Whirlpool AMD 384, AMD 383 INSTRUCTION FOR USE

4
PRECAUTIONS FOR USE
Warning:
• Never operate the air conditioner with wet hands.
• The rated voltage of this air conditioner is 220­240V with a tolerance of ±22V for fluctuation. The compressor will vibrate if the voltage is too low, causing damage to the cooling system.
• If you notice anything unusual (e.g. burnt smell), switch off the power supply immediately and contact the Whirlpool Authorized Service Centre nearest you. If the abnormal condition continues, the air conditioner could be damaged and could also cause electrocution or fire.
• Grounding: The unit must be reliably grounded. The grounding cable must be connected to the special grounding system in the building. If the building does not have a grounding system, ask an expert electrician to install one. Never connect the grounding cable to a gas pipe, water pipe, sewage pipe or other unless the professional considers it reliable.
• Set the room temperature appropriately. The difference between indoor and outdoor temperature should be 5°C. Appropriate adjustment of the temperature setting serves to reduce consumption.
• When the air conditioner is running, do not leave doors and windows open in the room. This will prevent loss of effectiveness of the air conditioner.
• Never block the air inlet or outlet of indoor and outdoor unit, as this will decrease the effect of the air conditioner or cause it to shut down or even catch fire.
• Spray cans, chemicals and gas tanks must be placed at least 1m away from the indoor and outdoor unit; they could cause fire or explosion
• Make sure to mount the outdoor unit on a sturdy base. If the base is damaged and unsteady, the unit could fall and cause injury.
• Do not stand or place anything on the outdoor unit. Persons or objects falling from the unit could cause injuries.
• Do not repair the air conditioner yourself. Incorrect repairs could cause electrocution or fire. Contact the Whirlpool Authorized Service Centre nearest you for repairs.
• Never reach with your finger or a stick into the indoor or outdoor unit.
• Never blow the air directly at pets or plants, as this may harm them.
• Never spray water onto the unit or wash the air conditioner with water.
• Never let the air conditioner blow on a heat source. This could put the flame out and cause carbon monoxide poisoning.
• To avoid any harm to your health, do not blow the cold air on your body too long or lower the room temperature too much.
• This air conditioner cannot be used for drying clothes or chilling foods.
• Do not spray any paint or pesticide on the unit, or it may cause fire.
Warning:
• Persistent abnormality indicates that the air conditioner may be damaged with the consequent risk of electric shock or fire. This may cause an electric shock.
• To prevent fire always use a special power supply circuit.
• Disconnect the air conditioner from the power supply if it is to be left unused for a long period.
• For 18-23K, 230V, with a tolerable fluctuation of ±23V. The compressor is subject to strong vibrations under very low voltages which can damage the refrigerating system. Electrical elements are easily damaged by high voltage.
• Ensure that the power supply is suitably protected by a special circuit with air breaker. The air conditioner automatically starts or stops according to requirements. Do not switch the air conditioner on and off too often as this can damage the appliance. This may cause an electric shock or injury.
• Do not cut or damage the external cable. Any damaged external cable must be replaced by qualified electricians.
5
DESCRIPTION OF AIR CONDITIONER
INDOOR UNIT
OUTDOOR UNIT
Drain Pipe To drain water produced while the unit is functioning
Refrigerant Tube
Air Inlet
Air Outlet
Indicator light state
1. POWER indicator light: on/off with system running / stop and flash when system in protection state.
2. COOL indicator light: on/off with the operation of cool ON/OFF.
3. HEAT indicator light: on/off with the operation of heat ON/OFF.
CAUTION:
Wrong wiring connection will cause electrical malfunction. Do not pull the wire when fixing it wire clamp. Do not let the wire too loose in the outdoor unit.
Wiring terminal
Power connection cord Power supply cord
Sign connection cord
Working temperature range
NOTE
1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid hazard.
2. The appliance shall be installed in accordance with national wiring regulations.
3. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be con­nected in fixed wiring.
Indoor side DB/WB (°C) Outdoor side DB/WB (°C)
Maximum cooling 32/23 48/30
Minimum cooling 21/15 18/-
Maximum heating 27/- 24/18
Minimum heating 20/- -7/-8
6
WIRE CONTROLLER (standard fitting)
WARNING!
Never install the wire controller in a place where there is water leakage. Avoid bumping, throwing, tossing or frequently opening the wire controller.
Each part of the manual controller
1. Timer display
2. Fan speed display (Auto, High, Middle, Low)
3. Defrosting display
4. Saving state display
5. Set temp. display
6. Ambient temp. display
7. Fresh air display
8. Mode (COOL, DRY, FAN, HEAT, AUTO)
9. Malfunction display
10. Sleep display
11. MODE button
12. Button for temperature increase
13. Button for temperature decrease
14. FAN button
15. SWING button
16. TIME button
17. ON/OFF button
18. Display of Swing state
Fig. 1
7
1) ON/OFF (Fig.2)
• Press this button the unit will start.
• When repress the button, the unit will stop running.
2) Fan control (Fig. 3) (The relevant contents are shown in the figure.)
• Press this button to change the fan speed of:
• At the DRY mode: the fan speed will be set for low fan speed automatically.
3) Temperature adjustment (Fig.4)
• Press the temperature adjustment button : For temperature increase; : For temperature decrease.
(Press this button once, the temperature will be increased or decreased by 1°C) NOTE: Lock function:
Press " " and " " at the same time for 5 seconds, the set temperature indicating area shall display "EE" and all keys' response shall be shut off, all buttons
will sound; and repress the " " and " " simultaneously for 5 seconds, the lock function will be released. When the displayer of long-distance monitoring or central controller has been shielded, the buttons and remote control signal will be shielded too, the setting temperature will display "CC".
• The set temperature range under each mode: HEAT 16°C ~ 30°C COOL 16°C ~ 30°C DRY 16°C ~ 30°C FAN The temp. cannot be set up AUTO The temp. cannot be set up
4) Swing mode set up (Fig.5)
• when pressing "SWING" button, the type style "SWING" will be displayed on LCD, the unit will run in Swing mode
• when repressing the "SWING" button, that the type style "SWING" will be disappeared, and the unit will stop running in Swing mode.
Note: The SLEEP function could be set up by wireless remote control.
5) Sleep mode set up (Fig. 6)
When under the cooling or dehumidifying mode, after receiving the SLEEP order for 1 hour, the previous set temperature Tset will be risen for 1°C, and another 1°C will be risen after 2 hours that means that the temperature been risen 2°C within 2 hours. Then the unit will run according to this set temperature. When under the heating mode, after receiving the SLEEP order for 1 hour, the previous set temperature Tset will be lower for 1°C, and another 1°C will be lower after 2 hours that means that the temperature been lowered 2°C within 2
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
8
hours. Then the unit will run according to this set temperature There is no SLEEP mode under fan mode. Note: the wired remote control has no SLEEP mode button; if SLEEP mode is needed to be set, complete the procedure by wireless remote control.
6) Running mode setup (Fig. 7)
• When pressing this button once, the operation mode will be changed as follow:
COOL DRY FAN HEAT AUTO
• At "COOL" mode, the "COOL" icon will light on, the current temperature should be set up lower than the ambient temperature. If the setting temperature is higher than the ambient temperature, the COOL mode will not start, only the fan is active.
• In "DRY" mode, the "DRY" icon will light up. The inner fan will run at low fan speed in a certain range. This DRY efficiency in this mode is more obvious than the one in COOL mode, and the power saving efficiency is better.
• In "HEAT" mode, the "HEAT" icon will light up. The setting temperature should be set up higher than the present temperature; if it is lower than the present ambient temperature, the HEAT mode is unavailable.
• In "FAN" mode, the "FAN" icon will light up.
• In "AUTO" mode, the " AUTO" icon will light up, according to the ambient temperature, the unit will automatically adjust the running mode.
• In "HEAT" mode, when the outdoor temperature is low and there is high humidity, and there is frost on the outdoor unit, the heating efficiency will be reduced. In this case, the product will start defrosting automatically, and displays the "DEFROST" icon.
NOTE: There is no HEAT mode in the cooling only unit, after the power saving set up, the auto mode will be shielded.
7) TIMER setup (Fig. 8)
At unit turned off, the timer on could be set up, at unit turned on, the timer off could be set up. After pressed the "TIMER" button, the unit could be set up, and the TIMER icon flashes, by pressing the buttons " ", " " could increase or decrease the time of timer, when repress the "TIMER" button, the Timer is valid, the units will start calculate the time. When the unit is in the TIMER, press the "TIMER" button could cancel the time.
NOTE: When the protection or malfunction happens after the timer on was set up, the time place will display the protection or the error codes, the timer button cannot be setup, but the time you have setup before is still available.
8) Outer ambient temperature display (Fig. 9)
Under normal condition, "ENV" will display the room ambient temperature, at unit turned on, or unit turned off status, press "SWING" button last for 5 seconds, the LCD will display "OUT ENV". A) If tested the outdoor temperature is the positive value, that the setting
temperature will not be displayed, the original environment temperature displayer displays the Fig 8 system internal tested outdoor environment temperature.
B) If tested the outdoor temperature is the negative value, the original
environment temperature displays the system inner tested the absolute value of the out environment. After displayed the outdoor environment temperature 10 seconds later, the system will back to the room ambient temperature displaying surface.
NOTE: If the unit has been unconnected with the outdoor ambient sensor, this function will be unavailable.
Fig.7
Fig. 8
Fig. 9
9
9) SAVE set up (Fig. 10)
At unit turned off, to press the "FAN" +" " buttons continuously for 5 seconds, adjust the Saver set menu, at this time displays "SAVE" "COOL" icons, (if it is the first setup, that will display the initial value:26 °C), at the temperature setting district, it displays the lower limit temperature,and the set temperature flashes,
by pressing " " and " " buttons to set the cooling temperature lower limit (the setting range is 16~30), press "ON/OFF" button to confirm; by pressing " " and " " buttons to set cooling temperature upper limit, it will flash and display at ambient temperature, (the setting range is 16-30), and press "ON/OFF" button to confirm.
NOTE: The upper limit temperature should not be lower than the setting lower limit temperature. If upper limit temperature is lower than the lower limit temperature, the system will default. The higher is the upper limit temperature, the lower is the lower limit temperature. Press "MODE" button, to complete the save setting in COOL, DRY mode, and transfer to the save setting in HEAT mode (There is no the function in cooling only unit), at this time, it displays the "SAVE", "HEAT" icons, after setup has been completed, then press "FAN" + " " button last for 5 seconds, and quit the SAVE setting operation. If the SAVE interface has been opened, the system will respond to the last button input after 20 seconds, there is no any operation, the system will quit the menu, and displays the normal unit off interface. The above setting has been completed, the system will display "SAVE" icon, no matter by buttons on displayer or the wireless remote control, the setting temperature should not exceed the former SAVE setup temperature range, for example as show in Fig. 9, we set up the cooling lower limit is 23 °C in SAVE setting, the upper limit is 27 °C , the user can set the cooling temperature between 23 °C to 27 °C by the wireless remote control and buttons on displayer. If the set up upper limit temperature is the same with the lower limit temperature that the system only can run at the corresponding modes at the set temperature. After the SAVE mode set up, at unit turned off, press the "FAN" + " " buttons for 5 seconds, will quit the SAVE setting function, but the former setting data will not clear, and the next time SAVE setting will be the initial setting temperature. After powered off, the SAVE setup function will be memorized, the next time power on, the SAVE setting is still active. Set up the SAVE mode, the SLEEP, AUTO modes will shield.
10) MEMORY function setup (Fig. 11)
At unit turned off, press "MODE" button for 10 seconds, could switch whether turn on or off the unit state after powered off, at setting temperature district displays 01, denote that the unit is turned off after powered off, 02 denote that do not memorize the unit turn on or turn off, press "ON/OFF" button quit setting. If the memory turn on and off interface is displayed, the system will quit the menu, the system will respond to the last button input after 10 seconds, there is not any operation, the system will quit the menu, and displays the normal unit off interface, the memory function setting still have been stored.
Fig. 10
Fig. 11
10
11) Malfunction display (Fig.12)
When the malfunction happened during operation, the displayer will display "ERROR" icon and flash, and meanwhile will display the error code, when there are multi-malfunction happened, the displayer will display the error codes circularly. The first number denotes the system number, if there is only one system in the display, it will not display the system number, the following two are error codes. For example as show in right figure, that denotes the system 1, low­pressure protection of compressor. The meaning of error codes as show in below:
E5 Material Malfunction will be showed by the indicator light on the Mother Board of Outside Unit.
NOTE When the "EH" malfunction happened, please cut off the power supply of unit
immediately, and please ask for the professional to repair!
Fig. 12
Fault code
Fault
Fault code
Fault
E0 Water pump malfunction F0
Failure of Indoor Room Sensor at Air Intake
E1 High pressure protection of compressor F1
Failure of Evaporator Temperature Sensor
E2 Indoor anti-frozen protection F2
Failure of Condenser Temperature Sensor
E3 Low pressure protection of compressor F3 Failure of Outdoor Ambient Sensor E4
Air discharge high-temperature protection of compressor
F4 Failure of Exhaust Temperature Sensor
E5 Overload protection of compressor F5
Failure of Indoor Room Sensor at Wire Controller
E6 Transmit malfunction E8 Indoor fan protection EE Keys are locked (not failure)
E9 Water flow protection CC
The unit is remotely monitored or controlled by centralized controller and the wire controller's functions are invalidated (not failure)
FF
Connected control communications Failure
• Week Timing Controller (With Centralized Control Function)
Centralized Control and Week Timer Functions: The centralized controller and the weekly timer are integrated in the same wire controller. The system has both the centralized control and the week timing functions. Up to 16 sets of units can be controlled simultaneously by the centralized controller (weekly timer). The weekly timer has the function of invalidating the lower unit. The weekly timing function is able to realized four timing ON/OFF periods for any unit every day, so as to achieve fully automatic operation. No timing control can be set for holidays.
This WEEKLY TIMER adopts 485 mode to communicate with manual control of every duct type unit, and it can control up to 16 units. Adopting 2-core twisted-pair wire, the longest communication distance of this TIMER is 1200m. After connected to power, the WEEKLY TIMER can display all connected units (sequence of unit is determined by code switch of manual control of every duct type unit). On and off of every duct type unit can be done through the Timer On / Off of this WEEKLY TIMER, and the button shield operation of manual control can be done through shield setting on WEEKLY TIMER. Mode selection and temperature adjustment and other operations are done through the manual control at every unit.
Note:
1. For upper unit checks 16 lower units consecutively, there will be no more than 16 seconds delay when setting works till unit responds.
2. Please let us know your requirement before your placing the order, for this WEEKLY TIMER will only be prepared when customer orders (communication joint with WEEKLY TIMER on manual control had been prepared).
11
WEEKLY TIMER (optional fitting)
Unit display
Single / Group display
Timer week display
Timer display
Timer state display
Timer time period display
Timer on/off time display
Unit on display Unit off display
Clock display
Confirm button
Decrease button
Increase button
Cancel/delete button
Single/Group button
Timer/Time button
On/Off button
Fig. 1
12
1. Press or to select the unit that needed to be control. It is available to control several units by Group Control (1~16), or control single unit by Single Control.
2. When selected a certain or several units by Single Control or Group Control, Timer setting and On/off setting can be set. Timer setting can set 4 on/off times in a day in one week; and on/off setting can be done by pressing on/off button.
3. Connection between WEEKLY TIMER and manual control is shown as following:
Week Timer
Manual control Manual control
16 units in max
Telephone wire box
Telephone wire box
Telephone wire box
Twisted-wire with crystal joint
Longest distance 1200 m
Corresponding relation between code switch and sequence of unit
(Note: Putting code switch to ON means 0)
P = Position S = Sequence
Power Supply ~ 220V
On/Off power
P S P S P S P S
0000 1 0010 5 0001 9 0011 13 1000 2 1010 6 1001 10 1011 14 0100 3 0110 7 0101 11 0111 15 1100 4 1110 8 1101 12 1111 16
13
WIRE CONTROLLER (with week timer functions)
1. Failure status displayTiming display
2. Fan speed display (Auto, High speed, Medium
speed, Low speed)
3. Defrosting status display
4. Energy saving status display
5. Set temperature display
6. Ambient temperature display
7. Fresh air status display (not supplied)
8. Mode (cooling, dehumidifying, fan, heating,
auto)
9. Failure status display
10. Sleep status display
11. Mode key
12. Set temperature increase key
13. Set temperature decrease key
14. Fan speed key (fresh air setting)
15. Sleep key (outdoor environment temperature
check)
16. Timing key
17. ON/OFF key
18. Timer day display
19. Timer segment display
Fig. 1
• Never install the wire controller in a place where is water leakage.
• Avoid bumping, throwing, tossing or frequently opening the wire controller.
Loading...
+ 22 hidden pages