Western Telematic MPC-8H-2, MPC-20VS16-3, MPC-20VD16-3, MPC-8H-1, MPC-20VS20-2 User Manual

...
0 (0)
WTI Part No. 13762
MPC Series
Managed Power Controllers
Models Covered:
MPC-8H-1 MPC-20VS20-1 MPC-20VS20-2 MPC-20VS16-3 MPC-20V-1 MPC-8H-2 MPC-20VD20-1 MPC-20VD20-2 MPC-20VD16-3 MPC-20V-2 MPC-16H-1 MPC-20VS30-1 MPC-20VS30-2 MPC-20VS32-3 MPC-DISPLAY MPC-16H-2 MPC-20VD30-1 MPC-20VD30-2 MPC-20VD32-3 MPC-18H-1 MPC-18H-2
Rev. G
Firmware Version 1.50 and Higher
User's Guide
Secure Racking
If Secure Racked units are installed in a closed or multi-unit rack assembly, they may require further evaluation by Certification Agencies. The following items must be considered.
1. The ambient within the rack may be greater than room ambient. Installation should be such that the amount of air flow required for safe operation is not compromised. The maximum temperature for the equipment in this environment is 55°C. Consideration should be given to the maximum rated ambient.
2. Installation should be such that a hazardous stability condition is not achieved due to uneven loading.
3. Side vents are used to dissipate heat generated within the unit. When mounting the unit in an equipment rack, make certain to allow adequate clearance for venting.
Input Supply
Check nameplate ratings to assure there is no overloading of supply circuits that could have an effect on overcurrent protection and supply wiring.
Warnings and Cautions:
Installation Instructions
Grounding
Reliable earthing of this equipment must be maintained. Particular attention should be given to supply connections when connecting to power strips, rather than direct connections to the branch circuit.
No Serviceable Parts Inside; Authorized Service Personnel Only
Do not attempt to repair or service this device yourself. Internal components must be serviced by authorized personnel only.
Shock Hazard - Do Not Enter
Lithium Battery CAUTION: Danger of explosion if battery is incorrectly replaced. Replace only with same or equivalent type recommended by the manufacturer. Discard used batteries according to the manufacturer's instructions.
i
Disconnect Power
If any of the following events are noted, immediately disconnect the unit from the outlet and contact qualified service personnel:
1. If the power cord becomes frayed or damaged.
2. If liquid has been spilled into the device or if the device has been exposed to rain or water.
Two Power Supply Cables
Note that some MPC series units feature two separate power circuits, and a separate power supply cable for each power circuit. If your MPC unit includes two power supply cables, make certain to disconnect both power supply cables from their power source before attempting to service or remove the unit.
Detached 15-Amp “Starter” Cable(s)
If the MPC unit includes a detached, 125 VAC, 15 Amp “Starter” Cable(s,) this allows you to connect the MPC to power for bench testing and initial start up is adequate for applications that only require 15 Amps. For 20-Amp power switching applications, please refer to the WTI Power Cable guide supplied with the unit, or use appropriate 20­Amp cables.
Warnings and Cautions
Units with Attached Power Supply Cable(s)
For MPC units that include attached power supply cable(s), the socket outlet(s) shall be installed near the equipment and shall be accessible.
ii
Agency Approvals
FCC Part 15 Regulation
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation
WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment
EMC, Safety, and R&TTE Directive Compliance
The CE mark is affixed to this product to confirm compliance with the following European Community Directives:
Council Directive 89/336/EEC of 3 May 1989 on the approximation of the laws of Member States relating to electromagnetic compatibility;
and
Council Directive 73/23/EEC of 19 February 1973 on the harmonization of the laws of Member States relating to electrical equipment designed for use within certain voltage limits;
and
Council Directive 1999/5/EC of 9 March on radio equipment and telecommunications terminal equipment and the mutual recognition of their conformity.
Industry Canada - EMI Information
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
iii
Table of Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2. Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1. MPC-H Series - Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2. MPC-H Series - Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.3. MPC-V Series - Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.4. Additional Button Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
3. Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1. Installing the MPC Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1.1. Apply Power to the MPC
3.1.2. Connect your PC to the MPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2. Communicating with the MPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.3. Installing and Operating the Optional MPC-DISPLAY Hardware . . . . . . . . . . . . . . . . . . 3-5
4. Hardware Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1. Connecting the Power Supply Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1.1. Installing the Power Supply Cable Keepers . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2. Connect the MPC to Your Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2. Connection to Switched Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.3. Serial Console Port Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.3.1. Connecting a Local PC
4.3.2. Connecting an External Modem
4.4. Connecting the Network Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.5. Connecting Remote MPC Units to the AUX Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.6. Connecting the Optional MPC-DISPLAY Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.7. Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
5. Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1. Communicating with the MPC Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1.1. The Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2. The Web Browser Interface
5.1.3. Access Via PDA
5.2. Configuration Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.3. Defining System Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
5.3.1. The Real Time Clock and Calendar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2. The Invalid Access Lockout Feature
5.3.3. Automated Mode
5.3.4. Log Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4.1. The Audit Log and Alarm Log
5.3.4.2. The Current Metering Log and Power Metering Log . . . . . . . . . . . .
5.3.4.3. Reading and Erasing Logs
5.3.5. Callback Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4. User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
5.4.1. Command Access Levels
5.4.2. Plug Access
5.4.3. Port Access
5.5. Managing User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
5.5.1. Viewing User Accounts
5.5.2. Adding User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.2.1. Granting User Account Access to Plugs on AUX Units . . . . . . . . . .
5.5.3. Modifying User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.4. Deleting User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3-3
4-1 4-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
5-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5-9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5-14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
5-15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
5-17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
5-24 5-27 5-28 5-28
iv
Table of Contents
5. Basic Configuration (continued)
5.6. The Plug Group Directory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
5.6.1. Viewing Plug Groups
5.6.2. Adding Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.2.1. Granting User Account Access to Plugs on AUX Units . . . . . . . . . .
5.6.3. Modifying Plug Groups
5.6.4. Deleting Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7. Defining Plug Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-36
5.7.1. The Boot Priority Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7.1.1. Example 1: Change Plug A3 to Priority 1 . . . . . . . . . . . . . . . . . . . .
5.7.1.2. Example 2: Change Plug A5 to Priority 2 . . . . . . . . . . . . . . . . . . . .
5.8. Serial Port Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-41
5.8.1. Console Port Configuration
5.8.2. Remote Port and AUX Port Configuration
5.9. Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-48
5.9.3. IP Security
5.9.3.1. Adding IP Addresses to the Allow and Deny Lists
5.9.3.2. Linux Operators and Wild Cards . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.3.3. IP Security Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.5. Domain Name Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.6. SNMP Access Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.7. SNMP Trap Parameters
5.9.8. LDAP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.8.1. Adding LDAP Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.8.2 Viewing LDAP Groups
5.9.8.3. Modifying LDAP Groups
5.9.8.4. Deleting LDAP Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.8.5. LDAP Kerberos Set Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.9. TACACS Parameters
5.9.10. RADIUS Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.10.1. Dictionary Support for RADIUS
5.9.11. Email Message Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.10. Save User Selected Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-69
5.10.1. Restore Configuration
6. Reboot Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1. Ping-No-Answer Reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.1.1. Adding Ping-No-Answer Reboots
6.1.2. Viewing Ping-No-Answer Reboot Profiles
6.2. Scheduled Reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.2.1. Adding Scheduled Reboots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.2. Viewing Scheduled Reboot Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9.1. Network Port Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-49
5.9.2. Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-51
5.9.4. Static Route . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
6.1.1.1. Granting Access to Plugs on AUX Units . . . . . . . . . . . . . . . . . . . . . . 6-4
6.1.3. Modifying Ping-No-Answer Reboot Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6.1.4. Deleting Ping-No-Answer Reboot Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6.2.1.1. Granting Access to Plugs on AUX Units . . . . . . . . . . . . . . . . . . . . . . 6-8
6.2.3. Modifying Scheduled Reboots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6.2.4. Deleting Scheduled Reboots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30
5-32 5-33
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-34
5-34
5-38 5-38 5-39
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-41
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45
. . . . . . . . . . . . . 5-52
5-53 5-53
5-54 5-55
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
5-58 5-60
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-61
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-62
5-62 5-63
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-64
5-65
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-66
5-68
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-69
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6-6
6-8
v
Table of Contents
7. Alarm Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1. The Over Current Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.1.1. Over Current Alarms - Load Shedding and Auto Recovery
7.2. The Over Temperature Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
7.2.1. Over Temperature Alarms - Load Shedding and Auto Recovery
7.3. The Circuit Breaker Open Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
7.4. The Lost Communication with AUX Units Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-13
7.5. The Lost Voltage (Line In) Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-15
7.6. The Ping-No-Answer Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17
7.7. The Invalid Access Lockout Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19
8. The Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1. The Network Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2. The Plug Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.3. The Plug Group Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.4. The Current Metering Log Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
8.5. The Current History Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.6. The Power Metering Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
8.7. The Power History Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
9. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1. Operation via the Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.2. Operation via the Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
9.2.4. Connecting to Serial Ports - Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3. The Automated Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12
9.4. Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.5. Logging Out of Command Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10. SSH Encryption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
11. Syslog Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
11.1. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
11.2. Testing Syslog Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
12. SNMP Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.1. Configuration: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.2. Testing the SNMP Trap Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-2
13. Operation via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.1. MPC SNMP Agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.2. SNMPv3 Authentication and Encryption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.3. Configuration via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
13.3.2. Adding Users
13.3.3. Modifying Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13.3.4. Deleting Users
13.4. Plug Control via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-4
13.4.1. Controlling Plugs
13.4.2. Controlling Plug Groups
9.1.1. The Plug Control Screen - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1.2. The Plug Group Control Screen - Web Browser Interface . . . . . . . . . . . . . . . . 9-2
9.2.1. The Plug Status Screen - Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
9.2.2. Switching and Reboot Commands - Text Interface . . . . . . . . . . . . . . . . . . . . . . 9-5
9.2.3. Applying Commands to Several Plugs - Text Interface . . . . . . . . . . . . . . . . . . . 9-8
13.3.1. Viewing Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-3
7.1.1.1. Granting Access to Plugs on AUX Units . . . . . . . . . . . . . . . . . . . . . . 7-6
7.2.1.1. Granting Access to Plugs on AUX Units . . . . . . . . . . . . . . . . . . . . . 7-11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-4
. . . . . . . . . . . . . . . 7-4
. . . . . . . . . . . 7-9
9-11
13-3
vi
Table of Contents
13. Operation via SNMP (continued)
13.5. Viewing MPC Status via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-5
13.5.1. Plug Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13.5.2. Unit Environment Status
13.5.3. System Environment Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13.6. Sending Traps via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-6
14. Setting Up SSL Encryption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1
14.1. Creating a Self Signed Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2
14.2. Creating a Signed Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-3
15. Saving and Restoring Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1
15.1. Sending Parameters to a File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1
15.2. Restoring Saved Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
15.3. Restoring Previously Saved Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
16. Upgrading MPC Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-1
17. Command Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17.1. Command Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-1
17.2. Command Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-2
17.3. Command Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-3
17.3.1. Display Commands
17.3.2. Control Commands
17.3.3. Configuration Commands
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-9
13-5
13-6
17-1
Appendices:
A. Specifications
B. Interface Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-
B.1. Serial Console Port (RS232) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-2 B.2. RJ-45 AUX Port Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-3
C. Connecting Devices to AUX & Remote Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Apx-4
C.1. Connecting an Auxiliary MPC Unit to the MPC AUX Port . . . . . . . . . . . . . . . . . . . . . Apx-4 C.2. Connecting an MPC-DISPLAY Unit to an MPC Master Unit . . . . . . . . . . . . . . . . . . . Apx-5 C.3. Connecting Other RJ-45 DCE Devices to the AUX & Remote Ports . . . . . . . . . . . . . Apx-6
D. Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-7
E. Rack Mounting
E.1. "L" Bracket Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-8 E.2. Mounting Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-10 E.3. Hook Bracket Mounting (MPC-20V Series Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-11 E.4. Zero-U Pocket Bracket Mounting (MPC-20V Series Only) . . . . . . . . . . . . . . . . . . . Apx-12
F. Output Cable Keeper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-13
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-8
2
vii
List of Figures
2.1. MPC-H Series - Front Panel (Model MPC-16H Shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2. MPC-H Series - Back Panel (Model MPC-16H-1 Shown) . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3. MPC-20V Series - Hardware Description (Model MPC-20VD20-1 Shown) . . . . . . . . . . . . 2-5
5.1. The Plug Status Screen (Text Interface; MPC-20V Shown)
5.2. The Home Screen (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3. The System Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4. The System Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5. The Add User Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6. The Add User Menu (Web Browser Interface)
5.7. The Add Plug to Group Menu (Text Interface)
5.8. The Add Plug Groups Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9. The Plug Parameters Menu (Text Interface)
5.10. The Plug Parameters Menu (Web Browser Interface)
5.11. Boot Priority Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
5.12. Boot Priority Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-39
5.13. Serial Port Configuration Menu (Text Interface)
5.14. Port Configuration Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.15. Remote/AUX Port Configuration Menu (Text Interface)
5.16. Remote/AUX Port Configuration Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . .
5.17. Network Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.18. Network Configuration Menu (Web Browser Interface)
9.1. The Help Menu (Administrator Mode; Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
11.1. The Test Menu (Text Interface, Administrator Mode Only) . . . . . . . . . . . . . . . . . . . . . . . .
14.1. Web Access Parameters (Text Interface Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1 B.1. RS232 Console Port Interface B.2. MPC Series AUX Port Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-3 C.1. DX9F-WTI-RJ Snap Adapter Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx­C.2. Connecting C.3. Connecting C.4. Connecting RJ-45 DCE Devices to the AUX & Remote Ports E.1. Mounting Holes; MPC-20V Back Panel E.2.
Attaching the "L" Brackets to the Equipment Rack (MPC-20V Shown) . . . . . . . . . . . . . Apx-9
E.3.
Attaching Mounting Buttons to MPC-20V (Vertical) Units . . . . . . . . . . . . . . . . . . . . . . Apx-10
E.4.
Mounting Button Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-10
E.5.
Attaching the Hook Brackets to the Equipment Rack . . . . . . . . . . . . . . . . . . . . . . . . . Apx-11 E.6. Zero-U Pocket Brackets (Cross Section; Nested in Pocket) E.7.
Zero-U Pocket Brackets (Cross Section; Outside Pocket to Allow Cable Cavity) . . . . Apx-12 F.1.
Installing the Output Cable Keeper (MPC-20V Series Units Only) . . . . . . . . . . . . . . . . Apx-13
Table of Contents
2-3
. . . . . . . . . . . . . . . . . . . . . . . . 5-2
5-3 5-6 5-6
5-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
5-31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35
. . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-40
5-40
. . . . . . . . . . . . . . . . . . . . . . . . . . 5-44
5-44
5-47
. . . . . . . . . . . . . . . . . . . . . . . . . . 5-47
11-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-2
4 an Optional MPC Auxilliary unit to the MPC Master Unit . . . . . . . . . . . . . . Apx-4 an Optional MPC-DISPLAY Unit to an MPC Series Master Unit . . . . . . . . . Apx-5
. . . . . . . . . . . . . . . . . . . . Apx-6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-9
. . . . . . . . . . . . . . . . . . . . Apx-12
viii
1. Introduction
WTI’s MPC series Managed Power Controllers allow secure, remote metering and management of AC powered rack mount equipment via SSL, SSH, SNMP, web browser, telnet, external modem or local terminal. The MPC can monitor power to your equipment, and automatically notify you when changes in current levels, temperature, circuit breaker status or other factors exceed user-defined threshold values.
The MPC features two separate power circuits with up to 20 Amps input feed handling capacity per branch circuit, and is available in a horizontal, rack mount version with eight or sixteen switched outlets, or as a “zero unit” vertical mount model with 20 switched outlets.
Power Metering and Management:
The MPC can constantly measure current consumption, temperature levels, ping response and other factors. If the MPC detects that user defined thresholds for these values have been exceeded, the unit can promptly notify you via email, SNMP, Syslog, LED or audible alarm. When temperature and current readings exceed user defined critical values, the MPC can also intelligently shed the current load by temporarily shutting down nonessential devices; when readings return to acceptable levels, the MPC can restore power to those devices to return to normal operating conditions.
In addition, the MPC can also notify you when the Invalid Access Lockout has been triggered, when one of the MPC circuit breakers is open, or when a loss of communication with the optional auxiliary units is detected. The MPC also records current consumption data to a convenient log file, which can be retrieved in ASCII, XML, or CSV format or displayed in graph format.
Security and Co-Location Features:
Secure Shell (SSHv2) encryption and address-specific IP security masks help to prevent unauthorized access to command and configuration functions.
The MPC also provides four different levels of security for user accounts: Administrator, SuperUser, User and ViewOnly. The Administrator level provides complete access to all plug functions, operating features and configuration menus. The SuperUser level allows switching and rebooting of all plugs but does not allow access to configuration functions. The User level allows access to only a select group of Administrator-defined plugs. The ViewOnly level allows you to check plug status and unit status, but does not allow switching or rebooting of outlets or access to configuration menus.
The MPC includes full Radius support, LDAP capability, TACACS capability, DHCP and an invalid access lockout feature. An Audit Log records all user access, login and logout times and command actions.
1-1
Convenient, Durable Design:
The MPC is available with an optional remote display panel, which can be used to show the status of MPC units installed in hard-to-reach spots, deep inside equipment racks. When additional outlets are needed, each MPC unit can also be connected to up to three Auxiliary/Remote MPC units, allowing control of up to 80 outlets via a single IP Address .
Model Numbers
The MPC series includes a variety of horizontal and vertical models to accommodate the power distribution needs of almost any rack mount application.
Introduction
Model No.
MPC-8H-1 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * MPC-8H-2 MPC-16H-1 MPC-16H-2 MPC-18H-1 MPC-18H-2 MPC-20V-1 MPC-20V-2 MPC-20VS20-1 MPC-20VS20-2 MPC-20VD20-1 MPC-20VD20-2 MPC-20VS30-1 MPC-20VS30-2 MPC-20VD30-1 MPC-20VD30-2 MPC-20VS16-3 MPC-20VD16-3 MPC-20VS32-3 MPC-20VD32-3
Input Feeds
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps * 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * 2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps * 1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps * 1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 16 Amps * 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * 2 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps * 1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps * 1 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 16 Amps * 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * 2 ea, 20 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps * 1 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 24 Amps * 1 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 24 Amps * 2 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 48 Amps * 2 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 48 Amps * 1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 16 Amps 2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 32 Amps 1 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 32 Amps 2 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 64 Amps
Input
Voltage
Max. Load
per Outlet
Max. Load
per Input
Max. Load
per Unit
* In accordance with UL requirements for branch circuits, this value has been
de-rated to 80%.
1-2
Typographic Conventions
^ (e.g. ^X) Indicates a control character. For example, the text "^X" (Control X) indicates the [Ctrl] key and the [X] key must be pressed simultaneously.
COURIER FONT Indicates characters typed on the keyboard. For example, /AC or /ON A2.
[Bold Font] Text set in bold face and enclosed in square brackets indicates a specific key. For example, [Enter] or [Esc].
< > Indicates required keyboard entries. For Example: /P <n>.
[ ] Indicates optional keyboard entries. For Example: /P [n].
Introduction
1-3
2. Unit Description
8.8.8
8.8.8
REMOTE
www.wti.com
MPC-16H
Managed Power
Controller
AUX 1
AUX 2 AUX 3 CONSOLE PORT
AUDIBLE
ALARM
DEFAULT
ON
INPUT A
PLUGS
PLUGS
INPUT B
A1 A2 A3 A4 A5 A6 A7 A8
B1 B2 B3 B4 B5 B6 B7 B8
DISPLAY
SELECTION
AMPS KWATTS
VOLTS
TEMP
1
2
3
4
5
6
7
8 9
2.1. MPC-H Series - Front Panel
Figure 2.1: MPC-H Series - Front Panel (Model MPC-16H Shown)
As shown in Figure 2.1, the MPC-H Series Front Panel includes the following components:
1. Power Circuit A - Indicator Lights: LED indicators, which light when power is applied to the corresponding outlet on Power Circuit A.
Note: MPC-18H series units feature a single power circuit (branch.) Accordingly, MPC-18H units also include only one set of Indicator lights and only one Digital Display.
2. Power Circuit A - Digital Display: An LED digital readout, which can be used to show Amps, Kilowatts, Volts or Temperature for Power Circuit A. Note that the Display Selection Button is used to determine which of these values will appear on the digital display..
3. Display Selection Button and Indicators: Determines which measurement will appear on the Digital Displays for Circuits A and B. Each time the Display Selection Button is pressed, the Digital Displays will toggle between Amps, Kilowatts, Volts, Temperature, Total Kilowatts and Total Amps. When either "Total Kilowatts" or "Total Amps" are selected, the MPC will display the total for Circuits A and B combined. An LED indicator will light to show which measurement is currently selected. Note that the "Total Kilowatts" and "Total Amps" displays are not available on MPC-H series units, or on some MPC-V series units. Please refer to Section 2.4 for additional button functions.
4. Power Circuit B - Digital Display: Same as Item 2 above, except displays values for Power Circuit B. (Not present on MPC-18H series units.)
2-1
Unit Description
5. Power Circuit B - Indicator Lights: Same as Item 1 above, except the LEDs light to indicate On/Off status of Power Circuit B outlets. (Not present on MPC-18H series units.).
6. Link Ports: Four RJ45 connectors, which can be used to link the MPC unit to up to three other MPC units, plus the optional MPC-DISPLAY, status display panel. When your MPC unit is linked to other MPC units, this allows control of up to four MPC units (one local unit, plus three remote units) via one IP address. If necessary, the Link Ports can also be reconfigured as RS232 serial ports (as described in Section 5.8.2) to allow communication with attached devices. The MPC includes three AUX Ports and one Remote Port; the remote port is intended for connection to the MPC-DISPLAY unit, and the AUX Ports are intended for connection to additional MPC units.
7. Console Port: A DB9, RS232 serial port (DTE), which can be used for connection to a local terminal or external modem, as described in Section 4. For a description of the Console Port interface, please refer to Appendix B.1.
8. Default Button: This button can be used to either reset the unit to default parameters or to perform several other functions, described in Section 2.4.
9. Audible Alarm Button and LED: When any of the Alarms discussed in Section 7 are triggered, this LED will light, and the MPC will emit an audible alarm signal. To turn off the audible alarm single, press the Audible Alarm Button once. Please refer to Section 2.4 for additional button functions.
2-2
Unit Description
BUS
A
BUS
B
BUS
A
BUS
B
A-1 A-2
A-3 A-4 A-5
A-6
A-7 A-8
B-1
B-2
B-3
B-4
B-5
B-6 B-7
B-8
10/100 BaseT
ACT
A
B
ALARM
LINK
1
3
4
3
2
6
5
7
8
6
Figure 2.2: MPC-H Series - Back Panel (Model MPC-16H-1 Shown)
2.2. MPC-H Series - Back Panel
As shown in Figure 2.2, the MPC-H Series Back Panel includes the following components:
1. Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies power to MPC control functions and the Circuit “A” outlets. Also includes cable keeper (not shown.)
Note: MPC-18H series units feature a single Power Inlet.
2. Power Circuit B - Power Inlet: An IEC320-C20 AC inlet which supplies power to MPC control functions and the Circuit “B” outlets. Also includes cable keeper (not shown.) (Not present on MPC-18H series units.)
3. Power Circuit A - Circuit Breaker(s): Note that on MPC-16H and MPC-18H models, there are two circuit breakers for each power circuit. The circuit breakers are rated as follows:
MPC-8H-1, MPC-16H-1 and MPC-18H-1: 20 Amp Circuit Breaker(s).
MPC-8H-2, MPC-16H-2 and MPC-18H-2: 16 Amp Circuit Breaker(s).
4. Power Circuit A - Switched Outlets: AC Outlets that can be switched On, Off or rebooted in response to user commands:
MPC-8H-1: Four (4) each, NEMA 5-20R Outlets.
MPC-8H-2: Four (4) each, IEC320-C13 Outlets.
MPC-16H-1: Eight (8) each, NEMA 5-20R Outlets.
MPC-16H-2: Eight (8) each, IEC320-C13 Outlets.
MPC-18H-1: Eight (8) each, NEMA 5-20R Outlets.
MPC-18H-2: Eight (8) each, IEC320-C13 Outlets.
2-3
Unit Description
5. Power Circuit B - Switched Outlets: Same as Item 4 above. (Not present on MPC-18H series units.)
6. Power Circuit B - Circuit Breaker(s): Same as Item 3 above. (Not present on MPC-18H series units.)
7. Alarm Indicator Lights: Two LEDs which light when an alarm condition is detected at the corresponding power circuit. For information on Alarm Configuration, please refer to Section 7. Note that MPC-18H series units include only one Alarm Indicator Light.
8. Network Port: An RJ45 Ethernet port for connection to your 100Base-T, TCP/IP network. Note that the MPC features a default IP address (192.168.168.168). This allows you to connect to the unit without first assigning an IP address. Note that the Network Port also includes two, small LED indicators for Link and Data Activity. For more information on Network Port configuration, please refer to Section 5.9.
2.3. MPC-V Series - Hardware Description
As shown in Figure 2.3, MPC-V Series units include the following components:
1. Default Button: This button can be used to either reset the unit to default parameters or to perform several other functions, as described in Section 2.4.
2. Audible Alarm Button and LED: Two LEDs which light when an alarm condition is detected at the corresponding power circuit. For information on Alarm Configuration, please refer to Section 7. Please refer to Section 2.4 for additional button functions Note that MPC-V series units that include only one power inlet will also include only one Alarm LED.
3. Display Selection Button and Indicators: Determines which measurement will appear on the Digital Displays for Circuits A and B. Each time the Display Selection Button is pressed, the Digital Displays will toggle between Amps, Kilowatts, Volts, Temperature, Total Kilowatts and Total Amps. When either "Total Kilowatts" or "Total Amps" are selected, the MPC will display the total for Circuits A and B combined. An LED indicator will light to show which measurement is currently selected. Please refer to Section 2.4 for additional button functions. Note that the "Total Kilowatts and "Total Amps" displays are not available on all MPC-V series units, and that MPC-V series units that include only one power inlet, will also include only one Digital Display.
4. Link Ports: Four RJ45 connectors, which can be used to link the MPC unit to up to three other MPC units, plus the optional MPC-DISPLAY, status display panel. When your MPC unit is linked to other MPC units, this allows control of up to four MPC units (one local unit, plus three remote units) via one IP address. If necessary, the Link Ports can also be reconfigured as RS232 serial ports (as described in Section 5.8.2) to allow communication with attached devices. The MPC includes three AUX Ports and one Remote Port; the remote port is intended for connection to the MPC-DISPLAY unit, and the AUX Ports are intended for connection to additional MPC units.
2-4
Managed Power Controller
MPC-20V
8.8.8
8.8.8
OFF
ON
20
I
O
OFF
ON
20
I
O
OFF
ON
20
I
O
OFF
ON
20
I
O
DEFAULT
AUDIBLE ALARM
ON
DISPLAY
SELECTION
AMPS
VOLTS
KWATTS
TOTAL A+B
KWATTS
AMPS
TEMP
ACT
LINK
AUX
1
AUX
3
REMOTE DISPLAY
AUX
2
Ethernet
10/100
CONSOLE
A B
BRANCH
A1
BRANCH
A2
BRANCH
B1
BRANCH
B2
PLUG A1
PLUG A2
PLUG A3
PLUG A4
PLUG A5
PLUG A6
PLUG A7
PLUG A8
PLUG A9
PLUG A10
PLUG B1
PLUG B2
PLUG B3
PLUG B4
PLUG B5
PLUG B6
PLUG B7
PLUG B8
PLUG B9
PLUG B10
A1
A2 B 1 B2
1 4
2 5
3 6
7
9 10
13
11
12
8
Unit Description
Figure 2.3: MPC-20V Series - Hardware Description (Model MPC-20VD20-1 Shown)
2-5
Unit Description
5. Network Port: An RJ45 Ethernet port for connection to your 100Base-T, TCP/IP network. Note that the MPC features a default IP address (192.168.168.168). This allows you to connect to the unit without first assigning an IP address. Note that the Network Port also includes two, small LED indicators for Link and Data Activity. For more information on Network Port configuration, please refer to Section 5.9.
6. Console Port: A DB9, RS232 serial port (DTE), which can be used for connection to a local terminal or external modem, as described in Section 4. For a description of the Console Port interface, please refer to Appendix B.1.
7. Power Circuit A - Digital Display: An LED digital readout, which can be used to show Amps, Kilowatts, Volts or Temperature for Power Circuit A. Note that the Display Selection Button (Item 3) is used to determine which of these values will appear on the digital display.
Note: Some MPC models include only one power circuit. Accordingly, MPC models that include only one power circuit, the unit will also have only one digital display.
8. Power Circuit B - Digital Display: Same as Item 7 above, except displays values for Power Circuit B. MPC Models that include only one power circuit will also have only one digital display. (Not included on MPC-V series models that feature a single power inlet.)
9. Power Circuit A - Switched Outlets and Indicator Lights: AC Outlets that can be switched On, Off or rebooted in response to user commands. Note that each outlet includes an LED Indicator, which lights when power is applied to the outlet.
Notes:
• Some MPC models include only one power circuit.
• Please refer to the table in Section 1 or Section 3 for power ratings for your
specific MPC model.
10. Power Circuit B - Switched Outlets and Indicator Lights: Same as Item 9 above, except outlets and LED indicators are for Power Circuit B. Note that some MPC models include only one power circuit. (Not included on MPC-V series models that feature a single power inlet.)
11. Circuit Breaker(s): Some MPC models include two power circuits, with two breakers for each circuit, and other MPC models include only one power circuit with two circuit breakers. For a description of the power rating for your specific MPC model, please refer to the table in Section 1 or Section 3.
12. Unit Bottom Plate: In all models except MPC-20V-1 and MPC-20V-2, the power inlets are located on the bottom plate of the unit. In MPC-20V-1 and MPC-20V-2 models, the power inlets are located at the bottom of the front panel.
2-6
Unit Description
13. Power Inlet(s): The power inlets are configured differently on MPC models, in accordance with the power rating, maximum load and the number of power circuits. Depending on your specific model, the MPC may include either one or two power inlets or either one or two power supply cables. Other MPC models may include either one or two permanently attached power supply cables. For a description of the power input configuration for your specific MPC unit, please fefer to the table in Section 1 or Section 3. Note that MPC models with detachable power cable(s) will also include a power inlet cable keeper.
2.4. Additional Button Functions
In addition to the button functions discussed in Sections 2.1, 2.2 and 2.3, the Default, Audible Alarm and Display Selection buttons can also be used to perform several additional functions described below:
Notes:
• All Front Panel Button functions can also be disabled via the System
Parameters menu, as described in Section 5.3.
• When the MPC is reset to factory defaults, all user-defined configuration
parameters will be cleared, and the default “super” user account will also be restored.
1. Reboot Operating System:
a) Press and hold the Default button for five seconds, and then release it.
b) The MPC will reboot it's operating system; all plugs will be left in their current
On/Off state.
c) If the optional MPC-DISPLAY unit is installed, and this operation is performed at
the MPC-DISPLAY unit, all connected MPC units will also be rebooted.
2. Set Parameters to Factory Defaults:
a) Simultaneously press both the Default button and the Display Selection button,
hold them for five seconds, and then release them.
b) All MPC parameters will be reset to their original factory default settings, and
the unit will then reboot. All plugs will be left in their current On/Off state.
c) This function will not be applied to other connected MPC units.
3. Toggle/Default All Plugs:
a) Simultaneously press both the Default button and Audible Alarm button, hold
them for five seconds, and then release them.
b) The MPC will switch all plugs to the Off state. If all plugs are already in the Off
state, then the unit will reset all plugs to their user defined default states.
c) This function will not be applied to other connected MPC units.
2-7
Unit Description
4. Enable/Disable Audible Alarm:
a) In the default state, the Audible Alarm is Enabled.
b) To disable the Audible Alarm, press and hold the Audible Alarm button for three
seconds and then release it. To enable the Audible Alarm, press and hold the Audible Alarm button for three seconds again.
c) If the optional MPC-DISPLAY unit is installed, and this operation is performed at
the MPC-DISPLAY unit, the audible alarm feature on all connected MPC units will also be disabled. If this operation is performed at one of the connected MPC units, then the operation will only be applied to that unit.
2-8
3. Getting Started
This Quick Start Guide describes a simplified installation procedure for the MPC series hardware, which will allow you to communicate with the unit in order to demonstrate basic features and check for proper operation.
Note that this Quick Start Guide does not provide a detailed description of unit configuration, or discuss advanced operating features in detail. In order to take full advantage of the features provided by this unit, it is recommended that you should refer to the remainder of this User’s Guide.
3.1. Installing the MPC Hardware
Note: This section describes the installation procedure for individual MPC
units.
• For Quick Start installation instructions for the optional MPC-DISPLAY unit,
please refer to Section 3.3.
• For instructions on connecting your local MPC unit to additional, remote MPC
units via the AUX ports, please refer to Sections 4.5 and 5.8.2.
3.1.1. Apply Power to the MPC
Refer to power rating nameplate on the MPC unit, and then connect the unit to an appropriate power source. Note that the MPC features two separate AC inputs and two separate power busses; connect power cables to the unit’s Circuit “A” and Circuit “B” Power Inlets, install the cable keepers (as described in Section 4.1.1), then connect the cables to an appropriate power supply. Refer to the table on the next page for information concerning power requirements and maximum load.
3-1
Getting Started
Model No.
MPC-8H-1 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * MPC-8H-2 MPC-16H-1 MPC-16H-2 MPC-18H-1 MPC-18H-2 MPC-20V-1 MPC-20V-2 MPC-20VS20-1 MPC-20VS20-2 MPC-20VD20-1 MPC-20VD20-2 MPC-20VS30-1 MPC-20VS30-2 MPC-20VD30-1 MPC-20VD30-2 MPC-20VS16-3 MPC-20VD16-3 MPC-20VS32-3 MPC-20VD32-3
Input Feeds
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps * 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * 2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps * 1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps * 1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 16 Amps * 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * 2 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps * 1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps * 1 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 16 Amps * 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps * 2 ea, 20 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps * 1 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 24 Amps * 1 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 24 Amps * 2 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 48 Amps * 2 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 48 Amps * 1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 16 Amps 2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 32 Amps 1 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 32 Amps 2 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 64 Amps
Input
Voltage
Max. Load
per Outlet
Max. Load
per Input
Max. Load
per Unit
* In accordance with UL requirements for branch circuits, this value has been
de-rated to 80%.
Notes:
• MPC-H Series model numbers that end with the “-1” suffix include 20 Amp
Circuit Breaker(s).
• MPC-H Series model numbers that end with the “-2” suffix include 16 Amp
Circuit Breaker(s).
• MPC-V Series model numbers that end with “-3” include 16 Amp Circuit
Breaker(s).
• MPC-V Series model numbers that end with “-1” or “-2” include 20 Amp
Circuit Breaker(s). The only exception is the MPC-20V-2, which includes 16 Amp Circuit Breakers.
• To determine the exact model number for your MPC unit, either refer to the
nameplate on the back of the unit, or access command mode as described in Section 3.2 and invoke the Product Status command; in the Text Interface, type /J * and press [Enter]; in the Web Browswer Interface, click on the "Product Status" Link on the left hand side of the screen.
3-2
Getting Started
3.1.2. Connect your PC to the MPC
The MPC can either be controlled by a local PC, that communicates with the unit via serial port, controlled via external modem, or controlled via TCP/IP network. In order to switch plugs or select parameters, commands are issued to the MPC via either the Network Port or Console Port. Note that it is not necessary to connect to both the Network and Console Ports, and that the Console Port can be connected to either a local PC or External Modem.
Network Port: Connect your 10Base-T or 100Base-T network interface to the MPC Network port.
Console Port: Use a null modem cable to connect your PC COM port to the MPC COM (RS232) Port.
External Modem: Use a standard AT to Modem cable to connect your external modem to the MPC Console (RS232) Port.
3.2. Communicating with the MPC
When properly installed and configured, the MPC will allow command mode access via Telnet, Web Browser, SNMP, SSH client, modem, or local PC.
Notes:
• In order to ensure security, Browser access is disabled in the default state.
To enable Web Browser access, please refer to Section 5.9.
• Default MPC serial port parameters are set as follows: 9600 bps,
RTS/CTS Handshaking, 8 Data Bits, One Stop Bit, No Parity. Although these parameters can be easily redefined, for this Quick Start procedure, it is recommended to configure your communications program to accept the default parameters.
• The MPC features a default IP Address (192.168.168.168) and a default
Subnet Mask (255.255.255.0.) This allows network access to command mode, providing that you are contacting the MPC from a node on the same subnet. When attempting to access the MPC from a node that is not on the same subnet, please refer to Section 5.9 for further configuration instructions.
3-3
Getting Started
1. Access Command Mode: The MPC includes two user interfaces; the Text Interface and the Web Browser Interface. The Text Interface is available via Local PC, SNMP, SSH Client, Telnet, or Modem, and the Web Browser interface is only available via TCP/IP network. In addition, when contacted via PDA, the MPC will also present a third interface, which is similar to the Web Browser Interface, but offers limited command functions.
a) Via Local PC: Start your communications program and then press [Enter].
b) Via SSH Client: Start your SSH client, enter the default IP address
(192.168.168.168) for the MPC and invoke the connect command.
c) Via Web Browser: Make certain that Web Browser access is enabled as
described in the Section 5.9 in this User's Guide. Start your JavaScript enabled Web Browser, enter the default MPC IP address (192.168.168.168) in the Web Browser address bar, and then press [Enter].
d) Via Telnet: Make certain that Telnet access is enabled as described in
Section 5.9. Start your Telnet client, and enter the MPC’s default IP address (192.168.168.168).
e) Via Modem: Make certain that the MPC's serial Console Port has been
configured for Modem Mode as described in Section 5.8, then use your communications program to dial the number for your external Modem connected to the Console Port.
2. Username / Password Prompt: A message will be displayed, which prompts you to enter your username (Login) and password. The default username is “super” (all lower case, no quotes), and the default password is also “super”. If a valid username and password are entered, the MPC will display either the Main Menu (Web Browser Interface) or the Port Status Screen (SSH, Telnet, or Modem.)
3. Test Switching Functions: You may wish to perform the following tests in order to make certain that the MPC is responding to commands. When switching and reboot commands are executed, the MPC's Status LEDs will also turn On or Off to indicate the status of each outlet.
a) Reboot Outlet:
i. Web Browser Interface: Click on the "Plug Control" link on the left hand
side of the screen to display the Plug Control Menu. From the Plug Control Menu, click the down arrow in the row for Plug A1 to display the dropdown menu, then select "Reboot" from the drop down menu and click on the "Execute Plug Actions" button.
ii. Text Interface: Type /BOOT A1 and press [Enter].
b) Switch Outlet Off:
i. Web Browser Interface: From the Plug Control Menu, click the down
arrow in the "Action" column for Plug A1 to display the drop down menu, then select "Off" from the drop down menu and click on the "Execute Plug Actions" button.
ii. Text Interface: Type /OFF A1 and press [Enter].
3-4
Getting Started
c) Switch Outlet On:
i. Web Browser Interface: From the Plug Control Menu, click the down
arrow in the "Action" column for Plug A1 to display the drop down menu, then select "On" from the drop down menu and click on the "Execute Plug Actions" button.
ii. Text Interface: Type /ON A1 and press [Enter].
3. Logging Out: When you log off using the proper MPC command, this ensures that the unit has completely exited from command mode, and is not waiting for the inactivity timeout to elapse before allowing additional connections.
a) Web Browser Interface: Click on the "LOGOUT" link on the left hand side of
the screen.
b) Text Interface: Type /X and press [Enter].
3.3. Installing and Operating the Optional MPC-DISPLAY Hardware
Use the supplied RJ-45 cable to connect the optional MPC-DISPLAY unit to the MPC unit. Connect one end of the RJ-45 cable to the “Remote” connector on the MPC front panel; connect the other end of the cable to the RJ-45 receptacle on the back side of the MPC-DISPLAY unit.
Note: The AUX Ports, located adjacent to the Remote port on the MPC front panel, are used for connection to additional, remote MPC units. For more information on connecting an MPC-DISPLAY unit or additional MPC units to the AUX or Remote ports, please refer to Sections 4.5 and 5.8.2 and Appendix C.2.
The MPC-DISPLAY unit will receive five volts of power (for operation) via the RJ-45 cable connected to the MPC unit.
To display amperage, kilowatts, volts and temperature for the MPC units that are attached to the MPC-DISPLAY, press the “Display” button to toggle to the LED for the desired MPC unit, and then press the “Display Selection” button several times to select the desired reading; each time the “Display Selection” button is pressed, the LED indicator adjacent to the button will toggle from Amps to kiloWatts to Volts to Temperature.
This completes the Quick Start Guide for the MPC. Prior to placing the unit into operation, it is recommended to refer to the remainder of this User’s Guide for important information regarding advanced configuration capabilities and more detailed operation instructions. If you have further questions regarding the MPC unit, please contact WTI Customer Support as described in Appendix D.
3-5
4. Hardware Installation
4.1. Connecting the Power Supply Cables
4.1.1. Installing the Power Supply Cable Keepers
The MPC includes cable keepers, which are designed to prevent the power supply cables from being accidentally disconnected from the unit.
Note: In addition to the Power Supply Cable Keepers described in this section, a Power Outlet Cable Keeper is also available for MPC-20V series units. Please refer to Appendix F for more information.
MPC-8H-1 and MPC-8H-2: The cable keepers for these units must be installed by the user.
1. First make certain that both of the MPC-8H’s two power cables are
disconnected from the power source.
2. Install the two standoff screws (included with the cable keeper) in the two
vacant screw holes, located between the two power inlets. When the standoff screws are in place, thread the two screws supplied with the cable keeper into the top end of both of the standoff screws.
3. Connect the power cables to the power inlets. Check to make sure that both
cables are firmly seated in the power inlet connectors.
4. Install the cable keeper plate, by slipping the plate over the two screws which
protrude from the top of the standoffs. Slip the cable keeper plate into place, so that the notches in the bottom of the plate slip over the power cables, and the holes in the middle of the plate align with the screws in the tops of the standoffs.
5. Tighten the two screws into the standoffs to secure the plate and the power
supply cables to the unit. Check to make certain that the cables are held firmly in place by the cable keepers.
MPC-16H-1 and MPC-16H-2: Sixteen-plug, horizontal units include pre-installed cable keepers. When attaching the power supply cables to the unit, first swing the cable keepers out of the way, then plug the power cables securely into the power inputs. When the cables are in place, snap the cable keepers over each plug to secure the cables to the unit.
4-1
Hardware Installation
MPC-18H-1 and MPC-18H-2: The cable keeper for these units must be installed by the user.
1. First make certain that the MPC-18H’s power supply cable is disconnected
from the power source.
2. Install the two standoff screws (included with the cable keeper) in the two
vacant screw holes, located next to the power inlet. When the standoff screws are in place, thread the two screws supplied with the cable keeper into the top end of both of the standoff screws.
3. Connect the power cable to the power inlet. Check to make sure that the cable
is firmly seated in the power inlet connector.
4. Install the cable keeper plate, by slipping the plate over the two screws which
protrude from the top of the standoffs. Slip the cable keeper plate into place, so that one of the notches in the bottom of the plate slips over the power cable, and the holes in the middle of the plate align with the screws in the tops of the standoffs.
5. Tighten the two screws into the standoffs to secure the plate and the power
supply cable to the unit. Check to make certain that the cable is held firmly in place by the cable keeper.
MPC-20V Series: The cable keepers for 20-outlet, vertical models must be installed by the user. Note that MPC-20V series units that feature non-detachable power supply cables do not include cable keepers.
1. First make certain that the MPC’s power supply cable(s) are disconnected
from the power source. Note that some MPC-20V Series units have two power supply cables and others have only one.
2. Install the screws (included with the cable keeper) in the two vacant screw
holes, located directly below the power inlet(s). Do not overtighten the two screws; leave enough room for the Cable Keeper assembly to be slid into place in Step 4 below.
3. Connect the power cable(s) to the power inlet(s). Check to make sure that the
cable(s) are firmly seated in the power inlet connector(s).
4. Install the cable keeper plate, by slipping the plate over the two screws that
were installed under the power inlets in Step 2 above. Slip the cable keeper into place, so that the notches in the front of the plate slip under the power cables, securing the cables in place.
5. Tighten the two screws to secure the plate and the power supply cables to
the unit. Check to make certain that the cables are held firmly in place by the cable keepers.
4-2
Hardware Installation
4.1.2. Connect the MPC to Your Power Supply
Refer to the cautions listed below and at the beginning of this User's Guide, and then connect the MPC unit to an appropriate power supply.
Note: Some MPC units are shipped with one or two detachable 125 VAC, 15 Amp "Starter" Cables. These cable(s) will allow you to connect a 120 VAC MPC unit to power for bench testing and initial start up and are adequate for applications that only require 15 Amps. For higher amp power switching applications, please refer to the WTI Power Cable Guide (which can be found on the CDROM included with the unit) or use appropriate cables.
CAUTIONS:
• Before attempting to install this unit, please review the warnings and
cautions listed at the front of the user’s guide.
• This device should only be operated with the type of power source
indicated on the instrument nameplate. If you are not sure of the type of power service available, please contact your local power company.
• Reliable earthing (grounding) of this unit must be maintained. Particular
attention should be given to supply connections when connecting to power strips, rather than directly to the branch circuit.
4.2. Connection to Switched Outlets
Connect the power cord from your switched device to one of the AC Outlets on the MPC unit. Note that when power is applied to the MPC, the AC Outlets will be switched “ON” by default.
Note that some MPC models feature two separate power busses, while others may feature only one power buss. Please refer to the table shown in Section 1 or Section 3.1 for more information regarding maximum power and load ratings for your specific MPC model.
4-3
Hardware Installation
4.3. Serial Console Port Connection
The MPC's Console Port is a male, RS-232C DB9 connector, wired in a DCE configuration. In the default state, the Console port is configured for 9600 bps, no parity, 8 data bits, 1 stop bit. The Console Port can be connected to either an external modem or a local PC, but not both items at the same time. Appendix B.1 describes the Console Port interface.
4.3.1. Connecting a Local PC
Use the supplied null modem cable to connect your PC COM port to the MPC's RS232 Console Port. Make certain that the Serial Port Mode is set to “Normal” as described in Section 5.8.1.
4.3.2. Connecting an External Modem
When connecting directly to an external modem, use a standard AT to Modem cable. Make certain that the modem is initialized at the same default parameters as the MPC Console Port. Make certain that the MPC Serial Port Mode is set to “Modem” as described in Section 5.8.1.
4.4. Connecting the Network Cable
The Network Port is an RJ45 Ethernet jack, for connection to a TCP/IP network. Connect your 100Base-T cable to the Network Port. Note that the MPC includes a default IP address (192.168.168.168) and a default subnet mask (255.255.255.0.) When installing the MPC in a working network environment, it is recommended to define network parameters as described in Section 5.9.
4-4
Hardware Installation
4.5. Connecting Remote MPC Units to the AUX Ports
If your application requires control of more outlets than are provided on your MPC unit, you can also connect up to three additional MPC units to the AUX ports on the MPC front panel. This allows you to control up to 80 outlets via a single IP address.
To connect optional, Auxiliary MPC units to your local MPC unit, proceed as follows:
1. Install Snap Adapter: Insert a DX9F-WTI-RJ snap adapter (not included) into the serial console port on the Auxiliary MPC unit. The DX9F-WTI-RJ snap adapter can be ordered from the WTI sales department. For a description of the Snap Adapter interface, please refer to Appendix C.1.
2. Install RJ-45 Cable: Connect a straight RJ-45 cable from the AUX port on your local MPC unit to the DX9F-WTI-RJ snap adapter, which has been installed in the serial Console port on the Auxiliary MPC unit.
3. Configuration and Operation: Please refer to Section 5.8.2 for additional configuration instructions for Auxiliary units, and Section 9 for additional operating instructions.
Notes:
• Once the local MPC unit and Auxiliary units have been installed and
configured, you must take care when temporarily disconnecting Auxiliary unit(s) from the local unit. Prior to disconnecting Auxiliary units, note the specific AUX port that each Auxiliary unit is initially connected to, and make certain to reconnect each Auxiliary unit to the same AUX port where it was previously connected.
• If Auxiliary units are connected to a different AUX port from where they were
located when previously configured, then the local MPC unit and Auxiliary units must be reconfigured in order to adapt to this change.
• When an Auxiliary unit is connected to the AUX port on your local MPC unit,
the AUX ports on the Auxiliary unit will be automatically disabled.
• The AUX ports can also be used for connection to console ports on devices
such as servers and other rack mount equipment. For more information, please refer to Appendix C.3 and Section 5.8.2.
4-5