Veris PX Installation Instructions

0 (0)
Veris PX Installation Instructions

Environmental Sensors

TM

INSTALLATION GUIDE

PX Series

NOTICE

Thisproductisnotintendedforlifeorsafetyapplications.

Donotinstallthisproductinhazardousorclassifiedlocations.

Readandunderstandtheinstructionsbeforeinstalling thisproduct.

Turno allpowersupplyingequipmentbeforeworkingonit.

Theinstallerisresponsibleforconformancetoallapplicablecodes.

Product Identification

Enclosure Local Display

 

NIST

Range

Response

PX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D =

Duct

L = LCD Display

N =

NIST

01

= 0-1"W.C./0-250Pa

S =

Selectable

P = Panel

X = No Display

X = None

02

= 0-10"W.C./0-2.500kPa

F = Selectable

Local Display

 

NIST

Range

Response

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PXU

 

 

 

 

 

 

 

 

05

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L = LCD Display

N = NIST

= 0-10”/0-2.500kPa = Selectable

X = No Display

X = None

 

 

 

 

 

 

 

 

PX Series

Digital Pressure Transducer

Dry Media

Installer’s Specifications

Media Compatibility

Dry air or inert gas

Input Power

12-30VDC, or 24VAC nominal; 2-wire: 20mA max.; 3-wire: 30mA max.

Output

Field-selectable: 2-wire, loop-powered 4-20mA

 

 

(DC only, clipped and capped), or 3-wire 0-5V/0-10V*

Pressure Ranges:

 

 

 

PX: 01

Unidirectional: 0.1/0.25/0.5/1.0” W.C. F.S., switch selectable

 

 

Bidirectional: ±0.1/±0.25/±0.5/±1.0” W.C. F.S., switch selectable

 

 

Unidirectional: 25 Pa/50 Pa/100 Pa/250 Pa, F.S., switch selectable

 

 

Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, F.S., switch selectable

 

PX: 02

Unidirectional: 1.0/2.5/5.0/10” W.C. F.S., switch selectable

 

 

 

Bidirectional: ±1.0/±2.5/±5.0/±10” W.C. F.S., switch selectable

 

Unidirectional: 0.250 kPa/0.500 kPa/1.000 kPa/2.500 kPa, F.S., switch selectable

 

Bidirectional: ±0.250 kPa/±0.500kPa/±1.000 kPa/±2.500 kPa, F.S., switch selectable

 

PXU: 05

Unidirectional: 0.1/0.25/0.5/1.0/2.5/5/10” W.C. F.S., switch selectable

 

 

 

Bidirectional: ±0.1/0.25/0.5/1.0/2.5/5/10” W.C. F.S., switch selectable

 

Unidirectional: 25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa F.S., switch selectable

 

Bidirectional: ±25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa F.S., switch selectable

Response Time

Standard: T95 in 20 sec, Fast: T95 in 2 sec, jumper selectable

 

Mode

Unidirectional or bidirectional, jumper selectable

 

Display (option)

Signed 3-1/2 digit LCD, indicates pressure, overrange indicator

 

Proof Pressure

3 psid (20.6kPa)

 

Burst Pressure

5 psid (34.5kPa)

 

Accuracy

±1% F.S. of selected range (combined linearity and hysteresis)

 

Temperature Effect

1” (250Pa) models: 0.05%/°C; 10” (2.5kPa) models: 0.01%/°C

 

 

 

(Relative to 25°C) 0° to 50°C (32° to 122°F)

Zero Drift (1-year)

1” (250Pa) models: 2.0% max.; 10” (2.5kPa) models: 0.5% max.

 

Zero Adjust

Pushbutton auto-zero and digital input (2-pos terminal block)

 

Operating Environment

0°- 60°C (32° to 140°F); 0 to 90% RH non-condensing

 

Fittings

Brass barb; 0.24” (6.1mm) o.d.

 

Physical

UL 94 V-O Fire Retardant ABS

 

EMC Conformance: EN 61000-6-3:2007 and A1:2011 Class B, EN 61000-6-1:2007

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

* Minimum input voltage for 4-20 mA operation: 250 Ω loop = 13 VDC; 500 Ω loop = 19 VDC

Dimensions

2.2" (55 mm)

3.3" (84 mm)

 

Inch H2O

 

 

Di erential Pressure

Z103591-0A

 

Transmitter

 

 

 

 

4.5" (114 mm)

quick install

1.Plan the installation. Panel or duct mount?

2.For duct mounting, thread the probe into the rear of the device housing.

3.Configure the internal tubing for the selected installation method.

4.Mount the housing vertically.

5.Attach pilot tubing.

8.0" (202 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Z205213-0D

 

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

07122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.