Yaskawa 626VM3C Users Manual

4.5 (2)

YASKAWA

Engineering Europe

Mechatronics Solutions

 

 

 

 

 

Varispeed 626VM3C drive station indexing function

This function can be used software NSC620025 or more.

This function is available at C1-39 bit1=1 [station indexing type]

This function is set by C5-** station indexing constant

Hitachi seiki machine: HT25G, HT30G, HT40G, HT50G are using this function for turret index.

 

Machine

 

 

Inverter type

 

 

Motor type

 

 

Station

 

 

 

 

 

 

 

 

 

 

HT25G

 

CIMR-VMC23P72

 

UAJPEA-15BJ20

12

 

 

 

 

 

 

 

 

 

 

HT30G

 

CIMR-VMC23P72

 

UAJPEA-15BJ20

12

 

 

 

 

 

 

 

 

 

 

HT40G

 

CIMR-VMC22P2

 

UAJPEA-08BJ20

12

 

 

 

 

 

 

 

 

 

 

HT50G

 

CIMR-VMC22P2

 

UAJPEA-08BJ20

12

 

 

 

 

 

 

 

 

 

 

 

 

 

Procedure: How to tune-up Turret for VM3C with Hitachi HT25/30/40/50G.

It’s necessary to tune-up turret after exchange inverter.

STEP1. Change parameter as below

>SET pm109=1 [ NC parameter edit valid ]

>PRM pm7015bit0=1 [ Zero return mode valid ]

>Inverter parameter C5-18bit6=1 [ Turret zero position offset auto measurement valid]

STEP2. Press TURRET VALID PB and TURRET INDEX PB at the same time.

>Check method that turret indexes like below.

>Turret no1 ->4 ->7 ->10 ->1 (Normally turret indexes like left whenever press index PB)

>If turning method is different from above mention, it's necessary to change C5-01. Refer to STEP3.

>If the turret doesn’t turn, check that turret must be clamp condition.

>If the turret doesn’t clamp, first press EMG STOP PB.

After that press SPINDLE STOP PB and TAPE PB at the same time. Whenever press these switches, turret is switched clamp and unclamp.

STEP3. Inverter parameter C5-01 should have set automatically. (Zero return complete)

>If turning method different from above (1>4>7>10>1).

In case of turret turned 2>5>8>11>2, add +16284 to actual C5-01’s value. In case of turret turned 3>6>9>12>3, add +8192 to actual C5-01’s value.

STEP4. Change back to original parameter.

>PRM pm7015bit0=0 [ Zero return mode invalid ]

>SET pm109=0 [ NC parameter edit invalid ]

>Inverter parameter C5-18bit6=0 [ Turret zero position offset auto measurement invalid]

STEP5. Turn the machine breaker off and turn on.

STEP6. Release User’s alarm: 5105 POWER OFF WHEN TURRET INDEX. (Do the SET-UP)

> Press SPINDLE STOP PB and VALID PB (Under the TAPE PB) and FEED HOLD PB at the same time.

STEP7. Test run by MDI mode.

> Confirm that indexing tool number and T command are correct.

__________________________________________________________________________________

ETY030104 VM3C Turret station indexing function - C5 Params 1/9

YASKAWA

Engineering Europe

Mechatronics Solutions

 

 

 

 

 

Parameter for station indexing function

 

 

 

 

 

 

 

 

 

Online

Online

Offline setting

 

 

 

 

 

 

 

 

 

Parameter

Constant Name for station indexing

Abbreviation

Min Range

Max Range

Unit

 

Default

HT25G

setting

setting

(STOP)

 

 

 

 

 

 

 

 

 

(RUN)

(STOP)

OFF/ON!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C1-09

Torque reference filter time constant

 

0.0

5.0

ms

 

1.0

2.0

OK

OK

OK

C1-39

Select signal 4

SEL4

0000 0000

1111 1111

HEX1

 

0000 0000

0000 0010

No

No

OK

C5-01

Home position offset

HOMEOFS

0

32767

Pulse

 

0

 

OK

OK

OK

C5-02

Position Control Proportional Gain 1

KPSTTN

1

99

1/sec

 

10

11

OK

OK

OK

 

C5-03

Speed Control Proportional Gain

KVSTTN

1

255

%/Hz

 

10

30

OK

OK

OK

 

C5-04

Speed Control Integral Time Constant

TISTTN

5

1000

ms

 

100

70

OK

OK

OK

 

 

 

 

 

 

 

 

 

0.15

 

 

 

C5-05

Acceleration time

STSFST

0.00

0.50

sec

 

0.30

No

OK

OK

C5-06

Positioning Completion Cancel Width

COINSET

0

255

Pulse

 

10

50

No

OK

OK

C5-07

Position Completion Detection Width

SOINRST

0

255

Pulse

 

10

50

No

OK

OK

 

C5-08

Station near range

NEARBND

0

32767

Pulse

 

100

100

No

OK

OK

C5-09

Zero speed signal level

ZSPDST

3

60

rpm

 

30

30

No

OK

OK

C5-10

1st speed (AUTO mode)

AUTOSPD1

50

MAXRPM

rpm

 

500

1500

No

OK

OK

C5-11

2nd speed (AUTO mode)

AUTOSPD2

50

MAXRPM

rpm

 

500

1500

No

OK

OK

C5-12

JOG speed

MANUSPD

50

MAXRPM

rpm

 

100

500

No

OK

OK

 

C5-13

Zero return speed

HOMESPD

50

200

rpm

 

100

100

No

OK

OK

C5-14

Motor code

STMOTOR

A0

FF

HEX1

 

A0

A1

No

No

OK

C5-15

Station number

STNUM

1

63

 

 

8

12

No

No

OK

C5-16

Gear ratio m (Motor side) *1

GRMTR

1

100

 

 

1

24

No

No

OK

 

 

C5-17

Gear ratio k (Load axis side) *1

GRMCH

1

100

 

 

1

1

No

No

OK

C5-18

Indexing control select signal 1

SELP 1

0000 0000

1111 1111

 

 

0000 0000

1000 0000

No

OK

OK

C5-19

Indexing control select signal 2

SELP 2

0000 0000

1111 1111

 

 

0000 0000

0000 0100

No

OK

OK

C5-20

Pending point offset

PEOFS

0

32767

Pulse

 

0

0

No

OK

OK

C5-21

 

 

 

 

 

 

 

 

 

 

 

C5-22

Position Control Proportional Gain 3

KPSTA

0

99

1/sec

 

0

23

OK

OK

OK

 

C5-23

Position Control Proportional Gain 2

KPSTB

0

99

1/sec

 

0

13

OK

OK

OK

 

C5-24

Starting point of Position Control Proportional

PESTB

0

32767

Pulse

 

0

2000

OK

OK

OK

Gain 2

 

 

 

 

 

 

 

 

 

 

 

 

C5-25

Arrival speed of soft start (starting) *2

VSFW

0

250

rpm

 

0

200

OK

OK

OK

C5-26

Time of soft start (starting) *2

TSFW

0

200

ms

 

0

75

OK

OK

OK

 

 

 

 

 

 

 

 

 

 

 

 

C5-18 b0

Position reference mode

PRMODE

0: Absolute

 

 

 

 

1: Incremental

 

 

b1

Incremental mode direction

INCDIR

0: Increase direction station number

 

1: decrease direction station number

 

b2

Zero return mode direction

HMDIR

0: Increase direction station number

 

1: decrease direction station number

 

b3

Jog mode direction

MANDIR

0: Increase direction station number

 

1: decrease direction station number

 

b4

 

 

 

 

 

 

 

 

 

 

 

b5

 

 

 

 

 

 

 

 

 

 

 

b6

Home position offset automatic measurement

HMAUTO

0: Invalid

 

 

 

 

1: Valid

 

 

 

b7

Motor direction

MTRDIR

0: Forward

 

 

 

 

1: Reverse

 

 

 

C5-19 b0

 

 

 

 

 

 

 

 

 

 

 

b1

 

 

 

 

 

 

 

 

 

 

 

b2

Variable KP control mode

VKPEN

0: Invalid

 

 

 

 

1: Valid (available C5-22~24)

b3

 

 

 

 

 

 

 

 

 

 

 

b4

 

 

 

 

 

 

 

 

 

 

 

b5

 

 

 

 

 

 

 

 

 

 

 

b6

Indication for Motor B(C8) constant

BMTRDSP

0: Invalid

 

 

 

 

1: Valid

 

 

 

b7

 

 

 

 

 

 

 

 

 

 

 

ETY030104 VM3C Turret station indexing function - C5 Params 2/9

Yaskawa 626VM3C Users Manual

YASKAWA

Engineering Europe

Mechatronics Solutions

 

 

 

 

 

Additional Variable for station indexing function

U5

NAME

ABBR.

UNIT

CONTENTS

 

 

 

 

 

U5-01

Input signal status [1CN]

NCIN3WD

HEX1

1CN Sequence input signal ON/OFF

 

 

 

 

status.

U5-02

Input signal status [5CN]

STTNIN

HEX1

5CN Sequence input signal ON/OFF

 

 

 

 

status.

U5-03

Output signal status [1CN]

STOUTWD

HEX1

1CN Sequence output signal ON/OFF

 

 

 

 

status.

U5-04

Station number reference

STNOCMD

 

Station number.

 

 

 

 

 

U5-05

Station number monitor

STNORSP

 

Actual number.

 

 

 

 

 

U5-06

 

 

 

 

U5-07

 

 

 

 

U5-08

Position deviation

SPERRL

Pulse

Difference between command stop

position and current stop position in pulses

 

 

 

 

 

 

 

 

 

U5-09

Positioning time

SPETIME

msec

Completion time in Auto mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b0

 

 

b1

 

 

b2

 

 

b3

b4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b9

 

 

 

 

EMG

 

 

 

 

 

SVON

 

 

 

START

 

 

 

 

 

 

 

 

 

 

 

SPDSEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bE

 

 

 

SSCB

 

 

 

 

DATSEL

 

MOTSEL

 

 

 

 

ZRN

 

 

 

 

RST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U5-01

[1CN] Sequence Input Signal Status Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STN1

 

 

 

 

 

STN2

 

 

 

 

STN4

 

 

 

 

STN8

 

 

 

 

STN1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STN32

 

 

 

 

 

 

 

 

 

 

 

 

 

ZLS

 

 

 

CLUMP

 

 

SETUP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MANU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U5-02 [5CN] Sequence Input Signal Status Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COIN

 

 

 

NEAR

 

 

 

ZSP

 

 

MOTSTS

POS0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POS1

 

 

POS2

 

DATSTS

 

 

 

FLT

TAM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U5-03 [1CN ] Sequence output Signal Status Display

ETY030104 VM3C Turret station indexing function - C5 Params 3/9