Yellow Jacket Brute II Operating Manual

0 (0)
Yellow Jacket Brute II Operating Manual

YELLOW JACKET®

BRUTEII Test & Charging Manifold

OWNER’S MANUAL

Due to the unusually high pressures and hazardous gasses used in refrigeration and air conditioning, only TRAINED refrigeration and air conditioning technicians should use this equipment. Proper procedures must be used.

Section 608 of the Federal Clean Air Act requires that all persons who maintain, service, repair, or dispose of appliances must be certified since November 14, 1994. Failure to comply can cost you and/or your company as much as $25,000 per day, per violation. The EPA also offers a reward up to $10,000 for providing information concerning violations to the Act.

PROCEDURES Key:

The various service and testing procedures below can be performed after the manifold gauge set has been installed as shown in the following diagrams.

# 1 # 2 # 4

I. TO PURGE HOSES BEFORE HOOKING UP

1 & 2 Connect hoses at E & F; do not

tighten

C & D Close valves

4Connect hose G to refrigerant

A & B Open valves

D & G Crack D & G valve to begin purge

E & F Tighten hose

II. TO OBSERVE OPERATING

IV. TO CHARGE

PRESSURES

REFRIGERATION

 

SUCTION (VAPOR) SIDE

A & B Close valves C & D Close valves

1 & 2 Connect hoses as illustrated

E & F Crack open back seat

III. TO CHARGE REFRIGERATION SUCTION (VAPOR) SIDE WITH SCHRADERS

Purge as in I Charge as in IV

Purge as in I

4Connect hose G to refrigerant

AOpen valve

B& C Close valves

DOpen valve and throttle

F Crack front seat

Over-pressuring the gauge voids warranty

PROCEDURES, cont.

# 5

V. TO PULL VACUUM

 

 

D

Close valve

 

 

H

Connect hose 3 to pump

 

 

C

Open valve

 

 

A & B Open valves

#18975

 

E & F Mid position valves

 

 

Note: To improve pull down time, use core removal tool (to minimize restrictions), and use minimum 3/8”or larger hose.

VI. TO SET LOW SIDE CONTROL BUILD UP PRESSURE

# 6

Disconnect pressure control line. Using flare union, screw

 

union into control line and other end of hose 1.

 

B, C & D Close valves

 

A

Open valve

 

EBack seat then crack open

FBack seat F

B

Open to regulate pressure; set control

REMOVING THE MANIFOLD FROM THE SYSTEM

After completing service operations, you must remove the manifold from the system without losing refrigerant or admitting air.

Close valves E & C.

Then open manifold valves A, B and D, 1/2 turn.

Close valve F.

This arrangement will move all the high-pressure refrigerant from the line and the high-pressure gauge and put it into the low side. Close all manifold valves and remove hoses.

PARTS LIST

YELLOW JACKET Products Div.

Ritchie Engineering Company, Inc.

10950 Hampshire Avenue South

Bloomington, MN 55438-2623

U.S.A.

Phone: 952-943-1333

Fax: 1-800-322-8684

Int’l Fax: 952-943-1605

 

 

e-mail: custserv@yellowjacket.com

Printed in U.S.A.

P/N 510079E

Web Site: www.yellowjacket.com

 

Loading...