Woodward easYgen-3000 Operation

37225B
easYgen-3000 Genset Control
Operation
Software Version 1.xxxx
Manual 37225B
Manual 37225B easYgen-3000 - Genset Control
WARNING
Read this entire manual and all other publications pertaining to the work to be performed before install­ing, operating, or servicing this equipment. Practice all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage.
The engine, turbine, or other type of prime mover should be equipped with an overspeed (overtempera­ture, or overpressure, where applicable) shutdown device(s), that operates totally independently of the prime mover control device(s) to protect against runaway or damage to the engine, turbine, or other type of prime mover with possible personal injury or loss of life should the mechanical-hydraulic gov­ernor(s) or electric control(s), the actuator(s), fuel control(s), the driving mechanism(s), the linkage(s), or the controlled device(s) fail.
Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical, or other operating limits may cause personal injury and/or property damage, including damage to the equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or "negligence" within the meaning of the product warranty thereby excluding warranty coverage for any resulting damage, and (ii) invalidate product certifications or listings.
CAUTION
To prevent damage to a control system that uses an alternator or battery-charging device, make sure the charging device is turned off before disconnecting the battery from the system.
Electronic controls contain static-sensitive parts. Observe the following precautions to prevent dam­age to these parts.
Discharge body static before handling the control (with power to the control turned off, contact a grounded surface and maintain contact while handling the control).
Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards.
Do not touch the components or conductors on a printed circuit board with your hands or with
conductive devices.
OUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was produced. To verify that you have the latest revision, be sure to check the Woodward website:
http://www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The latest version of most publications is available at:
http://www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get the latest copy.
Important definitions
WARNING
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, could result in damage to equipment.
NOTE
Provides other helpful information that does not fall under the warning or caution categories.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
© Woodward
All Rights Reserved.
Page 2/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Revision History
Rev. Date Editor Changes NEW 06-11-23 TP Release A 07-06-29 TP Minor corrections and update to reflect the new functionality B 08-02-07 TP Minor corrections; easYgen-3100 description added; message IDs added
Content
CHAPTER 1. GENERAL INFORMATION.........................................................................................5
Document Overview................................................................................................................................5
Short Description.....................................................................................................................................6
CHAPTER 2. EASYGEN-3200 NAVIGATION / OPERATION.............................................................7
Navigation...............................................................................................................................................8
Operation ..............................................................................................................................................24
Display........................................................................................................................................26
Mode...........................................................................................................................................27
Operation....................................................................................................................................28
LogicsManager ...........................................................................................................................29
CHAPTER 3. EASYGEN-3100 LEDS.........................................................................................30
CHAPTER 4. FUNCTIONAL DESCRIPTION ..................................................................................31
Overview ...............................................................................................................................................31
Application Modes.................................................................................................................................32
Application Mode {0} – Start/Stop...............................................................................................32
Application Mode {1o} – Open GCB...........................................................................................32
Application Mode {1oc} – Open/Close GCB...............................................................................32
Application Mode {2oc} – Open/Close GCB/MCB......................................................................32
Operating Modes...................................................................................................................................33
Operating Mode STOP...............................................................................................................33
Operating Mode MANUAL..........................................................................................................34
Operating Mode AUTOMATIC....................................................................................................35
CHAPTER 5. EASYGEN-3200 CONFIGURATION.........................................................................37
Structure of the Parameters..................................................................................................................37
Parameters............................................................................................................................................39
Language....................................................................................................................................39
Real-Time Clock - Time..............................................................................................................39
Real-Time Clock - Date ..............................................................................................................40
Display Contrast .........................................................................................................................40
Password....................................................................................................................................41
Deactivate Horn..........................................................................................................................41
Factory (Default) Values.............................................................................................................41
APPENDIX A. DISPLAY MESSAGES ..........................................................................................42
Status Messages...................................................................................................................................42
Alarm Messages ...................................................................................................................................44
APPENDIX B. RESTORING A LANGUAGE SETTING .....................................................................50
© Woodward Page 3/51
Manual 37225B easYgen-3000 - Genset Control
Figures And Tables
Figures
Figure 2-1: Front panel and display........................................................................................................................................... 7
Figure 2-2: Screen - Level overview........................................................................................................................................24
Figure 3-1: Position of the LEDs............................................................................................................................................. 30
Figure 5-1: Configuration screens (overview).........................................................................................................................37
Figure 5-2: Front panel and display......................................................................................................................................... 50
Tables
Table 1-1: Manual - Overview...................................................................................................................................................5
Table 2-1: Display - Measuring values.................................................................................................................................... 26
Table 4-1: Functional description - Overview.........................................................................................................................31
Table 4-2: Functional description - AMF conditions............................................................................................................... 35
Table 5-1: Message IDs for analog inputs ............................................................................................................................... 49
Table 5-2: Message IDs for discrete inputs..............................................................................................................................49
Table 5-3: Message IDs for external discrete inputs................................................................................................................ 49
Table 5-4: Message IDs for flexible limits .............................................................................................................................. 49
Page 4/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Chapter 1.
General Information
Document Overview
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Type English German
easYgen-3000 Series
easYgen-3000 - Installation 37223 GR37223 easYgen-3000 - Configuration 37224 GR37224 easYgen-3000 - Operation this manual Ö 37225 GR37225 easYgen-3000 - Application 37226 ­ easYgen-3000 - Interfaces 37383 ­ easYgen-3200 - Brief Operation Information 37399 GR37399 easYgen-3100 - Brief Operation Information 37409 -
Table 1-1: Manual - Overview
Intended Use The unit must only be operated as described in this manual. The prerequisite for a proper and safe operation of the product is correct transportation, storage, and installation as well as careful operation and main­tenance.
NOTE
This manual has been developed for a unit equipped with all available options. Inputs/outputs, func­tions, configuration screens, and other details described which do not exist on your unit may be ig­nored.
The present manual has been prepared to enable the installation and commissioning of the unit. Be­cause of the large variety of parameter settings, it is not possible to cover every combination. The manual is therefore only a guide. In case of incorrect entries or a total loss of functions, the default set­tings may be taken from the list of parameters in the configuration manual 37224 or from ToolKit and the respective *.SID file.
© Woodward Page 5/51
Manual 37225B easYgen-3000 - Genset Control
Short Description
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The easYgen-3000 Series generator set controllers provide the following functions:
Genset control
Engine, mains and generator protection
Engine data measurement -
o oil pressure and temperature, coolant temperature, battery voltage, speed,
service hours, etc.
Generator and mains data measurement ­o voltage, current, power, kvar, kW, kWh, etc.
Load/var sharing for up to 32 participants
Load-dependent start/stop
Automatic, Manual, and Stop operating modes
Application modes -
o no CB operation o open GCB o open/close GCB o open/close GCB/MCB
LogicsManager for processing measured values, discrete inputs, and internal states
Engine starter sequencing
Alarm display with circuit breaker trip and engine shutdown
AMF (automatic mains failure) standby genset control, with automatic engine start on a mains failure
detection and open transition breaker control
Critical mode operation
Synchronizing (phase matching and slip frequency) and mains parallel operation
External frequency, voltage, power, and power factor set point control via analog input or interface
FIFO event history with 300 entries
Multilingual user interface (English, German, French, Spanish, Italian, Portuguese, Turkish, Russian,
Chinese, Japanese)
ECU data visualization via J1939
CAN bus communication to engine controllers, plant management systems, expansion boards, and
ToolKit configuration and visualization software
RS-485 Modbus communication with plant management systems
RS-232 Modbus communication with plant management systems and ToolKit configuration and visu-
alization software
Type designation is as follows:
easYgen -xxxx- 5
Examples: EASYGEN-3200-5 (easYgen-3200, 100 & 400 Vac inputs, ../5 A measuring inputs, front panel flush-mounting) EASYGEN-3100-1 (easYgen-3100, 100 & 400 Vac inputs, ../1 A measuring inputs, cabinet back mounting)
CTs, current transformers, secondary
[1] = ../1 A [5] = ../5 A
Model
[-3100] = Model '3100' for switch cabinet back mounting [-3200] = Model '3200' for front-panel flush-mounting
Type
Page 6/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Chapter 2.
easYgen-3200 Navigation / Operation
3
1
2
3
4
13 9 10 11
12
14
5
6
7
8
Figure 2-1: Front panel and display
Figure 2-1 illustrates the front panel/display of the easYgen-3200 with push buttons, LEDs and Liquid Crystal display (LC display). A short description of the front panel is given below.
NOTE
This push button is always active and will stop the engine when pressed, except the op­erating modes are selected externally. In this case, the AUTO and MAN Mode push but-
tons are also disabled.
Function blocks
Buttons that have the same function within one screen are grouped into function blocks. The function blocks are defined as:
Display.........Change the method of voltage and power calculations displayed (page
Mode............ Change the mode of operation (page
27).
Operation.... Used to perform manual operation of the genset and the breakers (page
Navigation... Navigation between system and configuration screens, and alarm list (page
24).
28).
28).
1 2 3 5 6 7 8 9
10 11
Push buttons
The push buttons on the front panel are assigned to softkeys on the display. Each softkey is as­signed to a function depending on the mode of operation.
12
Liquid Crystal Display (LC display)
The display contains softkey characters, measuring values, modes of operation, and alarms. The functionality of the display screens as well as the description of th e functions is detailed in the "Navigation" section (page
13
14
LED
The left LED 13 indicates that the unit is in STOP mode. The right LED 14 indicates that alarm messages are active / present in the control unit.
© Woodward Page 7/51
8).
Manual 37225B easYgen-3000 - Genset Control
Navigation
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Individual display screens are listed in the following text. All softkeys, wh ich are available in the individual screens are described with their function.
Screen "Operating values - overview" / "Starting screen" [all application modes]
STOP operating mode:
AUTOMATIC operating mode:
MANUAL operating mode:
This screen appears upon startup of the unit.
Toggle between delta/wye voltage display. The index of the "V" symbol indicates whether delta or wye voltage is dis­played and which phases are displayed.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Display the alarm list (unacknowledged alarms).
Display the configuration menu screen.
Display the indication menu screen.
This softkey is only displayed in front of the mains symbol if the Alarm LED is flashing (An alarm is present, which has not yet been acknowledged as 'Seen'). This softkey re­sets the horn and acknowledges the alarm as 'Seen'.
Operating mode MANUAL: start/stop engine.
NOTE
If the mains data display is disabled (refer to Configuration Manual 37224), above screens will only show generator data with bigger digits.
Page 8/51 © Woodward
Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
Manual 37225B easYgen-3000 - Genset Control
Screen "Alarm list" [all application modes]
This screen appears after pressing the "Alarm" softkey in the start­ing screen. All alarm messages, which have not been acknowledged and cleared, are displayed. Each alarm is displayed with the alarm message and the date and time of the alarm occurred in the format yy-mon-dd hh:mm:ss.ss. Please note, that self-acknowledging alarm messages get a new timestamp when initializing the unit
(switching on). The
symbol indicates that this alarm condition is still present. A maximum of 16 alarm messages can be displayed. If 16 alarm messages are already displayed and further alarm mes­sages occur, these will not be displayed before displayed alarm messages are acknowledged and thus deleted from the list. The "!" following the letter symbols A through E indicate whether an alarm class is present
or not .
Return to the starting screen.
Scroll up to next alarm message.
Scroll down to next alarm message.
The selected alarm message (displayed inverted) will be ac­knowledged. This is only possible, if the alarm condition is no longer present. If the Alarm LED is still flashing (an alarm is present, which has not yet been acknowledged as 'Seen'), this softkey resets the horn and acknowledges the alarm as 'Seen'.
Screen "Next Page" [all application modes]
This screen appears after pressing the "Next Page" softkey.
Return to the starting screen.
Setpoints
Display the setpoints screen.
Synchroscope
Display the synchroscope screen.
Sequencing
Display the sequencing screen.
Counters and service
Display the counters and service screen.
Measured values
Display the measured values screen.
Diagnostic
Display the diagonstic screen.
© Woodward Page 9/51
Manual 37225B easYgen-3000 - Genset Control
Screen "Setpoints" [all application modes]
MANUAL operating mode:
AUTOMATIC operating mode:
This screen appears after pressing the "Setpoints" softkey in the "Next page" screen. The set point is displayed on the left and the actual value is displayed on the right half of the screen. The symbol
indicates the mains power and indicates the generator power. The figures 1 or 2 indicate whether set point 1 or set point 2 is used in AUTOMATIC operation. The source, which is used for set point 1 or set point 2, is displayed with the respective LogicsManager function number.
Return to "Next page" screen.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Scroll up one set point.
Scroll down one set point.
Raise the selected set point.
Lower the selected set point.
P .......Real power
Constant = fixed generator load control Import = fixed import power control Export = fixed export power control
PF.....Power factor
V.......Voltage
f ........Frequency
Page 10/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Screen "Synchroscope" [all application modes]
This screen appears after pressing the "Synchroscope" softkey in the "Next page" screen.
Return to "Next page" screen.
Synchroscope generator/busbar
Display the generator / busbar synchroscope screen.
Synchroscope busbar/mains
Display the busbar / mains synchroscope screen.
Screen "Synchroscope generator / busbar" [all application modes]
This screen appears after pressing the "Synchroscope Gen. / Bus­bar" softkey in the "Synchroscope" screen. The square symbol indicates the actual phase angle between busbar and generator. The 12 o'clock position on the top means 0° and the 6 o'clock position on the bottom means 180°. The frequency and voltage differences are indicated in the center of the circle.
Return to "Synchroscope" screen.
Display detail:
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: Raise voltage/frequency.
Operating mode MANUAL: Lower voltage/frequency.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
© Woodward Page 11/51
Manual 37225B easYgen-3000 - Genset Control
Screen "Synchroscope busbar / mains" [all application modes]
This screen appears after pressing the "Synchroscope Busbar / Mains" softkey in the "Synchroscope" screen. The square symbol indicates the actual phase angle between busbar and mains. The 12 o'clock position on the top means 0° and the 6 o'clock position on the bottom means 180°. The frequency and voltage differences are indicated in the center of the circle.
Return to "Synchroscope" screen.
Display detail:
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: Raise voltage/frequency.
Operating mode MANUAL: Lower voltage/frequency.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
Page 12/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Screen "Sequencing" [all application modes]
This screen appears after pressing the "Sequencing" softkey in the "Next page" screen. The sequencing screen shows all gensets par­ticipating in load sharing. The operation mode of each genset as well as the state of its GCB is shown on this screen. The symbol above the generator number indicates AUTOMATIC operating mode, below shows whether the respective GCB is closed ( (
indicates MANUAL, and indicates STOP. The field
) or open
). The bottom field displays the actual load sharing values. If this device is not participating in load sharing, "LD start stop Off" is displayed here.
Return to "Next page" screen.
Scroll down to genset 17 through 32 display.
Scroll up to genset 1 through 16 display.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
© Woodward Page 13/51
Manual 37225B easYgen-3000 - Genset Control
Screen "Counters and service" [all application modes]
This screen appears after pressing the "Counters and service" soft­key in the "Next page" screen.
Return to "Next page" screen.
Scroll down to the energy counter display screen.
Scroll up to the operating hours counter display screen.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
Hours of operation 0.00h - Operating hours counter
0.00h = Total operating hours (hours in operation,
the decimals are hundredths of an hour)
Number of starts 00 - Start counter
00 = Total number of starts
Hours until maintenance 000h - Maintenance counter
000h = Hours until next maintenance
Days until maintenance 000h - Maintenance counter
000h = Days until next maintenance
Gen. positive active energy 0.00 MWh - Generator posi-
tive active energy
0.00MWh = Total generator positive active energy
Gen. positive reactive energy 0.00 Mvarh - Generator
positive reactive energy
0.00Mvarh = Total generator positive reactive en­ergy
Gen. negative reactive energy 0.00 Mvarh - Generator
negative reactive energy
0.00Mvarh = Total generator negative reactive en­ergy
NOTE
Further information about resetting or setting the counters may be found in the Configuration Manual
37224.
Page 14/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Screen "Measured values" [all application modes]
This screen appears after pressing the "Measured values" softkey in the "Next page" screen.
Return to the "Next page" screen.
J1939 interface
Display the J1939 interface indication screen.
Analog inputs/outputs
Display the analog inputs and outputs indication screen.
Discrete inputs/outputs
Display the discrete inputs and outputs indication screen.
Generator
Display the generator indication screen.
Busbar
Display the busbar indication screen.
Mains
Display the mains indication screen.
Screen "J1939 interface" [all application modes]
This screen appears after pressing the "J1939 interface" softkey in the "Measured Values" screen. The values transmitted by the ECU are displayed here. If a value is not transmitted, "Missing" will be displayed.
Return to "Measured Values" screen.
Scroll up display screen.
Scroll down display screen.
© Woodward Page 15/51
Manual 37225B easYgen-3000 - Genset Control
Screen "Analog inputs/outputs" [all application modes]
"Analog inputs" screen:
"Analog outputs" screen:
These screens appear after pressing the "Analog inputs/outputs" softkey in the "Measured values" screen. The analog inputs and outputs are displayed. The analog outputs are displayed as a per­centage of the selected hardware range, i.e. 50 % of a 0 to 20 mA output refer to 10 mA.
Return to "Measured Values" screen.
Scroll down to the "Analog outputs" screen.
Scroll up to the "Analog inputs" screen.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
Page 16/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Screen "Discrete inputs/outputs" [all application modes]
This screen appears after pressing the "Discrete inputs/outputs" softkey in the "Measured values" screen. Discrete input and dis­crete output status are displayed.
Return to "Measured Values" screen.
Scroll down display screen to external discrete IOs.
Scroll up display screen to internal discrete IOs.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
Status display of the discrete inputs and discrete outputs. (Note: The configured logic for the discrete input "N.O./N.C." will determine how the easYgen reacts to the
of the discrete input. If the respective DI is config-
state ured to N.O, the unit reacts on the energized state ( is configured to N.C., it reacts on the de-energized state Discrete input:
Discrete output:
energized de-energized relay activated relay de-activated
); if it
.)
© Woodward Page 17/51
Manual 37225B easYgen-3000 - Genset Control
Screen "Generator" [all application modes]
This screen appears after pressing the "Generator" softkey in the "Measured values" screen. All measured generator values are dis­played in this screen.
Return to "Measured values" screen.
Scroll down display screen to additional generator values.
Scroll up display screen to main generator values.
Reset the maximum value display.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
V.......Voltage
I ........Current
P .......Real power
Q.......Reactive power
S........Apparent power
PF.....Power factor
Screen "Busbar" [all application modes]
Page 18/51 © Woodward
This screen appears after pressing the "Busbar" softkey in the "Measured values" screen. All measured busbar values are dis­played in this screen.
Return to "Measured values" screen.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
Manual 37225B easYgen-3000 - Genset Control
Screen "Mains" [all application modes]
This screen appears after pressing the "Mains" softkey in the "Measured values" screen. All measured generator values are dis­played in this screen.
Return to "Measured values" screen.
Scroll down display screen to additional mains values.
Scroll up display screen to main mains values.
Reset the maximum value display.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
V ...... Voltage
I........ Current
P....... Real power
Q...... Reactive power
S....... Apparent power
PF .... Power factor
Screen "Diagnostic" [all application modes]
This screen appears after pressing the "Diagnostic" softkey in the "Next page" screen.
Return to the "Next page" screen.
LogicsManager conditions
Display the LogicsManager conditions screen.
Actual date and time
Display the actual date and time screen.
Event History
Display the event history screen.
Version Display the version screen.
© Woodward Page 19/51
Manual 37225B easYgen-3000 - Genset Control
Screen "LogicsManager conditions" [all application modes]
This screen appears after pressing the "LogicsManager conditions" softkey in the "Diagnostic" screen. You are able to display the con­ditions of all LogicsManager command variables, which are lo­cated in their respective groups.
Return to "Diagnostic" screen.
Scroll up one group / command variable.
Command variables of group 4 (ex.):
Scroll down one group / command variable.
Select the highlighted command variable group and display the state of the command variables in this group.
Status display of the command variables:
The command variables is TRUE The command variables is FALSE
Screen "Actual date and time" [all application modes]
This screen appears after pressing the "Actual date and time" soft­key in the "Diagnostic" screen. This screen displays the actual date and time.
Return to "Diagnostic" screen.
Change into AUTOMATIC operating mode.
Page 20/51 © Woodward
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
xxxx-yyy-zz - Date
xxxx = Year
yyy = Month
zz = Day
xx:yy:zz - Time
xx = Hour
yy = Minute
zz = Second
Manual 37225B easYgen-3000 - Genset Control
Screen "Event History" [all application modes]
This screen appears after pressing the "Event History" softkey in the "Diagnostic" screen. A date/time stamp is added to each entry. Additional characters (+ and -) indicate the state of the event. The "+" character indicates an condition that is still active. If the condi­tion is no longer present anymore, it will be displayed again, but with a "-" indication.
Return to "Diagnostic" screen.
Scroll up one event.
Scroll down one event.
The selected (highlighted) entry may be deleted with this softkey if the password for code level CL2 or higher is en­tered.
Screen "Version" [all application modes]
This screen appears after pressing the "Version" softkey in the "Di­agnostic" screen. This screen displays the serial number of the unit and the firm- and software P/N, version, and revision.
Return to "Diagnostic" screen.
Change into AUTOMATIC operating mode.
Change into MANUAL operating mode.
Change into STOP operating mode.
Operating mode MANUAL: start/stop engine. Operating mode MANUAL: open GCB/MCB. Operating mode MANUAL: close GCB/MCB.
© Woodward Page 21/51
Manual 37225B easYgen-3000 - Genset Control
Screen "Parameter" [all application modes]
This screen appears after pressing the "Parameter" softkey.
Return to the starting screen.
Configure language / clock
Display the language and clock configuration screen.
Configure display
Display the display configuration screen.
Lamp test
This softkey illuminates all LEDs to check their function.
Display the configuration menu screen.
Enter password
Configuration
Display the password entry screen.
System management
Display the system management configuration screen.
Screen "Configure language / clock" [all application modes]
This screen appears after pressing the "Configure language / clock" softkey in the "Parameter" screen.
Return to the "Parameter" screen.
Scroll up one parameter.
Scroll down one parameter.
Select the parameter to be configured with this softkey. Change the parameter using the Confirm the change with the configuration without any changes using the
, , and softkeys.
softkey or exit parameter
softkey.
Screen "Configure display" [all application modes]
This screen appears after pressing the "Configure display" softkey in the "Parameter" screen. The contrast and brightness of the dis­play may be configured here.
Return to the "Parameter" screen.
Increase contrast/brightness.
Decrease contrast/brightness.
Pressing and holding the STOP button for at least 10 seconds restores the default settings for contrast and brightness in case the settings have been adjusted in a way that the display can't be read anymore.
Page 22/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Screen "Configuration" [all application modes]
This screen appears after pressing the "Configuration" softkey in the "Parameter" screen.
Return to the "Parameter" screen.
Configure interfaces
Display the interface configuration screen.
Configure LogicsManager
Display the LogicsManager configuration screen.
Configure counters
Display the counter configuration screen.
Configure application
Display the application configuration screen.
Configure monitoring
Display the monitoring configuration screen.
Configure measurement
Display the measurement configuration screen.
Screen "Enter password" [all application modes]
This screen appears after pressing the "Enter password" softkey in the "Parameter" screen. Only the password may be entered using this screen. The code levels are only displayed depending on the entered password.
Return to the "Parameter" screen.
Scroll up one parameter.
Scroll down one parameter.
Select the parameter to be configured with this button. Change the parameter using the Confirm the change with the configuration without any changes using the
, , and softkeys.
softkey or exit parameter
softkey.
Screen "System management" [all application modes]
This screen appears after pressing the "System management" soft­key in the "Parameter" screen. You may find a detailed structure of the configuration screens in
easYgen-3200 Configuration section starting on page 37.
the
Return to the "Parameter" screen.
Scroll up one parameter.
Scroll down one parameter.
Select the parameter to be configured with this button. Change the parameter using the Confirm the change with the configuration without any changes using the
, , and softkeys.
softkey or exit parameter
softkey.
© Woodward Page 23/51
Manual 37225B easYgen-3000 - Genset Control
A
Operation
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The display is partitioned into different areas to give an overview of the displayed data.
Operation
state
larm
Message
Values
Soft­keys
Soft­keys
Operation
Figure 2-2: Screen - Level overview
"Values"
The "values" section of the screen illustrates all meas­ured power related information including voltages, currents, frequencies, power, and power factor values.
Values
"Operation state"
Operation
state
The "operation state" section of the screen shows the actual operating information. Refer to
Appendix A: Status Messages on page 42 for a list of all operation states.
Page 24/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
"Alarm Message"
Alarm
Message
The "alarm message" section of the screen shows the last alarm message that is occurred and not yet ac­knowledged. Refer to on page
44 for a list of all alarm messages.
Appendix A: Alarm Messages
"Operation"
The "operation" section of the screen has a single-line diagram of the system application showing current status of the engine and power circuit breakers. This level is also used for manual operation of the genset.
Operation
"Softkeys"
The softkey characters permit navigation between screens, levels and functions as well as configuration and operation.
Soft­keys
Soft­keys
© Woodward Page 25/51
Manual 37225B easYgen-3000 - Genset Control
Display
Softkey "Voltage display"
The voltage display softkey changes the type of volt-
Values
age display. The amount of information available from the system depends on how the measuring is configured in the control.
Table 2-1 illustrates what values are available depending on the configured measurement type.
Measuring point Scroll display Symbol of'
the displayed voltage
Soft
Press
key
Generator
L1
L2
L3
N
Mains
V
L1
L2
L3
N
V
L1-L2MainsV L2-L3Mains
Gen L1-L2VGen L2-L3VGen L3-L1
Mains L3-L1
V
0× (6×) 1×
L2-NGen
Gen L1-N
Gen L3-N
V
V
V
G
3~
2× 3× 4× 5×
0× (6×) 1×
L2-NMainsV L3-NMains
Mains L1-N
V
V
2× 3× 4× 5×
Delta L1-L2 yes yes --- --­Delta L2-L3 yes yes --- --­Delta L3-L1 yes yes --- yes Wye L1-N yes --- yes yes Wye L2-N yes --- --- --­Wye L3-N yes --- --- yes
Delta L1-L2 yes yes --- --­Delta L2-L3 yes yes --- --­Delta L3-L1 yes yes --- yes Wye L1-N yes --- yes yes Wye L2-N yes --- --- --­Wye L3-N yes --- --- yes
Table 2-1: Display - Measuring values
Displayed at
parameter setting
3Ph
3Ph 3W
4W
1Ph 2W
1Ph 3W
Page 26/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Mode
Softkeys "Mode"
Mode" or "STOP", the operating mode is selected. Depending on the application mode selected, differ­ent softkeys are enabled or disabled in the display. The active operation mode is displayed left of the
By pressing the softkeys "AUTO Mode", "MAN
engine symbol. If the operation mode STOP is se­lected, the LED next to the push button is illuminated in addition to the mode being displayed left of the
Soft­keys
engine symbol.
Note: If the control unit has been configured for ex-
ternal operating mode selection, the AUTO and MAN Mode softkeys are not displayed and the STOP push button is disabled. The operating mode cannot be changed.
STOP Operating mode
When STOP is selected, the engine is stopped. The STOP mode is indicated in the lower left corner of the display by the
symbol.
AUTOMATIC Operating mode
When AUTOMATIC is selected, the control unit manages all engine start/stop and breaker control functions. These functions are performed in accordance with how the control is configured. The AUTOMATIC mode is indicated in the lower left corner of
the display by the
symbol.
MANUAL Operating mode
When MANUAL is selected, all engine and breaker control is performed manually via the softkeys along the bottom of the display. The MANUAL mode is indicated in the
lower left corner of the display by the
symbol.
© Woodward Page 27/51
Manual 37225B easYgen-3000 - Genset Control
Operation
Softkeys "Manual Mode"
symbol is displayed in the lower left corner), the softkeys are enabled for manual operation of the engine and the power circuit breakers. The symbols "0" and "1" indicate if a start/stop com-
If the unit is in the MANUAL operating mode (the
mand is being processed at the moment. The ar­rows on the breaker symbol indicate if an open/close command is being processed at the moment. The
Operation
delayed monitoring has expired and the monitoring functions are enabled. The power is detected at the respective measuring point
symbol indicates that the engine
symbol indicates that
(generator, busbar, or mains). The direction of the circular arrow indicates, if the generator or mains rotating field is clockwise clockwise
(CCW). The arrow symbol at the
(CW) or counter-
mains interchange point indicates whether power is exported (
) or imported ( ).
Engine Start/Stop
Starting process: By pressing this softkey the engine is started.
Successful: If the starting process was successful, the circular arrow speed is detected and the engine is running. The eye engine delayed monitoring has expired and the monitoring functions are enabled.
Unsuccessful: No change in the display until the start failure message appears.
Stop process:
Pressing the softkey again will stop the engine.
Successful: If the stop process was successful, the circular arrow
symbol indicates that the
indicates that
and the eye
symbol disappear.
Unsuccessful: No change in the display until the stop failure message appears.
Power circuit breaker open/close (GCB/MCB)
Close: By pressing the softkey under the desired circuit breaker, it is closed.
Successful: If the closing process was successful, the breaker symbol turns horizontal.
Unsuccessful: If the closing process was not successful, the breaker symbol remains
vertical.
Open:
To open this breaker this softkey is pressed while the breaker symbol is horizon-
tal. The arrows and the "Open GCB/MCB" messages indicate the open command.
Successful: If the opening process was successful, the breaker symbol turns vertical.
Unsuccessful: If the opening process was not successful, the breaker symbol remains
horizontal and the arrows will remain within the softkey character until the con­trol is able to open the breaker.
CAUTION
The breakers will open immediately without power reduction. If you want to open the breaker in a no-
load condition, you must reduce the load manually in the set point screen.
Page 28/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
LogicsManager
Some parameters of the easYgen are configured via the LogicsManager (refer to Configuration Manual 37224). A typical LogicsManager screen is shown in the following. You may configure a logical operation using various command variables, signs, and logical operators to achieve the desired logical output.
LogicsManager Screen
Leave current screen ("Escape" / "ESC")
By pressing this softkey character you exit and go to the previous screen. If the Escape key is used to leave a LogicsManager configuration screen, any unconfirmed changes made will not be stored.
Select parameter
By pressing these softkey characters you may select the LogicsManager parameter to be configured upwards or downwards.
Confirm selection
By pressing this softkey character you confirm the configured option of the selected
LogicsManager parameter.
Change option
By pressing these softkey characters you may change the option of the selected
LogicsManager parameter upwards or downwards.
Change variable group/cursor position
Command variable selection field: By pressing this softkey character you may change the command variable group. The
command variables within a group may be changed using the Time delay configuration field: By pressing this softkey character you may change the cursor position. The selected digit
may be changed using the
Help button
By pressing this softkey character you get to a help screen, which displays the logical operators of the LogicsManager. You may return to the LogicsManager with the Escape
softkey
.
For configuration of the LogicsManager the softkeys displayed in the right and bottom section are used. The softkey on the upper left opens a help screen. The softkeys are assigned with different functions.
and softkeys.
and softkeys.
© Woodward Page 29/51
Manual 37225B easYgen-3000 - Genset Control
Chapter 3.
easYgen-3100 LEDs
The easYgen-3100 unit with metal housing and without display and buttons features two LEDs on the front plate. The two LEDs have the following functionality:
COMMS LED
The communications LED is not functional.
RUN LED
- Illuminated green: the unit is energized and ready for operation
- Illuminated red: a shutdown alarm (alarm class C, D, E, or F) is present
Figure 3-1 indicates the position of the LEDs on the front plate of the easYgen-3100 unit.
Figure 3-1: Position of the LEDs
Page 30/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Chapter 4.
Functional Description
NOTE
This functional description of the easYgen refers to both versions, the easYgen-3100 and the easYgen-
3200. However, every information concerning display, push buttons (softkeys), and MANUAL operation
mode refers to the easYgen-3200 only.
Overview
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Operate the engine
Start engine by: the engine push button (Softkey) the discrete inputs --- emergency power (AMF) --- --- --- --- --- --- --- the interface ---
Stop engine by: the STOP push button the engine push button (Softkey) emergency power (AMF) --- --- --- --- --- --- --- the LogicsManager --- an alarm (i.e. overspeed lvl 2)
Operate GCB
close GCB the GCB push button (Softkey) --- --- --- --- emergency power (AMF) --- --- --- --- --- --- --- the LogicsManager --- --- --- --- ---
open GCB the STOP push button the GCB push button (Softkey) --- --- the LogicsManager --- --- --- an alarm (i.e. overvoltage) --- ---
Operate MCB
open MCB the MCB push button (Softkey) --- --- --- --- --- --- emergency power (AMF) --- --- --- --- --- --- --- the LogicsManager --- --- --- --- --- --- ---
close MCB the MCB push button (Softkey) --- --- --- --- --- --- the LogicsManager --- --- --- --- --- --- ---
Operation Mode MAN AUTO MAN AUTO MAN AUTO MAN AUTO
{0} {1o} {1oc} {2oc}
YES
YES YES YES YES YES YES YES YES YES
YES YES YES YES YES YES YES YES
YES YES YES YES YES YES YES YES
---
YES
YES
---
YES
YES
YES
YES
YES YES YES YES YES YES
Application Mode
---
---
---
---
YES
YES
---
YES
---
YES
YES
---
---
YES
---
YES
YES
---
Table 4-1: Functional description - Overview
---
YES
YES
---
YES
---
YES
---
YES
YES
---
---
YES
---
YES
---
YES
---
YES
YES
---
YES YES YES
---
YES YES
---
YES YES
---
YES
---
YES YES
---
YES
Application Mode (page 32): depends on the application; defines the number/function of the breakers ({0}, {1o}, {1oc}, {2oc}).
Operating Mode (page
33): depends on the application; separates between STOP, MANUAL and AUTOMATIC.
© Woodward Page 31/51
Manual 37225B easYgen-3000 - Genset Control
Application Modes
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The application mode may be changed only during configuration with the code level CL2 or higher password. The most important features of the four application modes are illustrated in the following section. A description of the functions that are possible during each application mode can be found in the Configuration Manual (pa­rameter 3401, manual 37224). able in each application mode.
Application Mode {0} – Start/Stop
This application mode provides the following functions:
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant tem-
G
3 3
1
perature, oil pressure, etc.)
Engine start/stop
S/S
Application Mode {1o} – Open GCB
This application mode provides the following functions:
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant tem-
open
GCB
G
3 3
1
perature, oil pressure, etc.)
Engine start/stop
Engine/generator protection (relay output to open GCB)
S/S
Mains failure detection
Table 4-1: Functional description - Overview describes which function is avail-
Application Mode {1oc} – Open/Close GCB
This application mode provides the following functions:
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant tem-
open/close
GCB
G
3 3
1
perature, oil pressure, etc.)
Engine start/stop
Engine/generator protection (relay output to open GCB)
GCB operation (relay output to close GCB)
S/S
Mains failure detection
Application Mode {2oc} – Open/Close GCB/MCB
This application mode provides the following functions:
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant tem­perature, oil pressure, etc.)
Engine start/stop
Engine/generator protection (relay output to open GCB)
GCB operation (relay output to close GCB)
MCB operation (relay output to open and close the MCB)
Mains failure detection (AMF auto mains failure operation) and automatic engine start/stop
S/S
MCB
GCB
G
3 1
open/close
3 3
1
Page 32/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Operating Modes
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Operating Mode STOP
NOTE
Selecting the operating mode STOP is not the same as an EMERGENCY STOP. In some cases the easYgen will perform additional logic functions, such as an engine cool down period, before the en­gine is stopped. It is recommended that an EMERGENCY STOP discrete input be utilized and pro-
grammed as an F class alarm.
In the STOP operating mode neither the engine nor the GCB can be operated. Dependent on the application mode the power circuit breakers cannot be operated. If the operating mode STOP has been selected while
the engine was already stopped
The GCB will not be closed
The fuel solenoid relay will not be enabled
The discrete inputs and CAN bus commands are ignored
The start push buttons (softkeys) are disabled (depending on the previous operating mode)
The engine/generator monitoring remains de-activated (exception: all monitoring that is not delayed by the
engine speed monitoring)
the engine was running
The GCB is opened Requirements:
- The easYgen is at least in application mode {1o} and
- the GCB is closed
The MCB will be closed Requirements:
- The easYgen is at least in application mode {2oc}
- the GCB is open
- the MCB is enabled
- the parameter "close MCB in STOP mode" is configured to YES
An engine cool down will be performed (the STOP LED is flashing)
The fuel solenoid relay will be disabled
The engine/generator monitoring will be de-activated (exception: all monitoring that is d elayed by the engine
speed monitoring)
The control unit screen will display the operations as they are performed
the engine performs a cool down
Pressing the STOP button again causes an immediate stop of the cool down and stops the engine
NOTE
If the conditions of the LogicsManager function "Enable MCB" (parameter 12923) are TRUE, the MCB will be closed again if it is open in STOP operating mode.
© Woodward Page 33/51
Manual 37225B easYgen-3000 - Genset Control
Operating Mode MANUAL
In the MANUAL operating mode (softkey "Mode MAN") the engine and the power circuit break­ers are operated via the push buttons along the bottom of the display (softkeys). All elements that may be operated via the softkeys have a black frame. All other elements cannot be operated. The single line diagram in the lowest line will change according to the application mode.
The single line diagrams are displayed as follows:
Single line diagram for application mode {0}.
When MANUAL operating mode is selected a black frame softkey character will appear around the engine to indicate that the push buttons below this softkey character may be used to start and stop the engine. This is shown below highlighted for the following functions.
Start the engine
Stop the engine
Single line diagram for application mode {1o}.
For a {1o} application both the engine and the GCB softkey characters appear with the following functions. The "X" sym­bol indicates that a breaker open command is issued or a clo­sure of the breaker is blocked. The dotted breaker line indi­cates no defined breaker state.
Start the engine
Stop the engine
Open the GCB
Examples for the single line diagrams
Examples for the single line diagrams
Single line diagram for application mode {1oc}.
For a {1oc} application both the engine and the GCB softkey characters appear with the following functions.
Examples for the single line diagrams
Start the engine
Stop the engine
Open the GCB
Close the GCB
Single line diagram for application mode {2oc}.
For a {2oc} application both the engine, the GCB and the MCB softkey characters appear with the following functions.
Examples for the single line diagrams
Start the engine
Stop the engine
Open the GCB
Close the GCB
Open the MCB
Close the MCB
Page 34/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Operating Mode AUTOMATIC
In the AUTOMATIC operating mode, all engine, GCB, and/or MCB functions are operated via an interface, or automatically by the control unit (i.e. a mains failure). The function of the easYgen depends on the configuration of the unit and how the external signals are used. The start /stop se­quence of the engine is described in more detail in manual 37224.
In the following text the main functions are briefly described.
Start engine
A Start in Auto requires.
Mains fault
An AMF start requires.
Mains decoupling GCB:
Mains decoupling MCB:
Remote start
The engine is started via a remote start signal.
The AUTOMATIC operating mode is enabled.
The function "Start req. in AUTO" is assigned via the LogicsManager
to a discrete input and the conditions are fulfilled (TRUE).
This discrete input or a start via interface is energized (logically HIGH signal) or the necessary command of the interface protocol is set (for explanation of the interface protocol refer to the interface manual
37383).
A class C alarm or higher is not present (for explanation of the alarm classes refer to manual 37224).
The engine is ready for operation.
The GCB is open.
AMF / Auto mains failure operation (only in application mode {2oc}) If the AUTOMATIC operating mode is enabled and the application mode is configured to {2oc} (2-breaker logic) and the mains fail, the engine and the power circuit breakers will be operated according to the conditions in the following table.
The AUTOMATIC operating mode is enabled.
The application mode is configured as {2oc}.
The parameter "Emergency power" is configured as ON.
The configured mains failure limits are reached.
The configured delay times have expired.
A class C alarm or higher is not present (for explanation of the alarm
classes refer to 37224).
The engine is ready for operation.
Status (prior to mains failure) Action (order)
Engine GCB MCB Engine GCB MCB
(open) 0 (open) 1 (start) 2 (close)
0
(stopped) (running) 0 (open) 0 (open)
1
1
0
(open) 1 (closed) 1 (start) 3 (close) 2 (open)
0
(open) 1 (closed)
0
(closed) 0 (open)
1 (closed) 1 (closed) 1 (closed) 1 (closed)
---
---
1 (close) 2 (close) 1 (open)
--- --- ---
1
---
---
Table 4-2: Functional description - AMF conditions
(open)
3 (close)
(remains
closed)
---
---
2
(close) (open)
1
© Woodward Page 35/51
Manual 37225B easYgen-3000 - Genset Control
Functional description of AMF conditions:
If the engine is not running prior to a mains failure and both, the GCB and MCB are open, the fol­lowing actions occur:
1. The engine starts
2. The GCB closes
3. The load is supplied by the generator set
If the engine is not running prior to a mains failure, the GCB is open, and the MCB is closed the following actions occur:
1. The engine starts
2. The MCB opens
3. The GCB closes
4. The load is supplied by the generator set
If the engine is running prior to a mains failure, the GCB is open, and the MCB is open the follow­ing actions occur:
1. The GCB closes
2. The load is supplied by the generator set
If the engine is running prior to a mains failure, the GCB is open, and the MCB is closed the fol­lowing actions occur:
1. The MCB opens
2. The GCB closes
3. The load is supplied by the generator set
If the engine is running prior to a mains failure, the GCB is closed, and the MCB is open the fol­lowing actions occur:
1. The generator set continues to supply the load
If the genset is operating in parallel with the mains prior to a mains failure, both br eakers are closed, the following actions occur:
1. A mains decoupling will be performed and the GCB or MCB will be opened depending on the
configuration of the mains decoupling function:
Mains decoupling configured to MCB or MCB->GCB: a. The MCB opens b. The GCB remains closed c. The engine keeps running
Mains decoupling configured to GCB or GCB->MCB: a. The GCB opens b. The MCB opens after the delay time c. The GCB closes d. The engine keeps running
2. The load is supplied by the generator set
Page 36/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Chapter 5.
easYgen-3200 Configuration
This chapter provides information "how to configure the unit via the LC display" as well as the description of all parameters that may be changed without a password. If you have the correct codes to configure the unit (this is verified via passwords), refer to manual 37224 for a description of all parameters, their setting range, and their influence to the operation of the unit.
Structure of the Parameters
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Access configuration menus
© Woodward Page 37/51
Figure 5-1: Configuration screens (overview)
By pressing the softkey, the Parameter menu will be displayed to permit configuration of the control unit. The different configuration screens may be displayed by selecting the respective softkey. Refer to
Figure 5-1
for a structure of the configuration screens.
Manual 37225B easYgen-3000 - Genset Control
Softkeys "Configuration - system management"
Navigation through the parameters is carried out using the softkeys press the parameter without saving any changes press
and . To edit the selected parameter
. To save the edited parameter press . To exit
.
Return to the previsous screen/exit parameter without saving changes ("Escape")
Navigate ......Pressing the softkey will return the operator to the previous display screen.
Edit..............I If it is desired to exit a parameter without saving changes made there,
press the softkey and the user will be returned to the previous screen.
Next parameter
This softkey permits the user to navigate down through the parameters. Only the pa­rameters assigned by the active password will be displayed. The parameters that may only be accessed after entering a password are described in the Configuration Manual
37224. If an Asian language is configured, some parameter screens may be displayed with an empty space at the bottom of the parameter list, which may be interpreted as an end of the list, although more parameters exist and are displayed when scrolling down.
Previous parameter
This softkey permits the user to navigate upwards through the parameters.
Decrease/change function
If the desired parameter has been selected by pressing the softkey, and the cursor has been moved to the appropriate position via the decreased by one using the
Increase/change function
softkey.
softkey, the value of the digit may be
If the desired parameter has been selected by pressing the softkey, and the cursor has been moved to the appropriate position via the increased by one using the
softkey.
softkey, the value of the digit may be
Select parameter/input confirmation ("Enter")
Navigate ......A highlighted parameter may be entered for configuration by pressing the
softkey. This permits the changing of the configured value within the
parameter.
Edit..............Any value that has been changed within a parameter is changed and stored
in the unit memory by pressing the
Next digit of the selected parameter
softkey.
If the parameter has a numeric value (i.e. the password) that is to be changed, the digits must be changed individually. The of the number to be changed. See the softkey symbols
Page 38/51 © Woodward
how to change the digit.
softkey permits navigation to each cursor position
and for an explanation of
Manual 37225B easYgen-3000 - Genset Control
Parameters
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
A description of all parameters, which may be edited/configured via the display, are described in the Configuration Manual 37224.
Language
EN DE
NOTE
Refer to Appendix B: Restoring a Language Setting on page 50 if your unit is configured to a language you are not able to read or understand.
Language Language
Change language {Language}
{Language}.. The selection of a language will affect the following text
in the control unit:
Text in the operating field which are not defined by an input (i.e. discrete inputs may be a user-defined text)
The alarm list and event history texts
All parameters which may be changed via the unit
panel
Real-Time Clock - Time
EN DE
EN DE
EN DE
Stunden
Minute
Minuten
Second
Sekunden
Hour
Adjust clock time: hour 0 to 23
The hour of the current time is set here. Example:
0.................... 0
23..................23
th
hour of the day.
rd
hour of the day.
Adjust clock time: minute 0 to 59
The minute of the current time is set here. Example:
0.................... 0
59..................59
th
minute of the hour.
th
minute of the hour.
Adjust clock time: second 0 to 59
The second of the current time is set here. Example:
0.................... 0
59..................59
th
second of the minute.
th
second of the minute.
© Woodward Page 39/51
Manual 37225B easYgen-3000 - Genset Control
Real-Time Clock - Date
EN DE
EN DE
EN DE
Day Tag
Month Monat
Year Jahr
Adjust date: day 1 to 31
The day of the current date is set here. Example:
1 ...................1
31 .................31
st
day of the month.
st
day of the month.
Adjust date: month 1 to 12
The month of the current date is set here. Example:
1 ...................1
12 .................12
st
month of the year.
th
month of the year.
Adjust date: year 0 to 99
The year of the current date is set here. Example:
0 ...................Year 2000.
99 .................Year 2099.
Display Contrast
EN DE
Configure display
Display konfig.
Configure display + / -
In the "Configure display" screen, the display contrast and brightness may be increased or decrease using these softkey characters.
.................Increase the display contrast/brightness.
.................Decrease the display contrast/brightness.
........If the display contrast and/or brightness has been de-
creased to the point that it is no longer visible, press and hold the STOP button for at least 5 seconds. This will re­store the contrast and brightness to the factory default setting.
Page 40/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Password
EN DE
EN DE
Password for CAN interface {x}
EN
Passwort CAN Schnittstelle {x}
DE
Code level CAN interface {x}
EN
Codeebene CAN Schnittstelle {x}
DE
Password for serial interface{x}
EN
Passwort serielle Schnittst. {x}
DE
Code level serial interface {x}
EN
Codebene serielle Schnittst. {x}
DE
Password display Passwort Display
Code level display
Codeebene Display
Password for access via the unit panel 0000 to 9999
A password must be entered to permit configuration of the unit via the unit panel. If a password is not entered only the displayed parameters may be edited.
Code level via display Info
This value displays the code level that is currently active for access via the front panel.
Password for access via CAN interface {x} 0000 to 9999
A password must be entered to permit configuration of the unit via CAN interface {x}. If a password is not entered, the displayed parame­ters may not be edited.
Code level CAN-Bus {x} Info
This value displays the code level that is currently active for access via the CAN bus.
Password for access via serial interface {x} 0000 to 9999
A password must be entered to permit configuration of the unit via se­rial interface {x}. If a password is not entered, the displayed parame­ters may not be edited.
Code level serial port {x} Info
This value displays the code level that is currently active for access via the serial interface {x}.
Deactivate Horn
EN DE
Time until horn reset
Zeit Hupenreset
Self acknowledgement of the horn signal 0 to 1.000 s
A horn signal is issued and the alarm LED flashes when a fault condi­tion occurs. This signal will be disabled when the config ured time ex­pires. This is the maximum time, for which a horn signal is active (it will also be deactivated if it is acknowledged before).
Factory (Default) Values
EN DE
EN
Standardwerte wiederherstellen
DE
© Woodward Page 41/51
Factory settings Werkseinstellung
Set default values
Factory setting YES/NO
The factory settings (default values) may be loaded. Select YES to en­able the following parameter to be displayed. It is possible to load the factory settings (default values) for all parameters, which are accessi­ble in the currently active code level.
Set default values YES/NO
Entering YES overwrites the current configured values with the default values. Only those parameters will be reset, which are permitted to change in the selected code level.
Manual 37225B easYgen-3000 - Genset Control
Appendix A.
Display Messages
Status Messages
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Message text and ID Meaning
AUTO mode ready
ID 13253
Aux. serv. postrun
ID 13201
Aux. services prerun
ID 13200
Cool down
ID 13204
Crank protect
ID 13214
Critical mode
ID 13202
Emergency/Critical
ID 13215
Emergency run
ID 13211
GCB dead bus close
ID 13209
GCB -> MCB Delay
ID 13261
GCB open ID 13255
Gen. stable time
ID 13250
Idle run active
ID 13216
Automatic mode ready for start
The unit is waiting for a start signal in Automatic operating mode and no alarm of class C, D, E, or F is present.
Postrun of the auxiliary operation is active
After the engine has stopped, auxiliary operations are enabled. These operations ensure that required equipment which is necessary for the operation of the engine continues to run (i.e. electric cooling fan).
Prerun of the auxiliary operation is active
Before the engine is started the signal "aux. services prerun" is enabled, so that all required equipment which is necessary for the operation of the engine can be initialized, started or switched.
Coasting of the engine is active
The no load operation is performed prior to the stopping of the engine. The no load operation is utilized to cool the engine.
Starter protection
To prevent the starter from being damaged by an engine that is rotating, a crank protection delay is active to ensure that the engine has time to stop rotating.
Critical mode (Sprinkler operation) is active
The sprinkler operation is activated. The exact description of the conditions and effects of the sprinkler operation are described in the configuration manual 37224.
Emergency operation during active critical operation {2oc}
Critical operation is activated.
Emergency power operation {2oc}
After the control unit detects that a mains fault has occurred, the engine is started after the emergency de­lay timer expires. The MCB is opened, the GCB is closed, and the generator set assumes the load. If the generator set is already running, operations continue until the emergency power operation conditions no longer exist. If the mains return, the mains settling timer becomes active first (see below).
Dead bus closing of the GCB {1oc}, {2oc}
The GCB is closed onto the de-energized busbar. The measured busbar voltage is below the configured dead bus detection limit.
GCB – MCB delay time is active {2oc}
If the breaker logic is configured to Open Transition and a transfer from generator to mains supply is ini­tiated, the transfer time delay will start after the replay "GCB is open" is received. The MCB close com­mand will be issued after the transfer time has expired.
The GCB is being opened {1oc}, {2oc}
A GCB open command has been issued.
Generator stable time is active
If the engine monitoring delay timer has expired, the generator settling time starts. This permits for an ad­ditional delay time before the breaker is closed in order to ensure that none of the engine delayed watch­dogs trips.
The control is in idle mode
No undervoltage, underfrequency, and underspeed monitoring is perform e d in idle mode. The flexible limits 33 through 40 are not monitored.
Page 42/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Message text and ID Meaning
Ignition ID 13213
In operation
ID 13251
Loading Generator
ID 13258
Mains settling
ID 13205
MCB dead bus close
ID 13210
MCB -> GCB Delay
ID 13262
MCB open ID 13257
Power limited prerun
ID 13252
Preglow
ID 13208
Ramp to rated
ID 13254
Start
ID 13206
Start – Pause
ID 13207
Start w/o Load
ID 13263
Stop engine
ID 13203
Synchronization GCB
ID 13259
Synchronization MCB
ID 13260
Turning
ID 13212
Unloading Generator
ID 13256
Unloading mains
ID 13264
Enable the ignition {Gas engine}
After the purging operation and before the fuel solenoid is opened.
The genset is in regular operation
The genset is in regular operation and is ready for supplying load.
The generator power will be increased to the set point
The generator power will be increased to the configured set point with a rate defined by the power con­trol set point ramp.
Mains settling time is active {2oc}
When the control unit detects that the mains fault is no longer present and power has been restored, the mains settling timer begins counting down. If the mains are stable after the expiration of the timer (the mains voltage has not fallen below or risen over the configured monitoring limits), the load is transferred from the generator supply to the mains supply.
Dead bus closing of the MCB {2oc}
The MCB is closed onto the de-energized busbar. The measured busbar voltage is below the configured dead bus detection limit.
MCB – GCB delay time is active {2oc}
If the breaker logic is configured to Open Transition and a transfer from mains to gener ator supply is ini­tiated, the transfer time delay will start after the reply "MCB is open" is received. The GCB close com­mand will be issued after the transfer time has expired.
The MCB is being opened {2oc}
An MCB open command has been issued.
Active power limited prerun is active
The real power set point is limited to the warm up power limit for the configured warm up time.
Preglow of the engine is active {Diesel engine}
The diesel engine is preheated prior to starting.
Engine is accelerating to rated speed
After firing speed has been exceeded, the engine monitoring delay timer starts. This message is displayed during this period.
Start engine is active
After the "Prerun auxiliary operation" expires, the engine is started according to the configured start logic (Diesel or gas engine). When the start sequence is active, various relays are enabled and representative signals are passed via the CAN bus to a secondary engine control.
Start pause while starting the engine is active
If the engine could not be started, the controller will pause for the configured time prior to attempting to issuing a start command again.
Start without load is active
A regular engine start is performed. The GCB operation is blocked to prevent a change from mains to generator supply.
Engine will be stopped
The engine will be stopped. The engine stop delay will be started when ignition speed has been fallen be­low. A restart is only possible if the engine stop delay has been expired.
The GCB will be synchronized
The control tries to synchronize the GCB.
The MCB will be synchronized
The control tries to synchronize the MCB.
Purging operation is active {Gas engine}
Before the fuel solenoid opens and the ignition of the gas engine is energized the remaining fuel, that may be present in the combustion chamber, will be removed by a purging operation. The starter turns the engine without enabling the ignition for a specified time to complete the purging operation. After the purging process, the ignition is energized.
The generator power will be decreased
The generator power will be decreased after a stop command has been issued with a rate defined by the power control set point ramp before the GCB will be opened.
The mains power will be decreased
The real power set point is increased with the configured rate after synchronizing the generator in inter­change transition mode. After the mains have been unloaded, the MCB will be opened.
© Woodward Page 43/51
Manual 37225B easYgen-3000 - Genset Control
Alarm Messages
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
Refer to the Configure Monitoring section of the Parameters chapter in the Configuration Manual 37224 for a detailed description of the monitoring functions, which trigger the alarm messages.
Message text and ID Meaning
Amber warning lamp
ID 15126
Bat. overvoltage 1
ID 10007
Bat. overvoltage 2
ID 10008
Bat. undervoltage 1
ID 10005
Bat. undervoltage 2
ID 10006
CAN fault J1939
ID 10017
CAN1 CANopen RPDO1
ID 10082
CAN1 CANopen RPDO2
ID 10083
CAN1 CANopen RPDO3
ID 10084
CAN2 ExpansionBoard1
ID 10085
CAN2 ExpansionBoard2
ID 10086
Charge alt. low volt
ID 4056
Eng. stop malfunct.
ID 2504
EEPROM failure
ID 1714
GCB fail to close
ID 2603
GCB fail to open
ID 2604
GCB syn. timeout
ID 3064
Amber warning lamp, J1939 interface
This watchdogs monitors, whether a specific alarm bit is received from the CAN J1939 interface. This enables to configure the control in a way that a reaction is caused by this bit (e.g. warning, shutdown). No alarm can be indicated if the CAN communication fails.
Battery overvoltage, limit value 1
The battery voltage has exceeded the limit value 1 for battery overvoltage for at least the configured time and did not fall below the value of the hysteresis.
Battery overvoltage, limit value 2
The battery voltage has exceeded the limit value 2 for battery overvoltage for at least the configured time and did not fall below the value of the hysteresis.
Battery undervoltage, limit value 1
The battery voltage has fallen below the limit value 1 for battery undervoltage for at least the configured time and has not exceeded the value of the hysteresis.
Battery undervoltage, limit value 2
The battery voltage has fallen below the limit value 2 for battery undervoltage for at least the configured time and has not exceeded the value of the hysteresis.
Interface alarm J1939
The communication with the ECU via the CAN bus interface has been interrupted and no data can be transmitted or received over the bus within the configured time.
Interface alarm CANopen RPDO1 on CAN bus 1
No message is received on RPDO1 on the respective CAN ID within the configured time.
Interface alarm CANopen RPDO2 on CAN bus 1
No message is received on RPDO2 on the respective CAN ID within the configured time.
Interface alarm CANopen RPDO3 on CAN bus 1
No message is received on RPDO3 on the respective CAN ID within the configured time.
Interface alarm CANopen Function 1 on CAN bus 2
No message is received from the external expansion board 1.
Interface alarm CANopen Function 2 on CAN bus 2
No message is received from the external expansion board 2.
Charging alternator voltage low
The charging alternator voltage has fallen below the critical limit for at least the configured time and has not exceeded the value of the hysteresis (the critical limit is 9 V for 12 V systems and 20 V for 24 V sys­tems).
Stop alarm of the engine
The engine failed to stop when given the stop command. When a stop command is issued a timer starts a countdown. If speed is still detected when this timer expires the controller recognizes an unsuccessful stop of the engine. An unsuccessful stop of the engine is determined if speed (measured by the generator frequency, the MPU, or the LogicsManager "ignition speed") is detected within the configured time after the stop signal has been issued.
The EEPROM checksum is corrupted
The EEPROM check at startup has resulted a defective EEPROM.
GCB failed to close
The easYgen has attempted to close the GCB the configured maximum number of attempts and failed. Depending on the configuration, the easYgen will continue to attempt to close the GCB as long as the conditions for closing the GCB are fulfilled.
GCB failed to open
The easYgen is still receiving the reply "GCB closed" after the GCB open monitoring timer has expired.
GCB synchronization time exceeded
The easYgen has failed to synchronize the GCB within the configured synchronization time.
Page 44/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Message text and ID Meaning
Gen act.pwr mismatch
ID 2924
Gen. PF lagging 1
ID 2337
Gen. PF lagging 2
ID 2338
Gen. PF leading 1
ID 2387
Gen. PF leading 2
ID 2388
Gen. overcurrent 1
ID 2218
Gen. overcurrent 2
ID 2219
Gen. overcurrent 3
ID 2220
Gen. overfrequency 1
ID 1912
Gen. overfrequency 2
ID 1913
Gen. overload IOP 1
ID 2314
Gen. overload IOP 2
ID 2315
Gen. overload MOP 1
ID 2362
Gen. overload MOP 2
ID 2363
Gen. overvoltage 1
ID 2012
Gen. overvoltage 2
ID 2013
Gen. rev/red. pwr.1
ID 2262
Gen. rev/red. pwr.2
ID 2263
Gen.ph.rot. mismatch
ID 3955
Gen.underfrequency 1
ID 1962
Gen.underfrequency 2
ID 1963
© Woodward Page 45/51
Generator active power mismatch
The deviation between the generator power and the active power set point has exceeded the limit for at least the configured time.
Generator overexcited, limit value 1
The power factor limit 1 has been exceeded at the generator towards inductive (i.e. the current is lag­ging) for at least the configured time and did not fall below the value of the hysteresis.
Generator overexcited, limit value 2
The power factor limit 2 has been exceeded at the generator towards inductive (i.e. the current is lag­ging) for at least the configured time and did not fall below the value of the hysteresis.
Generator underexcited, limit value 1
The power factor limit 1 has fallen below at the generator towards capacitive (i.e. the current is leading) for at least the configured time and did not exceed the value of the hysteresis.
Generator underexcited, limit value 2
The power factor limit 2 has fallen below at the generator towards capacitive (i.e. the current is leading) for at least the configured time and did not exceed the value of the hysteresis.
Generator overcurrent, limit value 1
The generator current has exceeded the limit value 1 for the generator overcurrent for at least the con­figured time and did not fall below the value of the hysteresis.
Generator overcurrent, limit value 2
The generator current has exceeded the limit value 2 for the generator overcurrent for at least the con­figured time and did not fall below the value of the hysteresis.
Generator overcurrent, limit value 3
The generator current has exceeded the limit value 3 for the generator overcurrent for at least the con­figured time and did not fall below the value of the hysteresis.
Generator overfrequency, limit value 1
The generator frequency has exceeded the limit value 1 for generator overfrequency for at least the con­figured time and did not fall below the value of the hysteresis.
Generator overfrequency, limit value 2
The generator frequency has exceeded the limit value 2 for generator overfrequency for at least the con­figured time and did not fall below the value of the hysteresis.
Generator overload IOP, limit value 1
The generator power has exceeded the limit value 1 for generator overload in isolated operation (MCB is open) for at least the configured time and did not fall below the value of the hysteresis.
Generator overload IOP, limit value 2
The generator power has exceeded the limit value 2 for generator overload in isolated operation (MCB is open) for at least the configured time and did not fall below the value of the hysteresis.
Generator overload MOP, limit value 1
The generator power has exceeded the limit value 1 for generator overload in mains parallel operation (GCB and MCB are closed) for at least the configured time and did not fall below the value of the hys­teresis.
Generator overload MOP, limit value 2
The generator power has exceeded the limit value 2 for generator overload in mains parallel operation (GCB and MCB are closed) for at least the configured time and did not fall below the value of the hys­teresis.
Generator overvoltage, limit value 1
The generator voltage has exceeded the limit value 1 for generator overvoltage for at least the config­ured time and did not fall below the value of the hysteresis.
Generator overvoltage, limit value 2
The generator voltage has exceeded the limit value 2 for generator overvoltage for at least the config­ured time and did not fall below the value of the hysteresis.
Generator reverse power, limit value 1 / Generator reduced power, limit value 1
The generator power has exceeded the limit value 1 for generator reverse power / generator reduced power for at least the configured time and did not fall below the value of the hysteresis.
Generator reverse power, limit value 2 / Generator reduced power, limit value 2
The generator power has exceeded the limit value 2 for generator reverse power / generator reduced power for at least the configured time and did not fall below the value of the hysteresis.
Generator rotating field mismatch
The generator rotating field does not correspond with the configured direction.
Generator underfrequency, limit value 1
The generator frequency has fallen below the limit value 1 for generator underfrequency for at least the configured time and has not exceeded the value of the hysteresis. Additionally, the alarm has not been acknowledged (unless the "Self acknowledgement" is configured YES).
Generator underfrequency, limit value 2
The generator frequency has fallen below the limit value 2 for generator underfrequency for at least the configured time and has not exceeded the value of the hysteresis.
Manual 37225B easYgen-3000 - Genset Control
Message text and ID Meaning
Gen. undervoltage 1
ID 2062
Gen. undervoltage 2
ID 2063
Gen unloading fault
ID 3124
Gen. volt. asymmetry
ID 3907
Ground fault 1
ID 3263
Ground fault 2
ID 3264
Inv. time overcurr.
ID 4038
Mains decoupling
ID 3114
Mains export power 1
ID 3241
Mains export power 2
ID 3242
Mains import power 1
ID 3217
Mains import power 2
ID 3218
Mains overfreq. 1
ID 2862
Mains overfreq. 2
ID 2863
Mains overvoltage 1
ID 2962
Mains overvoltage 2
ID 2963
Generator undervoltage, limit value 1
The generator voltage has fallen below the limit value 1 for generator undervoltage for at least the configured time and has not exceeded the value of the hysteresis.
Generator undervoltage, limit value 2
The generator voltage has fallen below the limit value 2 for generator undervoltage for at least the configured time and has not exceeded the value of the hysteresis.
Generator unloading mismatch
The easYgen failed to reduce the generator power below the configured unload limit within the con­figured time.
Voltage asymmetry
The generator phase-to-phase voltages have higher differences between each other than the config­ured limit value.
Generator ground current, limit value 1
The measured or calculated ground current has exceeded the limit value 1 for the generator ground current for at least the configured time and did not fall below the value of the hysteresis.
Generator ground current, limit value 2
The measured or calculated ground current has exceeded the limit value 2 for the generator ground current for at least the configured time and did not fall below the value of the hysteresis.
Generator inverse time-overcurrent
Current monitoring with tripping time depending on the m easured current. The higher the current is the faster the tripping time according to a defined curve. According to IEC 255 three different char­acteristics are available: normal, highly, and extremely inverse.
Mains decoupling is initiated
One or more monitoring function(s) considered for the mains decoupling functionality has triggered.
Mains export power, limit value 1
The mains export power has exceeded or fallen below the limit value 1 for mains export power for at least the configured time and did not fall below or exceed the value of the hysteresis.
Mains export power, limit value 2
The mains export power has exceeded or fallen below the limit value 2 for mains export power for at least the configured time and did not fall below or exceed the value of the hysteresis.
Mains import power, limit value 1
The mains import power has exceeded or fallen below the limit value 1 for mains import power for at least the configured time and did not fall below or exceed the value of the hysteresis.
Mains import power, limit value 2
The mains import power has exceeded or fallen below the limit value 2 for mains import power for at least the configured time and did not fall below or exceed the value of the hysteresis.
Mains overfrequency, limit value 1
The mains frequency has exceeded the limit value 1 for mains overfrequency for at least the config­ured time and did not fall below the value of the hysteresis.
Mains overfrequency, limit value 2
The mains frequency has exceeded the limit value 2 for mains overfrequency for at least the config­ured time and did not fall below the value of the hysteresis. Triggering this monitoring function causes the mains decoupling function to trigger.
Mains overvoltage, limit value 1
The mains voltage has exceeded the limit value 1 for mains overvoltage for at least the configured time and did not fall below the value of the hysteresis.
Mains overvoltage, limit value 2
The mains voltage has exceeded the limit value 2 for mains overvoltage for at least the configured time and did not fall below the value of the hysteresis. Triggering this monitoring function causes the mains decoupling function to trigger.
Page 46/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Message text and ID Meaning
Mains PF lagging 1
ID 2985
Mains PF lagging 2
ID 2986
Mains PF leading 1
ID 3035
Mains PF leading 2
ID 3036
Mains phase shift
ID 3057
Mains underfreq. 1
ID 2912
Mains underfreq. 2
ID 2913
Mains undervoltage 1
ID 3012
Mains undervoltage 2
ID 3013
Maint. days exceeded
ID 2560
Maint. hrs exceeded
ID 2561
MCB fail to close
ID 2623
MCB fail to open
ID 2624
MCB syn. timeout
ID 3074
Missing members
ID 4064
Mns act.pwr mismatch
ID 2934
Mns.ph.rot. mismatch
ID 3975
Operat. range failed
ID 2664
Overspeed 1
ID 2112
Overspeed 2
ID 2113
Mains overexcited, limit value 1
The power factor limit 1 has been exceeded at the mains interchange point towards inductive (i.e. the current is lagging) for at least the configured time and did not fall below the value of the hysteresis.
Mains overexcited, limit value 2
The power factor limit 2 has been exceeded at the mains interchange point towards inductive (i.e. the current is lagging) for at least the configured time and did not fall below the value of the hysteresis.
Mains underexcited, limit value 1
The power factor limit 1 has fallen below at the mains interchange point towards capacitive (i.e. the current is leading) for at least the configured time and did not exceed the value of the hysteresis.
Mains underexcited, limit value 2
The power factor limit 1 has fallen below at the mains interchange point towards capacitive (i.e. the current is leading) for at least the configured time and did not exceed the value of the hysteresis.
Mains phase shift
A mains phase shift, which has exceeded the configured limit, has occurred. Triggering this monitor­ing function causes the mains decoupling function to trigger.
Mains underfrequency, limit value 1
The mains frequency has fallen below the limit value 1 for mains underfre quency for at least the con­figured time and has not exceeded the value of the hysteresis.
Mains underfrequency, limit value 2
The mains frequency has fallen below the limit value 2 for mains underfre quency for at least the con­figured time and has not exceeded the value of the hysteresis. Triggering this monitoring function causes the mains decoupling function to trigger.
Mains undervoltage, limit value 1
The mains voltage has fallen below the limit value 1 for mains undervoltage for at least the config­ured time and has not exceeded the value of the hysteresis.
Mains undervoltage, limit value 2
The mains voltage has fallen below the limit value 2 for mains undervoltage for at least the config­ured time and has not exceeded the value of the hysteresis. Triggering this monitoring function causes the mains decoupling function to trigger.
Maintenance days exceeded
The generator run time has exceeded the configured number of days since the last maintenance pe­riod. Additionally, the alarm has not been acknowledged.
Maintenance hours exceeded
The generator run time has exceeded the configured number of operating hours since the last mainte­nance period. Additionally, the alarm has not been acknowledged.
MCB failed to close
The easYgen has attempted to close the MCB the configured maximum number of attempts and failed. Depending on the configuration, the easYgen will continue to attempt to close the GCB as long as the conditions for closing the MCB are fulfilled.
Failed MCB open
The easYgen is still receiving the reply MCB closed” after the MCB open monitoring timer has ex­pired.
MCB synchronization time exceeded
The easYgen has failed to synchronize the MCB within the configured synchronization time.
Missing load share members detected
The easYgen has detected that the number of available units for load sharing does not correspond with the configured number of members.
Mains active power mismatch
The deviation between the import/export power and the active import/export power set point has ex­ceeded the limit for at least the configured time.
Mains rotating field mismatch
The mains rotating field does not correspond with the configured direction.
Measured values not within operating range
An alarm will be issued if ignition speed is exceeded and the measured values for generator and/or mains are not within the configured operating range. No alarm will be issued in idle mode.
Engine overspeed, limit value 1
The engine speed has exceeded the limit value 1 for engine overspeed for at least the configured time and did not fall below the value of the hysteresis.
Engine overspeed, limit value 2
The engine speed has exceeded the limit value 2 for engine overspeed for at least the configured time and did not fall below the value of the hysteresis.
© Woodward Page 47/51
Manual 37225B easYgen-3000 - Genset Control
Message text and ID Meaning
Parameter alignment
ID 4073
Ph.rotation mismatch
ID 2944
Red stop lamp
ID 15125
Speed/freq. mismatch
ID 2457
Start fail
ID 3325
Unbalanced load 1
ID 2412
Unbalanced load 2
ID 2413
Underspeed 1
ID 2162
Underspeed 2
ID 2163
Unintended stop
ID 2652
Wb:<!-—Analog input x-->
refer to
Table 5-1 on page 49
<!-—Discrete input x-->
refer to
Table 5-2 on page 49
<!-—Ext. Discrete input x-->
refer to
Table 5-3 on page 49
<!—Flexible limit x-->
refer to
Table 5-3 on page 49
LDSS parameter mismatch detected
The easYgen has detected that not all LDSS parameters are configured identically at all par­ticipating units. Refer to the "Multi-unit configuration check" section in the "Parameters" chapter of the Configuration Manual 37224 for a list of all monitored parameters.
Generator/busbar/mains phase rotation different
Generator, busbar (easYgen-3400/3500 only), and mains have different r otating fields. A CB closure is blocked. The phase rotation monitoring is always enabled and cannot be disabled.
Red stop lamp, J1939 interface
This watchdog monitors, whether a specific alarm bit is received from the CAN J1939 in­terface. This enables to configure the control in a way that a reaction is caused by this bit (e.g. warning, shutdown). No alarm can be indicated if the CAN communication fails.
Difference in frequency/speed measurement alarm
The speed differential between the generator frequency (ascertained by the generator volt­age measurement) and the engine speed (measured by the MPU) has exceeded the config­ured limit value / differential frequency for at least the configured time and has not fallen below the value of the hysteresis. The alarm may also be triggered if the LogicsManager "ignition speed" is enabled and no electrical frequency is detected as well as the other way round.
Failure of engine to start alarm
The generator set has failed to start after the configured number of attempts. Depending on the configuration, no more start attempt will be carried out until the alarm is acknowledged.
Generator unbalanced load, limit value 1
The generator current has exceeded the limit value 1 for generator unbalanced load for at least the configured time and did not fall below the value of the hysteresis.
Generator unbalanced load, limit value 2
The generator current has exceeded the limit value 2 for generator unbalanced load for at least the configured time and did not fall below the value of the hysteresis.
Engine underspeed, limit value 1
The engine speed has fallen below the limit value 1 for engine underspeed and has not ex­ceeded the value of the hysteresis.
Engine underspeed, limit value 2
The engine speed has fallen below the limit value 2 for engine underspeed and has not ex­ceeded the value of the hysteresis.
Unintended Stop
The easYgen expects the generator to be running but a sudden underrun of the ignition speed has been detected.
Analog input {x}, wire break
During measurement of the analog input a wire break was detected. This text m a y be as­signed customer defined. The text in angular brackets is the default text.
Discrete input {x}, energized / de-energized
The actual state of the monitored discrete input is energized / de-energized (depending on the configuration) for at least the configured time. This text may be assigned customer de­fined. The text in angular brackets is the default text.
External discrete input {x}, energized / de-energized
The actual state of the monitored external discrete input is energized / de-energized (de­pending on the configuration) for at least the configured time. This text may be assigned customer defined. The text in angular brackets is the default text.
Flexible threshold {x}, overrun / underrun
The actual value of the monitored analog value has exceeded / fallen below the threshold (depending on the configuration) for at least the configured time and did not fall below / exceed the value of the hysteresis. This text may be assigned customer defined. The text in angular brackets is the default text.
Page 48/51 © Woodward
Manual 37225B easYgen-3000 - Genset Control
Analog input # 1 2 3 Message ID
10014 10015 10060
Table 5-1: Message IDs for analog inputs
Discrete input # 1 2 3 4 5 6 7 8 9 10 11 12 Message ID
10600 10601 10602 10603 10604 10605 10607 10608 10609 10610 10611 10612
Table 5-2: Message IDs for discrete inputs
External discrete input # 1 2 3 4 5 6 7 8 Message ID
16360 16361 16362 16364 16365 16366 16367 16368
External discrete input # 9 10 11 12 13 14 15 16 Message ID
16369 16370 16371 16372 16373 16374 16375 16376
Table 5-3: Message IDs for external discrete inputs
Flexible limit # 1 2 3 4 5 6 7 8 9 10 Message ID Flexible limit # 11 12 13 14 15 16 17 18 19 20 Message ID Flexible limit # 21 22 23 24 25 26 27 28 29 30 Message ID Flexible limit # 31 32 33 34 35 36 37 38 39 40 Message ID
10018 10019 10020 10021 10022 10023 10024 10025 10026 10027
10028 10029 10030 10031 10032 10033 10034 10035 10036 10037
10038 10039 10040 10041 10042 10043 10044 10045 10046 10047
10048 10049 10050 10051 10052 10053 10054 10055 10056 10057
Table 5-4: Message IDs for flexible limits
© Woodward Page 49/51
Manual 37225B easYgen-3000 - Genset Control
Appendix B.
Restoring a Language Setting
Due to the multilingual capability of the unit, it may happen that the display language of the easYgen-3200 is set to a language, the operator is unable to read or understand, by mistake. In this case, the following proceeding helps to restore the desired language. The default setting is English.
3
1
2
3
4
13 9 10 11
12
14
5
6
7
8
Figure 5-2: Front panel and display
Figure 5-2 refers to the different softkeys, which appear in the configured language. In order to change the lan­guage setting, press the softkeys in the following order:
5
1. Press softkey
2. Press softkey
3. Press softkey
4. Press softkey
5. Press softkeys
6. Press softkey
until you return to the starting screen (as indicated above)
6
once to access the "Parameter" screen
1
once to access the "Configure language / clock" screen
8
once to edit the language setting
10
or 11 to select the desired language
8
once to commit the language setting
Now, the display language is restored to the desired language again.
Page 50/51 © Woodward
We appreciate your comments about the content of our publications.
Please send comments to: stgt-documentation@woodward.com
Please include the manual number from the front cover of this publication.
Woodward GmbH
Handwerkstrasse 29 - 70565 Stuttgart - Germany
Phone +49 (0) 711 789 54-0 Fax +49 (0) 711 789 54-100
stgt-info@woodward.com
Homepage
http://www.woodward.com/power
Woodward has company-owned plants, subsidiaries, and branches, as well as authorized
distributors and other authorized service and sales facilities throughout the world.
Complete address/phone/fax/e-mail information
for all locations is available on our website (www.woodward.com).
2008/2/Stuttgart
Loading...