United States Stove 1537M, 1557M User Manual

0 (0)
United States Stove 1537M, 1557M User Manual

Models:

1537M

1557M

OWNERS MANUAL

SOLID

FUEL

WARM AIR FURNACE

FOR PARALLEL INSTALLATION WITH EXISTING FORCED AIR-GAS OR OIL FIRED FURNACE.

FOR INSTALLATION AS A CENTRAL FURNACE

THE HOTBLAST FURNACE HAS BEEN APPROVED FOR U.S. INSTALLATIONS ONLY.

CAUTION:

READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING THE INSTALLATION OR OPERATING THE FURNACE

IMPROPER INSTALLATION MAY VOID

YOUR WARRANTY

DO NOT USE THIS FURNACE IN A MOBILE HOME OR TRAILER

 

 

 

 

TAT

 

 

 

 

 

 

DS ESS

 

 

 

I

E

 

T

 

 

 

 

 

 

O

 

T

 

 

 

 

 

 

USSC

N

 

 

 

 

 

V

 

 

 

 

 

E

U

 

 

 

 

 

 

 

 

 

 

C

Y

 

 

 

 

 

 

OMPAN

 

 

 

UNITED STATES STOVE COMPANY

227 Industrial Park Road

P.O.Box 151

South Pittsburg, TN 37380

(423) 837-2100

 

T

ER

T

 

I

 

 

E

K

N

 

 

 

a

 

 

 

e

US

W

r

 

s

y

 

 

 

 

 

 

n

e

 

 

 

 

 

 

ockH

r

 

 

 

 

 

 

 

 

 

 

1

851559D

CONGRATULATIONS!

You've purchased one of America's Finest Wood and Coal Burning Furnaces. By heating with wood and coal you're helping CONSERVE AMERICA'S ENERGY! Wood is our Renewable Energy Resource. Please do your part to preserve our wood supply. Plant at least one tree each year. Future generations will thank you.

NOTE: YOUR UNIT MUST BE INSTALLED BY A

QUALIFIED FURNACE INSTALLER.

TOOLS AND MATERIALS NEEDED

TOOLS

MATERIAL

Pencil

6" Pipe, 6" Elbow, Collar and Thimble;

6 Foot Folding Rule or Tape

as required (24 gauge min.)

Tin Snips

1/2" Sheet Metal Screws

Drill, Hand or Electric

6" Inside diameter UL Listed Residential

Drill Bit- 1/8" Dia.

Type 103HT or Building Heating Appliance

(For Sheet Metal Screws)

Chimney or existing masonry chimney w/ Liner

Screw Driver (Blade-Type)

Electrical Wiring

Gloves

6" Draft Regulator

Sabre Saw

1/2" Conduit (Conduit Connectors)

5/16" Nut Driver or

Furnace Cement (Manufacturer

5/16" Socket w/Ratchet

Recommends: Rutland Black-Code 78

 

or Equivalent)

 

Plenum and Duct work as required.

2

CAUTION LABELS

Your Furnace has the following labels. Read and Obey all labels.

DANGER: RISK OF FIRE OR EXPLOSION.

DO NOT burn garbage, gasoline, drain oil, or other flammable liquids.

WARNING: FIRE HAZARD.

DO NOT operate with fire draft exceeding .06 inches w.c.

DO NOT operate with fuel loading or ash removal doors open.

DO NOT store fuels, paints, thinners, flammable liquids, or other highly volatile substances in the furnace room.

CAUTION: HOT SURFACES

Keep children away.

Do not touch during operation.

CAUTION!

INSPECT FLUE PIPES, FLUE PIPE JOINTS AND FLUE PIPE SEALS REGULARLY TO ENSURE THAT SMOKE AND FLUE GASES ARE NOT DRAWN INTO, AND CIRCULATED BY, THE AIR CIRCULATION SYSTEM.

CAUTION!

CLEANOUT OF THE HEAT EXCHANGER, FLUE PIPE, CHIMNEY, AND DRAFT INDUCER (IF USED), IS ESPECIALLY IMPORTANT AT THE END OF THE HEATINGSEASONTOMINIMIZECORROSIONDURINGTHESUMMERMONTHS, CAUSED BY ACCUMULATED ASH.

SAFETY NOTICE: If this heater is not properly installed, a house fire may result. For your safety, follow the installation directions. Contact local building or fire officials about restrictions and installation inspection requirements in your area.

3

RULES FOR SAFE INSTALLATION AND OPERATION

Read these rules and the instructions carefully. Failure to follow them will cause a hazard that could result in death, serious bodily injury, and/or property damage.

1.Check your local codes. The installation must comply with their rulings.

2.Do not install this furnace in a mobile home or trailer.

3.Always connect this furnace to a chimney and vent to the outside. Never vent to another room or inside a building.

4.Do not connect this furnace to an aluminum Type B gas vent. This is not safe and is prohibited by the National Fire Protection Association Code. This furnace requires a masonry or UL Listed Factory Built Chimney for residential Type 103 HT or Building Heating

Appliance Chimney. Use a 6" diameter chimney or larger, that is high enough to give a good draft. (See page 7)

5.Be sure that if a masonry chimney is used, it is safely constructed, lined and in good repair. Have the chimney inspected by the Fire Department or an inspector.

6.Inspect chimney connector and chimney before and frequently during the heating season for any deposit of creosote or soot which must be removed (See Chimney Maintenance, page 15).

7.Provide air for combustion into the room where the furnace is located. If the intake is not in the same room, air must have free access to the room.

8.CAST IRON PARTS MUST BE "SEASONED" TO AVOID CRACKING, BUILD ONLY

SMALL FIRES ON FIRST USE.

9.To prevent injury, do not allow anyone to use this furnace who is unfamiliar with the correct operation of the furnace.

10.For further information on using your furnace safely, obtain a copy of the National Fire

Protection Association (NFPA) publication "Chimney's, Fireplaces and Solid Fuel Burning Appliances" NFPA 211. The address of the NFPA is Batterymarch Park, Quincy, MA 02269.

11.Keep the ashpit section free of excess ashes. Do not allow ashes to stack higher than the sides of the ash pan.

12.DISPOSAL OF ASHESPlace ashes in a metal container with a tight fitting lid. Keep the closed container on a noncombustible floor or on the ground, well away from all combustible materials. Keep the ashes in the closed container until all cinders have thoroughly cooled. The ashes may be buried in the ground or picked up by a refuse collector.

13.CAUTIONThe special paints used on your furnace may give off some smoke while they are curing during first few fires., Build small fires at first. The metal used in construction of the furnace and duct work has a light coating of oil. This could give off smoke and/or odor from registers when furnace is used for the first time. This should disappear after a short period of time. Once this burn-off has occurred, it should not reoccur.

14.CARING FOR PAINTED PARTSThis furnace has a painted outside jacket, which is durable, but it will not stand rough handling or abuse. When installing your furnace, use care in handling. Clean with soap and warm water when furnace in not hot. DO NOT use any acids or scouring soap, as these wear and dull the finish. DISCOLORATION WILL OCCUR

IF THE FURNACE IS OVERHEATED. FOLLOW OPERATING INSTRUCTIONS CAREFULLY.

15.Keep the feed and ash doors closed at all times except while tending the furnace.

Your Furnace is designed to be installed in a parallel air flow arrangement with a gas or oil-fired forced air upflow-type central furnace, or it may be installed as a central furnace.

4

HOW THE FURNACE FUNCTIONS

Your Hotblast Furnace is designed to be a supplemental or central heating source for your home. This Solid Fuel Furnace may be installed in conjunction with a properly operating central furnace that is listed or certified in accordance with nationally recognized safety standards and equipped with the required controls and other safety features and which has been installed in accordance with appropriate standards of the National Fire Protection Association with installation clearances specified in the furnace nameplate marking. The installation must be accomplished by a qualified agency (one who is engaged in, and is responsible for, or is thoroughly familiar with the installation and operation of the gas, oil, and solid fuel burning heating appliances, who is experienced in such work, familiar with all the requirements of the authority having jurisdiction.) The installation shall be in strict accordance with the manufacturer's installation instructions furnished with the solid fuel furnace.

The chimney connector of the furnace is to be installed to provide clearances to combustible material not less than specified in the individual classifications and marked on the furnace. The chimney connector must be connected to a chimney suitable for use with residential type or building heating appliances which burn solid fuel.

The Furnace is designed to operate in either parallel or series air flow arrangement with the central furnace or as a central furnace.

CENTRAL FURNACE INSTALLATION: As a central furnace, the unit functions independently of any other system. The blower will come on when the plenum temperature reaches the setting on the blower control.

PARALLEL INSTALLATION: (U.S. ONLY)

(See Optional Wiring Diagram, Page 13, Fig. 14) The design is such that when the blower comes on, the blower on the central system also comes on. The blower will only come on when the temperature in the plenum has reached the setting on the blower control. This is to insure that there is sufficient warm air in the system to make it efficient for the unit to operate. When the central system thermostat calls for heat, the central system will operate by the burner igniting and the blower coming on. It is possible that both systems will operate simultaneously. It is recommended that for the most efficient use of your Hotblast Furnace, that it be fired as much as possible in order to reduce the demand on your existing central heating system. This unit has an optional forced draft kit that operates from a wall thermostat. When the temperature falls below the setting on the wall thermostat, the forced draft will come on (U.S. Stove Option 11/DKU)

The warm air supply outlet of the Hotblast

Furnace shall not be connected to the cold air return of the central furnace, because the possibility exists of components of the central furnace overheating and causing the central furnace to operate other than is intended.

5

DIMENSIONS OF FURNACE

FIGURE 1 1537M

6

LOCATING THE FURNACE

1.The furnace should be located in the same room as the central system and as close as possible, but not closer than 9". There should be no wall between the furnace and the warm air outlet duct that is connected directly to the warm air outlet plenum of the central furnace. (See Fig. 2)

2.The unit will require installation with the following clearances:

Unit to sidewall...............

12"(305mm)

Unit to backwall............

30"(760mm)

Chimney connector pipe to sidewall

.....................................21"(530mm) Chimney connector pipe to backwall

.....................................18"(460mm) Hot air ducts to combustibles

.......................................6"(150mm) (Refer to Fig. 2 & 3)

3.Place the furnace on a noncombustible floor.

4.Check figures 2 and 3. Be sure you have the clearances shown from the furnace and the connector pipe to combustible surfaces. If you have a solid brick or stone wall behind your furnace, you can place the furnace as close as you wish to the wall. If the wall is only faced with brick or stone, treat it as a combustible wall.

Figure 2

Figure 3

7

CHIMNEY CONNECTION

Fig. 4

MASONRY CHIMNEY

Before using an existing masonry chimney, clean the chimney and inspect the flue liner to be sure it is safe to use. Make repairs before attaching the furnace. See page 4, item 5. Look at Fig. 4. The connector pipe and fittings you will need to connect directly to a masonry chimney are shown.

The chimney connection should be as short as possible.

If the connector pipe must go through a combustible wall before entering the masonry chimney, consult a qualified mason or chimney dealer. The installation must conform to local fire codes, and

N.F.P.A. 211.

DO NOT CONNECT THIS FURNACE TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

The chimney used for a furnace must not be used to ventilate the cellar or basement. If there is a cleanout opening at the base of the chimney, close it tightly.

Fig. 5

LISTED FACTORY BUILT CHIMNEY

Carefully follow chimney manufacturer's instructions. Use only a Listed Residential Type or

Building Heating Appliance Chimney. If your chimney starts at the ceiling (Fig. 5), you will need enough 6" pipe to reach the ceiling.

The top of the chimney must be at least 3 feet above the roof and be at least 2 feet higher than any point of the roof within 10 feet (Fig. 5).

8

RULES FOR CONNECTOR PIPE INSTALLATION

1. The crimped end of the chimney connector fits inside the furnace flue collar. Install additional chimney connectors and elbow with the CRIMPED END TOWARD THE FURNACE. This will allow any condensation in the flue to run back into the furnace. Use 6" dia. steel pipe and elbows for connection to chimney. Never use less than 24 gauge and although blued steel is satisfactory, high temp painted black is much more desirable.

2.Slope any horizontal pipe upward toward the chimney at least 1/4 inch for each foot of horizontal run.

3.You must have at least 18 inches of clearance between any horizontal piping and the ceiling. (See Fig. 3)

4.The chimney connector must not extend into the chimney flue. (See Fig. 6)

5.Seal each chimney connector pipe joint with furnace cement. Also seal the pipe at the chimney.

6.Use 3 sheet metal screws at each chimney pipe joint to make the piping rigid.

7.The chimney connector may include a section for a barometric draft regulator between the furnace and the chimney (Fig. 4,5, &7). The barometric draft regulator must be installed in the same room (same pressure zone) as the furnace.

8.Install the barometric draft regulator strictly in accordance with the instructions that are provided with the barometric draft regulator.

9.A solid damper must be used in the chimney connecting pipes between the flue collar and the chimney. When used in conjunction with a barometric draft regulator, the solid damper must be placed between the barometric and the chimney. (See Fig. 4,5,7)

Adjusting the Barometric Draft Regulator

1.Drill a hole in the chimney connector within 18" of the flue collar below the barometric draft regulator just large enough for the tube of the manometer.

2.Build a fire after all chimney connections have been made.

3.Use a manometer to measure the draft in the flue.

4.Adjust the Barometric Draft Regulator to obtain a draft of 0.05 - 0.06" W.C. under stable fire conditions.

RIGHT

WRONG

WRONG

Fig. 6

Fig. 7

9