Level and Pressure
Operating Instructions
Hydrostatic pressure transmitters D85
p
Contents
Contents
|
Safety information ........................................................................ |
2 |
|
|
Note Ex area ................................................................................ |
2 |
|
1 |
Product description |
|
|
|
1.1 |
Function and configuration .................................................. |
4 |
|
1.2 |
Electronics version without adjustment .............................. |
5 |
|
1.3 |
Electronics version with integrated adjustment |
|
|
|
in connection housing .......................................................... |
7 |
|
1.4 |
Electronics for connection to VEGADIS 12 ........................ |
8 |
|
1.5 |
Technical data ....................................................................... |
9 |
|
1.6 |
Approvals and certificates ................................................ |
13 |
|
1.7 |
Dimensions ......................................................................... |
14 |
2 |
Mounting |
|
|
|
2.1 |
Mounting instructions ......................................................... |
18 |
|
2.2 |
Compensation of the atmospheric pressure ................... |
18 |
Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules.
For safety and warranty reasons, any internal work on the instruments, apart from that involved in normal installation and electrical connection, must be carried out only by qualified VEGA personnel.
Please note the attached safety instructions containing important information on installation and operation in Ex areas.
These safety instructions are part of the operating instructions and come with the Ex approved instruments.
2 |
Pressure transmitter D85 |
Contents
3 Electrical connection |
|
|
3.1 |
Connection instructions ..................................................... |
19 |
3.2 |
Terminal assignment .......................................................... |
20 |
3.3 |
Connection to external connection housing |
|
|
VEGABOX 01 ..................................................................... |
21 |
3.4 |
Connection examples ........................................................ |
22 |
4 |
Setup |
|
|
|
4.1 |
Adjustment structure ......................................................... |
23 |
|
4.2 |
Sensor without adjustment ................................................ |
24 |
|
4.3 |
Sensor with adjustment insert, adjustment |
|
|
|
in the sensor ....................................................................... |
24 |
|
4.4 |
Setup with HART® handheld ............................................. |
26 |
|
5.5 |
Adjustment with PC directly on the sensor ...................... |
32 |
6 |
Diagnostics ............................................................................... |
40 |
|
7 |
Instrument modification |
|
|
|
7.1 |
Retrofitting the adjustment insert ...................................... |
41 |
Pressure transmitter D85 |
3 |
Product description
1.1 Function and configuration |
Output signal |
The pressure transmitter D85 is an efficient instrument for hydrostatic level measurement. A dry metallic-capacitive measuring cell is used as pressure sensor element.
Pressure transmitter D85
Measuring cell: dry, metallic-capacitive Diaphragm: flush, stainless steel (Duratherm 600)
Series: flanged version
Standard application: All kind of level measurements, best suited for food processing and pharmaceutical industries and for product temperatures up to 200°C
The hydrostatic pressure of the medium effects a capacitance change in the measuring cell. This capacitance change is detected by an ASIC (Application Specific Integrated Circuit) and converted into a pressure-proportional signal by the integrated electronic module with microcontroller. Precise, high-resolution digital processing of measurement data ensures excellent technical data.
To improve reliability, the functionality of important electronic components is continuously checked, and internal parameters such as sensor value, temperature and operating voltage are closely monitored.
The output signal is transferred as a digital or analogue signal from the pressure transmitter to the signal conditioning instrument:
•analogue output signal
-unstandardised (in conjunction with VEGA signal conditioning instrument)
-4 … 20 mA standardised
•digital output signal (VBUS) for connection to a digital VEGA signal conditioning instrument (VEGAMET 514V, 515V or VEGALOG 571)
4 |
Pressure transmitter D85 |
Product description
Electronics version A:
Pressure transmitter for connection to VEGA signal conditioning instruments
VEGAMET VEGALOG
e.g. IP 66
VEGABOX 01
Zum Anschluss an
For connection to Druckmessumformer mit
pressure transmitters with analogem Ausgangssignal
analog output
VEGAMET VEGALOG
e.g. IP 67
Electronics version B:
Pressure transmitter for connection to VEGA signal conditioning instruments (digital
transmission VBUS)
VEGAMET VEGALOG
e.g. IP 66
VEGABOX 01
Zum Anschluss an
For connection to Druckmessumformer mit
pressure transmitters with analogem Ausgangssignal
analog output
VEGAMET VEGALOG
e.g. IP 67
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pressure transmitter D85 |
5 |
Product description
Electronics version I:
Pressure transmitter 4 … 20 mA, HART® , VVO
4-20mA
1 2 3 4 5
+-
PLC/DCS
250 W
e.g. IP 66
|
VEGABOX 01 |
|
Zum Anschluss an |
|
For connection to |
4-20mA |
Druckmessumformer mit |
pressure transmitters with |
|
analogem Ausgangssignal |
|
|
analog output |
1 2 3 4 5
+-
PLC/DCS
250 W
e.g. IP 67
VVO
HART® handheld
6 |
Pressure transmitter D85 |
Product description
Electronics version K:
Pressure transmitter 4 … 20 mA, HART® , VVO adjustable
1 2 3 4 5
+-
PLC/DCS
e.g. IP 66 |
250 W |
|
VEGABOX 01 |
Zum Anschluss an
For connection to Druckmessumformer mit
pressure transmitters with analogem Ausgangssignal analog output
1 2 3 4 5
+-
PLC/DCS
250 W
e.g. IP 67
VVO
HART® handheld
Pressure transmitter D85 |
7 |
Product description
1.4 Electronics for connection to VEGADIS 12 |
|
Electronics version L: |
|
Pressure transmitter 4 … 20 mA, HART® , VVO |
VEGADIS 12 |
|
Zum Anschluß an
VEGADIS 12
1 2 3 4 5
+-
|
|
PLC/ |
e.g. IP 66 |
250 W |
DCS |
|
||
|
|
|
|
VEGADIS 12 |
|
Zum Anschluß an
VEGADIS 12
1 2 3 4 5
+-
PLC/
DCS
250 W
e.g. IP 67
VVO
HART® handheld
8 |
Pressure transmitter D85 |
Product description
Nominal meas. range (gauge pressure) |
Gauge pr. resistance |
Low pr. resistance |
0…0.1 bar / 0…10 kPa |
2.5 bar / 250 kPa |
-0.1 bar / -10 kPa |
0…0.2 bar / 0…20 kPa |
5 bar / 500 kPa |
-0.2 bar / -20 kPa |
0…0.4 bar / 0…40 kPa |
10 bar / 1 000 kPa |
-0.4 bar / -40 kPa |
0…1.0 bar / 0…100 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
0…2.5 bar / 0…250 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
0…5.0 bar / 0…500 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
0…10.0 bar / 0…1 000 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
|
|
|
0…20.0 bar / 0…2 000 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
-0.5…+0.5 bar / -50…+50 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
-1.0…0.0 bar / -100…0 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
-1.0…+1.5 bar / -100…+150 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
|
|
|
-1.0…+4.0 bar / -100…+400 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
-1.0…+10.0 bar / -100…+1 000 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
-1.0…+20.0 bar / -100…+2 000 kPa |
25 bar / 2 500 kPa |
-1.0 bar / -100 kPa |
Mechanical data
Materials, wetted parts
Process connection |
stainless steel 1.4571, 1.4435 |
|
Diaphragm |
Duratherm 600 |
|
Materials, non-wetted parts |
|
|
Housing |
Alu (sea-water resistant) Pe-powder coated, |
|
|
|
stainless steel 1.4571 |
Cooling body (option) |
Alu eloxated |
|
Heat screen (option) |
Alu eloxated |
|
External connection housing |
high resistance plastic PBT (Polyester) |
|
Ground terminal |
stainless steel 1.4305 |
|
Window of the display module |
safety glass |
|
Weights |
|
|
Basic weight without housing |
approx. 1.6 kg |
|
External housing |
approx. 400 g |
|
Adjustment and display elements |
|
|
Pressure transmitter |
|
|
- |
terminal insert |
without adjustment elements |
- |
adjustment insert |
2 keys, 1 rotary switch |
Pressure transmitter D85 |
9 |
|
|
|
|
Product description |
Electrical data |
|
|
||
Adjustment ranges |
|
|
||
Zero |
adjustable from -20 … +95 % of nominal range |
|||
Span |
adjustable from 3.3 … 120 % of nominal range |
|||
Supply and signal circuit (analogue transmission, 4 … 20 mA), |
||||
electronics version A, C, I and K |
|
|
||
Supply voltage |
12 … 36 V DC |
|||
permissible residual ripple |
USS |
£ 1 V |
||
- |
at 100 Hz … 10 kHz |
USS |
£ 10 mV |
|
Output signal |
|
|
||
- |
terminal insert |
- analogue transmission (not standardised) |
||
|
|
|
- 4 … 20 mA |
|
- |
adjustment insert |
4 … 20 mA (adjustable) |
||
Current limitation |
approx. 22 mA |
|||
Fault signal |
22 mA (3.6 mA) |
|||
Integration time |
0 … 10 s |
|||
Rise time |
70 ms (ti = 0 sec; 0 … 63 %) |
|||
Max. permissible load |
see load diagram: |
Load in W
900 |
|
|
|
|
|
600 |
|
|
|
|
|
300 |
|
|
|
|
|
|
|
|
|
|
Supply voltage |
12 |
18 |
24 |
30 |
36 |
in V |
|
10 |
Pressure transmitter D85 |
Product description
Supply and signal circuit (analogue transmission, 4 … 20 mA), additional data for electronics version L
Supply voltage for pressure transmitters in conjunction with VEGADIS 12
-without display
-with display Max. input current
Current signal range Max. permissible load
12 … 36 V DC
17 … 36 V DC
150mA
3.5… 22 mA
see load diagram:
Load diagram with display
Load in W
700 |
|
|
|
500 |
|
|
|
300 |
|
|
|
100 |
|
|
Supply voltage |
|
|
in V |
|
|
|
|
|
18 |
24 |
30 |
36 |
Supply and signal circuit on VEGA signal conditioning instruments (digital signal transmission VBUS), additional data for electronics version B
Supply voltage |
25 … 36 V DC, from VEGAMET (VBUS) or |
|
|
|
from VEGALOG 571 with EV input card |
Data transmission |
digital (VBUS) |
|
Connection cable |
2-wire screened |
|
Cable length |
max. 1000 m |
|
Integrated overvoltage protection (option) |
||
Nominal response DC voltage |
|
|
- |
protective diode |
40 V |
- |
gas separator |
650 V |
Nominal leakage current |
|
|
- |
gas separator |
20 kA |
Connection cables |
|
|
Cable entry |
|
|
- |
housing |
2 x M20x1.5 (for cable ø 5…9mm or 9…12mm) |
- |
external connection housing |
2 x M20x1.5 (for cable ø 5…9mm or 9…12mm) |
Screw terminals |
|
|
- |
sensor |
for wire cross-sections of up to 2.5 mm2 |
- |
external connection housing |
for wire cross-sections of up to 2.5 mm2 |
Pressure transmitter D85 |
11 |
Product description
Protective measures 1)
Protection |
IP 66, IP 67, IP 68 |
VEGABOX 01 |
IP 66 and IP 67 |
Protection class |
III |
Overvoltage category |
III |
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770) |
|
|
- |
temperature |
15°C … 30°C |
- |
humidity |
45 % … 75 % |
- |
air pressure |
86 kPa … 106 kPa |
Determination of characteristics |
limit point adjustment acc. to DIN 16 086 |
|
Characteristics |
linear |
|
Deviation in characteristics |
|
|
- |
Turn Down 1 : 1 |
< 0.25 % with accuracy class 0.25 |
|
|
< 0.1 % with accuracy class 0.1 |
- |
Turn Down up to 1 : 5 |
typ. < 0.3 % with accuracy class 0.25 |
|
|
typ. < 0.1 % with accuracy class 0.1 |
- |
Turn Down up to 1 : 10 |
typ. < 0.4 % with accuracy class 0.25 |
|
|
typ. < 0.2 % with accuracy class 0.1 |
Hysteresis |
< 0.05 % |
|
Repeatability |
< 0.05 % |
|
Influence of the ambient temperature |
|
|
Average temperature coefficient |
|
|
of the zero signal 2) 3) |
|
|
- |
Turn Down 1 : 1 |
< 0.15 %/10 K with accuracy class 0.25 |
|
|
< 0.05 %/10 K with accuracy class 0.1 |
- |
Turn Down up to 1 : 5 |
typ. < 0.225 %/10 K with accuracy class 0.25 |
|
|
typ. < 0.075 %/10 K with accuracy class 0.1 |
- |
Turn Down up to 1 : 10 |
typ. < 0.3 %/10 K with accuracy class 0.25 |
|
|
typ. < 0.1 %/10 K with accuracy class 0.1 |
Long-term stability |
|
|
Long-term stability of the zero signal 4) |
< 0.25 % per 2 years |
|
Other actuating variables |
|
|
Calibration position |
upright, diaphragm points downwards |
|
Influence of the installation position |
< 5 mbar |
|
Vibration resistance |
mechanical vibrations with 4 g and |
|
|
|
5 … 100 Hz, tested acc. to the regulations of |
|
|
German Lloyd GL-characteristics 2 |
1)Maintaining the housing protection IP 66 or IP 67 requires the use of a seal that correctly fits the cable in the cable entry. If the supplied seal does not fit, a suitable seal must be provided by the customer.
2)Relating to the nominal range.
3)In compensated temperature range of 0°C … +80°C, reference temperature 20°C.
4)Acc. to IEC 770, item 6.3.2 relating to the nominal range.
12 |
Pressure transmitter D85 |
Product description
Operating conditions
Ambient conditions
Ambient temperature |
-40°C … +85°C |
|
- |
with indicating module |
-10°C … +60°C |
Storage and transport temperature |
-50°C … +100°C |
|
Product temperature |
-40°C … +100°C |
|
- |
with cooling body |
-40°C … +150°C |
- |
with cooling body and additional |
|
|
heat shield |
-40°C … +200°C |
Approvals
-Ex Zone 2
-CENELEC EEx ia IIC
-ATEX II 1G EEx ia IIC
If the use of approved instruments is required for certain applications, the appropriate official documents (test reports, test certificates and conformity certificates) must be observed. These are supplied with the respective instrument.
CE conformity
D85 pressure transmitters meet the requirements of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards:
EMC |
Emission |
EN 50 081 - 1: 1992 |
|
Susceptibility |
EN 50 082 - 2: 1995 |
NSR |
|
EN 61 010: 1993 |
NAMUR regulations
Full compliance with the NAMUR regulations NE21 and NE 43.
Pressure transmitter D85 |
13 |
Product description
Housings
ø 76 |
67
ø 75 |
91 |
ø 41,6
46 |
63 |
93 |
ø 41,6 |
ø 41,6 |
46 |
90 |
14 |
Pressure transmitter D85 |