Fill / vent the system
Procedure for boilers with
internal lling facility
not for <DE> <AT>
- Fill the entire heating system and boiler via the lling facility or an on-site
ll & drain valve up to approx. 0.5 - 1 bar, whilst simultaneously venting the
heating system.
- Close the shut-off valves on the heating water side of the boiler (ow and
return).
- Push the drain hose onto the drain valve of the hydraulic assembly.
- Clean the heat exchanger by opening the internal lling facility and the
drain valve simultaneously on the hydraulic assembly (make sure there is
no air remaining in the heat exchanger).
Procedure for boilers without
internal lling facility
Filling the system
Fill the system and vent it thoroughly to safeguard the perfect
function of the gas red boiler.
Otherwise there is a risk of faults.
The heating water must not be mixed with inhibitors or antifreeze;
otherwise leaks and ooding could result.
- Close the gas ball valve.
- Before connecting the gas red boiler to the heating system, ush the entire
system to remove residues such as welding pearls, hemp, putty, etc. from
the pipework and to remove air that may have collected.
- Fill the DHW system of the boiler until water ows out of a DHW draw-off point.
- To ll the heating system use the ll & drain connections. Open the cap of the
automatic air vent valve on the heating circuit pump by approx. 2 revolutions, but
do not remove the cap.
- Open all radiator valves and the shut-off valves on the heating water side of the
boiler.
- Fill the entire heating system and boiler via the ll & drain valves (Wolf
accessory) up to approx. 0.5 bar, whilst simultaneously venting the heating
system.
- Close the return shut-off valve on the heating water side of the boiler.
- Attach drain hose to the drain valve on the hydraulic assembly (alternative, if only
a ll & drain connection is provided).
- Clean the heat exchanger by opening the ll & drain valve and/or the
drain valve simultaneously on the hydraulic assembly
(make sure there is no air remaining in the heat exchanger).
- Remove the drain hose and open the boiler shut-off valve(s) on the heating water
side again.
- After venting, raise the system pressure to 2.5 bar.
- Start the boiler, set the heating water temperature selector to position "2"
(pump running, illuminated signal ring (status display) constantly green).
- Vent the pump; for this, briey open and then retighten the air vent
screw, optimum venting in pump stage 3.
Top up with water when the system pressure falls severely.
- Open the gas shut-off valve. Press the reset button.
- When in constant use the heating circuit vents automatically via the heating
circuit pump, venting optimum at pump stage 3. After venting set to pump
stage 1 or 2 for reduced noise, depending on customer preference.
- At system pressure below 1.0 bar the boiler may experience faults.
If necessary ll on heating side.
Internal lling
facility not for
<DE><AT>
Drain
valve
Fig.: Shut off valves (accessory)
Gas shut-off valve
Heating ow
(incl. ll & drain
connection)
Heating return
(incl. ll & drain
connection)
Automatic
air-vent valve
Fill & drain
Connection
Note