VICOR IAM4820C2N, IAM4820C2S, IAM4820C31, IAM4820C32, IAM4820C3S Datasheet

...
0 (0)

45 Data Sheet

IAM48TM

Features

Wide input voltage range

High surge withstand

97% Efficiency

Input reverse polarity protection

On/Off control feature

MicroMod Package

Primary Function

Inrush current limiting

Input transient protection

Products Highlights

The 2nd Generation IAM48 is a component level, DC input front-end designed to occupy minimum board space while providing maximum transient protection for today’s sophisticated electrical systems. The IAM48, in combination with Vicor’s 48V input 2nd Generation DC-DC converters, provides a highly efficient, high density power system with outputs from 1 to 100Vdc.

When the IAM48 is used with the Vicor FM48-FiltMod, the combination meets the conducted EMI specifications of Telcordia, FCC and European Norms.

Compatible Products

FM48-FiltMod

2nd Generation 48V input DC-DC converters

Part Numbers

IAM 48 10 C 1 1

Output

 

 

 

 

 

Current

 

 

 

 

 

10=10Amp

 

 

 

 

 

20=20Amp

 

 

 

 

Pin Style

 

 

 

Baseplate

 

1= Short Pin

 

 

 

Product Grade

 

1=Slotted

 

C=-20° to 100°C

 

 

2= Long Pin

 

2=Threaded

 

S= Short ModuMate

T=-40° to 100°C

 

3=Thru-hole

 

N= Long ModuMate

 

 

 

 

 

 

Input Power

Conditioning Module

Shown actual size: 2.28 x 1.45 x 0.5 in 57,9 x 36,8 x 12,7 mm

Absolute Maximum Rating

Parameter

Rating

Unit

Notes

+In to –In

80

Vdc

Continuous

+In to –In

100

V

100ms

+Out to –Out

75

Vdc

Continuous

Mounting torque

5(0.57)

in-lbs

6 each, #4-40 or M3

Pin soldering temperature

500 (260)

°F(°C)

<5 sec; wave solder

Pin soldering temperature

750 (390)

°F(°C)

<7 sec; hand solder

Storage temperature C–,T–Grade

-40 to +125

°C

 

Operating temperature C–Grade

-20 to +100

°C

Baseplate

Operating temperature T–Grade

-40 to +100

°C

Baseplate

 

 

 

 

IAM48 Specifications

(typical at TBP = 25°C, nominal line, unless otherwise specified)

Parameter

Min

Typ

Max

Remarks

Input voltage

36Vdc

48Vdc

76Vdc

Continuous

Inrush limiting

 

 

14mA/µF

6A with 330µF capacitor (See Fig 1)

Safety approvals

UL 1950, CSA 22.2-950, EN 60950

 

Transient immunity

 

 

 

 

Telcordia-GR-499-CORE Section 132

200V

1µsec duration

ETS 300 386-1 Class 2

 

 

200V

5.0µsec rise time, 50µsec duration surge

 

 

 

250V

1-100 nsec burst

 

 

 

 

When used with Vicor

 

 

 

 

FM-48 filter module

Dielectric withstand

1,500Vrms

 

 

Input/Output to base

Output current

 

 

 

Delivered current to any

IAM4810C12

 

 

10A

combination of Vicor’s 2nd Generation

IAM4820C12

 

 

20A

48Vin DC-DC converters

Efficiency

 

97%

 

Internal voltage drop is 1.1V max.

 

 

@ 20A, 100°C baseplate

 

 

 

 

ON/OFF control

 

 

 

 

ENABLE(ON)

0.0Vdc

 

1.0Vdc

Referenced to –Vout.

DISABLE(OFF)

3.5Vdc

 

5.0Vdc

100KΩ internal pull-up resistor

Reverse polarity protection

 

 

No damage to module, external

 

 

fuse required

 

 

 

 

External capacitance

 

 

 

See Fig 3

IAM4810C12

10µF

 

150µF

100V

IAM4820C12

100µF

 

330µF

100V

Weight

1.7 ounces (50 grams)

 

Warranty

 

2 years

 

 

 

 

 

 

 

Set your site on VICOR at www.vicorpower.com

VICOR IAM4820C2N, IAM4820C2S, IAM4820C31, IAM4820C32, IAM4820C3S Datasheet

Typical Inrush Limiting and Transient Immunity Characteristics

Inrush Limiting

 

 

 

Transient Immunity

 

Tek Stop: Single Seq. 5.00MS/s

 

Tek Run: 10.0MS/s

 

[ T

 

]

 

 

Ch1 Zoom:

1.0X Vert 0.005X Horz

 

 

 

 

INPUT CURRENT

 

 

@ 200.0V

 

 

INPUT TRANSIENT

 

INPUT VOLTAGE

 

 

 

Ch1=Input

 

 

 

 

 

 

 

 

 

 

Ch2=Output

 

 

 

 

Ch1=Vdc in

 

4

 

 

 

Ch2=Vdc out

 

 

 

 

 

Ch3=Idc in

 

 

 

 

 

@0.2A/mV

 

 

OUTPUT VOLTAGE

 

OUTPUT VOLTAGE

 

 

 

48V offset

 

 

 

 

2

 

 

 

 

 

2

 

 

 

Ch1 25.0V Ch2 25.0V M5.00 s Ch4

 

Ch1 10.0 V Ch2

10.0 V

M2.00ms Ch1

31.8 V

8.2A

Ch4

10.0mVΩ

 

 

 

 

Figure 1—Inrush current with 330µF

 

Figure 2— Output response to a transient on the

on the IAM4820C12.

 

 

 

48V input of a FM48-FiltMod/IAM48 combination.

Typical Transient, Surge Protection and Filtering Solution

Note: The IAM48 is shown in the on state.

To disable, open the connection to pin 3.

–IN

4

– IN

 

– OUT

5

7

– IN

– OUT

1

 

3

NC

FM48

GND

 

6

NC

IAM48IA 2 NC

2

 

 

6

 

 

2

NC

 

 

Off/On

3

+IN

1

+IN

 

+ OUT

7

5

+ IN

+OUT

4

Figure 3

–IN –OUT

PR

2nd Generation

–S

 

48Vdc Input

SC

PC

DC-DC Converters

+S

+IN

 

+OUT

Set your site on VICOR at www.vicorpower.com

Loading...