Watlow Electric 987, 986, 989, 988 User Manual

4.5 (2)
Series 988
1/8 DIN Microprocessor-Based Temperature/Process Controller
0600-0009-0001 Rev W
March 1999
Supersedes: 0600-0009-0001 Rev V
$10.00
Made in the U.S.A.
Printed on Recycled Paper 10% Postconsumer Waste
Includes 986, 987, 988 and 989
User Levels:
• New User........................... go to Introduction
• Experienced User................... go to page 4.1
Installers:
• Set-up..................................... go to page 1.1
• Wiring & Installation................ go to page 2.1
Watlow Controls
1241 Bundy Blvd., P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: (507) 454-5300, Fax: (507) 452-4507 http://www.watlow.com
Registered Company
Winona, Minnesota USA
ISO 9001
9
6
TOTAL
3 Year Warranty

WATLOW Series 988 User’s ManualTable of Contents

Table of Contents
Introduction to the Watlow Series 988
Controllers
ii Using this Manual
ii Document Every Step
iii Notes, Cautions and Warnings
iii Technical Assistance
iii We Value Your Feedback
Chapter 1
Hardware Setup
1.1 Dip Switch Locations and Functions
Chapter 2
Installation and Wiring
2.1 Panel Cutout and Dimensions
2.2 Installing the Series 988
2.4 Wiring the Series 988
2.4 Input-to-output Isolation
2.4 Power Wiring
2.5 Sensor Installation Guidelines
2.6 Wiring Example
2.8 Input 1 Wiring
2.9 Input 2 Wiring
2.11 Event Input 1 Wiring
2.12 Output 1 Wiring
2.13 Output 2 Wiring
2.14 Output 3 Wiring
2.15 Output 4 Wiring
Chapter 3
Front Panel and Display Loop
3.1 Keys and Displays
3.2 Display Loop
Chapter 4
The Setup Menus
4.1 Navigating the Setup Menus
4.2 Input Menu
4.18 Output Menu
4.34 Global Menu
4.44 Communications Menu
Chapter 5
The Operation Menus
5.1 Navigating the Operation Menus
5.2 System Menu
5.9 PID A and PID B Menus
Chapter 6
The Factory Menus
6.1 Navigating the Factory Menus
6.2 Panel Lockout Menu
6.7 Diagnostics Menu
6.13 Calibration Menu
Chapter 7
Tuning, Manual Operation,
Alarms and Error Codes
7.1 Auto-tuning (Heat and/or Cool)
7.2 Manual Tuning
7.4 Manual and Automatic Operation
7.5 Changing the Output 3 Alarm Jumper
7.6 Using Alarms
7.8 Error Code E1 and E2 Messages
7.9 Error Code Actions
Chapter 8
General Software
8.2 Burst Fire
8.4 Communications
8.6 Dead Band
8.8 Digital Events
8.10 Heater Current
8.12 Input Filter
8.14 Input Linearization
8.16 Ramp to Set Point
8.18 Remote Set Point
8.20 Retransmit
8.22 Slidewire Feedback
Appendix
A.2 Glossary
A.4 Specifications
A.5 Warranty and Returns
A.6 Index
A.10 Menu Overview
A.11 Model Number – Ordering Information
A.12 Declaration of Conformity
WATLOW Series 988 User’s Manual i
Introduction
Introduction to the
W atlow Series 988 Controllers
Figure Int.1 -
The Series 988
Controllers.
Watlow’s Series 988 controllers set a new standard in the controller indus-
try by packing an impressive array of features into an 1/8-DIN package.
No other controller offers the flexibility, compact size and durability of the
Series 988. It can control a wide variety of temperature and process appli-
cations, with a broad range of input and output options that allow control
of virtually any process variable.
The Series 988 is the only 1/8 DIN controller that can provide single-unit
cascade control of a process. Its other features include heater current
monitoring, remote set point input, ratio control and valve control through
slidewire feedback. The Series 988 also delivers expanded auto-tuning
capabilities, increased alarm functionality and several unique control algo-
rithms.
When we refer to the “Series 988” controller, we refer also to the horizontal
and low-voltage versions of the Series 988: the 986, 987, 988 and 989. We
recommend that you read all of this manual’s introduction to familiarize
yourself with the conventions and content of this manual and the steps to
setting up a Series 988 controller. Make sure you understand the
“Caution” and “Warning” symbols we use in the book.
ii WATLOW Series 988 User’s Manual
Introduction
Introduction

Using this Manual

This manual provides the information you will need to install and operate
a Series 988 controller.
If you need information about Series 988 configurations and model num-
bers, refer to the Appendix of this manual or, for more detailed informa-
tion, to Optimizing Your Process System with the Series 988 Controller: An
Application Guide for the Watlow Series 988 Family.
If your Series 988 controller will be used for data communications, you
will also need our communications manual, Data Communications with the
Watlow Series 988 Family of Controllers (green cover).
Series 988 controllers are calibrated in the factory, but if you need to do
periodic calibration you will need our calibration manual, Calibrating
Watlow Process Controllers, (blue cover).
This manual explains the five steps of setting up a Series 988 controller:
1. Set and document all of the DIP switches, if applicable: Chapter 1.
2. Mount the controller: Chapter 2.
3. Wire and document the controller wiring: Chapter 2.
4. Configure and document the controller software: Chapters 3-6.
5. Run, test and adjust your application. Update documentation.
Chapters 7 and 8 and the Appendix provide detailed advice, definitions
and specifications along with application examples to help you optimize
the safety and performance of your application. Use the Table of Contents
and Index to find specific information.

Document Every Step

The Series 988 provides powerful and complex features. Carefully docu-
ment each step of the setup and any subsequent changes. This will make
it much easier to change, adjust and troubleshoot your application.
Make the configuration documentation available to engineers and techni-
cians, on all shifts, who may need to work with the Series 988. We provide
space in this manual to record configurations. You may prefer to photo-
copy the blank forms and keep them in a separate binder. However you
maintain your documentation, be sure to replace all old copies of the doc-
umentation with updated versions whenever the controller configuration is
changed.
˜
NOTE:
The Menu Overview
in the Appendix
shows all the
menus and
prompts.
˜
NOTE:
The 12-digit number
is printed on the top
of the stickers on
each side of the
controller’s case
and on the right-
hand or top circuit
board.
Introduction
WATLOW Series 988 User’s Manual iii
Introduction

Notes, Cautions and Warnings

We use note, caution and warning symbols throughout this book to draw
your attention to important operational and safety information.
A bold text “NOTE” marks a short message in the margin to alert you to
an important detail.
A bold text “CAUTION” safety alert appears with information that is
important for protecting your equipment and performance. Be especially
careful to read and follow all cautions that apply to your application.
A bold text “WARNING” safety alert appears with information that is
important for protecting you, others and equipment from damage. Pay
very close attention to all warnings that apply to your application.
The ç symbol (an exclamation point in a triangle) precedes a general
CAUTION or WARNING statement.
The Ó symbol (a lightning bolt in a triangle) precedes an electric shock
hazard CAUTION or WARNING safety statement.

Technical Assistance

If you encounter a problem with your Watlow controller, review all of your
configuration information for each step of the setup to verify that your
selections are consistent with your applications.
If the problem persists after checking all the steps, you can get technical
assistance by calling Watlow Controls at (507) 454-5300, between 7 a.m.
and 5 p.m. CST, and asking for an applications engineer. When you call
have the following information on hand: the controller’s model number
(the 12-digit number is printed on the top of the stickers on each side of
the controller’s case and on the right-hand or top circuit board); your
user’s manual; all configuration information; and the Diagnostics Menu
readings.

We Value Your Feedback

Your comments and suggestions on this manual are welcome. Please send
them to, Technical Writer, Watlow Controls, 1241 Bundy Blvd., P.O. Box
5580, Winona, MN 55987-5580 or call (507) 454-5300 or fax (507) 452-
4507. The Series 988 User’s Manual is copyrighted by Watlow Winona,
Inc., © March 1999, with all rights reserved. (1657)
WATLOW Series 988 User’s Manual 1.1
Hardware Setup, Chapter 1

Chapter 1 Hardware Setup

DIP Switch Locations and Functions

The Watlow Series 988 has at least one and as many as six dual in-line
package (DIP) switches inside the controller, depending on the model
number. They allow users to configure the controller for a variety of input
sensors, to provide power for external signal conditioners or to lockout
front panel access to some functions.
To set any DIP switch:
• Remove the controller from the case by pressing firmly on the two release
tabs on one side or the top of the bezel until they unsnap. Then firmly
press the two release tabs on the opposite side or the bottom of the con-
trol until they unsnap. You will need to gently rock the bezel back and
forth to release it from the chassis.
• Use the illustrations on the following pages to locate and set each DIP switch.
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
DISPLAY
SERIES 988
MODE
AUTO
MAN
Release
Tabs
Release
Tabs
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
MODE
SERIES 989
DSPY
AUTO
MAN
Release
Tabs
Release
Tabs
Figure 1.1 - Press
the release tabs to
remove the con-
troller chassis.
1.2 WATLOW Series 988 User’s Manual
Hardware Setup, Chapter 1
DIP Switches
Figure 1.2 -
Input DIP switches.
Input 1 Input 2
(98 _ _-2_ _ _-_ _ _ _)(98 _ _-_2_ _-_ _ _ _)
RTD (100 )
thermocouple: R, S or B
thermocouple: J, K, T, N, E, C, D, Pt2
or 0-50mV (high impedance)
0-20 or 4-20mA; 0-5, 1-5 or 0-10V
O
N
123
O
N
123
O
N
123
O
N
123
O
N
123
O
N
123
O
N
123
O
N
123
Controller Chassis
Rear View
Input 1 DIP
Input 2 DIP
ON
ON
1. Set the input DIP
switches to match the
sensors you are using
in your application.
Only controllers with
model number 98_ _-
2_ _ _-_ _ _ _ or 98_ _-
_2_ _-_ _ _ _ have an
input DIP switch.
˜
NOTE:
The Input 2 DIP
switch is mounted
upside down.
˜
NOTE:
Only controllers
with the indicated
model numbers
have these DIP
switches.
DIP Switches
WATLOW Series 988 User’s Manual 1.3
Hardware Setup, Chapter 1
Output 2
Option B oa r d a nd D IP
Output 4
Option B oa r d a nd D IP
Con t ro ller Chassis
Top View (986 & 988)
Left-side View (987 & 989)
Output 3
Option B oa r d a nd D IP
Output 1
Option Board
offon
on
on
off
off
Figure 1.3 -
External signal con-
ditioner power sup-
ply DIPs.
Output 2 Output 3 Output 4
(98 _ _-_ _ _T-_ _ _ _) (98 _ _-_ _ _ _-T_ _ _) (98 _ _-_ _ _ _-_T_ _)
20V ± 5% @ 30mA
12V ± 5% @ 30mA
5V ± 5% @ 30mA
O
N
12
O
N
12
O
N
12
O
N
12
O
N
12
O
N
12
O
N
12
O
N
12
O
N
12
2. Set DIP switches for
outputs equipped with
an external signal con-
ditioner power supply.
Only controllers with
model number 98_ _-_
_ _T-_ _ _ _, 98_ _-_ _ _
_-T_ _ _ or 98_ _-_ _ _
_-_T_ _ have an exter-
nal signal conditioner
power supply.
˜
NOTE:
For other voltages
or current settings
contact the factory.
3. When the DIP switches are set, gently insert the controller chassis into
the case and push it firmly into place until all four tabs snap into place.
˜
NOTE:
Only controllers
with the indicated
model numbers
have these DIP
switches.
1.4 WATLOW Series 988 User’s Manual
Hardware Setup, Chapter 1
DIP Switches
Figure 1.4 -
Lockout DIP switch.
no hardware lockout or
(Switch 1 has no effect.)
lockout Setup and Factory menus or
(Switch 1 has no effect.)
O
N
12
O
N
12
O
N
12
O
N
12
4. The lockout DIP switch
hides the Setup Menus
(Input, Output, Global and
Communications) and the
Factory Menus (Panel
Lockout, Diagnostics and
Calibration). All units have
a lockout DIP switch.
ç
CAUTION:
The lockout DIP
switch makes the
Setup and Factory
menus unavailable.
Configure all the
Setup and Factory
menus before lock-
ing them out.
Failure to do so
could result in dam-
age to equipment in
the event of a setup
error.
Input
Output Global
Panel
Lockout
Diagnostics Calibration
Commu-
nications
[InPt]
[`SEt]
[OtPt]
[`SEt]
[PLOC]
[Fcty]
[diAG]
[Fcty]
[`CAL]
[Fcty]
[GLbL]
[`SEt]
[CO
M
[`SEt]
WATLOW Series 988 User’s Manual 2.1
Installation and Wiring, Chapter 2

Chapter 2 Installation and Wiring

Panel Cutout
Maximum Panel
Thickness
0.38" (9.65mm)
3.62" + 0.03 -0.00
(92mm + 0.8)
1.77 + 0.02 -0.00
(45mm + 0.6)
4.03"
(102mm)
2.18"
(55 mm)
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
DISPLAY
SERIES 988
MODE
AUTO
MAN
4.03"
(102mm)
2.18"
(55 mm)
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
MODE
SERIES 989
DSPY
AUTO
MAN
Figure 2.1 -
Series 988 and
Series 989
dimensions and
terminal number
layout.
Panel
Adjustable
Mounting Bracket
4.06"
(103 mm)
0.68"
(17 mm)
˜
NOTE:
Adjustable mount-
ing brackets can be
side-mounted.
˜
NOTE:
Space panel
cutouts at least 1.66
inches (42.2mm)
apart.
˜
NOTE:
Holes can be cut in
the panel using a
Greenlee 1/8 DIN
Hydraulic Kit
#60068 (punch
#60069, die #60070).
12
13
14
15
16
17
18
19
3
4
5
6
7
8
9
11
22
21
1
20
23
10
24
2
98765432
19 18 17 16 15 14 13 12
10
23
24
20
1
21
22
11
2.2 WATLOW Series 988 User’s Manual
Installation and Wiring, Chapter 2
Installation

Installing the Series 988

Installing and mounting requires access to the back of the panel.
1. Make a panel cutout using the panel cutout dimensions from the previ-
ous page.
2. To remove the controller chassis from its case, press in firmly on the two
tabs on one side or the top of the bezel until they unsnap, then unsnap
the two tabs on the opposite side or the bottom. Pull the chassis out of
the case by gently rocking it.
3. Slide the case into the panel cutout. Check to see that the gasket is not
twisted, and is seated within the case bezel flush with the panel. Slide
Panel
Adjustable
Mounting Bracket
Bezel
External Gasket
Mounting Collar
Release Tabs
Top and Bottom (986 or 988)
or Side (987 or 989) View
Mounting Slots
Side (986 or 988)
or Top and Bottom (987 or 989) View
˜
NOTE:
Removing the con-
troller chassis from
its case makes
mounting easier.
Figure 2.2 -
Side and top view.
WATLOW Series 988 User’s Manual 2.3
Installation and Wiring, Chapter 2
the mounting collar over the back of the control.
4. Loosen the mounting bracket screws enough to allow for the mounting
collar and panel thickness. Place each mounting bracket into the
mounting slots (head of the screw facing the back of the controller).
Push each bracket backward then down to secure it to the control
case. To guarantee a proper NEMA 4X seal, Series 986 and 988
units (vertical) must have the mounting brackets located on either
side of the unit. When installing Series 987 and 989 units (horizon-
tal) the brackets must be on the top and bottom of the unit.
5. Make sure the case is seated properly. Tighten the installation screws
firmly against the mounting collar to secure the unit. To ensure a
NEMA 4X seal, there should be no space between the bezel and
panel. Overtightening the screws will distort the case and make it diffi-
cult to remove or replace the controller.
6. Make sure the inside gasket is seated properly and not twisted.
Insert the controller chassis into its case and press the bezel until all
four tabs snap.
7. To release the mounting brackets, loosen the mounting bracket screws
and push the brackets forward, then pull it up and out.
ç
CAUTION:
Follow the installa-
tion procedure
exactly to guarantee
a proper NEMA 4X
seal. Make sure the
gasket between the
panel and the rim of
the case is not
twisted and is seat-
ed properly. Failure
to do so could
result in damage to
equipment.
Installation
2.4 WATLOW Series 988 User’s Manual
Installation and Wiring, Chapter 2
Wiring

Wiring the Series 988

Wiring options depend on the model number and DIP switch settings.
Check the terminal designation stickers on either side of the controller
and compare your model number to those shown here and with the model
number breakdown on the inside back cover of this manual.

Input-to-output Isolation

The Series 988 uses optical isolation between the analog inputs and the
controller outputs/digital input. This isolation provides a 500VÅ (ac) bar-
rier to prevent ground loops when using grounded sensors and/or periph-
eral equipment.
Here is a breakdown of the isolation barriers:
• Analog inputs 1 and 2 are grouped together.
• Outputs 1 through 4 and the standard event input are grouped together.
This does not apply to Output 4 when configured as communications.
• The digital communications output (4) is separate from the above
groups.

Power Wiring

100 to 240V
(ac/dc) nominal, (85 to 264 actual)
Vertical Package 98 8 _ - _ _ _ _ - _ _ _ _
Horizontal Package 98 9 _ - _ _ _ _ - _ _ _ _
24 to 28 V
(ac/dc) nominal, (20 to 30 actual)
Vertical Package 98 6
_ - _ _ _ _ - _ _ _ _
Horizontal Package 98 7
_ - _ _ _ _ - _ _ _ _
fuse
22
21
earth ground
11
L2L1
+
-
WARNING:
To avoid potential
electric shock, use
National Electric
Code (NEC) safety
practices when
wiring and connect-
ing this unit to a
power source and
to electrical sensors
or peripheral
devices. Failure to
do so could result
in injury or death.
˜
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter con-
nected to input 1 or
input 2.
Figure 2.4 -
Power wiring.
WATLOW Series 988 User’s Manual 2.5
Installation and Wiring, Chapter 2
Wiring

Sensor Installation Guidelines

Maintain isolation between input 1 and input 2 to prevent a ground loop.
A ground loop may cause incorrect readings, dashes across the upper dis-
play or the display of error codes.
Thermocouple input: Extension wire for thermocouples must be of the
same alloy as the thermocouple itself to limit errors.
Using grounded thermocouples for both input 1 and input 2 may create
ground loop problems. To correct this problem, replace at least one of the
grounded thermocouples with an ungrounded thermocouple. If the appli-
cation requires grounded thermocouples, use an isolated transmitter,
such as a Watlow Gordon 5702 isolated transmitter.
RTD (100 ) input: Each 1 of lead wire resistance can cause a +2°C
error when using a two-wire RTD. A three-wire RTD sensor overcomes this
problem. All three wires must have the same electrical resistance (i.e.,
same gauge, same length, multi-stranded or solid, same metal).
Process input: Isolation must be maintained between input 1 and input
2. If both input 1 and input 2 are used as process inputs, a separate
power supply and transmitter must be used for each input. Output option
T (external signal conditioner power supply) can be used to supply power
for only one input.
ç
CAUTION:
The Series 988 will
not function with
two grounded ther-
mocouple inputs.
Avoid using a
grounded thermo-
couple for both
input 1 and input 2.
Failure to follow this
guideline could
result in damage to
equipment.
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter connect-
ed to input 1 or
input 2.
2.6 WATLOW Series 988 User’s Manual
Installation and Wiring, Chapter 2

Wiring Example

Figure 2.6 -
System wiring
example.
988A-10CA-AARR
rear view
(+)
10
9
2221
12
13
(-)
L1
L2
(-)
120VÅ (ac)
fuse
92A3-1DJ1-0000
limit control
heater
process sensor limit sensor
optional
normally open
momentary switch
red
high-limit
mechanical
contactor
earth ground
(+)
dc input
SSR
SSR-240-10A-DC1
in
out
12
43
13 14
10
+
11
-
high-temperature
light
coil
11
15
1
120VÅ (ac)
L1
L2
2
9
10
4
5
1 2
1
2
(+)
(-)
3
11
18
12
13
14
15
2
1CR
16
high-temperature light
1
2
3
4
8
9
10
11
12
R
SSR-240-10A-DC1
solid-state relay, dc input
17
1
8
heater
out
24-240VÅ (ac)
(+)
(-)
in
3-32VÎ (dc)
1 CR-1
910
2
12 13
67
21 22
5
6
7
limit control
Series 988
988A-10CA-AARR
temperature control
Series 92
92A3-1DJ1-0000
13
4
3
5
11
12
13
14
10
(+)
(-)
11
WARNING:
To avoid potential
electric shock, use
National Electric
Code (NEC) safety
practices when
wiring and connect-
ing this unit to a
power source and
to electrical sen-
sors or peripheral
devices. Failure to
do so could result
in injury or death.
ç
WARNING:
Install high or low
temperature limit
control protection
in systems where
an over tempera-
ture fault condition
could present a fire
hazard or other haz-
ard. Failure to
install temperature
limit control protec-
tion where a poten-
tial hazard exists
could result in dam-
age to equipment,
property and injury
to personnel.
ç
WARNING:
To avoid damage to
property and equip-
ment, and/or injury
of loss of life, use
National Electric
Code (NEC) stan-
dard wiring prac-
tices to install and
operate the Series
988. Failure to do
so could result in
such damage,
and/or injury or
death.
WATLOW Series 988 User’s Manual 2.7
Installation and Wiring, Chapter 2

Wiring Notes

L1 L2
power
earth ground
11
21 22
ç
WARNING:
To avoid damage to
property and equip-
ment, and/or injury
of loss of life, use
National Electric
Code (NEC) stan-
dard wiring prac-
tices to install and
operate the Series
988. Failure to do
so could result in
such damage,
and/or injury or
death.
Figure 2.7 -
Wiring notes.
˜
NOTE:
Sketch in your
application on this
page or a copy of it.
See wiring exam-
ples in this chapter
and in the Appen-
dix.
2.8 WATLOW Series 988 User’s Manual
Installation and Wiring, Chapter 2

Input 1 Wiring

Figure 2.8c — 0-5V
ÎÎ
, 1-5V
ÎÎ
or 0-10V
ÎÎ
(dc) Process
Universal signal conditioner
98 _ _ - 2 _ _ _ - _ _ _ _
Input impedance: 10K
Figure 2.8a — Thermocouple or 0-50mV (high impedance)
Thermocouple only
98 _ _ - 1 _ _ _ - _ _ _ _ (no DIP switches)
Universal signal conditioner
98 _ _ - 2 _ _ _ - _ _ _ _
Input impedance: 20M
Figure 2.8b — RTD (2- or 3-wire) (100 )
Universal signal conditioner
98 _ _ - 2 _ _ _ - _ _ _ _
9
10
+
-
0-50mV
9
10
8
S2
S1
S3
10
9
-
+
Figure 2.8d — 0-20mA or 4-20mA Process
Universal signal conditioner
98 _ _ - 2 _ _ _ - _ _ _ _
Input impedance: 7
10
8
-
+
9
10
8
S2
S1
DIP Switch
Setting
R, S, B
DIP Settings
J, K, T, N, C, E, D, Pt2,
0-50mV DIP Settings
DIP Switch
Setting
DIP Switch
Setting
˜
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
O
N
123
O
N
123
O
N
123
O
N
123
O
N
123
9
10
+
-
Jumper
#9 to #10
for 2-wire
RTD
Figure 2.9d — 0-20mA or 4-20mA Process
Universal signal conditioner
98 _ _ - _ 2 _ _ - _ _ _ _
Input impedance: 7
Figure 2.9c —
0-5V
ÎÎ
, 1-5V
ÎÎ
or 0-10V
ÎÎ
(dc) Process
Universal signal conditioner
98 _ _ - _ 2 _ _ - _ _ _ _
Input impedance: 10K
Figure 2.9b — RTD (2- or 3-wire) (100 )
Universal signal conditioner
98 _ _ - _ 2 _ _ - _ _ _ _
WATLOW Series 988 User’s Manual 2.9
Installation and Wiring, Chapter 2

Input 2 Wiring

20
19
-
+
Figure 2.9a — Thermocouple or 0-50mV (high impedance)
Thermocouple only
98 _ _ - _ 1 _ _ - _ _ _ _ (no DIP switches)
Universal signal conditioner
98 _ _ - _ 2 _ _ - _ _ _ _
Input impedance: 20M
19
20
+
-
Jumper
#19 to #20
for 2-wire
RTD
19
20
18
S2
S1
DIP Switch
Setting
R, S, B
DIP Settings
J, K, T, N, C, E, D, Pt2,
0-50mV DIP Settings
DIP Switch
Setting
19
20
18
S2
S1
S3
O
N
123
O
N
123
O
N
123
O
N
123
20
18
-
+
DIP Switch
Setting
O
N
123
19
20
+
-
0-50mV
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
Figure 2.10b — Current Transformer Input
98 _ _ - _ 4 _ _ - _ _ _ _
The current transformer must be purchased separately. Watlow current
transformer part number 16-0246 (up to 50 amps).
Systems that use more than 50 Amps need an interstage transformer.
For example, if you use a 300A current transformer, part #16-0073, and
an interstage transformer, part #16-0176, the 300A current transformer
provides a 5A signal to the interstage transformer. In turn, the trans-
former sends a 20mA maximum signal to the controller.
20
19
T3
T1
T2
Phase
dot
2.10 WATLOW Series 988 User’s Manual
Installation and Wiring, Chapter 2
Input 2 Wiring
20
19
L2
L1
CT
Load wire
Center leg not used
Figure 2.10a — Slidewire Feedback or Potentiometer Input
98 _ _ - _ 3 _ _ - _ _ _ _
19
20
18
CW
CCW
Wiper
NOTE:
See Chapter 8 for
information on
slidewire feedback.
˜
NOTE:
A process output
cannot be installed
on output 1 when
using a current
transformer input.
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
AC Load
19
20
0 to 5A
AC
0 to
20mA
A
Bk
Red
Red
Wh Bk
Bk Wh
Bk
16-0176
Transformer
CT
CT
T1
T3
T2
5A
20mA
19
20
Single-phase Single-phase current sensing up to 300 amps
3-phase using 2 current transformers 3-phase current sensing up to 300 amps.
WATLOW Series 988 User’s Manual 2.11
Installation and Wiring, Chapter 2
Figure 2.10c — Digital Event Input 2
98 _ _ - _ 5 _ _ - _ _ _ _
open 0-3VÎ (dc) Event Input 2 off
closed 14-36VÎ (dc) Event Input 2 on
Figure 2.11a — Digital Event Input 1
Available on all units.
open 14-36VÎ (dc) Event Input 1 off
closed 0-3VÎ (dc) Event Input 1 on
20
18
+5VÎ (VDC)
100
750
4.7K
1K
.01µf
19
Internal Circuitry
23 24
+-
24
23
+24VÎ (dc)
10K
4.99K
OPTO
ISOLATOR
750
.01µf
4.99K
Internal Circuitry
20
18
20
19
+
-
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).

Event Input 1 Wiring

2.12 WATLOW Series 988 User’s Manual
Installation and Wiring, Chapter 2
Figure 2.12a — AC Outputs
Solid-state Relay
with
Contact Suppression
98 _ _ - _ _ B _ - _ _ _ _
0.5 amps, minimum off-state impedance: 20K
Electromechanical Relay
with
Contact Suppression
(Suppression between NO and COM contacts only)
98 _ _ - _ _ D _ - _ _ _ _
Form C, 5 amps, minimum off-state impedance: 20K
Electromechanical Relay
without
Contact Suppression
98 _ _ - _ _ E _ - _ _ _ _
Form C, 5 amps off-state impedance: 31M
Solid-state Relay
without
Contact Suppression
98 _ _ - _ _ K _ - _ _ _ _
0.5 amps, off-state impedance: 31M

Output 1 Wiring

Figure 2.12b — Switched DC, Open Collector
98 _ _ - _ _ C _ - _ _ _ _
Maximum voltage: 42V
ÎÎ
(dc)
Maximum current: 1A
External
Load
COM
L1
L2
Fuse
NO
12
13
NC
14
(#14 for D & E outputs only)
12
External
Load
+
13
14
-
COM
Figure 2.12d — 0-5V
ÎÎ
, 1-5V
ÎÎ
and 0-10V
ÎÎ
(dc) Process
98 _ _ - _ _ F _ - _ _ _ _
Minimum load impedance: 1K
Figure 2.12c — 0-20mA and 4-20mA Process
98 _ _ - _ _ F _ - _ _ _ _
Maximum load impedance: 800
14
-
+
12
14
-
+
13
+
Internal Circuitry
12
13
14
790
19 to 32VÎ (dc)
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.
WATLOW Series 988 User’s Manual 2.13
Installation and Wiring, Chapter 2

Output 2 Wiring

Figure 2.13b — Switched DC, Open Collector
98 _ _ - _ _ _ C - _ _ _ _
Maximum voltage: 42V
ÎÎ
(dc)
Maximum current: 1A
15
External
Load
+
16
17
-
COM
Figure 2.13d — 0-5V
ÎÎ
, 1-5V
ÎÎ
and 0-10V
ÎÎ
(dc) Process
98 _ _ - _ _ _ F - _ _ _ _
Minimum load impedance: 1K
Figure 2.13c — 0-20mA and 4-20mA Process
98 _ _ - _ _ _ F - _ _ _ _
Maximum load impedance: 800
15
+
-
17
16
+
-
17
Figure 2.13e — External Signal Conditioner Power Supply
98 _ _ - _ _ _ T - _ _ _ _
15
16
1
2
+
-
+V
-V
Transmitter
4-20mA out
Input
1 or 2
-
+
Figure 2.13a — AC Outputs
Solid-state Relay
with
Contact Suppression
98 _ _ - _ _ _ B - _ _ _ _
0.5 amps, minimum off-state impedance: 20K
Electromechanical Relay
with
Contact Suppression
(Suppression between NO and COM contacts only)
98 _ _ - _ _ _ D - _ _ _ _
Form C, 5 amps, minimum off-state impedance: 20K
Electromechanical Relay
without
Contact Suppression
98 _ _ - _ _ _ E - _ _ _ _
Form C, 5 amps off-state impedance: 31M
Solid-state Relay
without
Contact Suppression
98 _ _ - _ _ _ K - _ _ _ _
0.5 amps, off-state impedance: 31M
External
Load
COM
L1
L2
Fuse
NO
15
16
NC
17
(#17 for D & E outputs only)
+
Internal Circuitry
15
16
17
790
19 to 32VÎ (dc)
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
˜
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter connect-
ed to input 1 or
input 2.
NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.
Loop powered
Figure 2.14c — Process Retransmit
0-20mA, 4-20mA, Load impedance: 600 max.
98 _ _ - _ _ _ _ - M _ _ _
0-5V
ÎÎ
, 1-5V
ÎÎ
, 0-10V
ÎÎ
(VDC), Load impedance: 500 min.
98 _ _ - _ _ _ _ - N _ _ _
2.14 WATLOW Series 988 User’s Manual
Installation and Wiring, Chapter 2
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter con-
nected to input 1 or
input 2.
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
Figure 2.14d — External Signal Conditioner Power Supply
98 _ _ - _ _ _ _ - T _ _ _
Figure 2.14a — AC Outputs
Solid-state Relay
with
Contact Suppression
98 _ _ - _ _ _ _ - B _ _ _
0.5 amps, minimum off-state impedance: 20K
Electromechanical Relay
without
Contact Suppression
98 _ _ - _ _ _ _ - J _ _ _ _
Form A or B, 5 amps, off-state impedance: 31M
Solid-state Relay
without
Contact Suppression
98 _ _ - _ _ _ _ - K _ _ _ _
0.5 amps, off-state impedance: 31M
External
Load
COM
L1
L2
Fuse
NO Form A
1
2
NC Form B
or
-
-
Figure 2.14b — Switched DC
98 _ _ - _ _ _ _ - C _ _ _
Minimum load resistance: 500
1
2
External
Load
-
+
1
2
+
-
+V
-V
Transmitter
4-20mA out
Input
1 or 2
+
-
Form B
Form A
Form A or B
alarm jumper
settings (98__-
____-J___ only)
˜
NOTE:
See Chapter 1 for
power supply DIP
switch information.
+
Internal Circuitry
1
2
790
19 to 32VÎ (dc)
1
2
+
-

Output 3 Wiring

NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.
Loop powered
WATLOW Series 988 User’s Manual 2.15
Installation and Wiring, Chapter 2
Figure 2.15b — Switched DC, Open Collector
98 _ _ - _ _ _ _ - _ C _ _
Maximum voltage: 42V
ÎÎ
(dc)
Maximum current: 1A
Figure 2.15a — AC Outputs
Solid-state Relay
with
Contact Suppression
98 _ _ - _ _ _ _ - _ B _ _
0.5 amps, minimum off-state impedance: 20K
Electromechanical Relay
with
Contact Suppression
(Suppression between NO and COM contacts only)
98 _ _ - _ _ _ _ - _ D _ _ _
Form C, 5 amps, minimum off-state impedance: 20K
Electromechanical Relay
without
Contact Suppression
98 _ _ - _ _ _ _ - _ E _ _ _
Form C, 5 amps, off-state impedance: 31M
Solid-state Relay
without
Contact Suppression
98 _ _ - _ _ _ _ - _ K _ _ _
0.5 amps, off-state impedance: 31M

Output 4 Wiring

External
Load
COM
L1
L2
Fuse
NO
5
6
NC
(#7 for D & E outputs only)
7
5
External
Load
6
+
7
-
COM
Figure 2.15c — External Signal Conditioner Power Supply
98 _ _ - _ _ _ _ - _ T _ _
5
6
+
-
+V
-V
Transmitter
4-20mA out
Input
1 or 2
+
-
Controllers with Output 4 (R, S, or U)
For data communications wiring refer to “
Data Communications
with the Watlow Series 988 Family of Controllers”
manual. This
manual can be downloaded from Watlow’s website at
www.watlow.com
, Product Techical Information - Controls.
NOTE:
Input-to-output iso-
lation is defeated
when the external
transmitter power
supply is used to
power a signal con-
ditioner connected
to input 1 or input 2.
˜
NOTE:
See Chapter 1 for
power supply DIP
switch information.
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
+
Internal Circuitry
5
6
7
790
19 to 32VÎ (dc)
NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.
Loop powered
WATLOW Series 988 User’s Manual 3.1
Front Panel and Display Loop, Chapter 3

Chapter 3 Front Panel and Display Loop

Upper Display
Indicates the actual process value,
prompt parameter value or error
code.
DEV LED
When lit, the lower display shows
the most recent deviation unit from
the set point.
% OUT LED
When lit, the lower display shows
the current percent output.
Up-arrow Key
Increases the value or changes the
parameter in the upper display
(except for set point changes in the
Display Loop, which occur in the
lower display). Hold the key down
to increase the value rapidly. New
data takes effect in five seconds or
when the Mode key or Display key
is pressed.
Up + Down Keys
Press simultaneously for three sec-
onds to go to the Setup Menu.
Continue to press both keys for
another three seconds to go to the
Factory Menu. Access to the Setup
and Factory menus can be dis-
abled with lockout DIP switch.
Lower Display
Indicates the set point, deviation,
percent power, temperature unit,
menu prompt name or alarm code.
L1, L2, L3, L4
These LED’s indicate when output
1, 2, 3 or 4 are active. Outputs can
be configured as:
Ot1 Control
Ot2 Control or Alarm
Ot3 Alarm or Retransmit
Ot4 Alarm or Communications
(flashes on transmit and
receive)
Display Key
Pressing this key enters the
Display Loop. Press the Display
key at any time to return to this
loop. The next page has more
information on the Display Loop.
Auto/Man Key
In Manual mode the lower display
shows percent output. Pressed
once, it clears any latched alarm. If
pressed again within five seconds
it will toggle between Auto and
Manual mode.
Auto/Man LED
Lit when the control is in Manual
operation. Press the Auto/Man key
twice to enter Automatic operation.
When blinking, press the Auto/Man
key to toggle between Auto and
Manual. After five seconds without
pressing the Auto/Man key, the
LED stops blinking and returns to
its previous state.
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
DISPLAY
SERIES 988
MODE
AUTO
MAN
Mode Key
Enters new data and steps to
the next prompt in the current
menu.
Mode + Up-arrow Keys
Hold the Mode key then press
the Up-arrow key to move
backwards through the cur-
rent menu. Scrolling stops
when you reach the top of the
menu.
Figure 3.1 -
Series 988 Keys and Displays
Down-arrow Key
Decreases the value or changes
the parameter in the upper display
(except for set point changes in the
Display Loop, which occur in the
lower display). Hold the key down
to decrease the value rapidly. New
data takes effect in five seconds or
when the Mode key or Display key
is pressed.

Keys and Displays

3.2 WATLOW Series 988 User’s Manual
Front Panel and Display Loop, Chapter 3

Display Loop

Display Loop
The Display Loop is the “home” state of the Series 988 controller. Pressing
the Display key returns the controller to the Display Loop from any
prompt in any menu. The controller automatically returns to the Display
Loop from any menu when a minute passes without any keys being
pressed.
Figure 3.2 -
The Display Loop
DISPLAY
units selected (units, °F or °C)
set point 1 (change with Up-arrow > or Down-arrow < key)
input 2 process (appears only if controller equipped with input 2 hardware)
deviation from set point, process 1 minus set point 1 (DEV light on)
percent output (%OUT light on)
DISPLAY
current input 1 reading
current input 2 reading
current input 1 reading
current input 1 reading
current input 1 reading
DISPLAY
DISPLAY
DISPLAY
DISPLAY
[`988]
[`988]
[`988]
[Pr`2]
[`988]
[`988]
[`988]
[`100]
[`988]
[``°C]
˜
NOTE:
If [``no] is selected
for [`In2], in the
Input Menu, the
[Pr`2] prompt will
not appear.
˜
NOTE:
For information on
input 1 [`In1] and
input 2 [`In2]
ranges, refer to
Chapter 4.
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
DISPLAY
SERIES 988
MODE
AUTO
MAN
WATLOW Series 988 User’s Manual 4.1
Setup Menus, Chapter 4

Navigating the Setup Menus

To reach the Setup Menus, begin in the Display Loop and press both the Up-
arrow > and Down-arrow < keys for three seconds. The Setup Menu
prompt [`SEt] will appear in the lower display, and the Input Menu prompt
[InPt] will appear in the upper display. The four Setup Menus are: Input
[InPt]; Output [OtPt]; Global [GLbL]; and Communications [COM]. Use the
Up-arrow > or Down-arrow < key to select a menu and the Mode key µ
to step through a menu. The Communications Menu appears only on units
equipped with the data communications option.
You will not see every prompt in any of these menus. The unit’s configuration
and model number determine which prompts appear. After stepping through
each menu, the Series 988 returns to the Setup Menu prompt [`SEt]. Use
the Up-arrow > and Down-arrow < keys to select the next menu, or use
the Mode key µ to advance through the same menu again. To move back-
wards through the menu hold the Mode key µ down and press the Up-
arrow key >. Use the Up-arrow > or Down-arrow < key to change the
prompt setting.
Refer to the Appendix for model number options. For information about
communications and the communications prompts, refer to the supple-
mental manual Data Communications with the Watlow Series 988 Family of
Controllers.

Chapter 4 The Setup Menus

Figure 4.1 -
Navigating the
Setup Menus.
Input
Menu
p. 4.2
Output
Menu
p. 4.18
Global
Menu
p. 4.34
Communications
Menu
p. 4.44
[Inpt]
[`Set]
[`Set] [`Set]
[`Set]
[OtPt] [gLbL] [COm]
Begin in the Display Loop, and press the Up-arrow
> and Down-arrow < keys simultaneously to
reach the Setup Menus.
Press the Up-arrow key > to select one of the
Setup Menus.
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
DISPLAY
SERIES 988
MODE
AUTO
MAN
˜
NOTE:
The lockout DIP
switch hides the
Setup Menus. See
Chapter 1.
˜
NOTE:
Press the Display
key to return to
the Display Loop
from any point in
any menu.
NOTE:
When navigating
through menus,
outputs will be dis-
abled.
4.2 WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
MODE
*Slidewire Hysteresis
*Hunt
*Linearization 2
*Software Filter 2
*RTD Calibration Curve 2
*Calibration Offset 2
*Learn High
*Learn Low
*Range High 2
*Range Low 2
*Decimal 2
*Remote Set Point
*Input 2
*Linearization 1
Software Filter 1
*RTD Calibration Curve 1
Range High 1
Calibration Offset 1
Setup Prompt
Input 1
*Decimal 1
Range Low 1
Enter your settings,
from the controller's
upper display.
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
Input 2 (p. 4.9)
Input 1 (p. 4.3)
Slidewire (p. 4.16)
[Inpt]
[`Set]
[`In1]
[deC1]
[`rL1]
[`rH1]
[CAL1]
[rtd1]
[Ftr1]
[Lin1]
[`ln2]
[`rSp]
[deC2]
[`RL2]
[`RH2]
[LrnL]
[LrnH]
[CAL2]
[rtd2]
[Ftr2]
[Lin2]
[Hunt]
[SHYS]
Figure 4.2 -
The Input Menu.
Setup-Input
Select the Input Menu, then press
the Mode key µ to step through the
prompts.
TL
W
W
A
PROCESS
L1 L2 L3 L4
DEV
% OUT
DISPLAY
SERIES 988
MODE
AUTO
MAN
Press the Up-arrow key > or the
Down-arrow key < to select one of
the prompt values.
[Ftr1] [Ftr1] [Ftr1] [Ftr1]
[```0] [```1] [```2] [``60]
[root]
[Lin1]
[``no]
[Lin1]
*Prompts may not appear,
depending on controller
configuration.

Reaching the Input Menu

Input Prompts
When you are in the Setup menus, the Series 988 displays the menu selec-
tion ( [InPt], [OtPt], [GLbL] or [COM] ) in the upper display, and [`SEt] in
the lower display.
The Up-arrow > or Down-arrow key < selects another menu. Press the
Mode key µ to display the prompt in the lower display and its value in the
upper display. Use the Up-arrow > or Down-arrow < key to change the
value in the upper display. The new value will not take effect until after a
five-second delay or until you press the Mode key µ.
Input 1
Select sensor type for input 1. This selection must match the sensor type
connected to terminals 8, 9 and 10. See Appendix for more information
about sensors.
Changing the value of [`In1] changes all other prompts to the factory
default values, except the Communications and Lockout menus, the
[`C_F] prompt in the Global Menu and the [`dFL] prompt in the
Calibration Menu. If you change the value, the default warning [dFLt]
will flash in the upper display.
Changes do not take effect automatically after five seconds; you must
press the Mode key µ to enter the sensor type change and advance to
the next prompt.
[`In1] This prompt always appears.
If Default
↓ ↓
98_ _-1_ _ _-_ _ _ _
no DIP J K T N E W5 W3 Pt2 0-50mV
[```J] [```H] [```t] [```n] [```E] [```C] [```d] [`Pt2] [0-50]
thermocouple [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1]
only
98_ _-2_ _ _-_ _ _ _
Input 1 DIP J K T N E W5 W3 Pt2 0-50mV
[```J] [```H] [```t] [```n] [```E] [```C] [```d] [`Pt2] [0-50]
[`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1]
thermocouple
Input 1 DIP RSB
[```r] [```S] [```b]
[`In1] [`In1] [`In1]
thermocouple
O
N
123
O
N
123
WATLOW Series 988 User’s Manual 4.3
Setup Menus, Chapter 4
Setup-Input
˜
NOTE:
Decimal points may
not always be in the
position specified
below depending on
the the settings in
the Decimal 1
[dEC1] and Decimal
2 [dEC2] parame-
ters in the Input
Menu.
ç
CAUTION:
Changing the value
of [`In1] changes
most other prompts
to the factory
default values.
Document all set-
tings before chang-
ing sensor type.
Verify the correct
sensor type before
making a change.
Failure to follow
this guideline could
result in damage to
equipment or prop-
erty. Document all
settings before
changing sensor
type.
[`In1]
Input 1 continued
on next page.
[`In1]
4.4 WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
[`In1]
Input 1 continued
from previous
page.
Setup-Input
If Default
↓↓
Input 1 DIP RTD RTD(0.1°)
[`rtd] [`r†d]
[`In1] [`In1]
RTD
Input 1 DIP 4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
[4-20] [0-20] [`0-5] [`1-5] [0-10]
[`In1] [`In1] [`In1] [`In1] [`In1]
process
Decimal 1
Select the decimal point location for process type input 1 data. This
prompt, in conjunction with the Range Low and Range High prompts,
allows you to format and limit units of measure for process 1.
• All prompts with units of measure related to input 1 will display in the
selected decimal format.
• This affects propbands, alarm set points, process set points, calibration
offsets, deadbands and ranges.
[dEC1] This prompt appears only if you have set input 1 [`In1] to a
process input or to a thermocouple input set to 0-50mV.
Default
[```)] [``)0] [`)00] [)000]
[dEC1] [DEC1] [dEC1] [dEC1]
O
N
123
O
N
123
[dEC1]