Weil-McLain CGs User Manual

0 (0)

GOLD CGs

Gas-Fired Water Boiler

Venting Supplement

Vertical Direct Venting

For use withWeil-McLain Through-

Roof orThrough-Unused-Chimney

Termination Kit

87300

This Venting Supplement must only be used by a qualified installer/service technician. Read these instructions completely before beginning the installation. Failure to follow all instructions in proper order can cause severe personal injury, death or substantial property damage.

To install a new vent system follow instructions in:

• This Venting Supplement.

• CGs Boiler Manual.

• Vent pipe manufacturer’s instructions supplied with vent material.

Part Number 550-141-873/0502

GOLD CGs Gas-Fired Water Boiler

Table of contents

 

1.

Please — read before proceeding .................................

3

 

Hazard definitions ....................................................................................

3

 

Venting method definitions .....................................................................

3

 

To the installer ..........................................................................................

3

2.

Determine venting method ..........................................

4

 

Direct exhaust vent methods ..................................................................

4

 

Direct vent methods .................................................................................

5

3.

Combustion air supply — eliminate contamination .....

6

4.

Obtain vent system components .................................

7

5.

Install vent starter .....................................................

10

6.

Vertical direct vent — vent termination ....................

11

7.

Installation guidelines ...............................................

11

8.

Verify vent system length ..........................................

12

9.

Installation — assembly .............................................

14

2

Part Number 550-141-873/0502

Vertical Direct Venting — Venting Supplement

1. Please — read before proceeding . . . . .

Hazard definitions

Venting method definitions

To the installer

The following terms are used throughout this Venting Supplement to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.

Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.

Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.

Indicates presence of hazards that will or can cause minor personal injury or property damage.

Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.

Direct vent — Uses outside combustion air with combustion air connector piping sealed at all joints and seams. Also known as sealed combustion. All CGs flue gas vents are pressurized, requiring careful sealing of all joints. See also CGs Venting Supplement — Direct Vent: Sidewall & Direct Exhaust: Vertical and Sidewall for alternate direct vent method.

Direct exhaust venting — Uses inside combustion air with no combustion air connector piping. All CGs flue gas vents are pressurized, requiring careful sealing of all joints. Also known as non-direct venting. See CGs Venting

Supplement — Direct Vent: Sidewall & Direct Exhaust: Vertical and Sidewall venting supplement for application information.

Chimney draft vent — Uses the natural draft provided by a vertical vent or chimney. (This method cannot be used with CGs boilers.)

Chimney draft venting cannot be used for CGs boilers. Vent system must be constructed only using venting materials listed in this Venting Supplement. Existing vertical vents or chimneys may only be used as raceways for routing vent or vent/air piping as described in this supplement or CGs Direct Vent Supplements.

Boiler must be vented and supplied with combustion air as described in this supplement. Failure to do so will result in severe personal injury, death or substantial property damage.

Use only the sealant specified by the vent pipe manufacturer, applied per their instructions. Vent piping must be sealed gas-tight to prevent possibility of flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or death.

Provide combustion and ventilation air openings as described in the CGs Boiler Manual and this supplement. Failure to provide adequate air supply could result in severe personal injury, death or substantial property damage.

Part Number 550-141-873/0502

3

GOLD CGs Gas-Fired Water Boiler

2. Determine venting method

To prevent potential of severe personal injury or death, check for areas and products listed on page 6 before installing boiler. If found:

remove products permanently

OR

provide outside combustion air (direct vent installation).

Direct exhaust venting

Use only when openings for inside combustion air can be supplied in accordance with the CGs Boiler manual, this venting supplement and with all applicable codes.

You must direct vent the boiler if the boiler area may contain contaminants as described in this supplement.

Two direct exhaust vent options are permitted: sidewall and vertical, per instructions in CGs Direct Venting:

Sidewall & Direct ExhaustVenting:Vertical or Sidewall

Venting Supplement.

Figure 1 Typical sidewall direct exhaust

Figure 2 Typical vertical direct exhaust

 

 

vent installation

 

vent installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

87250

1. Sidewall direct exhaust venting

— using vent manufacturer’s termination fittings listed in this supplement. See Figure 1.

See instructions on pages 6, 7, 8, 9 and 10 – 13.

87251

2. Vertical direct exhaust venting

— using penetration through roof or using existing unused chimney or vent as raceway for vent pipe. See Figure 2.

See instructions in CGs Direct Vent: Sidewall & Direct Exhaust: Vertical or Sidewall Venting Supplement.

4

Part Number 550-141-873/0502

Weil-McLain CGs User Manual

Vertical Direct Venting — Venting Supplement

Direct vent methods

Figure 4 Typical vertical direct vent installation

Combustion air is provided by air piping connecting from the boiler Air intake fitting to the outside.

You must direct vent the boiler (pipe outside air to boiler air intake fitting) if the boiler area may contain contaminants as described in this supplement.

Two direct vent options are permitted:

1.Sidewall direct vent

using Weil-McLain Vent/Air IntakeTermination Kit. See instructions in CGs Direct Vent: Sidewall & Direct Exhaust: Vertical or Sidewall Venting Supplement. Termination kit is included with CGs boiler. See Figure 3.

2.Vertical direct vent

using Weil-McLain Through-Roof orThrough- Unused-ChimneyTermination Kit. Instructions for vertical direct venting are covered in this supplement. See Figure 4.

Figure 3 Typical sidewall direct vent installation

87203

87205

Part Number 550-141-873/0502

5