Watts Autotrol Magnum User Manual

0 (0)

Magnum Cv and Magnum IT Valves

Installation and Service Manual

Table of Contents

Section

1.0

Installation Profile Summary

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- 1

2.0

Introduction to the Magnum Cv and Magnum IT Series -

-

-

-

-

-

-

-

-

-

-

-

-

-

- 2

 

2.1

Assembling the Control to the Valve

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- 3

 

2.2

General Specifications

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- 7

 

2.3

Dimensional Specifications

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- 8

3.0

General Installation Information -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

10

 

3.1

Typical Installation Drawings -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

12

4.0

Flow Diagrams

- - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

13

5.0 Control Settings - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

19

 

5.1

Manual Control -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

19

 

5.2

Mechanical Control

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

24

 

 

5.2.1 Common Settings - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

24

 

 

5.2.2 Regenerating Iron Filter - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

25

 

 

5.2.3 Backwashing Filter - - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

25

 

 

5.2.4 Salt Use Table - - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

26

 

 

5.2.5

Potassium Permanganate Use Table-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

27

 

5.3

Impulse Controls

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

28

 

5.4

Electronic Controls- - - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

29

 

 

5.4.1 Connecting the 962 Control- - - - - - - - -

-

-

-

-

-

-

-

-

-

-

31

 

 

5.4.2

Connecting the 962M and the 962S

Control -

-

-

-

-

-

-

-

-

-

-

32

 

 

5.4.3

Connecting the 962 Twin and Triple Parallel Control-

-

-

-

-

-

-

-

33

6.0

Programming Tables for Electronic Controls -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

34

 

6.1

Table I - Level I Values -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

34

 

6.2

Table IIA - Level II Program Values 962 Single Twin or Triple Parallel

 

 

 

 

 

 

 

 

Tank Softener or Dealkalizer -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

35

 

6.3

Table IIB - Level II Program Values 962F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Tank Filter Mode Parameters

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

36

 

6.4

Table IIC - Level II Program Values 962 Twin Tank Alternating

 

 

 

 

 

 

 

 

 

 

 

Softener - - - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

37

 

6.5

Table IID - Level II Program Values - Electronic Timeclock

 

 

 

 

 

 

 

 

 

 

 

 

Filter -

- - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

38

 

6.6

Table IIE - Level II Program Values - Electronic Timeclock

 

 

 

 

 

 

 

 

 

 

 

 

Softener

- - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

39

 

6.7

Explanation of Parameter Values for the 962 Single and Parallel

 

 

 

 

 

 

 

 

 

Tank Controls - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

40

 

6.8

New Features in the 962 Family Controls -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

42

 

6.9

Table III Historical Data

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

43

 

6.10 Table IV Error Messages

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

44

7.0

Multi-Tank Systems

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

45

 

7.1

Twin Alternating - - - -

- -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

45

 

 

7.1.1 Control Set-up -

-

-

-

-

- - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

46

 

 

7.1.2 Additional Checks

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

47

 

7.2

Twin and Triple Parallel

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

48

 

 

7.2.1 Control Set-up

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

50

8.0

Start-Up Procedure

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

51

9.0

Service Instructions

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

52

 

9.1

Magnum Valve Cartridge Removal Procedure -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

54

10.0

Performance Data

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

55

 

10.1

Injector Data- - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

55

 

10.2

Refill Control Chart (P6 Values)

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

57

 

10.3

Injector Chart (P7 Values) -

- - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

58

 

10.4

Drain Line Flow Control Chart -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

59

 

10.5

Autotrol Drain Line Flow Controls (5 gpm - 40 gpm)-

-

-

-

-

-

-

-

-

-

-

-

60

11.0 Wiring Diagrams - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

61

 

11.1

962 Series Remote Start

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

61

 

11.2

952 Impulse - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

62

 

11.3

952 QC Impulse -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

62

 

11.4

962 Twin and Triple Parallel

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

63

 

11.5

962 Twin Alternating

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

64

12.0

Assembly Drawings and Parts Lists

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

65

 

12.1

942Man and 942FMan Manual Controls -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

65

 

12.2

942 and 942F Timeclock Controls -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

66

 

12.3

952,952F, and 952QC Impulse Controls -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

67

 

12.4

962, 962F, 962TC, 962FTC, 962M, and 962S Electronic Controls

-

-

-

-

-

69

 

12.5

Injector Assemblies

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

72

 

12.6

Refill Control Assemblies -

-

-

-

- - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

73

 

12.7

2-inch Turbine Assembly - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

74

 

12.8

Installation Adapters - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

75

 

12.9

Valve Cartridges - - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

77

 

12.10 Cam and Pilot Valve Assemblies -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

78

 

12.11 Kits and Assemblies - - - - - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

80

 

12.12 962 Optional Switch Kits Available

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

81

1.0 Installation Profile Summary

Installation Date: ______________________________

Installation Location: ___________________________

Installer(s): ____________________________________

Phone Number:________________________________

Valve Number:_________________________________

Application Type: (Softener) (Filter) (Dealkalizer)

Water Source:

(Public Well) (Private Well)

(Surface Supply)

(Other)

Water Test Results:

Hardness:_______________ Iron:_______________

Other: ________________________________________

Misc:

Capacity: _______ Flow Rates:______ min. ____ max. Tank Size: Diameter ________ Height: __________

Resin or Media Volume:_________________________

Resin or Media Type: ___________________________

Brine Tank Volume:_____________________________

Salt Setting per Regeneration: ___________________

Control Valve Configuration:

Valve Type:____________________________________

(Hard Water Bypass) (No Hard Water Bypass)

Refill Control:______________________________ gpm Injector Control: ___________________________ gpm Backwash Control: _________________________ gpm

Manual Control:

(Softener) (Filter)

Mechanical Timeclock:

(7 day) (12 day)

Salt Setting: __________________________________

Regeneration Frequency:

S M T W T F S

1

2

3

4

5

6

7

8

9

10

11

12

______________________________________________

______________________________________________

Impulse

(480) (Other) ___________________________________

Salt Setting:____________________________________

Electronic Demand Settings

 

P1

Time of Day

_________________

P2

Time of Day Regen

_________________

P3

Hardness of Water

_________________

P4

Salt Amount

_________________

P5

Capacity of Unit

_________________

P6

Refill Control Value

_________________

P7

Brine Draw Value

_________________

P9

Backwash Time

_________________

P10

Slow Rinse Time

_________________

P11

Fast Rinse Time

_________________

P12

Units of Measure

_________________

P13

Clock Mode

_________________

P14

Calendar Override

_________________

P15

Reserve Type

_________________

P16

Fixed Reserve Cap.

 

 

or Initial Ave. Value

_________________

P17

Operation Type

_________________

P18

Salt Change Lock Out

_________________

P19

Flow Sensor Size

_________________

P20

K-Factor or Pulse

 

 

Equivalent

_________________

P21

Remote Regeneration

 

 

Switch Delay

_________________

P22

Factory Use Only

_________________

Twin Parallel

Triple Parallel

Regeneration Type (P15): ___________

3 = Fixed Reserve with Immediate Regeneration

Fixed Reserve (P16):____________% (0% only)

Twin Alternating

Regeneration Type (P15): ___________

0 = Immediate Regen

1 = Delayed Regen Fixed Reserve (P16): _____________ %

1

2.0 Introduction to the Magnum Cv and Magnum IT Series

The Magnum CvTM and Magnum ITTM Series valves offer a high degree of installation simplicity and flexibility.

Figure 2.1 provides an overview of the major components and connections of the 2-inch (5.08-cm) Magnum IT valve.

The Magnum valve is available in either a 1-1/2-inch (3.81-cm) (Magnum CvTM) or a 2-inch (5.08-cm) (Magnum IT™) configuration. Throughout

this manual, the 2-inch (5.08-cm) Magnum Cv is shown in illustrations where the model type is irrelevant to what is being demonstrated.

Magnum ITTM Series Valve

Internal Turbine

Assembly

Figure 2.1

2

2.1 Assembling the Control to the Magnum Valve

The control and the Magnum valve work together as an integral system to ensure synchronization. Follow the steps outlined below to install the control on the Magnum valve.

Remove Cam Cover

Remove the cam cover by pressing in on the cover release tabs (Figure 2.2). Note the cover locking tab and the slot in the top plate. When you reassemble the cover, the locking tab is placed in the slot first and the cover lowered into position.

Slide Camshaft

Slide the camshaft toward the back of the valve by pressing on the release tab and pulling on the back end of the camshaft (Figure 2.4). The front end of the camshaft will be flush with the mounting plate.

Release Tabs

Locking Tab and Slot

Cover Release Tabs

Figure 2.2

Align Camshaft

The camshaft is keyed and should only be engaged or disengaged when in the position illustrated (Figure 2.3). If the camshaft is not in the proper position, rotate the cam assembly counterclockwise until the camshaft arrow aligns with pillow block arrow.

Camshaft Arrow

Pillow Block Arrow

 

Figure 2.3

Figure 2.4

Mount Control

Mount the control onto the valve by sliding the mounting tabs over the mounting plate. Note that all models of Magnum controls mount to the valve in the same manner (Figure 2.5).

Mounting Tabs

Mounting Plate

Figure 2.5

Engage Assembly

Engage the control by pressing on the release tab and pushing the camshaft into the control (Figure 2.6). Do not force the camshaft. If the camshaft does not slide freely into the control, check the alignment of the camshaft to ensure it is in the proper position

(Figure 2.3). The control indicator must be in the

REGENERATION COMPLETE position for the 942, 942Man, 952, and 962 when engaging the camshaft into the control. The control indicator must be in the BACKWASH COMPLETE position for the 942F, 942FMan 952F, and 962F when engaging the camshaft

3

into the control. The control indicator must be in the midpoint of the SERVICE position for the 962M and 962S when engaging the camshaft into the control.

Release Tab and

Camshaft

Figure 2.6

Important:

When 942, 942Man, 952, or 962 controls are installed, control dials must be in the REGENERATION COMPLETE position.

When 942F, 942FMan, or 952F controls are installed, control dials must be in the BACKWASH COMPLETE position.

When 962M or 962S controls are installed, control dials must be in the SERVICE position.

To disassemble the control from the valve, reverse the assembling procedure.

Inlet, Outlet and Drain Connections

The inlet, outlet, and drain connections are designed to accept an GE Osmonics supplied CPVC or brass adapter (Figure 2.7). The adapters provide a convenient union for the three connection ports on the valve. In addition, they incorporate a positive O-ring face seal for ease of installation and leak free operation. DO NOT OVERTIGHTEN THE ADAPTERS. As a general guideline, hand tightening the nut onto the valve will be adequate. If additional tightening is required, never exceed a quarter turn beyond the hand tight position.

The outlet of the 2-inch Magnum IT has an integrated turbine. The turbine measures the flow of water through the outlet. This information is used by the control to determine the best time to recycle.

Figure 2.7

No Hardwater Bypass Feature

The Magnum control valve may be configured for “Hard Water Bypass” or “No Hard Water Bypass”. With Hard Water Bypass, unsoftened or unfiltered water is allowed to bypass the Magnum control valve during regeneration or backwash. With No Hard Water Bypass, a valve cartridge ensures that no unsoftened or unfiltered water bypasses the valve during regeneration or backwash.

It is easy to observe which option is installed in the valve. Note that the Hard Water Bypass End Cap has much longer standoffs than the No Hard Water Bypass cartridge. The No Hard Water Bypass assembly will look identical to the other three valve cartridges on the valve and will have a label identifying the cartridge assembly (Figure 2.8).

No Hard Water Bypass

No Unfiltered Water Bypass

Normal Standoffs

Extended Standoffs

With Hard Water Bypass

End Cap

Figure 2.8

4

Hydraulic Output Signal

An optional hydraulic output signal is available on the valve. An optional cam lobe on pilot valve #6 is used on the camshaft assembly to initiate the hydraulic output signal during regeneration or backwash (Figure 2.9).

The hydraulic line pressure signal will be available through the 1/4-inch connection on the back of the valve marked “AUX”. (Remove the tube cap installed for shipping.)

Optional cam lobes available are:

P/N 1000554 Provides a hydraulic signal from the beginning of BACKWASH through the start of REFILL.

P/N 1000553 Provides a hydraulic signal from the beginning of BACKWASH through the end of REFILL.

P/N 1001622 Used on Twin Alternating Systems Only. Provides a hydraulic signal from the beginning of BACKWASH through and during STANDBY.

P/N 1041064 Breakaway cam. Can be programmed to send a hydraulic signal at any time during the REGENERATION or BACKWASH cycle. Note: The camshaft must be turning for the signal to change states, i.e. switch from OFF to ON, or from ON to OFF.

For hydraulic output signal install one of following cam lobes:

1000553

1000554

1001622

1041064

Optional Cam

Lobe Position #6

“Hydraulic Output

Signal”

Figure 2.9

Auxiliary Hydraulic

Output Port “AUX”

Pilot Drain Port

Figure 2.10

Magnum Tank Adapter

The tank adapter on the control valve is designed to be compatible with a 4 inch-8UN (8 threads per inch) tank opening. In addition, the adapter is designed to accept a full 1-1/2-inch (3.81-cm) riser pipe with outside diameter of 1.90 to 1.91 inches (48.26 to 48.51 mm) (Figure 2.11). The riser pipe is sealed by an O-ring on the inside of the tank adapter, Figure 2.11. It is recommended that the riser pipe extend beyond the top of the tank by 1/4 inch ± 3/8 inch (6 mm ± 9 mm).

TankO-ringO-ring

0.8125" (20.64 mm)

Top of Tank

.375" (9.52 mm)

RiserO-ringO-ring

Figure 2.11

Optional Switch Assembly

On single, twin parallel, and triple parallel tank configurations, a single optional feedback switch kit is available to provide an electrical signal during the entire regeneration or backwash cycle (Figure 2.12). The switch may be wired in the “Normally Open” or “Normally Closed” position and is rated for 0.1 amp at 125 volts AC. An optional 5.0 amp switch at 1/10 HP 125/250 volts AC is available upon request.

5

Common

Normally Open

Normally Closed

Figure 2.12

On ALL Magnum tank configurations, optional multiswitch kits are available to provide additional electrical or switch closure signals during the regeneration or backwash cycles. Coupled with the optional breakaway cams, signals can be sent to external system equipment at virtually any time while the control/camshaft motor is running. Consult the instruction sheet covering the multi-switch option for additional application and programming information. The instruction sheet is sent with the switch kit.

6

2.2 Magnum General Specifications

Operating and Environmental

 

Operating Pressure ...............................................................................................

25 to 125 psig (172 to 862 kPa)

 

100 psig (688kPa) maximum in Canada

Operating Water Temperature Range.................................................................................

34 to 100oF (1 to 36oC)

Ambient Temperature Range..............................................................................................

34 to 120oF (1 to 50oC)

Cap Bolt Torque ...................................................................................................

35-40 inch lbs. (3.95 to 4.51 Nm)

Connections

 

Inlet and Outlet...................................................................................................................

1-1/2 inch-Magnum Cv

 

2-inch-Magnum IT

Tank .......................................................................................................................................................

4-inch-8UN

Brine ....................................................................................................................................................

3/4-inch NPT

Pilot Drain and Auxiliary Hydraulic Out ....................................................................................

1/4-inch tube fitting

Riser Pipe Fitting .....................................................................................................................

1-1/2-inch (3.81-cm)

Drain ........................................................................................................................................

1-1/2-inch (3.81-cm)

Physical

 

Dimensions.....................................................................................................

Refer to drawings on pages 8 and 9

Approximate Weight (Valve and Control)....................................................................................

23.3 lbs. (10.6 kg.)

Electrical*

 

Voltage - 962 Series Control ..........................................................................

12 VAC wall mount transformer only

Voltage - 942 Series Control ..................................................................

120 VAC, 12 VAC wall mount transformer

Voltage - 952 Series Control ........................................................................................................

24 VAC, 120 VAC

Power Draw........................................................................................................................................

4.5 volt-amps

*See section on Electronic Controls for alternative electrical configurations.

7

3.993 (10.14 cm)

6.493 (16.5 cm)

7.500 (19.05 cm)

22.796 (57.90 cm)

8

13.481 (34.24 cm)

9.000 (22.86 cm)

11.471 (29.13 cm)

8.680 (22.04 cm)

4.018 (10.20 cm)

2.817 (7.15 cm)

7.000 (17.78 cm)

14.000 (35.56 cm)

19.500 (49.53 cm)

1.113 (2.82 cm)

15.539 (39.47 cm)

Inlet, inch-1/2 1

Cv Magnum 3.2

Drain and Outlet

Specifications Dimensional

Magnum IT Dimensional Specifications 2-Inch Inlet and Outlet, 1 1/2-Inch Drain

13.481

9.000

8.710 3.998 6.500 16.250

7.000

9.750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.817

4.429

15.539

1.113

11.376

4.500

4.500

4.429

13.993

27.224

9

3.0 General Installation Information

Please review the following items thoroughly to ensure an efficient and safe installation of the water treatment system. Page 12 shows typical installation line drawings for the Magnum valves.

Operating Conditions - A minimum dynamic operating water pressure of 25 psig (172 kPa) is required for the Magnum control valve to operate properly. Water pressure is not to exceed 125 psig (862 kPa). In Canada, water pressure is not to exceed 100 psig (688 kPa). Water temperature is not to exceed 100oF (36oC). Do not subject the valve to freezing conditions.

Space Requirements - Allow adequate space for the water treatment system and associated piping. The General Specifications section (pages 7-9) provides the overall dimensions of the control valve as well as the dimensional reference information for each of the connection ports. A minimum of 4 1/2 inches (11.5 cm) front and rear clearance is required for cartridge assembly and removal.

Plumbing - Always follow good plumbing practices and conform to local codes. Check existing pipes for lime and/or iron buildup. Replace piping if heavy buildup exists and initiate the proper treatment to prevent additional occurrences. Locate the equipment close to a drain that is capable of handling the maximum drain flow rate during backwash.

Flexible Connectors - Some tanks expand and contract over the acceptable range of operating water pressures of the Magnum control valve. The use of flexible connectors is recommended on polywound or fiberglass tank installations of 24-inch (60.96-cm) diameter and larger. Follow the tank manufacturer’s instructions for more information.

Inlet and Outlet Piping - Inlet and outlet plumbing should be adequately supported to avoid excessive loads on the valve. Install a manual bypass system to provide for occasions when the water conditioner must be bypassed for servicing.

Drain LIne Piping - To prevent mineral loss during backwash, and to ensure proper operation of the Magnum Cv Series control valve, A DRAIN LINE FLOW CONTROL must be plumbed into the drain line prior to placing the valve in the service mode. Flow controls from 5 to 40 gpm (18.92 to 151.4 Lpm) are available from GE Osmonics and can be easily installed in the drain line (Figure 3.1). Flow controls greater than 40 gpm (151.4 Lpm) must be plumbed externally. Selection of the proper drain line flow control will depend on the tank size and media used for the installation. See Table 10.3.

The following general drain line piping guidelines should be observed:

1 inch (2.54 cm) or larger piping

Should not exceed 20 feet (6.1 m)

Should not be elevated higher than the control valve

No shut-off valves should be installed in drain line

Minimal number of elbows and fittings should be installed in drain line

Piping must be self-supporting

Install air gap to provide a siphon break

Flow control should be installed as close to the Magnum Cv Series control valve as possible if an external flow control is used.

Drain Line Flow Control Disk

Figure 3.1

Brining System - The Magnum control valve utilizes timed water refill to add water to the salt tank. A refill tube with check ball is required in the brine tank that will not restrict the refill or brine draw flow rate capabilities of the valve. Although not required, a separate brine valve (safety float) system is recommended for use with Magnum installations. Select a “High-Flow” brine valve that will not restrict the refill or brine draw flow rate capabilities of the valve. The “Performance Data and Charts” section (Section 10.0) of this manual contains flow rate information for various size injectors and refill controllers.

Pilot Drain - During regeneration, a small amount of water (200 ml or 1 cup) is discharged from the 1/4-inch (6.3-mm) tube fitting on the back of the valve marked DRAIN (Figure 3.2). To prevent this water from being discharged to the floor, plumb this connection to a nonpressurized drain or to the brine tank. Do not plug or apply back pressure to the pilot drain at any time.

Crimping the pilot drain line or installing the line to go up, which causes backpressure, will prevent the diaphragm cartridges from shifting properly through the cycles of regeneration or backwash.

10

Auxiliary Hydraulic

Output Port - Plugged

Pilot Drain Port

Figure 3.2

Electrical

1.Electrical requirements for the installation will depend on the configuration of the control.

2.The standard North American Series 962 electronic control is supplied with a 12 volt wall mount transformer. Optional wall mount transformers are available in the following configurations: Japanese plug @ 100 volts/50 or 60 Hz, Australian/Argentine plug @ 240 volts/50 Hz, British plug @ 240 volts/50 Hz, European/Italian plug @ 230 volts/50 Hz. Optional transformers must be ordered separately for all international 12 VAC configurations.

3.The standard North American Series 952 impulse controls use 120 VAC or 24 VAC/50 or 60 Hz power.

Lubricants

It is very important that 100% silicone lubricant is the only lubricant used for installing the Magnum control valve. Any other lubricant may cause material degradation and potential failure of the valve components.

NOTE: Some silicone based lubricants contain petroleum-based ingredients. If there is a question about the lubrication that you are using contact the manufacturer of that lubricant.

11

3.1 Typical Installation Drawings

Inlet Valve

Drain Line Flow Control (Required)

Drain

962 Control

1.5” Riser Tube

Hub & Lateral

Magnum Cv

Magnum IT

Manual Bypass Valve

Outlet Valve

Note: Support Inlet and Outlet Piping

Turbine (standard Adequately. with 962 Control)

Brine Line

Brine Tank

Figure 3.3 Magnum Cv and Magnum IT, Single Tank Softener Units with 962 Electronic Control

12

4.0 Flow Diagrams

The Magnum control valve utilizes a series of pilot valves to properly position the diaphragm valve cartridges (Figure 4.1). The pilot valves are activated by the camshaft (Figure 4.2). The flow diagrams that follow represent the Service Cycle for a 5-cycle softener, 3-cycle filter, and 5-cycle twin alternating softener

configuration. Both the Hardwater Bypass and No Hardwater Bypass service flow diagrams are presented.

Figure 4.1 Pilot Valve Principle of Operation

Figure 4.2 Cam Assembly

13

14

Magnum

5 Cycle - Co-current - Hard Water Bypass - Softener

Service Cycle

Outlet

 

 

 

 

 

 

 

 

 

Brine

 

 

 

 

 

 

 

 

 

Tank

Hard Water

 

 

 

 

 

 

 

 

Refill

Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control

3

2

 

 

 

 

 

 

 

 

Tank Bottom

 

 

 

 

 

 

 

 

 

 

6

5

4

3

2

1

B2

B1

Pilot

 

 

 

 

 

 

 

 

 

Valves

Pilot Drain

 

 

 

 

 

 

 

 

 

Aux. Pilot

 

 

 

 

 

 

 

 

Injector

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Screen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Injector

 

Pressure

 

 

 

 

 

 

 

 

 

Tank Top

 

 

 

 

 

 

 

 

Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pilot

 

 

 

 

 

 

 

 

 

Screen

4

1

 

 

 

 

Untreated

 

 

 

 

 

 

 

 

 

Water

 

 

 

Treated

Water

 

 

Backwash

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

Regenerant

 

 

 

 

 

 

 

 

 

6

5

4

3

2

1

B2

B1

 

 

Service CLSD

CLSD OPEN CLSD OPEN OPEN CLSD CLSD

Inlet

Drain

Backwash CLSD

OPEN CLSD OPEN OPEN CLSD CLSD CLSD

 

 

Brine/Slow Rinse CLSD

OPEN CLSD OPEN CLSD OPEN OPEN OPEN

 

 

Fast Rinse CLSD

OPEN OPEN OPEN CLSD OPEN CLSD CLSD

Resin Tank

 

Refill/Service CLSD

CLSD

OPEN

CLSD

OPEN

OPEN

OPEN

OPEN

15

Magnum

5 Cycle - Co-current - No Hard Water Bypass - Softener

 

Service Cycle

Outlet

No Hard

Water Bypass

3

Tank Bottom

Pilot Drain

Aux. Pilot

Output

Tank Top

4

2

6

5

4

3

2

1

B2

B1

 

 

 

 

 

Injector

1

Untreated

 

Water

 

Treated

 

Water

 

Backwash

 

Water

 

Regenerant

Brine

Tank

Refill

Control

Pilot

Valves

Injector

Screen

Pressure

Regulator

Pilot

Screen

Inlet

Drain

Resin Tank

6

5

4

3

2

1

B2

B1

Service CLSD CLSD OPEN CLSD OPEN

OPEN

CLSD

CLSD

Backwash CLSD OPEN CLSD OPEN OPEN CLSD CLSD CLSD

Brine/Slow Rinse CLSD OPEN CLSD OPEN CLSD OPEN OPEN OPEN

Fast Rinse CLSD OPEN OPEN OPEN CLSD OPEN CLSD CLSD

Refill/Service CLSD

CLSD

OPEN

CLSD

OPEN

OPEN

OPEN

OPEN

16

Magnum

3 Cycle - Unfiltered Water Bypass - Filter

Service Cycle

Outlet

Unfiltered

 

 

 

 

 

 

 

 

 

 

 

 

Water Bypass

 

 

 

 

 

 

 

 

 

 

 

 

3

2

 

 

 

 

 

 

 

 

 

 

 

Tank Bottom

 

 

 

 

 

 

 

 

 

 

 

 

 

6

5

4

3

2

1

B2

B1

 

 

Pilot

 

 

 

 

 

 

 

 

 

 

 

Valves

Pilot Drain

 

 

 

 

 

 

 

 

 

 

 

 

Aux. Pilot

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Plugged Injector

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

Tank Top

 

 

 

 

 

 

 

 

 

 

Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pilot

 

 

 

 

 

 

 

 

 

 

 

Screen

4

1

 

 

 

 

Untreated

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

 

 

 

Treated

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

 

 

 

Backwash

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

 

 

 

Regenerant

 

 

 

 

 

 

Inlet

Drain

 

 

 

 

6

5

4

3

2

1

B2 B1

 

 

 

 

 

 

Service CLSD CLSD OPEN CLSD OPEN OPEN CLSD CLSD

 

 

 

 

 

 

Backwash CLSD OPEN CLSD OPEN OPEN CLSD CLSD CLSD

Media Tank

 

 

 

 

 

Fast Rinse CLSD OPEN

OPEN

OPEN

CLSD

OPEN

CLSD CLSD

17

Magnum

3 Cycle - No Unfiltered Water Bypass - Filter

 

Service Cycle

Outlet

No Unfiltered

Water Bypass

3

Tank Bottom

Pilot Drain

Aux. Pilot

Output

Tank Top

4

2

6

5

4

3

2

1

B2

B1

Pilot

 

 

 

 

 

 

 

 

Valves

Plugged Injector

Pressure

Regulator

Pilot

Screen

1

Untreated

 

Water

 

Treated

 

Water

 

Backwash

 

Water

Regenerant

Inlet

Drain

6

5

4

3

2

1

B2 B1

 

 

Service CLSD CLSD OPEN CLSD OPEN OPEN CLSD CLSD

 

 

Backwash CLSD OPEN CLSD OPEN OPEN CLSD CLSD CLSD

Media Tank

 

Fast Rinse CLSD

OPEN

OPEN

OPEN

CLSD

OPEN

CLSD CLSD

Watts Autotrol Magnum User Manual

18

Magnum

5 Cycle - Co-current - Twin Alternating Softener

Service Cycle

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

Brine

 

 

 

 

 

 

 

 

 

 

 

 

Tank

 

No Hard

 

 

 

 

 

 

 

 

 

 

 

Refill

 

Water Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control

3

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Tank Bottom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

5

4

3

2

1

B2

B1

 

 

Pilot

 

 

 

 

 

 

 

 

 

 

 

 

 

Valves

Pilot Drain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Aux. Pilot

 

 

 

 

 

 

 

 

 

 

 

Injector

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Screen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Injector

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Tank Top

 

 

 

 

 

 

 

 

 

 

 

Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pilot

 

 

 

 

 

 

 

 

 

 

 

 

 

Screen

4

1

 

 

 

 

Untreated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Treated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backwash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Regenerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

5

4

3

2

1

B2

B1

 

 

 

 

 

 

Service CLSD CLSD OPEN CLSD OPEN OPEN CLSD CLSD

 

 

 

 

 

 

First Standby CLSD CLSD OPEN OPEN OPEN OPEN CLSD CLSD

 

 

 

 

 

 

Backwash CLSD OPEN CLSD OPEN OPEN CLSD CLSD CLSD

Inlet

Drain

 

 

 

Brine/Slow Rinse CLSD

OPEN

CLSD

OPEN CLSD OPEN OPEN OPEN

 

 

 

 

 

 

Fast Rinse CLSD OPEN OPEN OPEN CLSD OPEN CLSD CLSD

 

 

 

 

 

 

Refill CLSD CLSD OPEN OPEN OPEN OPEN OPEN OPEN

Resin Tank

 

 

 

 

Second Standby CLSD

CLSD

OPEN

OPEN

OPEN

OPEN

CLSD

CLSD

5.0Control Settings

5.1Manual

Series 942Man Controls

The 942Man represents the maximum in versatility and ease of operation for the manual control valve system. Upgrade to an automatic system is easily accomplished by switching the manual control to a clock or demand control.

DO NOT TURN THE INDICATOR KNOB CLOCKWISE AT ANY TIME.

Regeneration Instructions

1.Move indicator knob COUNTERCLOCKWISE from the Regeneration Complete position to the center of the Backwash (Figure 5.1) position. DO NOT turn the knob clockwise.

Figure 5.1

2.The indicator knob should remain in the Backwash position for the appropriate amount of time. Specific backwash times are determined by the inlet water quality (i.e.: the amount of iron, manganese, turbidity), the amount of time between regenerations, water pressure, and flow. The typical backwash time is 10-15 minutes*. The unit should be in backwash until water at the drain is clear.

3.When the backwash is complete, move the indicator knob COUNTERCLOCKWISE to the center of the Brine/Slow Rinse position

(Figure 5.2). See the “Suggested Brine Draw/Slow Rinse Table” to determine the correct draw/rinse time. Please note that the tables are given at three salting levels and four pressures. The indicator knob should remain in the Brine/Slow Rinse position for the time* indicated in the table.

*Note: The times given are only general guidelines. Adjustment of the times may be necessary for specific applications and conditions.

Figure 5.2

4.When the slow rinse is complete, move the indicator knob COUNTERCLOCKWISE to the center of the Fast Rinse position (Figure 5.3). The indicator knob should remain in the Fast Rinse position for the appropriate amount of time. specific fast rinse times are determined by water quality, clarity of drain water, water pressure, and flow. Fast rinse serves to eliminate excess salt and repack the resin bed for the service run. Typically fast rinse should continue for 5 - 15 minutes*.

Important: If excessive fast rinse time is required to return the service effluent to quality, there could be an underlying cause, such as low pressure, fouled resin bed, fouled injector, etc.

Figure 5.3

5.When the fast rinse is complete, move the indicator knob COUNTERCLOCKWISE to the Refill position (Figure 5.4). Determine the correct refill time* from Table 5.1 below. The indicator knob should remain in the Refill position for the time indicated in the table.

19

Figure 5.4

Table 5.1 Suggested Refill Times

Tank

Resin

 

Refill Flow Rate

Minimum Salting

Medium Salting

Maximum

Refill PN

 

gpm (lpm)

(6 lbs/ft3)

(10 lbs/ft3)

Salting (15 lb/ft3)

Diameter

cu.ft.

 

@ 60 psig

 

 

(96.1 kg/m3)

( 160.18 kg/m3)

(240.27 kg/m3)

 

 

 

 

(414 kPa)

 

 

 

 

 

 

 

14 in (35.5 cm)

3

1040679

0.7

(2.6 lpm)

9 minutes

15 minutes

22 minutes

 

 

 

 

 

 

 

 

16 in (40.6 cm)

4

1040680

0.8

(3 lpm)

10 minutes

17 minutes

25 minutes

 

 

 

 

 

 

 

 

18 in (45.7 cm)

5

1040681

1.0

(3.8 lpm)

10 minutes

17 minutes

25 minutes

 

 

 

 

 

 

 

 

21 in (53.5 cm)

7

1040682

1.4

(5.31 lpm)

10 minutes

17 minutes

25 minutes

 

 

 

 

 

 

 

 

24 in (60.9 cm)

10

1040683

2.0

(7.6 lpm)

10 minutes

17 minutes

25 minutes

 

 

 

 

 

 

 

 

30 in (76.2 cm)

15

1040684

3.0

(11.4 lpm)

10 minutes

17 minutes

25 minutes

 

 

 

 

 

 

 

 

36 in (91.4 cm)

20

1040685

5.0

(18.9 lpm)

8 minutes

14 minutes

20 minutes

6.When the refill is complete move the indicator knob COUNTERCLOCKWISE to the Regeneration Complete position (Figure 5.5). The unit will now provide softened water.

Figure 5.5

*Note: The times given are only general guidelines. Adjustment of the times may be necessary for specific applications and conditions.

Regenerating Iron Filters - Model 942Man

Refer to Regenerating Iron Filters Model 942 in Section 5.2 for information on this type of system application. All common control settings, control regenerant settings, and regenerant usage which apply to the 942Man control are the same as those used on the 942 control.

When using the 942Man control however, the time of each cycle cannot be predicted exactly. Note the following regeneration cycle parameters:

Backwash the filter until the drain water flows clear, typically 5 - 15 minutes.

Regenerant draw continues until the check ball closes to end draw.

Slow Rinse should continue until there is NO pink color to the drain water flow. This is typically four times that of the regenerant draw time.

Fast Rinse time continues until there is no pink color to the drain water flow, typically 5 - 15 minutes.

Refill time is determined by the size of the refill flow control and the amount of regenerant required for a particular size system. Refer to Regenerant Use Table in Section 5.2.

20

Table 5.2 Suggested Brine Draw/Slow Rinse Times Based on 25 psi and 2.5 Bed Volumes of Slow Rinse

Tank Size in. (cm)

14 (35.5)

16 (40.6)

18 (45.7)

21 (53.3)

24 (60.9)

30 (76.2)

36 (91.4)

 

 

 

 

 

 

 

 

Resin Vol. cu. ft. (cu m)

3 (0.085)

4 (0.113)

5 (0.142)

7 (0.200)

10 (0.283)

15 (0.425)

20 (0.566)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/ Rinse Time

78 min

72 min

85 min

73 min

79 min

89 min

77 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Min.] (kg)

18 (6.72)

24 (8.96)

30 (11.2)

42 (15.68)

60 (22.39)

90 33.59)

120

(44.79)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

60

80

100

140

200

300

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

87 min

83 min

98 min

87 min

89 min

100 min

86 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Mid] (kg)

30 (11.2)

40 (14.93)

50 (18.66)

70 (21.13)

100

150

200

(37.32)

(55.99)

(74.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

75

100

125

175

250

375

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

99 min

98 min

113 min

103 min

102 min

114 min

98 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Max]

45 (16.8)

60 (22.39)

75 (27.99)

105 (39.19

150

225

300

(55.99)

(83.98)

(111.97)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

90

120

150

210

300

450

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Injector Number

1000441

1000442

1000443

1000444

1000445

1000446

1000447

 

 

 

 

 

 

 

 

Table 5.3 Suggested Brine Draw/Slow Rinse Times Based on 50 psi and 2.5 Bed Volumes of Slow Rinse

Tank Size in. (cm)

14 (35.5)

16 (40.6)

18 (45.7)

21 (53.3)

24 (60.9)

30 (76.2)

36 (91.4)

 

 

 

 

 

 

 

 

Resin Vol. cu. ft. (cu m)

3 (0.085)

4 (0.113)

5 (0.142)

7 (0.200)

10 (0.283)

15 (0.425)

20 (0.566)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/ Rinse Time

65 min

58 min

70 min

65 min

66 min

76 min

68 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Min.] (kg)

18 (6.72)

24 (8.96)

30 (11.2)

42 (15.68)

60 (22.39)

90 33.59)

120

(44.79)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

60

80

100

140

200

300

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

74 min

70 min

83 min

77 min

77 min

87 min

77 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Mid] (kg)

30 (11.2)

40 (14.93)

50 (18.66)

70 (21.13)

100

150

200

(37.32)

(55.99)

(74.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

75

100

125

175

250

375

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

99 min

85 min

98 min

94 min

90 min

101 min

89 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Max]

45 (16.8)

60 (22.39)

75 (27.99)

105 (39.19

150

225

300

(55.99)

(83.98)

(111.97)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

90

120

150

210

300

450

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Injector Number

1000441

1000442

1000443

1000444

1000445

1000446

1000447

 

 

 

 

 

 

 

 

21

Table 5.4 Suggested Brine Draw/Slow Rinse Times Based on 75 psi and 2.5 Bed Volumes of Slow Rinse

Tank Size in. (cm)

14 (35.5)

16 (40.6)

18 (45.7)

21 (53.3)

24 (60.9)

30 (76.2)

36 (91.4)

 

 

 

 

 

 

 

 

Resin Vol. cu. ft. (cu m)

3 (0.085)

4 (0.113)

5 (0.142)

7 (0.200)

10 (0.283)

15 (0.425)

20 (0.566)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/ Rinse Time

55 min

52 min

61 min

57 min

58 min

66 min

55 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Min.] (kg)

18 (6.72)

24 (8.96)

30 (11.2)

42 (15.68)

60 (22.39)

90 33.59)

120

(44.79)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

60

80

100

140

200

300

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

64 min

64 min

73 min

70 min

69 min

76 min

64 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Mid] (kg)

30 (11.2)

40 (14.93)

50 (18.66)

70 (21.13)

100

150

200

(37.32)

(55.99)

(74.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

75

100

125

175

250

375

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

75 min

79 min

88 min

85 min

82 min

90 min

75 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Max]

45 (16.8)

60 (22.39)

75 (27.99)

105 (39.19

150

225

300

(55.99)

(83.98)

(111.97)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

90

120

150

210

300

450

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Injector Number

1000441

1000442

1000443

1000444

1000445

1000446

1000447

 

 

 

 

 

 

 

 

Table 5.5 Suggested Brine Draw/Slow Rinse Times Based on 100 psi and 2.5 Bed Volumes of Slow Rinse

Tank Size in. (cm)

14 (35.5)

16 (40.6)

18 (45.7)

21 (53.3)

24 (60.9)

30 (76.2)

36 (91.4)

 

 

 

 

 

 

 

 

Resin Vol. cu. ft. (cu m)

3 (0.085)

4 (0.113)

5 (0.142)

7 (0.200)

10 (0.283)

15 (0.425)

20 (0.566)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/ Rinse Time

50 min

48 min

56 min

53 min

54 min

59 min

50 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Min.] (kg)

18 (6.72)

24 (8.96)

30 (11.2)

42 (15.68)

60 (22.39)

90 33.59)

120

(44.79)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

60

80

100

140

200

300

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

59 min

60 min

68 min

65 min

64 min

69 min

59 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Mid] (kg)

30 (11.2)

40 (14.93)

50 (18.66)

70 (21.13)

100

150

200

(37.32)

(55.99)

(74.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

75

100

125

175

250

375

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine/Rinse Time

70 min

75 min

83 min

81 min

77 min

82 min

70 min

 

 

 

 

 

 

 

 

Total Lb. Salt [Max]

45 (16.8)

60 (22.39)

75 (27.99)

105 (39.19

150

225

300

(55.99)

(83.98)

(111.97)

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (kgr)

90

120

150

210

300

450

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Injector Number

1000441

1000442

1000443

1000444

1000445

1000446

1000447

 

 

 

 

 

 

 

 

Minimum salting: 6 lb. salt = 20 kgr/cu. ft.

Medium salting: 10 lb. salt = 25 kgr/cu. ft.

Maximum salting: 15 lb. salt = 30 kgr/cu. ft.

22

Loading...
+ 60 hidden pages