 to 24 V DC, 1 A, 8 points

 

 

 

 

 

 

F3YD14-5A

TR output sink type, 12 to 24 V DC, 0.5 A, 14 points

 

 

 

 

 

 

F3YD14-5B

TR output source type, 12 to 24 V DC, 0.5 A, 14 points

 

Transistor output module

 

 

 

F3YD32-1A

TR output sink type, 12 to 24 V DC, 0.1 A, 32 points

 

 

 

 

 

 

F3YD32-1B

TR output souece type, 12 to 24 V DC, 0.1 A, 32 points

 

 

 

 

 

 

F3YD32-1T

TTL output, 5 V DC, 16 mA, 32 points

 

 

 

 

 

 

F3YD64-1F

TR output sink type, 24 V DC, 0.1 A, 64 points *2

NEW

 

 

 

 

 

F3YD64-1A

TR output sink type, 24 V DC, 0.1 A, 64 points

 

 

 

 

 

 

F3YD64-1M

TR output matrix scan, 12 to 24 V DC, 0.1 A, 64 points ( 8 x 8 )

 

 

 

 

 

 

F3WD64-3F

DC Input sink/source, 24 V DC, 32 points *1

NEW

 

TR Output sink type, 24 V DC, 0.1 A, 32 points *2

 

F3WD64-4F

DC Input sink/source, 12 V DC, 32 points *1

NEW

I/O module

TR Output sink type, 12 V DC, 0.1 A, 32 points *2

F3WD64-3N

DC Input sink/source, 24 V DC, 32 points

 

 

 

 

 

TR Output sink type, 24 V DC, 0.1 A, 32 points

 

 

F3WD64-4N

DC Input sink/source, 12 V DC, 32 points *1

 

 

 

TR Output sink type, 12 V DC, 0.1 A, 32 points

 

*1: Input response of 100 s or more can be set when F3SP28, F3SP38, F3SP53 or F3SP58 module is used.

*2: The output HOLD/RESET for a fatal failure of a CPU can be set when F3SP28, F3SP38, F3SP53 or F3SP58 module is used.

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-5

z Analog I/O and Temperature Control Modules

Module Description

Model

Specifications

 

 

 

Analog input module

F3AD04-0N

0 to 5/1 to 5/-10 to 10 V DC input, 4 points

 

 

F3AD08-1N

0 to 5/1 to 5/-10 to 10 V DC input, 8 points

 

 

 

 

 

F3DA02-0N

–10 to 10 V/4 to 20 mA DC output, 2 points

Analog output module

 

 

F3DA04-1N

–10 to 10 V/4 to 20 mA DC output, 4 points

 

 

 

 

F3DA08-5N

–10 to 10 V DC output, 8 points

 

 

 

 

F3CT04-0N

Thermocouple or mV input, 0.5 second scan, 4

 

loops

 

 

Temperature

F3CT04-1N

Thermocouple or mV input, 0.5 second scan, 4 to

20 mA DC output, 4 loops

 

control/monitoring module

 

 

F3CR04-0N

RTD input, 0.5 second scan, 4 loops

 

 

 

 

 

F3CR04-1N

RTD input, 0.5 second scan, 4 to 20 mA DC

 

output, 4 loops

 

 

PID control module

F3CV04-1N

DC-voltage input, 0.5 second scan, 4 loops

 

 

 

z Communication Modules

Module Description

Model

 

Specifications

 

 

 

 

 

F3LC11-1F

1

RS-232-C port; 115.2 kbps max.

 

 

 

 

Personal computer link

F3LC11-1N

1

RS-232C port; 19200 bps max.

 

 

 

module

F3LC11-2N

1

RS-422-A/RS-485 port; 19200 bps max.

 

 

 

 

 

 

F3LC12-1F

2

RS-232-C ports; 115.2 kbps max.

 

 

 

 

UT link module

F3LC51-2N

1

RS-422-A/RS-485 port of 38400bps max. for

easy connection with a temperature controller

 

 

DeviceNet interface module

F3LD01-0N

1

DeviceNet port of 500 kpps max., with

master/scanner functions

 

 

Ethernet interface module

F3LE01-5T

10Mbps, 10BASE5/10BASE-T

RS-232-C communication

F3RS22-0N

2

RS-232-C ports; 19200 bps max.

module

 

 

 

RS-422 communication

F3RS41-0N

1

RS-422-A/RS-485 port; 19200 bps max.

module

 

 

 

Ladder communication

F3RZ81-0N

1

RS-232-C port; 19200 bps max.

 

 

 

module

F3RZ91-0N

1

RS-422/RS-485 port; 19200 bps max.

 

 

 

 

 

GP-IB communication

F3GB01-0N

1

GP-IB communication port

module

 

 

 

z FA Link and Fiber-optic FA-bus Modules

Module Description

Model

Specifications

 

 

 

FA link H module

F3LP02-0N

Up to 32 stations with a transmission distance

of 1 km max., 1.25 Mbps

 

 

Fiber-optic FA link H module

F3LP12-0N

Up to 32 stations with an extensive distance

of 10 km max., 1.25 Mbps

 

 

Fiber-optic FA-bus module

F3LR01-0N

Up to 6 stations with a base-to-base distance

of 200 m max., 10 Mbps

 

 

Fiber-optic FA-bus 2 module

F3LR02-0N

Up to 32 stations with an extensive distance

of 1.4 km max., 10 Mbps

 

 

NEW

NEW

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-6

z Counter and Positioning Modules

Module Description

Model

Specifications

 

 

 

High-speed counter module

F3XP01-0H

100 kpps, 1 channel, 32 bits

 

 

F3XP02-0H

100 kpps, 2 channels, 32 bits

 

 

 

 

Pulse input module

F3XS04-3N

20 kHz, 4 channels, 24 V input, 16 bits

 

 

F3XS04-4N

20 kHz, 4 channels, 12 V input, 16 bits

 

 

 

 

Positioning module

F3NC11-0N

1-axis position and speed control with a max.

speed of 250 kbps

(Advanced model with

 

 

2-axis position and speed control with a max.

positioning pulse output)

F3NC12-0N

speed of 250 kbps

 

 

Positioning module

F3NC51-0N

1-axis position and speed control with a max.

speed of 2M pps

(Model with speed-control

 

 

1-axis position and speed control with a max.

voltage output)

F3NC52-0N

speed of 2M pps

 

 

Positioning module

F3YP04-0N

4-axis position control with a max. speed of

250000 pps

(Model with multichannel

 

 

8-axis position control with a max. speed of

pulse output)

F3YP08-0N

250000 pps

 

 

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-7

z Cables

Cable Description

Model

Style

Specifications

Code

 

 

 

Cable for programming

KM11-2T

*A

*1

tools

D-sub, 9-pin, male, 3 m long

KM11-3T

*A

D-sub, 9-pin, male, 5 m long*1

 

 

 

 

 

 

KM11-4T

*A

D-sub, 9-pin, male, 10 m long*1

 

 

 

 

CPU port/9-pin D-sub

KM10-0C

D-sub, 9-pin, female, approx. 0.5 m long

adapter cable

 

 

 

Fiber-optic cord*3 *4 for

KM60-S06

Cord for system expansion inside panel enclosure; 0.6 m long

wiring inside panel

 

 

 

KM60-001

Cord for system expansion inside panel enclosure; 1 m long

enclosure (compatible

with F3LR01, F3LR02 and

 

 

 

KM60-003

Cord for system expansion inside panel enclosure; 3 m long

F3LP12)

 

 

 

Fiber-optic cable*3 *4 for

KM61-010

Cable for indoor system expansion; 10 m long

indoor wiring, supplied

 

 

 

 

 

Cable for indoor system expansion; 100 m long

with tension member

KM61-100

(supplied with one pulling eye)

(compatible with F3LR01,

 

 

 

 

Cable for indoor system expansion; 150 m long

F3LR02 and F3LP12)

KM61-150

(supplied with one pulling eye)

 

 

 

 

KM61-200

Cable for indoor system expansion; 200 m long

 

(supplied with one pulling eye)

 

 

 

Fiber-optic cable*3 *4 for

KM62-100

Cable for outdoor system expansion; 100 m long

outdoor wiring, supplied

(supplied with one pulling eye)

 

 

with tension member

KM62-200

Cable for outdoor system expansion; 200 m long

(compatible with

(supplied with one pulling eye)

 

 

F3LR01 [up to 200 m],

KM62-300

Cable for outdoor system expansion; 300 m long

F3LR02 [up to 200 m],

(supplied with one pulling eye)

 

 

and

KM62-400

Cable for outdoor system expansion; 400 m long

F3LP12 [up to 1000 m])

(supplied with one pulling eye)

 

 

 

KM62-500

Cable for outdoor system expansion; 500 m long

 

(supplied with one pulling eye)

 

 

 

 

KM62-600

Cable for outdoor system expansion; 600 m long

 

(supplied with one pulling eye)

 

 

 

 

KM62-700

Cable for outdoor system expansion; 700 m long

 

(supplied with one pulling eye)

 

 

 

 

KM62-800

Cable for outdoor system expansion; 800 m long

 

(supplied with one pulling eye)

 

 

 

 

KM62-900

Cable for outdoor system expansion; 900 m long

 

(supplied with one pulling eye)

 

 

 

 

KM62-L01

Cable for outdoor system expansion; 1000 m long

 

(supplied with one pulling eye)

 

 

 

Fiber-optic cable*3 for

KM67-300

Cable for outdoor system expansion; 300 m long

outdoor wiring, supplied

(supplied with one pulling eye)

 

 

with tension member

KM67-400

Cable for outdoor system expansion; 400 m long

(compatible with F3LR02

(supplied with one pulling eye)

 

 

(200 to 500 m))

KM67-500

Cable for outdoor system expansion; 500 m long

 

(supplied with one pulling eye)

 

 

 

Cable for connector

KM55-005

For connection between module and connector terminal block; 0.5 m long

terminal blocks*2

 

 

 

KM55-010

For connection between module and connector terminal block; 1 m long

 

 

 

 

 

 

KM55-015

For connection between module and connector terminal block; 1.5 m long

 

 

 

 

 

KM55-020

For connection between module and connector terminal block; 2 m long

 

 

 

 

 

KM55-025

For connection between module and connector terminal block; 2.5 m long

 

 

 

 

 

KM55-030

For connection between module and connector terminal block; 3 m long

 

 

 

 

*1 : Supports DOS/V.

*2 : Cannot be used with F3YP04 and F3YP08 since they use 48-pin connectors.

*3 : For details, see “Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module” Manual (IM34M6H45-01E). *4 : For details, see “FA Link H Module and Fiber-optic FA Link H Module” Manual (IM34M6H43-01E).

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-8

z Spare Parts

 

Module Description

Model

Specifications

 

 

 

Terminal block unit*

TA40-0N

40 points; voltage rating: 5 to 24 V DC

 

 

 

 

 

 

TA50-0N

Connector terminal block 40 points (M3.5 screw)

 

 

 

Connector terminal block*

TA50-1N

Connector terminal block 40 points (M3 screw)

 

 

TA60-0N

Connector terminal block 40 points (Europe

 

 

terminal type)

 

 

 

Blank module

F3BL00-0N

For empty I/O slots

 

 

 

 

* :

Cannot be used with F3YP04

and F3YP08 modules since they use 48-pin connectors

z Accessory

 

Description

Part

Applicable Module

 

Number

 

 

 

Terminal for 10-point terminal block

A1474JT

F3XH04, F3XA08, F3XD08,

 

 

 

F3YD04, F3YA08, F3YC08-0N,

Terminal cover for 10-point terminal block

A1472JT

F3YD08, F3AD04, F3DA02

 

 

 

Terminal for 18-point terminal block

A1496JT

F3XD16, F3YD14, F3YC08-0C, F3YC16,

 

 

 

F3CR04, F3CV04, F3AD08, F3DA04,

Terminal cover for 18-point terminal block

A1494JT

F3DA08,F3XS04, F3HB08

 

 

 

 

Soldered connector (40-pin plug)

*

F3XD32, F3XD64, F3WD64,

A1451JD

F3XP01, F3XP02

 

 

 

Cover for connector (40-pin plug)

A1452JD*

F3YD32, F3YD64, F3NC01, F3NC02

 

 

 

F3NC11, F3NC12, F3NC51, F3NC52

Soldered connector (48-pin plug)

A1612JD*

F3YP04, F3YP08

 

 

 

Cover for connector (48-pin plug) - 2 units

A1613JD*

 

 

 

 

 

Dustproof connector cover - 20 units

T9031AS

F3BU04, F3BU06, F3BU09, F3BU13,

F3BU16

 

 

 

Rail-mounting kit

T9031AP*

F3BU04, F3BU06

 

 

T9031AQ*

F3BU09, F3BU13

 

 

* :

Not supplied with the product

 

 

IM 34M6C11-01E 6th Edition : May 10, 2001-00

A2-9

A2.3 Power Supply Modules

„ F3PU10-0N/F3PU20-0N Power Supply Modules

z Specifications

 

Item

 

Specifications

 

 

 

 

 

 

 

 

F3PU10-0N

 

 

F3PU20-0N

 

 

 

 

 

 

 

 

 

 

 

Supply voltage range

 

100 to 240 V AC, single phase 50/60 Hz

 

 

 

 

 

 

 

 

Range of supply voltage

 

85 to 264 V AC 50/60 Hz±3 Hz

 

change

 

 

 

 

 

 

 

 

Power consumption

 

35VA

 

 

85VA

 

 

 

 

 

 

 

Inrush current

 

20 A max.

(120 V AC, Ta=25°C)

 

 

45 A max. (240 V AC, Ta=25°C)

 

 

 

 

 

 

1 A time-lag fuse

 

 

2 A time-lag fuse

 

Fuse

 

(Built into the L and N terminals

 

(Built into the L and N terminals and

 

 

 

and cannot be replaced.)

 

 

cannot be replaced.)

 

Rated output voltage

 

 

5 V DC

 

 

 

 

 

 

 

 

Rated output current

 

2.0 A

 

 

4.3 A

 

 

 

 

 

 

Insulation resistance

 

5 M Ω min. when tested between a group of external AC terminals and

 

 

the FG terminal using a 500 VDC insulation resistance tester

 

 

 

 

Withstanding voltage

 

1500 V AC for one minute

 

 

between a group of external AC terminals and the FG terminal

 

 

 

 

Leakage current

 

 

3.5 mA max

 

 

 

 

 

 

 

Allowable momentary power

 

 

20 ms

 

failure time

 

 

 

 

 

 

 

 

 

 

External dimensions

 

28.9 (W) × 100 (H) × 83.2 (D) mm*

 

58 (W) × 100 (H) × 83.2 (D) mm *

 

 

 

 

 

 

 

 

Weight

 

190 gf

 

 

320 gf

 

 

 

 

 

 

 

 

Applicable base module

 

Dedicated to

 

 

Dedicated to

 

 

F3BU04 and F3BU06

 

 

F3BU09, F3BU13 and F3BU16

 

 

 

 

 

*:

Excluding protrusions

(see the dimensional figures for more information)

 

z Components and Their Functions

 

 

 

The figure below shows the power supply modules with their covers removed.

 

F3PU10-0N

 

 

 

F3PU20-0N

 

 

RDY indicator (green)

 

Lit when the power

 

 

 

RDY

 

supply module is

 

RDY

 

 

 

 

 

 

 

 

normal.

 

 

 

PU 10-0N

POWER

FAIL signal contact output

 

PU 20-0N

POWER

 

 

Contact ratings: 24V DC, 0.3A

 

 

FAIL

 

 

Normal operating

System Failure and

FAIL

 

OUTPUT

 

 

OUTPUT

 

FAIL1

 

 

time

Power Failure Times

FAIL1

 

COM

Across FAIL1 and COM

Open

Short

COM

 

Across FAIL2 and COM

Short

Open

 

 

 

 

FAIL2

FG

Subject to JIS class 3 grounding

FAIL2

 

 

 

 

FG

LG

 

independently

 

FG

 

 

Connect to FG and grounded

 

 

LG

 

LG

 

 

 

 

 

 

N

Power supply

 

100 to 240V AC

 

N

 

 

 

 

 

 

 

L

 

 

 

 

L

 

INPUT

 

 

 

 

INPUT

 

100-240VAC `

 

 

 

100-240VAC `

 

 

 

 

 

 

 

FA020303.VSD

Figure A2.2 F3PU10-0N and F3PU20-0N Power Supply Modules

IM 34M6C11-01E 6th Edition : May 10, 2001-00