Xylem SSW-07 User Manual [en, es]

0 (0)
Motors | Automation | Energy | Transmission & Distribution | Coatings
Soft-Starter
Arrancador Suave
Soft-Starter
SSW-07
User's Manual Manual del Usuario Manual do Usuário
SOFT-STARTER USER’S MANUAL
MANUAL DEL USUARIO DEL ARRANCADOR SUAVE
English
Español
MANUAL DO USUÁRIO DA SOFT-STARTER
Series: SSW-07 Document: 0899.5832 / 10
English - Español - Português
Português
07/2012
Summary of revisions / Sumario de las revisiones / Sumário das revisões
The information below describes the revisions in this manual.
Revision Description Chapter
1 First Edition ­2 General Revision ­3 General Revision ­4 Size 4 Included -
5 and 6 Table 3.1 and 8.2 corrected 3 and 8
English
Revision after the Size 4 UL certication.
7
Changed: item 3.2.3; 3.2.4.1; 3.2.4.2; 3.2.7;
4.8; 5.2; E77 in the table 6.1; table 8.1
8
9 General Revision -
Included new functions of
software version V1.4x
3, 4, 5, 6
and 8
3,4
and 5
La información abajo describe las revisiones ocurridas en este manual.
Español
Português
Revisión Descripción Capítulo
1 Primer Edición ­2 Revisión General ­3 Revisión General ­4 Inclusión Mecánica 4 -
5 y 6 Correción de las tablas 3.1 y 8.2 3 y 8
Corrección luego de la certicación UL de la Mecánica 4. Modicado: ítem 3.2.3; 3.2.4.1;
7
8
9 Revisión General -
3.2.4.2; 3.2.7; 4.8; 5.2; E77 en la tabla 6.1; tabla 8.1
Inclusión de las nuevas funciones de la
version de software V1.4x
3, 4, 5, 6
y 8
3, 4 y 5
A informação abaixo descreve as revisões ocorridas neste manual.
Revisão Descrição Capítulo
1 Primeira Edição ­2 Revisão Geral ­3 Revisão Geral ­4 Inclusão da mecânica 4 -
5 e 6 Correções das tabelas 3.1 e 8.2 3 e 8
Correção depois da certicação UL da
7
8
9 Revisão Geral -
Mecânica 4. Alterado: item 3.2.3; 3.2.4.1;
3.2.4.2; 3.2.7; 4.8; 5.2; E77 na tabela 6.1; tabela 8.1
Inclusão das novas funções da versão
de software V1.4x
3, 4, 5,
6 e 8
3, 4 e 5

Summary

CHAPTER 1
Safety Instructions
1.1 Safety Notices in the Manual ................................................5
1.2 Safety Notices on the Product ..............................................5
1.3 Preliminary Recommendations .............................................5
CHAPTER 2
General Information
2.1 About this Manual ................................................................7
2.2 About the Soft-Starter SSW-07 ............................................7
2.3 Soft-Starter SSW-07 Identication Plate ............................8
2.4 Receiving and Storage .......................................................11
CHAPTER 3
Installation and Connection
3.1 Mechanical Installation .......................................................12
3.1.1 Environmental Conditions ............................................12
3.1.2 Soft-Starter SSW-07 Dimensions ................................12
3.1.3 Mounting Specications ...............................................13
3.1.3.1 Mounting Inside a Panel .....................................14
3.1.3.2 Mounting on Surface ..........................................15
3.2 Electrical Installation ...........................................................15
3.2.1 Power Terminals ...........................................................16
3.2.2 Location of the Grounding, Control and Power
Connections ..................................................................17
3.2.3 Recommended Power and Grounding Cables ............18
3.2.4 Power Supply Connection to the Soft-Starter SSW-07 18
3.2.4.1 Power Supply Capacity .......................................19
3.2.4.2 Recommended Fuses .........................................19
3.2.4.3 Recommended Contactors .................................20
3.2.5 Soft-Starter SSW-07 Connection to the Motor .............20
3.2.5.1 Standard Three-Wire Connection .......................21
3.2.6 Grounding Connections ...............................................21
3.2.7 Control and Signal Connections ...................................22
3.3 Recommended Set-ups ......................................................23
3.3.1 Recommended Set-up with Command via Two-wire
Digital Inputs and Isolation Contactor ..........................24
3.3.2 Recommended Set-up with Command via Three-wire
Digital Inputs and Circuit-Breaker ................................24
3.3.3 Recommended Set-up with Command via Two-wire
Digital Inputs and Direction of Rotation .......................25
3.3.4 Recommended Set-up with Command via Two-wires
Digital Inputs and DC-Braking .....................................26
3.3.5 Symbols .......................................................................27

English

Summary
English
CHAPTER 4
Setting the SSW-07
4.1 Control Type Setting ...........................................................28
4.2 Kick Start ............................................................................29
4.3 Initial Voltage Setting ..........................................................29
4.4 Current Limit Setting ...........................................................30
4.5 Acceleration Ramp Time Setting ........................................31
4.6 Deceleration Ramp Time Setting ........................................31
4.7 Motor Current Setting .........................................................32
4.8 Motor Electronic Overload Protection ................................33
4.9 Reset ..................................................................................36
4.10 DI2 Digital Input Setting ....................................................36
4.11 Output Relay Operation ....................................................37
4.12 Relay Output RL1 Programming ......................................37
CHAPTER 5
Programming Information and Suggestions
5.1 Applications and Programming ...........................................38
5.1.1 Voltage Ramp Starting .................................................39
5.1.2 Current Limit Starting ...................................................40
5.1.3 Starting with Pump Control (P202 = 2) ........................40
5.1.4 Programming the control type in pump control ............42
5.2 Protections and Programming ............................................43
5.2.1 Suggestion on How to Program the Thermal Class .....43
5.2.2 Service Factor ..............................................................45
CHAPTER 6
Solution and Troubleshooting
6.1 Faults and Possible Causes ...............................................47
6.2 Troubleshooting ..................................................................50
6.3 Preventive Maintenance .....................................................51
CHAPTER 7
Options and Accessories
7.1 IP20 Kit ...............................................................................52
CHAPTER 8
Technical Characteristics
8.1 Nominal Powers and Currents According to UL508 ...........53
8.2 Nominal Powers and Currents for Standard IP55,
IV Pole Weg Motor .............................................................53
8.3 Power Data .........................................................................54
8.4 Electronics and Programming Data ....................................54
CHAPTER 1

SAFETY INSTRUCTIONS

This Manual contains the necessary information for the correct use of the Soft-Starter SSW-07.
It was written to be used by qualied personnel with suitable training or technical qualications to operate this type of equipment.

1.1 SAFETY NOTICES IN THE MANUAL

1.2 SAFETY NOTICES ON THE PRODUCT

The following safety notices will be used in the text.
DANGER! The nonobservance of the procedures recommended in this warning can lead to death, serious injuries and considerable material damage.
ATTENTION! Failure to observe the recommended procedures in this notice may lead to material damage.
NOTE! The text intents to supply important information for the correct understanding and good operation of the product.
The following symbols may be attached to the product as a safety notice.
English

1.3 PRELIMINARY RECOMMENDATIONS

High Voltages.
Components are sensitive to electrostatic discharge. Do not touch them.
Mandatory connection to ground protection (PE).
DANGER!
Only personnel with suitable qualication and familiar with the
Soft-Starter SSW-07 and associated equipment should plan or implement the installation, start-up, operation and maintenance of this equipment. These personnel must follow all safety instructions in this manual
and/ or dened by local regulations.
Failure to follow these safety instructions may result in personnel injury and/or equipment damage.
5
CHAPTER 1 - SAFETY INSTRUCTIONS
NOTE!
In this Manual, qualied personnel are those trained to:
1. Install, ground, power-up, and operate the Soft-Starter SSW-07 according to this manual and the required safety procedures;
2. Use protection equipment according to established regulations;
3. Give First Aid.
DANGER!
Always disconnect the general power supply before touching any electrical component associated to the Soft-Starter SSW-07.
English
High voltage may be present even after the power supply is disconnected. Wait at least 3 minutes for the total discharge of the capacitors. Always connect the equipment’s heatsink to the protection ground (PE), at the proper connection point.
ATTENTION!
All electronic boards have components that are sensitive to electrostatic discharges. Do not touch these components or connectors directly.
If necessary, rst touch the grounded metallic heatsink or use a
suitable grounded wrist strap.
Do not apply any high voltage test on the Soft-Starter SSW-07!
If necessary, contact the manufacturer.
NOTE!
Soft-Starters SSW-07 may interfere with other electronic equipment. Follow the measures in Chapter 3 to reduce these effects.
NOTE!
Read this manual completely before installing or operating the Soft-Starter SSW-07.
6

GENERAL INFORMATION

Tampa para
Trifásica
Opcionais Plug-In
Ajustes e Habilitar as Proteções
DIP Swith para
LED's para Indicação
Entrada de Alimentação
de Status da SSW-07
Sda para Motor
Saida a Relé (13,14/23 e 24)
CHAPTER 2

2.1 ABOUT THIS MANUAL

2.2 ABOUT THE SOFT-STARTER
SSW-07
This manual presents the Soft-Starter installation, how to start it up, its main technical characteristics and how to identify and correct the most common problems. The manuals listed next must be consulted in order to get more information regarding the functions, accessories and working conditions:
Programming Manual, with a detailed description of the
parameters and its functions;
RS232 / RS485 Communication Manual. DeviceNet Communication Manual.
These manuals are supplied in electronic format on the CD-ROM that accompanies the Soft-Starter, or can be obtained at WEG’s web site: http://www.weg.net.
The Soft-Starter SSW-07 is a high performance product that permits the start control of the three phase AC induction motors. Thus, it prevents mechanical shocks on the load and current peaks in the supply line.
Three-phase Power Supply
English
Trimpots to adjust
DIP switch to adjust
the Thermal Class
Electronic Power Supply
(A1 and A2)/
Start/Stop Command
of the Motor (D1) and
Reset (DI2 and DI3)
Figure 2.1 - Frontal view of the SSW-07
DIP Switch for Soft-Starter adjustment and protection enabling
Status Indication LEDs of the SSW-07
Lid for optional Plug-in Modules
Relay Output (13, 14/23 and 24)
Motor Output
7
CHAPTER 2 - GENERAL INFORMATION
English
Three-Phase
Power Supply
R S
U
V W
Three-Phase Motor
Programmable
Digital Inputs
Dl1
Dl2
Dl3
T
Control
Power Supply
A1
A2
3 x
Digital Signal
2 x
Processor
DSP
PE
Figure 2.2 - Soft-Starter SSW-07 block diagram
Programmable Digital
Outputs
13
14/23 24
RL1
RL2

2.3 SOFT-STARTER SSW-07 IDENTIFICATION PLATE

WEG Stock
SSW-07 Model
Input Data (Voltage, Number of Phases, Current and Frequency)
Control Power Supply Data (Voltage, Frequency)
Serial Number
Figure 2.3 - Soft-Starter SSW-07 identication plate
Item Number
Software
Version
Manufacturing date
(14 corresponds to
week and H to year)
8
CHAPTER 2 - GENERAL INFORMATION
VISTA FRONTAL
VISTA DE X
Position of the Identication Plate on the Soft-Starter SSW-07:
FRONTAL VIEW X VIEW
English
X
Figure 2.4 - Location of the labels
9
CHAPTER 2 - GENERAL INFORMATION
End of
Code
Special
Software
Blank =
Standard
S1 = Special
Software
English
Special
Hardware
Blank =
Degree of
Protection
Blank =
S = Standard
O = with
220-575 Vac Optional:
(2)
Standard
H1 = Electronics
supply: 110 to
130 Vac
H2 = Electronics
(1)
Standard
IP=IP20
Optional
(2)
supply: 208 to
240 Vac
10
HOW TO SPECIFY THE SSW-07 MODEL:
Three-
Phase
SSW-07
Nominal Current
WEG Soft-
Starter
EX SSW-07 0017 T 5 S _ _ _ _ _ _ Z
Market
Power
Supply
0017 = 17 A
0024 = 24 A
0030 = 30 A
Series
SSW-07
BR = Brazil
EX = Export
0045 = 45 A
0061 = 61 A
0085 = 85 A
0130 = 130 A
0171 = 171 A
0200 = 200 A
0255 = 255 A
0312 = 312 A
0365 = 365 A
0412 = 412 A
(1) Only for models 130 A to 412 A.
(2) Only for the 255 A to 412 A models.
NOTE!
The option eld (S or O) denes if the Soft-Starter SSW-07 will be a standard version or if it will include any optional. If standard, the
code ends here.
Always put the letter Z at the end. For example:
EXSSW070017T5SZ = Standard Soft-Starter SSW-07 with 17 A and 220 V to 575 V to three-phase input with the User’s Guide in
English, Spanish and Portuguese.
If there is any optional, the elds must be lled out in the correct sequence until the code is completed with the letter Z.
The standard product as dened by this code is described as:
Degree of Protection: IP20 from 17 A to 85 A and IP00 from 130 A to 412 A.
CHAPTER 2 - GENERAL INFORMATION

2.4 RECEIVING AND STORAGE

The Soft-Starter SSW-07 is supplied in a cardboard box. On the
outside of the package there is an identication plate which is
identical to the one placed on the Soft-Starter SSW-07. To open the package: 1- Put it on a table; 2- Open the package; 3- Take out the Soft-Starter.
Check if:
The Identication plate of the Soft-Starter SSW-07 matches the
model purchased:
Damage has occurred during transport. If so, contact the carrier
immediately.
If the Soft-Starter SSW-07 is not installed immediately, store it in
its package in a clean and dry place with temperature between
-25 °C (-13 °F) and 65 °C (149 °F). 1 hour at -40 °C (-40 °F) is permitted.
English
SSW-07
Model
17 A 24 A 30 A 45 A 61 A
85 A 130 A 171 A 200 A 255 A 312 A 365 A 412 A
Height
H
mm
(in)
221
(8.70)
260
(10.24)
356
(14.02)
415
(16.34)
Table 2.1 - Dimensions of the package in mm (in)
Width
L
mm
(in)
180
(7.09)
198
(7.80)
273
(10.75)
265
(10.43)
Depth
P
mm
(in)
145
(5.71)
245
(9.65)
295
(11.61)
320
(12.6)
Volume
3
cm (in3)
5768
(352.2)
12613
(770.8)
28670 (1750)
35192 (2147)
Weight
kg
(lb)
1.65
(3.64)
3.82
(8.42)
8.36
(18.43)
12.8
(28.2)
Figure 2.5 - Dimensions of the package
11
C
A
B
P
L

3.1 MECHANICAL INSTALLATION

CHAPTER 3

INSTALLATION AND CONNECTION

This chapter describes the procedures for the electrical and mechanical installation of the Soft-Starter SSW-07. The guidelines and suggestions must be followed for the correct operation of the Soft-Starter SSW-07.
3.1.1 Environmental
English
Conditions
The location of the Soft-Starters SSW-07 is an important factor to assure the correct operation and high product reliability.
Avoid:
Direct exposure to sunlight, rain, high moisture and sea air ; Exposure to explosive or corrosive gases and liquids; Exposure to excessive vibration, dust or any metallic and/or oil
particles in the air.
Allowed Environmental Conditions:
Surrounding air Temperature: 0 ºC to 55 ºC (32 ºF to 131 ºF) -
nominal conditions.
Relative air moisture: 5 % to 90 %, with no-condensation. Maximum altitude: 1,000 m (3,300 ft) above sea level - nominal
conditions.
From, 1,000 m to 4,000 m (3,300 ft to 13,200 ft) above sea level -
current reduction of 1 % for each 100 m (330 ft) above 1,000 m (3,300 ft).
From 2000 m to 4000 m (6,600 ft to 13,200 ft) above sea level -
voltage reduction of 1.1 % for each 100m (330 ft) above 2,000 m
(6,600 ft). Pollution degree: 2 (according to the UL508). Normally, only non conductive pollution. Condensation must not
cause conduction in the particles in the air.
3.1.2 Soft-Starter SSW-07 Dimensions
B
D
D
C
12
The external dimensions and mounting holes are shown in gure
3.1 and table 3.1 below.
A
Figure 3.1 - SSW-07 dimensions
L
H
H
P
CHAPTER 3 - INSTALLATION AND CONNECTION
Height
SSW-07
Model
17 A 24 A 30 A
45 A 61 A 85 A
130 A 171 A 200 A
255 A 312 A 365 A 412 A
H
mm
(in)
162
(6.38)95(3.74)
208
(8.19)
276
(10.9)
331
(13.0)
* IP20 with optional.
3.1.3 Mounting
Specications
Width
L
mm
(in)
144
(5.67)
223
(8.78)
227
(8.94)
Depth
P
mm
(in)
157
(6.18)85(3.35)
203
(7.99)
220
(8.66)
242
(9.53)
A
mm
(in)
132
(5.2)
208
(8.19)
200
(7.87)
B
mm
(in)
120
(4.72)5(0.20)4(0.16) M4
148
(5.83)6(0.24)
210
(8.27)
280
(11.0)15(0.59)9(0.35)
C
mm
(in)
7.5
(0.3)
D
Mounting
mm
(in)
3.4
(0.13) M4
5
(0.2) M5
Screw
M8
Weight
kg
(lb)
1.3
(2.9) IP20
3.3
(7.28) IP20
7.6
(16.8)
11.5
(25.4)
Table 3.1 - Installation data with dimensions in mm (in)
To install the Soft-Starter SSW-07 leave at least the free spaces
surrounding the Soft-Starter as in gure 3.2 below. The dimensions
of these free spaces are described in table 3.2.
Degree
of
Protection
IP00 *
English
IP00 *
SSW-07 Model
17 A 24 A 30 A 45 A 61 A
85 A 130 A 171 A 200 A
A mm (in)
50 (2)
80
(3.2)
100
(4)
B mm (in)
50
(2)
80
(3.2)
100
(4)
C
mm
(in)
30
(1.2)
30
(1.2)
30
(1.2)
255 A 312 A 365 A
150
(6)
150
(6)
30
(1.2)
412 A
Table 3.2 - Recommended free spaces
Install the Soft-Starter SSW-07 in the vertical position according to the following recommendations:
1) Install on a reasonably at surface;
2) Do not put heat sensitive components immediately above the Soft-Starter SSW-07.
ATTENTION!
If a Soft-Starter SSW-07 is installed on top of another use the minimum distance A + B and diverge from the top Soft-Starter the hot air that comes from the one beneath it.
13
CHAPTER 3 - INSTALLATION AND CONNECTION
ATTENTION!
Independent conduits or cable trays must be planned for physic separation of signal, control and power cables. (Refer to item 3.2 Electrical Installation).
A
A
English
SAIDA
Air Flow
FLUXO DE AR
Outlet
C
C
3.1.3.1 Mounting Inside a Panel
SSW-07
Model
130 A 12 117 129 171 A 12 154 166 200 A 12 180 192 255 A 12 230 242 312 A 12 281 293 365 A 12 329 341 412 A 12 371 383
Air Flow
B
B
Figure 3.2 - Free spaces for ventilation
ENTRADA FLUXO DE AR
Inlet
For Soft-Starters SSW-07 installed in panels or closed metallic boxes exhaustion/cooling is required so the temperature does not exceed the maximum allowed. Refer to dissipated nominal power in table 3.3.
Average Power
Dissipated Power
in the electronics
(W)
17 A 12 15.3 27.3 24 A 12 21.6 33.6 30 A 12 27 39 45 A 12 41 53 61 A 12 55 67 85 A 12 77 89
dissipated 10 starts/h
3 x In @ 30 s
(W)
Total Average Power
dissipated
10 starts/h
3 x In @ 30 s
(W)
14
Table 3.3 - Dissipated power for ventilator panel dimensioning
CHAPTER 3 - INSTALLATION AND CONNECTION
3.1.3.2 Mounting on Surface
Figure 3.3 shows the installation of the Soft-Starter SSW-07 on the surface of a mounting plate.
English
Figure 3.3 - Installation procedures of the Soft-Starter SSW-07 on a surface
3.2 ELECTRICAL
INSTALLATION
DANGER!
The Soft-Starter SSW-07 cannot be used as an emergency stop device.
DANGER!
Be sure that the AC input power is disconnected before making any terminal connection.
ATTENTION!
The information below may be used as a guide to achieve a proper installation. Follow also the applicable local standards for electrical installations.
ATTENTION!
If a power isolating contactor or circuit breaker with minimum voltage
coil is not used at the rst power on, then power up the electronics rst, adjust the trimpots that are necessary to put the SSW-07 into
operation and only after this energize the power section.
15
CHAPTER 3 - INSTALLATION AND CONNECTION
Circuit-breaker
T S R
Line
English
Fuses
R/1L1 S/3L2 T/5L3
3.2.1 Power Terminals
U/2T1 V/4T2 W/6T3 PE
Figure 3.4 - Standard power/grounding connections
PE
PE
The power terminal blocks vary in size and conguration, depending on the SSW-07 soft-starter model, as can be observed at the gures
3.5 and 3.6.
Terminals:
R / 1L1, S / 3L2 and T / 5L3: AC supply line. U / 2T1, V / 4T2 and W / 6T3: Motor connection.
16
CHAPTER 3 - INSTALLATION AND CONNECTION
R/1L1 S/3L2 T/5L3
Output Power
BORNE DE SAIDA POTENCIA
Terminal
Models 17 A to 85 A Models 130 A to 412 A
Input
BORNE DE ENTRADA
Power Terminal
POTENCIA
SSW-07
Model
17 A 24 A 30 A 45 A 61 A
85 A 130 A 171 A 200 A 255 A 312 A 365 A 412 A
Figure 3.5 - Power terminals
Enclosure
Size
Screw/
Terminal
Size 01 Terminal
Size 02 Terminal
Size 03
Size 04
M8
(5/16”)
M10
(3/8”)
R/1L1
Output
BORNE DE SAIDA POTENCIA
Power Terminal
U/2T1
S/3L2
V/4T2
Input
BORNE DE ENTRADA POTENCIA
Power Terminal
Line / Motor Grounding
Torque
Nm
Screw
(in lb)
3
(27)
5.5
(49)
19
(168)
37
(328)
M4
(5/32”)
M5
(3/16”)
M6
(1/4”)
Terminal
T/5L3
W/6T3
English
Torque
Nm
(in lb)
4.5
(40)
6
(53)
8.3
(73)
0.5
(4.5)
Table 3.4 - Maximum torque for power connection
3.2.2 Location of the Grounding, Control and Power Connections
Control
Control
CONTROLE
Control
CONTROLE
48.2
(1.90)
39.0 (1.54)
ATERRAMENTO
39.0
(1.54)
13.3
(0.52)
114
(4.48)
56.3
(2.22)
62.8
(2.48)
32.7
(1.29)
ATERRAMENTO
33.0
36.3
84,8
(3.34)
(1.30)
14.8
14.8
(0.59)
(0.59)
(1.43)
Grounding Grounding Grounding
Dimensions in mm (in).
Figure 3.6 - Location of the grounding, control and power connections
CONTROLE
63.0
(2.48)
(2.48)
ATERRAMENTO
63.0
22.7
(0.89)
60.5
(2.38)
39.7
(1.56)
148
(5.81)
Grounding
ATERRAMENTO
75.5
(2.97)
Control
CONTROLE
75.5
(2.97)
25.1
(0.99)
197
(7.75)
17
CHAPTER 3 - INSTALLATION AND CONNECTION
3.2.3 Recommended Power and Grounding Cables
English
The described specications in table 3.5 are valid only for the
following conditions: Copper wires for 70 ºC (158 ºF) with PVC insulation for ambient
temperature of 40 ºC (104 ºF), installed in perforated and not agglomerated conduits.
Naked or silver coated copper busbars with round edges with 1
mm radius with ambient temperature of 40 ºC (104 ºF) and bus temperature of 80 °C (176 °F).
NOTE!
For correct cable dimensioning, consider the installation condition and the maximum permitted line voltage drop.
SSW-07
Model
17 A 4 12 4 12 24 A 6 10 6 10 30 A 6 10 6 10 45 A 10 8 6 10 61 A 16 6 10 8
85 A 25 4 10 8 130 A 50 1 25 4 171 A 70 2/0 35 2 200 A 95 3/0 50 1 255 A 120 250 kcmil 2.5 14 312 A 185 350 kcmil 2.5 14 365 A 240 500 kcmil 2.5 14 412 A 300 600 kcmil 2.5 14
Power Cable Grounding Cable
2
) AWG (mm2) AWG
(mm
3.2.4 Power Supply Connection to the Soft-Starter SSW-07
18
Table 3.5 - Minimum cable gauge specication
DANGER!
The AC input must be compatible with the voltage range of the Soft-Starter SSW-07.
DANGER!
Provide a power supply disconnecting switch for the Soft-Starter SSW-07. This disconnecting switch must disconnect the AC input voltage to the Soft-Starter SSW-07 whenever necessary (for example: during maintenance services). If a disconnected switch or a contactor is inserted in the motor supply line never operate these devices with the motor running or when the Soft-Starter SSW-07 is enabled.
ATTENTION!
The overvoltage control in the line that feeds the soft-starter must be done using overvoltage suppressors with a clamping voltage of 680 Vac (phase-to-phase connection) and an energy absorption capability of 40 joules (17 A to 200 A models) and 80 joules (255 A to 412 A models).
CHAPTER 3 - INSTALLATION AND CONNECTION
NOTE!
Use the wire sizes and fuses recommended in tables 3.5 and 3.7. The connector tightening torque is indicated in table 3.4. Use only copper wires 70 °C (158 °F).
3.2.4.1 Power Supply Capacity
The Soft-Starter SSW-07 is suitable to be used in a circuit capable of supplying not more than X (according to table 3.6) symmetrical rms amperes, Y maximum volts when protected by ultra-rapid fuses.
SSW-07 Model
17 A 5 24 A 5 30 A 5 45 A 5 61 A 5
85 A 10 130 A 10 171 A 10 200 A 10 255 A 25 312 A 25 365 A 25 412 A 25
Table 3.6 - Maximum current capacity of the power supply
Y = 220-575 V
X (kA)
The SSW-07 can be installed on power supplies with a higher fault level, if it is protected by ultra-rapid fuses with an adequate
2
interrupting current and an I
t according to item 3.2.4.2.
English
3.2.4.2 Recommended Fuses
The fuses to be used on the input must be high speed semiconductor fuses with l2t lower or equal to 75 % of the SCR value indicated in
2
table 3.7 (A
s). The fuse rated current should preferably be equal or greater than the motor starting current to avoid cyclic overloads and fuse opening in the forbidden region of the Time x Current curve. These fuses will protect the SSW-07 in case of a short-circuit. Normal fuses can also be used, instead of the high speed, which will protect the installation from short-circuits, but the SSW-07 will not be protected.
For the electronic supply protection of the SSW-07 must be used
fuse type D, or circuit breaker type C as specied in table 3.7.
I²t of
SSW-07
Model
17 A 720 63 FNH1-63-K-A 10806688 50 6.6URD30TTF0050 170M2611
24 A 4000 80 FNH00-80-K-A 10705995 80 6.6URD30TTF0080 170M1366 30 A 4000 100 FNH00-100-K-A 10707110 80 6.6URD30TTF0080 170M1366 45 A 8000 125 FNH00-125-K-A 10707231 100 6.6URD30TTF0100 170M1367 61 A 10500 160 FNH00-160-K-A 10701724 125 6.6URD30TTF0125 170M1368 85 A 51200 250 FNH00-250-K-A 10711445 200 6.6URD30TTF0200 170M1370
130 A 97000 400 FNH1-400-K-A 10815073 315 6.6URD31TTF0315 170M1372 171 A 168000 500 FNH2-500-K-A 10824109 450 6.6URD32TTF0450 170M3170 200 A 245000 630 FNH2-630-K-A 10824110 500 6.6URD32TTF0500 170M3171 255 A 90000 500 FNH3-500-K-A 10833056 400 6.6URD32TTF0400 170M5158 312 A 238000 710 FNH3-710-K-A 10833591 500 6.6URD33TTF0500 170M3171 365 A 238000 710 FNH3-710-K-A 10833591 550 6.6URD33TTF0550 170M5161 412 A 320000 2 x 500 A FNH3-500-K-A 10833056 700 6.6URD33TTF0700 170M6161
the SCR (A²s)
WEG Fuses with CE Certication Fuses with UL Certication (A)
Fuse
Nominal
Current
(A)
Fuse Model
(Blade Contacts)
Part
Number
WEG
Fuse
Nominal
Current
(A)
Ferraz Shawmut/
Mersen
Flush End Contacts
Cooper
Bussmann
Bolted
Contacts
Control
Fuse
2 A
(D Type)
or
2 A
Circuit
Breakers
(C Type)
Table 3.7 - Recommended fuses
19
CHAPTER 3 - INSTALLATION AND CONNECTION
NOTE!
The maximum I2t of the SSW-07 255 A fuse is smaller than 200 A because of the thyristor constructive type used on this soft-starter.
3.2.4.3 Recommended Contactors
English
3.2.5 Soft-Starter
SSW-07 Connection to the Motor
When the SSW-07 is used in applications that require an isolator
contactor, according to the gure 3.10 (K1), the use of WEG
contactors is recommended.
SSW-07 Model WEG Contactor
17 A CWM18 24 A CWM25 30 A CWM32 45 A CWM50 61 A CWM65
85 A CWM95 130 A CWM150 171 A CWM180 200 A CWM250 255 A CWM250 312 A CWM300 365 A CWME400 412 A CWME400
Table 3.8 - Recommended contactors
DANGER!
Power factor correction capacitors must never be installed at the output of the Soft-Starter SSW-07. (U / 2T1, V / 4T2 and W / 6T3).
ATTENTION!
To ensure that the protections based on the current reading and display operate correctly, for example the overload, the motor nominal current must not be lower than 50 % of the nominal Soft­Starter SSW-07 current.
NOTE!
Use the wire sizes and fuses recommended in tables 3.5, 3.6 and
3.7. The connector tightening torque is indicated in table 3.4. Use only copper wires.
NOTE! The Soft-Starter SSW-07 is provided with electronic protection against motor overload. This protection must be set according to
the specic motor. When several motors are connected to the same
Soft-Starter SSW-07 use individual overload relays for each motor.
20
CHAPTER 3 - INSTALLATION AND CONNECTION
3.2.5.1 Standard Three-Wire Connection
3.2.6 Grounding
Connections
Line current of the Soft-Starter SSW-07 is equal to the motor current.
R S T N PE
R
U
1/U1
S
V
4/U2
6/W2
3/W1
T
2/V1
5/V2
Figure 3.7 - Soft-Starter SSW-07 with standard connection
R S T N PE
R
W
U
1/U1
2/V1
4/U2
S
5/V2
6/W2
T
WV
3/W1
DANGER!
The Soft-Starter must be grounded for safety purposes (PE). The ground connection must comply with the local regulations. Make the ground connection to a grounding bar or to the general grounding point (resistance 10 ohms).
English
DANGER!
The AC input for the Soft-Starter SSW-07 must have a ground connection.
DANGER!
Do not use the neutral conductor for grounding purpose. Use dedicated ground conductor.
ATTENTION!
Do not share the ground wiring with other equipment that operate with high current (for examples: high voltage motors, welding machines, etc.). When several Soft-Starters SSW-07 are used,
observe the connections in the gure 3.8.
GROUNDING BAR
BARRA DE ATERRAMENTO
INTERNAL TO THE PANEL
INTERNA AO PAINEL
GROUNDING BAR
BARRA DE ATERRAMENTO
INTERNAL TO THE PANEL
INTERNA AO PAINEL
Figure 3.8 - Grounding connections for more than one Soft-Starter SSW-07
21
CHAPTER 3 - INSTALLATION AND CONNECTION
EMI - Electronic Interference
The Soft-Starter SSW-07 is developed to be used in industrial systems (Class A) according to Standard EN60947-4-2. It’s necessary to have a distance of 0.25 m (10 in) between the Soft- Starter SSW-07 control cables and motor cables. Example: PLC wiring, temperature controllers, thermocouple cables, etc.
Grounding of the Motor frame
Always ground the motor frame. The Soft-Starter SSW-07 output wiring to the motor must be installed separately from the input wiring as well as from the control and signal wiring.
English
3.2.7 Control and Signal Connections
Terminal Description Specications
A1
A2
Terminal Factory Default Specications
DI1 Starts/Stops Motor DI2 Fault reset DI3 Fault reset
13 Relay 1 output - Operation
14/23 Relay common point
24 Relay 2 output - Full voltage
The control connections (digital inputs and relay outputs) are made
through the terminals (refer to gure 3.9).
Voltage: 110 to 240 Vac (-15 % to +10 %) (models from 17 A to 200 A)
Electronics Supply
Grounding Only for the 255 to 412 A models
Table 3.9 - Description of the control connector pins
110 to 130 Vac or 208 to 240 Vac (-15 % to 10 %) (models from 255 A to 412 A).
3 isolated digital inputs Voltage: 110 to 240 Vac (-15 % to +10 %) Current: 2 mA Max.
Contact capacity: Voltage: 250 Vac Current: 1 A
Torque Nm
(in lb)
0.5 (4.5)
22
Figure 3.9 - Control terminals of the Soft-Starter SSW-07
NOTE!
It is recommended to use shielded cables for the Dix inputs when using long cables (above 30 m) in noisy environments. The metallic shield and A2 must be grounded.
CHAPTER 3 - INSTALLATION AND CONNECTION

3.3 RECOMMENDED SET-UPS

Some recommended set-ups are shown here and they can be completely or partly used. The main warning notes for all the recommended set-ups are shown below and are described in the schemes by their respective numbers.
NOTES!
The use of fuses or circuit breakers at the input circuit is
1
necessary for the entire installation protection. It is not necessary to use ultra-fast fuses for the SSW-07 operation; however, their use is recommended for the soft-starter complete protection.
The transformer “T1” is optional and must be used when there
2
is a difference between the line voltage and the electronic power voltage.
In case that damage at the SSW-07 Soft-Starter power circuit
3
keeps the motor running (e.g., shorted thyristors), the motor protection is obtained with the use of the power isolating contactor (K1) or circuit breaker (Q1).
English
Start push-button.
4
Stop push-button.
5
Start/Stop switch. Bear in mind that when using two-wire digital
6
input command (normally open switch with retention), in case of a power interruption, upon return of power, the motor will be started immediately if the switch remains closed.
In case of maintenance of the Soft-Starter SSW-07 or the motor
7
it is necessary to remove the input fuses or disconnect the power supply to ensure the complete equipment disconnection from the power supply.
The emergency stop can be used by disconnecting the
8
electronics power supply.
Undervoltage release for the Q1 power isolation circuit breaker.
9
23
CHAPTER 3 - INSTALLATION AND CONNECTION
3.3.1 Recommended Set-up with Command via Two-wire Digital Inputs and Isolation Contactor
English
Refer to notes in item 3.3.
R S T
PE
K1
R S T
U V W
M 3~
T1
K1
RL1
23
14
24
RL2
DI1A2A1
DI2
DI3
13
Figure 3.10 - Recommended set-up with commands via two-wire digital inputs
and isolation contactor
3.3.2 Recommended Set-up with Command via Three­wire Digital Inputs and Circuit- Breaker
Refer to notes in item 3.3.
R S T
PE
Q1
R S T
U V W
M 3~
T1
Q1
DI1A2A1
DI2
DI3
13
14
23
RL1 RL2
24
24
Figure 3.11 - Recommended set-up with commands via three-wire digital
inputs and a circuit-breaker
NOTE!
It’s necessary to program the digital input DI2 for the three-wire command function. Refer to item 4.10.
NOTE!
The RL1 shall be set to the “No fault” function. Refer to item 4.12.
3.3.3 Recommended Set-up with Command via Two-wire Digital Inputs and Direction of Rotation
P220 = 1 P230 = 1 P263 = 1 (DI1 = Start/Stop two wires) P265 = 4 (DI3 = Rotation Direction) P277 = 4 (RL1 = FWD/REV - K1) P278 = 4 (RL2 = FWD/REV - K2)
CHAPTER 3 - INSTALLATION AND CONNECTION
R S T
PE
K1
K2 K2
T1
K1
English
Refer to notes in item 3.3.
Figure 3.12 - Recommended Set-up with Command via Two-wire Digital
NOTE!
To program the parameters shown above, is necessary the use of keypad or serial communication. See the Programming Manual for more information.
R S T
U V W
M 3~
DI1A2A1
Inputs and Direction of Rotation
DI2
DI3
RL1
23
14
24
RL2
13
25
CHAPTER 3 - INSTALLATION AND CONNECTION
3.3.4 Recommended Set-up with Command via Two-wires Digital Inputs and DC­Braking
P220 = 1 P230 = 1 P263 = 1 (DI1 = Start/Stop two wires)
English
P265 = 5 (DI3 = Brake Off) P277 = 1 (RL1 = Running) P278 = 5 (RL2 = DC-Braking)
P501 ≥ 1 (DC Braking Time ≥ 1s)
R S T
PE
K1
T1
K1
K2
Refer to notes in item 3.3.
NOTE!
To program the parameters shown above, is necessary the use of keypad or serial communication. See the Programming Manual for more information.
K2
R S T
U V W
M 3~
DI1A2A1
DI2
DI3
13
RL1
23
14
24
RL2
Figure 3.13 - Recommended Set-up with Command via Two-wires Digital
Inputs and DC-Braking
26
3.3.5 Symbols
CHAPTER 3 - INSTALLATION AND CONNECTION
Electrical connection between two signals
Connection terminals Thyristor/SCR
Relay or contactor coil
M
3~
Normally open contact (NO) Transformer
Indicator light N.O Contact (with retention)
Circuit-breaker (opens under load)
Resistor Normally open (NO)
Fuse
Three-phase motor
Normally closed (NC) push-button
push-button
English
Capacitor Circuit-breaker with
undervoltage release
27
CHAPTER 4

SETTING THE SSW-07

This chapter describes how to make the necessary settings for the correct functioning of the SSW-07.

4.1 CONTROL TYPE SETTING

English
DIP Switch Control
Type Setting
Figure 4.1 - Control type setting
Select the type of starting control that best adapts to the application.
Voltage Ramp Starting:
This is the most commonly used method. Very easy to program and set. The Soft-Starter SSW-07 imposes the voltage applied to the motor. Generally applied to loads with a lower initial torque or a square torque. This kind of control can be used as an initial working test.
Current Limit Starting:
The maximum current level is maintained during the start, being set according to the application necessities. Generally applied to loads with a higher initial torque or a constant torque. This kind of control is used to adapt the start to the capacity limits of the supply network.
NOTES!
1. The Current Ramp control type, is only programmed using keypad or serial communication. See the Programming Manual for more details.
2. To program the control type in Pump control, see the Programming Manual or item 5.1.4.
28
CHAPTER 4 - SETTING THE SSW-07

4.2 KICK START

Kick Start Enabling
DIP Switch
English
Figure 4.2 - Kick Start enabling
Soft-Starter SSW-07 offers a Kick Start function for loads that present a large initial resistance to movement. This function is enabled through the Kick Start DIP Switch. The duration of the voltage pulse is set through the trimpot Kick Start Time. The voltage pulse applied is of 80 % Un during the programmed trimpot Kick Start Time.

4.3 INITIAL VOLTAGE SETTING

NOTE!
Use this function only for specic applications and where necessary.
Set the initial voltage to a value that the motor starts to run as soon as the start command is given to the SSW-07.
Initial Voltage
Setting Trimpot
The dot indicates the factory default setting
Figure 4.3 - Initial voltage setting
29
Loading...
+ 131 hidden pages