Yaskawa G5 User Manual

Traverse (P-Jump) Control
G5+ Software Option
Software Number: VSG111061
Part Number: CIMR-G5MXXXXXF-005
With this factory-installed FLASH software, the GPD515/G5 has the ability to modulate the output frequency around the set frequency reference. This function provides an evenly wound roll for those winding applications that would experience localized build-ups without this feature. The terms disturb, p-jump, ribbon break and wobbulator are also used to describe this function.
Specifications:
P-Jump Function / Inertia Compensation
P-Jump ON/OFF Select
P-Jump Limit
Adjustable Duty Cycle
Sawtooth Waveform Generation / Ribbon
Break
Percent Trim Adjustment
Independent P-Jump Adjustment
Independent Accel/Decel Times
Control Mode: P-Jump in V/f only
Serial Communications: DeviceNet,
Profibus, Modbus Plus, Modbus RTU.
This document is an addendum to Technical Manual TM4515, listing the effect of this software on the parameters in the drive and function descriptions in the manual.
Date: 07/01/04, Rev: 04-07 Page 1 of 7 TM.G5SW.005
(1) XXXX refers to the base Model Number of
the drive in which the software is installed.
Traverse (P-Jump) Control
Date: 07/01/04, Rev: 04-07 Page 2 of 7 TM.G5SW.005
1.0 Wiring
Wire the incoming power, motor, and accessories and control wiring as specified in the GPD515 Technical Manual TM4515.
2.0 I/O Definitions
2.1 New Multi-Function Digital Input Settings
For Parameters H1-01 through H1-06. Addition to Table 5-2 Multi-Function Input Terminal Data Settings (Section 5.32)
Data Function Description Availability
80 Disturbed Waveform
2.2 New Multi-Function Digital Output Settings
For Parameters F5-01, F5-02 and H2-01 through H2-03. Addition to Table 5-3 Multi-Function Output Terminal Data Settings (Section 5.33)
Data Function Description Availability
40 Disturb – Up Status Closed during the accelerating period 41 During Disturb Closed when Disturb Function is
2.3 New Multi-Function Analog Input Settings
For Parameters H3-05 and H3-09.
None.
2.4 New Multi-Function Analog Output Settings
For Parameters F4-01, F4-03, H4-01 and H4-04.
None.
Off
(2)
Open = Disturb function enabled Closed = Disturb function disabled
when Disturb function is enabled Active
V/f Only
(2)
V/f Only V/f Only
(2)
GPD 515 Technical Manual TM4515
Date: 07/01/04, Rev: 04-07 Page 3 of 7 TM.G5SW.005