Wolf ATEX Operation And Maintenance Instruction Manual

LL-366 Issue 16
DF433
Wolf ATEX 400VA GRP Transformer Operation and Maintenance Instructions Please Retain – Read Before Use
This Wolf ATEX Transformer has a durable GRP enclosure housed in a stainless steel skid, within the enclosure is a transformer component with maximum load of 400 VA. The Transformer is approved as Group II equipment for use in zone 1 & 2 potentially explosive gases, vapours, mists and dusts where the T3 temperature class permits.
Approval Codes/Certification:
II 2 GD Ex ed IIC T3 IP66
Ex tD A21 T195ºC
(Tamb = -20 to +55ºC) Supply Voltage: 230VAC or 110VAC +6%, -10%
Output Voltage: 110VAC or 24VAC
Check equipment label for confirmation of exact rating. Certificate ‘X’ suffix - Do not open Transformer while energized.
. Notified Body LCIE Paris – Head Office
33, Avenue du General Leclerc 92260 Fontenay-aux-Roses France
Notified body number: 0081
See attached ATX EC Declaration of Conformity.
IMPORTANT
1. Read this leaflet carefully before commencing to use the Transformer and retain it for future use.
2. Check the rating label to ensure the Transformer is suitable for the supply provided, ambient temperature present and IP rating.
3. The Transformer housing is constructed from GRP (Glass Reinforced Polyester) and the mounted sockets are plastic, the end user must ensure that these materials are suitable for the atmosphere the transformer will be used in. Excessive force should not be used on plastic components.
4. The Transformer must not be opened when energized, even after disconnection from the mains supply a delay of 5 minutes should be observed before opening.
5. Ensure all replacement fuses are of the correct type and current rating.
6. Prices and design are subject to alteration without notice. All products sold are subject to our conditions of sale. A copy of these instructions with any relevant revisions can be found at www.wolf-safety.co.uk
USE OF ATEX TRANSFORMERS
1. The Transformer is designed to supply a maximum load of 400 VA, if this is exceeded the internal output fuse may blow. Any apparatus operated from the transformer should be checked to ensure that the maximum load is not exceeded.
2. The fuse ratings used in 24 Volt output transformers have been selected for use with Wolf temporary lighting products. For the fuses to provide the required level of protection the output cable to any connected device must be limited to a maximum 35 metres of 4mm
2
cable or 20 metres of
2.5mm
2
cable. Longer cable lengths and smaller cable diameters will increase cable impedance; this may prevent correct fuse operation, resulting in overheating, damage to the Transformer and a potentially unsafe condition in the safe or hazardous area. Apparatus with long cable lengths (>20m) must be checked to ensure the calculated voltage drop will not prevent the apparatus from operating within the specified voltage tolerance (+ 6%, -10%).
3. The fuse ratings used in 110Volt output transformers have been selected for use with Wolf temporary lighting products. For the fuses to provide the required level of protection the output cable to any connected device must be limited to a maximum 150 metres of 4mm
2
cable or 90 metres of 2.5mm
2
cable. Longer cable lengths and smaller
cable diameters will increase cable impedance, this may prevent correct fuse operation, resulting in overheating, damage to the transformer and a potentially unsafe condition in the safe or hazardous area.
4. It is the user’s responsibility to ensure that any cable configuration used with this Transformer will not compromise the integral fuse protection of the unit.
5. All Transformers have terminal blocks suitable for up to 4mm
2
live, neutral and earth. Only one conductor should be fitted to each terminal block, for screwed type terminal blocks all terminals should be fully tightened down whether a conductor is fitted or not.
6. Approved cable glands must be used and be suitable for the type of cable used. Any unused cable entries should be blanked off with an approved stopper plug to maintain a minimum IP rating as marked on the certification label.
MAINTENANCE
1. Isolate the Transformer from the mains and wait 5 minutes before opening.
2. It is essential that all Transformers are maintained in accordance with the requirements of EN60079-17
3. A visual check should be carried out to ensure all internal cable is in good condition, and not suffering any sign of damage or degradation. All internal connections should be checked to ensure that they are correctly secured.
4. The condition of the gaskets on the GRP enclosure should be inspected to ensure there is no breakdown in the IP66 rating.
5. If changing the input or output fuse care should be taken to replace with the correct type of fuse and secure the screwed cover on fully.
6. IMPORTANT. No modifications are permitted to the Transformer,
DISPOSAL OF WASTE MATERIAL
Disposal of packaging, Transformer and associated parts should be carried out in accordance with national regulations.
Ingress protection level: IP66
WARNING: USE ONLY GENUINE WOLF REPLACEMENT PARTS.
Spares list:-
Input
Voltage
Input Fuse
Wolf Part
Number
Output
Voltage
Output
fuse
Wolf Part
Number
110V
4Amp
(aM)
LL-377 24V
16Amp
(gG)
LL-379
230V
2Amp
(aM)
LL-1002 24V
16Amp
(gG)
LL-379
230V
2Amp
(aM)
LL-1002 110V
4Amp
(gG)
LL-1007
Output
Voltage
Output
fuse
Wolf Part
Number
Transformers with part No suffix /1F10
or /2F10 (2 x O/P fuse)
24V
10Amp
(gG)
LL-1110
Transformers with part No suffix /1F8 or
/2F8 (2 x O/P fuse) )
24V
8Amp
(gG)
LL-1024
Transformers with part No suffix /1F6 or
/2F6 (2 x O/P fuse)
24V
6Amp
(gG)
LL-1016
LL-376 230/110 input - 24v output 400VA transformer component. LL-378 24 volt ATX socket.
For further spares or if your transformer does not appear in the list above please contact Wolf Safety.
The Wolf Safety Lamp Co. Ltd has a policy of continuous product improvement. Changes in design details may be made without prior notice.
LL-366 Issue 16
DF433
Wolf ATEX 400VA Transformer Usage Guidance Document
Following are details of fuse values and cable length and size that are recommended for use with Wolf ATEX Transformers .
Transformers – 230 or 110 Volt Input, 24 Volt Output – Fuse Values
Transformer Type Input Voltage & Input
Fuse Rating
Output Voltage & Output Fuse
Rating
Example of compatible lighting sets:
GRP/ Stainless steel
230V, 2Amp (aM) 24V, 16Amp (gG) Up to 4 x LL-500
or up to 4 x WF-300
or up to 8 x LX-400
or up to 4 x LL-24 @ 20m*
GRP/ Stainless steel
110V, 4Amp (aM) 24V, 16Amp (gG)
GRP/ Stainless steel
230V, 2Amp (aM) 24V, 10Amp (gG) Up to 2 x WF-300 @ 50m††
or up to 3 x LL-500 @ 35m†
or up to 3 x WF-300 @ 35m†
or up to 6 x LX-400 @ 35m‡
GRP/ Stainless steel
110V, 4Amp (aM) 24V, 10Amp (gG)
GRP/ Stainless steel
230V, 2Amp (aM) 24V, 8Amp (gG) Up to 4 x LL-420
or up to 2 x LL-420 + 2 x WF-300
or up to 2 x LL-420 + 2 x LL-500 or up to 2 x LL-420 + 4 x LX-400
or up to 2 x LL-24 @ 50m**
GRP/ Stainless steel
110V, 4Amp (aM) 24V, 8Amp (gG)
GRP/ Stainless steel
230V, 2Amp (aM) 24V, 6Amp (gG)
Up to 4 x LL-420/20 (20m cable)
GRP/ Stainless steel
110V, 4Amp (aM) 24V, 6Amp (gG)
The fuse ratings are for the GRP and Stainless Steel 400VA transformers supplied by Wolf Safety.
For transformers with part numbers suffixed /2FXX equipped with 2 off output fuses (1 fuse per side), the permissible total number of lights will
increase. However this increase must not exceed the fuse rating and/or VA rating of the transformer and the maximum cable lengths in the table
below must be observed.
Transformers – 230 or 110 Volt Input, 24 Volt Output – Cable length and size
Product Plug type Cable type Cable size Max. cable length from transformer socket LL-500/WF-300 ATX SY 4mm2 35m total WF-300 ATX SY 4mm2 50m††(2 lamps, 10A o/p fuse) LX-400 ATX SY 2.5mm2 20m total LL-500/WF-300/LX-400 Ceag SY 2.5mm2 20m total LL-500/WF-300/LX-400 Ceag/ATX Ship’s 2.5mm2 20m total LL-500/WF-300 Ceag/ATX Ship’s 2.5mm2 35m†(3 lamps, 10A o/p fuse) LX-400 Ceag/ATX SY/Ship’s 2.5mm2 35m‡(6 lamps, 10A o/p fuse) LL-420 (10m cable) Ceag/ATX HO7FRN 1.0mm2 10m total LL-420/20 (20m cable) Ceag/ATX HO7FRN 1.0mm2 20m total LL-24 Ceag/ATX SY/Ship’s 2.5mm2 20m*(4 lamps, 16A o/p fuse) LL-24 Ceag/ATX SY/Ship’s 2.5mm2 50m**(2 lamps, 8A o/p fuse)
A total of 4 x LL-500 or WF-300 lights, or a total of 8 x LX-400 lights, can be connected to a 400VA transformer, dependent on the configuration - see
above; no other equipment must be connected to the transformer.
LL-500 and WF-300 lamps cannot be linked at 24V. ‐ LX-400 lamps (up to 4 units) can be linked with a total of no more than 20m of cable with a 16A (gG) fuse or 35m of cable with a 10A (gG) fuse. ‐ LL-420 handlamp must be connected directly to a transformer socket. ‐
Transformers – 230 Volt Input, 110 Volt Output – Fuse Values
Transformer Type Input Voltage and Input Fuse Rating Output Voltage and Output Fuse Rating
GRP 230V, 2Amp (aM) 110V, 4Amp (gG)
The fuse ratings are for the GRP and Stainless Steel 400VA transformers supplied by Wolf Safety.
Transformers – 230 Volt Input, 110 Volt Output – Cable length and size
Product Type Maximum Number of Lamps Per
Transformer
Maximum Cable Length 4mm
2
Maximum Cable Length 2.5mm2
LL-500 5 150 metres 110 metres WF-300 5 150 metres 110 metres LX-400 12 150 metres 110 metres
Transformers – 230 or 110 Volt Input, 12 Volt Output – Fuse Values
Transformer Type Input Voltage &
Input Fuse Rating
Output Voltage & Output
Fuse Rating
Example of compatible lighting sets:
GRP/ Stainless steel 230V, 2Amp (aM) 12V, 10Amp (gG)
Up to 2 x LL-12 @ 15m cable
GRP/ Stainless steel 110V, 4Amp (aM) 12V, 10Amp (gG) GRP/ Stainless steel 230V, 2Amp (aM) 12V, 6Amp (gG)
Up to 1 x LL-12 @ 35m cable
GRP/ Stainless steel 110V, 4Amp (aM) 12V, 6Amp (gG)
The fuse ratings are for the GRP and Stainless Steel 400VA transformers supplied by Wolf Safety.
Transformers – 230 or 110 Volt Input, 12 Volt Output – Cable length and size
Product Plug type Cable type Cable size Max. cable length from transformer socket LL-12 ATX SY 2.5mm2 15m (2 lamps, 10A o/p fuse) LL-12 ATX SY 2.5mm2 35m (1 lamps, 6A o/p fuse)
‐ ‐ A total of 1 or 2 x LL-12 lamps may be connected to a 12v output transformer, dependent on the configuration - see above; no other equipment must be