Wolf VW30S, VI42B, VI42S, PW662418, PWC542418 Installation manual

...
0 (0)

MODEL 801640

Page 1

EXTERIOR VENTILATOR KITS

WARNING

 

CAUTION !

 

 

 

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1.Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer or your distributor.

2.Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.

3.Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.

4.Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.

5.When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

6.Ducted fans must always be vented to the outdoors.

7.Do not use this unit with an additional speed control device.

8.To reduce the risk of fire, use only steel ductwork.

9.This unit must be grounded.

TO REDUCE THE RISK OF A COOKTOP GREASE FIRE:

1.Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.

2.Always turn hood ON when cooking at high heat or when cooking flaming foods.

3.Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.

4.Use proper pan size. Always use cookware appropriate for the size of the surface element.

TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A COOKTOP GREASE FIRE, OBSERVE THE FOLLOWING:*

1.SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.

2.NEVER PICK UP A FLAMING PAN - You may be burned.

3.DO NOT USE WATER, including wet dishcloths or towels - violent steam explosion will result.

4.Use an extinguisher ONLY if:

A.You know you have a Class ABC extinguisher and you already know how to operate it.

B.The fire is small and contained in the area where it started.

C.The fire department is being called.

D.You can fight the fire with your back to an exit.

*Based on “Kitchen Fire Safety Tips” published by NFPA.

1.For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.

2.To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.

3.Your ventilator motor has a thermal overload which will automatically shut off the motor if it becomes overheated. The motor will restart when it cools down. If the motor continues to shut off and restart, have the hood serviced.

4.Please read specification label on product for further information and requirements.

SPECIFICATIONS

MODEL

VOLTS

AMPS

CFM

DUCT SIZE

 

 

 

 

 

801640

120

2.4

600

10 "DIA.

 

 

 

 

 

PLAN THE INSTALLATION

1.Locate the ventilator so the length of the duct run and number of elbows and transitions needed are kept to a minimum.

2.Where possible, ventilator should be located between wall studs or roof rafters.

3.Avoid pipes, wires, or other ductwork that may be running through the wall.

4.Be sure that there is enough space for any transitions that may be needed between the ventilator and the connecting ductwork.

5.For best performance, locate transitions nearest to ventilator.

Wolf VW30S, VI42B, VI42S, PW662418, PWC542418 Installation manual

ROOF MOUNT INSTALLATION

MODEL 801640

Page 2

For use with Wolf CTWH30/CTWH36 wall mount, IH4227 island chimney hoods, 10” tall & 30” wide x 18” tall wall hoods.

PREPARE THE ROOF

 

 

WIRE THE VENTILATOR

 

 

20¾"

 

 

BLACK

 

 

 

 

 

 

TO

 

 

 

 

8½"

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

REMOVE

 

11"

 

 

 

103/8"

 

SHINGLES

 

dia.

 

 

 

Rafter

Pilot

Rafter

hole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hole

 

 

120 VAC

WHITE

GREEN

 

 

 

 

 

 

 

 

 

20½"

LINE IN

TO

 

 

 

 

TO

 

Roof

 

Roof

 

WHITE

 

 

 

 

 

GREEN

 

 

91/8"

q 5 Remove 7 COVER SCREWS and lift off ventilator cover.

 

 

1¼"

 

Remove BIRD SCREEN and WIRING COVER.

 

 

dia. hole

 

 

q 6 Feed the electric power cable through the 1¼" DIAMETER

 

 

 

 

 

HOLE and connect cable to ventilator with a proper

 

 

 

 

 

connector for the type of cable being used.

 

 

 

 

 

q 7 Connect BLACK TO BLACK, WHITE TO WHITE, and the

 

 

7¼"

 

 

GREEN TO GREEN or bare wire. Replace wiring cover.

 

 

OUTSIDE - ROOF VIEW

INSTALL THE VENTILATOR

 

 

 

 

 

From inside the attic space:

 

 

 

 

6

 

 

7 Cover

 

Mounting

q 1 Drill a PILOT HOLE up through the roof, 8½" from the

 

 

Holes

Screws

 

inside edge of a ROOF RAFTER.

 

 

 

 

 

 

 

From outside - on the roof:

 

 

 

 

Remove

q 2 Measure and mark the 20¾" x 20½" rectangle. Cut and

 

 

roofing

remove only the shingles inside this rectangle.

Shipping

nails from

q 3 Measure and mark the 11" DIAMETER HOLE and the

top 2/3 of

Cardboard

1¼" DIAMETER HOLE. Cut these holes all the way through

shingles.

the roof.

 

 

 

 

 

 

 

 

 

2"

 

Wiring

 

 

 

 

 

 

Cover

 

 

 

 

29½"

 

 

 

Bird Screen

 

 

 

 

Flashing Sheet

 

 

 

 

 

7"

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTSIDE - ROOF VIEW

 

25"

 

 

q 8 Remove SHIPPING CARDBOARD from blower wheel.

 

 

2"

 

 

q 9 Remove roofing nails from top 2/3 of shingles around cut-

 

 

 

 

out area.

 

 

 

 

 

 

 

q 10 Slide the ventilator's FLASHING SHEET up and under

For flat roof installations:

 

 

the loosened shingles until ventilator's discharge collar

q 4 Build a curb that will mount the blower at a minimum pitch

fits into 11" diameter hole.

 

q 11 Use the 6 screws (provided) to attach the ventilator to the

of 2/12. Discharge end of the blower should be pointed

away from prevailing winds.

 

 

roof. 6 MOUNTING HOLES are provided.

 

 

 

 

 

q 12 Seal the screw heads, loosened shingles, and edges of

 

 

 

 

 

the flashing sheet, with a good grade of roofing cement.

 

 

 

 

 

q 13 Check for free movement of the spring-loaded damper,

 

 

 

 

 

re-install BIRD SCREEN and ventilator cover. Turn on

 

 

 

 

 

power and check operation.

 

WALL MOUNT INSTALLATION

MODEL 801640

Page 3

For use with Wolf CTWH30/CTWH36 wall mount, IH4227 island chimney hoods, 10” tall & 30” wide x 18” tall wall hoods.

PREPARE THE WALL

WIRE THE VENTILATOR

 

 

 

25"

 

 

 

 

10¾"

 

 

 

 

 

8½"

REMOVE

 

 

 

 

SIDING

 

 

 

Stud

 

 

127

/8"

 

 

11" dia.

 

 

Wall

Pilot

 

hole

 

 

 

 

 

 

 

 

 

 

 

 

Hole

 

 

 

 

 

 

Stud

29½"

 

 

 

 

 

 

 

 

1¼"

Wall

91/8"

 

 

 

dia. hole

 

 

 

 

 

 

7¼"

OUTSIDE - WALL VIEW

From inside the wall:

q 1 Drill a PILOT HOLE through the wall, 8½" from the inside edge of a WALL STUD.

From outside - on the wall:

q 2 Measure and mark the 25" x 29½" rectangle. Cut and remove only the siding inside this rectangle.

q 3 Measure and mark the 11" DIAMETER HOLE and the 1¼" DIAMETER HOLE. Cut these holes all the way through the wall.

BLACK

TO

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 VAC

 

WHITE

GREEN

 

LINE IN

 

 

TO

 

 

 

TO

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

q 4 Remove 7 COVER SCREWS and lift off ventilator cover. Remove BIRD SCREEN and WIRING COVER.

q 5 Feed the electric power cable through the 1¼" DIAMETER HOLE and connect cable to ventilator with a proper connector for the type of cable being used.

q 6 Connect BLACK TO BLACK, WHITE TO WHITE, and the

GREEN TO GREEN or bare wire. Replace wiring cover.

INSTALL THE VENTILATOR

 

6

7 Cover

Mounting

Holes

Screws

 

 

Shipping

 

Cardboard

 

Wiring

 

Cover

 

Bird Screen

 

Flashing Sheet

OUTSIDE - WALL VIEW

q 7 Remove SHIPPING CARDBOARD from blower wheel.

q 8 Place ventilator on wall so that ventilator's discharge collar fits into 11" diameter hole.

q 9 Use the 6 screws (provided) to attach the ventilator to the wall. 6 MOUNTING HOLES are provided.

q 10 Seal the screw heads and edges of the flashing sheet with a good grade of roofing cement.

q 11 Check for free movement of the spring-loaded damper, re-install BIRD SCREEN and ventilator cover. Turn on power and check operation.

MODEL 801640

Page 4

ATTACH POWER CORD TO HOOD

Some hoods require the use of a separate power cord and strain relief bushing (included), for proper wiring of exterior blowers. Please refer to the hood manual for proper installation instructions.

MODEL 801641

Page 1

EXTERIOR VENTILATOR KITS

WARNING

 

CAUTION !

 

 

 

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1.Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer or your distributor.

2.Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.

3.Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.

4.Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.

5.When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

6.Ducted fans must always be vented to the outdoors.

7.Do not use this unit with an additional speed control device.

8.To reduce the risk of fire, use only steel ductwork.

9.This unit must be grounded.

TO REDUCE THE RISK OF A COOKTOP GREASE FIRE:

1.Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.

2.Always turn hood ON when cooking at high heat or when cooking flaming foods.

3.Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.

4.Use proper pan size. Always use cookware appropriate for the size of the surface element.

TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A COOKTOP GREASE FIRE, OBSERVE THE FOLLOWING:*

1.SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.

2.NEVER PICK UP A FLAMING PAN - You may be burned.

3.DO NOT USE WATER, including wet dishcloths or towels - violent steam explosion will result.

4.Use an extinguisher ONLY if:

A.You know you have a Class ABC extinguisher and you already know how to operate it.

B.The fire is small and contained in the area where it started.

C.The fire department is being called.

D.You can fight the fire with your back to an exit.

*Based on “Kitchen Fire Safety Tips” published by NFPA.

1.For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.

2.To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.

3.Your ventilator motor has a thermal overload which will automatically shut off the motor if it becomes overheated. The motor will restart when it cools down. If the motor continues to shut off and restart, have the hood serviced.

4.Please read specification label on product for further information and requirements.

SPECIFICATIONS

MODEL

VOLTS

AMPS

CFM

DUCT SIZE

 

 

 

 

 

801641

120

5.7

900

10 "DIA.

 

 

 

 

 

PLAN THE INSTALLATION

1.Locate the ventilator so the length of the duct run and number of elbows and transitions needed are kept to a minimum.

2.Where possible, ventilator should be located between wall studs or roof rafters.

3.Avoid pipes, wires, or other ductwork that may be running through the wall.

4.Be sure that there is enough space for any transitions that may be needed between the ventilator and the connecting ductwork.

5.For best performance, locate transitions nearest to ventilator.