User’s Guide

SIBTF10xx-1xx-MR & SIBTF10xx-1xx-MS

Substation-Rated Industrial Ethernet Switch

10/100Base-TX to 100Base-FX

Single or Redundant Wide Input Power Supply

The SIBTF10xx-1xx-Mx Ethernet industrial switches allow connecting 10Base-T Ethernet/100Base-TX fast Ethernet twisted-pair copper network devices to network devices on a 100Base-FX fast Ethernet fiber

network.

140-MR

The SIBTF10xx-140-MR has four RJ-45 copper ports and one fiber port. The SIBTF10xx-140-MR model includes redundant power-supply terminal blocks that can handle 48–170VDC or 90–125VAC, 50/60Hz input power. The SIBTF10xx-140-MS model, not shown, has a single power-supply terminal block (TB).

The SIBTF10xx-130-MR has three RJ-45 copper ports and two fiber ports. The SIBTF10xx-130-MR model includes redundant power-supply terminal blocks that can handle 48–170VDC or 90–125VAC, 50/60Hz input power. The SIBTF10xx-130-MS model, not shown, has a single power-supply terminal block (TB).

130-MR

The SIBTF10xx-110-MR has one RJ-45 copper port and one fiber port. The SIBTF10xx-110-MR model includes redundant power-supply terminal blocks that can handle 48–170VDC or 90–125VAC, 50/60Hz input power. The SIBTF10xx-110-MS model, not shown, has a single power-supply terminal block (TB).

 

Available Models . . . . . . . . . . .

. .2

 

Installation . . . . . . . . . . . . . . . . .

.4

 

Operation . . . . . . . . . . . . . . . . . .

15

 

Cable Specifications . . . . . . . . . .

20

 

Technical Specifications . . . . . . .

22

 

Troubleshooting . . . . . . . . . . . . .

24

110-MR

 

 

 

Contact Us . . . . . . . . . . . . . . . . .

26

 

Compliance Information . . . . . . .

27

SIBTF10xx-1xx-Mx

Available Models

Available SIBTF10xx-140-MR and MS models*

Part Number

(4) Copper - 10Base-T/

(1) Duplex Fiber-Optic - 100Base-FX port

 

100Base-TX ports

 

 

 

 

 

 

 

SIBTF1011-140-Mx

RJ-45

ST, 1300 nm multimode, duplex

 

100 m (328 ft)

2 km (1.2 miles)

 

 

 

SIBTF1013-140-Mx

RJ-45

SC, 1300 nm multimode, duplex

 

100 m (328 ft)

2 km (1.2 miles)

 

 

 

SIBTF1014-140-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

20 km (12.4 miles)

 

 

 

SIBTF1015-140-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

40 km (24.8 miles)

 

 

 

SIBTF1016-140-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

60 km (37.2 miles)

 

 

 

SIBTF1017-140-Mx

RJ-45

SC, 1550 nm single mode, duplex

 

100 m (328 ft)

80 km (49.7 miles)

 

 

 

 

 

 

*MR = Redundant power-supply terminal blocks, MS = Single power-supply terminal block.

Note: The cable distances listed are maximum distances typically. The actual distance is dependent upon the physical characteristics of the network.

Available SIBTF10xx-130-MR and MS models*

Part Number

(3) Copper - 10Base-T/

(2) Duplex Fiber-Optic - 100Base-FX

 

100Base-TX Ports

Ports

 

 

 

 

 

 

SIBTF1011-130-Mx

RJ-45

ST, 1300 nm multimode, duplex

 

100 m (328 ft)

2 km (1.2 miles)

 

 

 

SIBTF1013-130-Mx

RJ-45

SC, 1300 nm multimode, duplex

 

100 m (328 ft)

2 km (1.2 miles)

 

 

 

SIBTF1014-130-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

20 km (12.4 miles)

 

 

 

SIBTF1015-130-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

40 km (24.8 miles)

 

 

 

SIBTF1016-130-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

60 km (37.2 miles)

 

 

 

SIBTF1017-130-Mx

RJ-45

SC, 1550 nm single mode, duplex

 

100 m (328 ft)

80 km (49.7 miles)

 

 

 

*MR = Redundant power-supply terminal blocks, MS = Single power-supply terminal block.

Note: The cable distances listed are maximum distances typically. The actual distance is dependent upon the physical characteristics of the network.

Available Models -- continued

Available SIBTF10xx-110-MR and MS models*

Part Number

(1) Copper - 10Base-T/

(1) Duplex Fiber-Optic - 100Base-FX Port

 

100Base-TX Port

 

 

 

 

SIBTF1011-110-Mx

RJ-45

ST, 1300 nm multimode, duplex

 

100 m (328 ft)

2 km (1.2 miles)

 

 

 

SIBTF1013-110-Mx

RJ-45

SC, 1300 nm multimode, duplex

 

100 m (328 ft)

2 km (1.2 miles)

 

 

 

SIBTF1014-110-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

20 km (12.4 miles)

 

 

 

SIBTF1015-110-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

40 km (24.8 miles)

 

 

 

SIBTF1016-110-Mx

RJ-45

SC, 1310 nm single mode, duplex

 

100 m (328 ft)

60 km (37.2 miles)

 

 

 

SIBTF1017-110-Mx

RJ-45

SC, 1550 nm single mode, duplex

 

100 m (328 ft)

80 km (49.7 miles)

 

 

 

 

 

 

*MR = Redundant power-supply terminal blocks, MS = Single power-supply terminal block..

Note: The cable distances listed are maximum distances typically. The actual distance is dependent upon the physical characteristics of the network.

2

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

3

SIBTF10xx-1xx-Mx

Installation

Features

The SIBTF10xx-140-MR industrial switch includes four (4) RJ-45, twisted-pair copper ports and one (1) 100 Mb fiber optic port.

The Auto-Negotiation feature on port “1” can be turned OFF and forced to a selected speed (100 Mb/s or 10 Mb/s) also duplex mode (full or half).

All SIBTF models include a primary input terminal block (TB) for 48170VDC or 90125VAC power, a 2.5A, 250V fuse, an LED power indicator, and a red-fault LED. The red-fault LED “ON state” indicates the microcontroller did not initialize correctly.

The “MR” models include an auxiliary power-supply terminal block—not available on “MS” models.

See Figure 1.

Figure 1: SIBTF10xx-140-MR Front Panel

Installation -- continued

Features -- continued

The SIBTF10xx-130-MS industrial switch includes three (3) RJ-45, twisted-pair copper ports and one (2) 100 Mb fiber optic port.

The Auto-Negotiation feature on port “1” can be turned OFF and forced to a selected speed (100 Mb/s or 10 Mb/s) and duplex mode (full or half).

All SIBTF models include a primary input terminal block (TB) for 48170VDC or 90125VAC input power power, a 2.5A, 250V fuse, an LED power indicator, and a red-fault LED. The red-fault LED “ON state” indicates the microcontroller did not initialize correctly.

The “MR” models include an auxiliary power-supply terminal block—not available on “MS” models.

See Figure 2.

Figure 2: SIBTF10xx-130-MR Front Panel

4

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

5

SIBTF10xx-1xx-Mx

Installation -- continued

Features -- continued

The SIBTF10xx-110-MS industrial switch includes one (1) RJ-45, twisted-pair copper port and one (1) 100 Mb fiber optic port.

The Auto-Negotiation feature on port “1” can be turned OFF and forced to a selected speed (100 Mb/s or 10 Mb/s) and duplex mode (full or half).

All SIBTF models include a primary input terminal block (TB) for 48170VDC or 90125VAC power, a 2.5A, 250V fuse, an LED power indicator, and a fault LED. The red-fault LED “ON state” indicates the microcontroller did not initialize correctly.

The “MR” models include an auxiliary power-supply terminal block—not available on “MS” models.

See Figure 3.

Figure 3: SIBTF10xx-110-MR Front Panel

Installation -- continued

Enclosure top view (configuration switches)

The SIBTF10xx-1xx-Mx has eight (8) configuration (DIP) switches located under the switch cover on top of the enclosure. See Figure 4.

Switch Position 1

 

 

 

 

1

 

-

Swi

Config

 

 

 

tches

 

 

Figure 4: Enclosure Top View Configuration Switches

Setting configuration switches

To set the DIP switches:

1.Using a small, phillips-head screwdriver, loosen (do not remove) the two screws that secure the cover to the switch.

2.Swing the switch cover counter-clockwise to expose the DIP switches.

3.Use a small, flathead screwdriver to set the recessed switches as required by the network application.*

4.Slide the switch cover back over the DIP switches and then secure it by tightening both screws.

*Note: Switches 1, 2, and 3 apply only to twisted-pair “copper port #1.”

6

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

7

SIBTF10xx-1xx-Mx

Installation -- continued

DIP switch settings

 

 

1

 

 

 

 

 

 

 

 

 

1. Port 1 copper Auto-Negotiation:

 

 

 

 

 

 

 

 

 

 

 

UP (Enabled) - Advertises switch speed and mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capabilities to the network:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto-Negotiation E nabled

 

 

• 100Mb/s full-duplex

• 100Mb/s half-duplex,

 

 

 

 

 

 

 

 

 

 

 

• 10Mb/s full-duplex

• 10Mb/s half-duplex.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN (Disabled) - Does not advertise switch speed Auto-Negotiation Disabled and mode capabilities to the network. With Auto-

Negotiate disabled switches 2 and 3 are used to set the twisted-pair speed and mode.

2.Port 1 copper speed:

UP (100Base-TX) - Sets the twisted-pair speed to 100Base-TX.

DOWN (10Base-T) - Sets the twisted-pair speed to 10Base-T.

3.Port 1 copper duplex:

UP (Full-Duplex) - The twisted-pair cable distances are constrained by the cable requirements.

DOWN (Half-Duplex): - The twisted-pair cable distances are constrained by the 512-Bit Rule.

4.Fiber port FX 1 duplex:

UP (Full-Duplex) - The cable distances for the fiber port are constrained by the cable requirements.

DOWN (Half-Duplex) - The cable distances for the fiber port are constrained by the 512-Bit Rule.

5.Fiber port FX 2 duplex (model 130 only):

UP (Full-Duplex) - The cable distances for the fiber port are constrained by the cable requirements.

DOWN (Half-Duplex) - The cable distances for the fiber port are constrained by the 512-Bit Rule.

2

100Base-TX

10Bas e-TX

3

Full Duplex

Half Duplex

4

Full Duplex (fiber)

Half Duplex (fiber)

5

Full Duplex (fiber)

Half Duplex (fiber)

Installation -- continued

6. Link Pass-Through (model 110 only):

UP (Enable) - When Link Pass-Through is enabled, a fault on one side of the switch stops the signal and data transmission on the other side. See the detailed explanation of Link Pass-Through on page 18.

DOWN (Disable) - When Link Pass-Through is disabled, a fault on one side of the switch does not stop the signal and data transmission on the other side.

6

Link PassThrough E nabled

Link PassThrough Disabled

7. Fiber redundancy (model 130 only):

UP (Disable) - When fiber redundancy is disabled, the two fiber ports (1 and 2) act as normal bridging ports.

DOWN (Enable) - When fiber redundancy is enabled, the two fiber ports (1 and 2) are configured as forwarding or disabled. At any given time one port will be disabled and one port will be forwarding.

8. AutoCross:

UP (Enable) - The switch will connect to a straightthrough or a crossover twisted-pair copper cable automatically.

DOWN (Disable) - In the down position the straightthrough or crossover twisted-pair copper cable must be installed according to the site requirements.

7

Redundant Fiber E nabled

Redundant Fiber Disabled

8

AutoCross E nabled

AutoCross Disab led

8

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

9

SIBTF10xx-1xx-Mx

Installation -- continued

WARNING: Make sure that the external power source is turned OFF before attempting to connect power leads to the industrial switch. Failure to observe this warning could result in an electrical shock.

WARNING: The SIBTF10xx-1xx-Mx is a class I device. It has a provision for protective earth grounding. Equipment grounding is vital to ensure safe operation. The SIBTF switch must be earth grounded during and after installation. Failure to observe this warning could result in an electric shock.

Note: DO NOT use bare (exposed) or un-lugged power-source wires to connect to the industrial switch.

Connecting primary power

The industrial switch is designed to accommodate 48 – 170VDC or 90 – 125VAC, 50/60 Hz input power via its primary terminal block (TB).

To provide power to the industrial switch via the primary TB, view Figure 5, and then do the following:

1.Verify that the external power source is turned OFF and disconnect.

2.Loosen the grounding screw and then connect the power source functional-ground lead to the grown screw, as shown in Figure 5. Tighten the screw to secure.

3.Loosen the TB screw marked “-” and then connect the power source neutral or (-) negative lead to the TB negative terminal, as shown in Figure 5. Tighten the screw to secure.

4.Loosen the TB screw marked “+” and then connect the power source line phase or positive (+) lead to the TB positive terminal, as shown in Figure 5. Tighten the screw to secure.

5.Re-connect and turn ON the external power source.

6.Verify that the industrial switch has powered up by observing the illuminated “Power Good” LED on the front panel.

N

PRI.

L

POWER INPUT 48 - 170 VDC 90 - 125 VAC

Figure 5: Primary Power Connection

Installation -- continued

WARNING: Make sure that the external power source is turned OFF before attempting to connect power leads to the industrial switch. Failure to observe this warning could result in an electrical shock.

WARNING: The SIBTF10xx-1xx-Mx is a class I device. It has a provision for protective earth grounding. Equipment grounding is vital to ensure safe operation. The SIBTF switch must be earth grounded during and after installation. Failure to observe this warning could result in an electric shock.

Note: DO NOT use bare (exposed) or un-lugged power-source wires to connect to the SIBTF10xx-10x-MR industrial switch.

Connecting auxiliary power

The SIBTF10xx-10x-MR switches support a redundant power supply. If the primary power source fails, the auxiliary power source supplies power to the industrial switch.

To provide auxiliary power to the industrial switch, view Figure 6 and do the following:

1.Verify that the external power source is turned OFF and disconnected.

2.Loosen the grounding screw and connect the power source functional-ground lead to the grown screw, as shown in Figure 6. Tighten the screw to secure.

3.Loosen the TB screw marked “-” and then connect the power source neutral or (-) negative lead to the TB negative terminal, as shown in Figure 6. Tighten the screw to secure.

4.Loosen the TB screw marked “+” and then connect the power source line phase or positive (+) lead to the TB positive terminal, as shown in Figure 6. Tighten the screw to secure.

5.Re-connect and turn ON the external power source.

6.Verify that the industrial switch is powered UP: auxiliary “Power Good” LED on the lower front panel will be ON.

AUX.

Figure 6: Auxiliary Power Connection

10

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

11

SIBTF10xx-1xx-Mx

Installation -- continued

Internal relay connections

The internal relay can activate an external fault indicator. The fault indicator connects to the relay contacts on the front panel. An example would be a fault circuit connected to a warning light located in a control room. The light can be connected in a normally open (NO) or normally closed (NC) configuration with respect to circuit common (C) to turn the light ON/OFF when a fault occurs.

To connect a fault indicator to the relay, view Figure 7 and then do the following:

1.Verify that the external power source is turned OFF.

2.Loosen the relay’s “NO” screw and then connect the fault indicator’s return lead to terminal “NO.” Tighten the screw to secure.

3.Loosen the relay’s “C” screw and then connect the fault indicator’s common lead terminal “C.” Tighten the screw to secure.

Or:

4.Loosen the relay’s “NC” screw and then connect the fault indicator’s return lead to terminal “NC.” Tighten the screw to secure.

5.Loosen the relay’s “C” screw and then connect the fault indicator’s common lead terminal “C.” Tighten the screw to secure.

Relay

NC

NC

Contacts

 

 

(600W max.)

 

 

30 VDC

C

C

@2.0A

 

 

125 VAC

 

 

@0.5A

NO

NO

Figure 7: Internal Relay Connections

Two wiring scenarios:

Wiring the relay in the normally closed (NC) configuration can be used to monitor alarm indicators connected in series, where any single event will cause all alarm indicators to trigger.

Wiring the relay in the normally open (NO) configuration can be used to monitor alarm indicators connected in parallel, where any single event will cause that events alarm indicator to trigger: i.e., a light turning ON or OFF.

CAUTION: Calculate the maximum possible current in each power wire and relay-contact wire. Observe all electrical codes for maximum current allowed. If the current goes above the maximum ratings, the wiring could overheat and cause serious damage to the network wiring or equipment.

Installation -- continued

DIN-Rail

The industrial switch includes an aluminum DIN-Rail mounting bracket attached to the back panel of the enclosure. See Figure 8.

Back View

DIN Rail

Mounting Bracket

Figure 8: DIN-Rail Bracket

Mounting the enclosure to a DIN-Rail

CAUTION: The SIBTF10xx-1xx switch is convection cooled, requiring unrestricted bottom-to-top airflow. Mounting the device in other orientations could result in unreliable operation or device failure.

CAUTION: To prevent debris from falling through the ventilation holes, local and national electrical and fire codes might require orienting the device with its small-diameter vent holes downward.

To mount the enclosure onto a DIN-Rail:

1.Insert the top of the DIN-Rail into the upper slot of the mounting plate.

2.Push down and then rotate the industrial switch inward to snap it into place onto the DIN-Rail.

An illustration of the procedure is shown in Figure 9.

Step 1

Step 2

Mounting Plate

DIN-Rail

Figure 9: Enclosure Mounted to DIN-Rail

12

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

13

 

 

 

 

SIBTF10xx-1xx-Mx

Installation -- continued

Installing fiber cable

To install a fiber cable, view Figure 10, and then do the following:

1.Locate or build 100Base-FX fiber cable with male, two-stranded TX to RX connectors installed at both ends.

2.Connect the fiber cables to the industrial switch as follows:

Connect the male TX cable connector to the female TX port.

Connect the male RX cable connector to the female RX port.

3.Connect the fiber cables to the other device (another media converter, hub, etc.) as follows:

Connect the male TX cable connector to the female RX port.

Connect the male RX cable connector to the female TX port.

Connect fiber cable

Connect fiber cable

to media converter

to other device

as shown.

(media converter,

 

hub, etc.) as shown

RX

RX

TX

TX

Figure 10: Fiber Cable Installation

Installing copper cable

The AutoCross feature allows connecting straight-through (MDI) or crossover (MDI- X) copper cable to the RJ-45 port of a second device.

To install an Ethernet cable, view Figure 11, and then do the following:

1.Locate or build 10Base-T or 100Base-TX copper cables with male, RJ-45 connectors installed on both ends.

2.Connect the RJ-45 connector at one end of the cable to the RJ-45 port on the industrial switch.

3.Connect the RJ-45 connector at the other end of the cable to the RJ-45 port on the second device (PLC, workstation, etc.).

Installation -- continued

Installing copper cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ports

 

 

 

 

 

 

 

 

RJ-45 Port

 

bridge

P LC, works tat ion, e tc.

 

 

 

 

 

 

Figure 11: Copper Cable Installation

Operation

Copper/fiber status LEDs

Copper LEDs

The SIBTF10xx-1xx-Mx comes equipped with status LEDs to monitor the network connections for the copper and fiber ports.

The numbered LEDs refer to the numbered copper and fiber ports. For example, LED #1 refers to the twisted-pair copper port #1; LED #2 refers to fiber port #2. See Figure 12.

Each port has three associated LEDs: Full duplex (FD), 10MB, and 100MB.

Copper Port

Fiber Port

Figure 12: Copper and Fiber Port Status LEDs

14

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

15

SIBTF10xx-1xx-Mx

Operation -- continued

Copper/fiber status LEDs -- continued

Copper LEDs

The function of the copper port LEDs (1, 2, 3, and 4) are as follows:

 

100MB

ON

The copper port has established a link at

100 MB/s.

100MB

Flashing

The copper port is transmitting signals at 100 Mb/s.

10MB

ON

The copper port has established a link at

10 MB/s.

10MB

Flashing

The copper port is transmitting signals at 10 Mb/s.

FD

ON

The copper port is in full-duplex mode.

 

FD

OFF

The copper port is in half-duplex mode.

 

Fiber LEDs

The functions of the fiber port LEDs (2 and 5) are as follows:

100MB

ON

The fiber port has established a link.

100MB

Flashing

The fiber port is transmitting signals.

10MB

--

N/A

10MB

--

N/A.

FD

ON

The fiber port is in full-duplex mode.

FD

OFF

The fiber port is in half-duplex mode.

Fault (red) LED

Fault LED ON (red) indicates that the microcontroller did not initialize correctly; as a result, the switch will not power up.

Fault LED

Copper Port

Fiber Port

Figure 13: Fault LED

Operation -- continued

Product Features

Immunity standards

The industrial switch is designed to meet EN61000-6-2, IEEE1613.

Congestion reduction

The SIBTF10xx-1xx industrial switch does not forward collision signals or error packets from one collision domain to another, which improves baseline-network performance. In addition, the industrial switch filters packets destined for local devices, which reduces network congestion.

Rate conversion

The SIBTF10xx-1xx industrial switch allows connecting 10Mb/s terminal devices on a 10Base-T legacy Ethernet copper network and/or 100Mb/s terminal devices on a 100Base-TX fast Ethernet copper network to 100Mb/s terminal devices on a 100Base FX fast Ethernet fiber network.

Full-Duplex network

In a full-duplex network, maximum cable lengths are determined by the type of cables used. See cable specifications section for the different SIBTF10xx-1xx models. The 512-Bit Rule does not apply in a full-duplex network.

Half-Duplex network (512-Bit Rule)

In a half-duplex network, the maximum cable lengths are determined by the round trip delay limitations of each fast Ethernet collision domain. (A collision domain is the longest path between any two terminal devices: e.g., a terminal, switch, or router.)

The 512-Bit Rule determines the maximum length of cable permitted by calculating the round-trip delay in bit-times (BT) of a particular collision domain. If the result is less than or equal to 512 BT, the path is good.

For more information on the 512-Bit Rule, see the white paper titled “Collision Domains” on the Transition Networks website at: www.transition.com.

16

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

17

SIBTF10xx-1xx-Mx

Operation -- continued

Product features -- continued

Auto-Negotiation

The Auto-Negotiation feature allows the SIBTF10xx-1xx industrial switch to configure itself to achieve the best possible mode of operation over a link automatically. The industrial switch broadcasts its speed (10 Mb/s or 100 Mb/s) and duplex capabilities (full or half) to the other devices and negotiates the best mode of operation. Auto-Negotiation allows quick and easy installation because the optimal link is established automatically.

In a scenario where the industrial switch is linked to a non-negotiating device, the admin person may want to disable Auto-Negotiation. In this instance, the mode of operation will drop to the lowest common denominator between the two devices: 10 Mb/s, half-duplex. Disabling this feature provides the ability to force the connection to the best mode of operation.

Link Pass-Through

The SIBTF10xx-110 industrial switch provides a Link Pass-Through feature, which allows monitoring its fiber (FX) and copper (RX) (receive) ports for signal loss. Refer to Figure 14, in the event of an RX signal loss (1), the industrial switch will automatically disable the TX (transmit) signal (2) thus “passing through” the link loss

(3). The far-end device is automatically notified of the link loss (4), which prevents date losses by transmitting data over an invalid link unknowingly.

 

media converter A

 

 

media converter B

 

 

disables the fiber TX link

loses the fiber RX link

 

Near-End

Media

2

3

Media

Far-End

 

 

Device

Converter A

 

 

Converter B

Device

 

1

 

 

4

 

original fault

 

 

media converter B

on the copper link

 

 

disables the copper link

Figure 14: Link Pass-Through

Fiber Redundancy

The SIBTF10xx-130 industrial switch provides stable, fiber redundancy in highly critical Ethernet and Fast Ethernet segments.

When the fiber redundancy feature is enabled, only one fiber connection (primary) is active at a time. This primary connection is in the forwarding stage while the other fiber connection (secondary) is put in the standby state.

When failure on the primary fiber connection occurs, it is detected by the switch. The secondary connection is activated and becomes the primary link. The original fiber link is disabled until the failure on the primary fiber connection is corrected. Once corrected, the original order is restored.

Note: The fiber redundancy feature is for point-to-point applications, and not for redundant ring applications.

Operation -- continued

AutoCross™

When the AutoCross feature is activated, it allows the use of straight-through MDI or crossover MDI-X cables for connecting to 10Base-T or 100Base-TX devices. AutoCross determines the characteristics of the connection and automatically configures the unit to link up, regardless of the cable configuration, either MDI or MDI-X.

Replacing the fuse

Note: The fuse may be “hot swapped” (i.e., replaced while the industrial switch is in operation) provided the power source associated with the burned-out fuse has been disconnected. For example, the primary fuse may be replaced provided that power to the primary power contacts has been turned OFF.

To replace the fuse, view Figure 15, and then do the following:

1.Turn OFF and disconnect the power source associated with the blown fuse.

2.Using a flat-head screwdriver, unscrew (counter-clockwise) and remove the fuse holder. See Figure 15.

3.Carefully remove the fuse from the fuse holder.

4.Install a same size and rated (2.5 A, 250 V) replacement fuse in the fuse holder.

5.Insert the fuse holder with the fuse into the switch and rotate clockwise to secure.

6.Re-connect and turn ON the power source.

7.Verify that the industrial switch is powered UP: “Power Good” LED on the upper front panel will be ON.

 

Front Panel

 

 

PR I.

 

Po wer

 

 

Good

 

 

 

Indust rial

 

FUSE

Switch

 

2.5A

PR I. SIBFT

 

250V

 

 

N

 

Fuse

 

PR I.

 

 

L

Fuse Holder

Figure 15: Fuse Replacement

18

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

19

SIBTF10xx-1xx-Mx

Cable Specifications

The physical characteristics must meet or exceed IEEE 802.3™ specifications.

Copper Cable

Category 3: (Minimum requirement for 10 Mb/s operation)

Gauge

24 to 22 AWG

Attenuation

11.5 dB/100m @ 5-10 MHz

Maximum Cable Distance

100 meters

Category 5: (Minimum requirement for 100 Mb/s operation)

Gauge

24 to 22 AWG

Attenuation

22.0 dB/100m @ 100 MHz

Maximum Cable Distance

100 meters

Straight-through or crossover twisted-pair cable may be used.

Shielded (STP) or unshielded (UTP) twisted-pair cable may be used.

Pins 1&2 and 3&6 are the two active pairs in an Ethernet network .

Use only dedicated wire pairs for the active pins:

(e.g., blue/white & white/blue, orange/white & white/orange, etc.)

 

Straight-Through Cable

 

 

 

Crossover Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twisted Pair #1

 

 

 

1

 

1

Twisted Pair #1

 

 

1

 

1

 

 

 

 

2

 

2

 

2

 

2

 

 

 

 

 

 

 

 

 

 

 

Twisted Pair #2

 

 

 

3

 

3

Twisted Pair #2

 

 

3

 

3

 

 

 

 

 

 

 

 

 

 

 

 

6

 

6

 

6

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 16: Copper Cable Configurations

• Do not use flat or silver satin wire.

WARNING: Visible and invisible laser radiation when open. Do not stare into the beam or view the beam directly or with optical instruments. Failure to observe this warning could result in an eye injury or blindness.

WARNING: Use of controls, adjustments, or the performance of procedures other than those specified herein may result in hazardous radiation exposure.

Fiber cable

Bit Error Rate:

single mode fiber (recommended): Multimode fiber (recommended): Multimode fiber (optional):

SIBTF1011-1xx-Mx

Fiber Optic Transmitter Power:

Fiber Optic Receiver Sensitivity:

Link Budget:

<10-9 9 μm

62.5/125 μm

100/140, 85/140, 50/125 μm

1300 nm multimode

min: -19.0 dBm

max: -14.0 dBm

min: -30.0 dBm

max: -14.0 dBm

11.0 dB

 

Cable Specifications -- continued

SIBTF1013-1xx-Mx

1300 nm multimode

Fiber Optic Transmitter Power:

min: -19.0 dBm

max: -14.0 dBm

Fiber Optic Receiver Sensitivity:

min: -30.0 dBm

max: -14.0 dBm

Link Budget:

11.0 dB

 

SIBTF1014-1xx-Mx

1310 nm single mode

Fiber-optic Transmitter Power:

min: -15.0 dBm

max: -8.0 dBm

Fiber-optic Receiver Sensitivity:

min: -31.0 dBm

max: -8.0 dBm

Link Budget:

16.0 dB

 

SIBTF1015-1xx-Mx

1310 nm single mode

Fiber-optic Transmitter Power:

min: -8.0 dBm

max: -2.0 dBm

Fiber-optic Receiver Sensitivity:

min: -34.0 dBm

max: -7.0 dBm

Link Budget:

26.0 dB

 

SIBTF1016-1xx-Mx

1310 nm single mode

Fiber-optic Transmitter Power:

min: -5.0 dBm

max: 0.0 dBm

Fiber-optic Receiver Sensitivity:

min: -34.0 dBm

max: -7.0 dBm

Link Budget:

29.0 dB

 

SIBTF1017-1xx-Mx

1550 nm single mode

Fiber-optic Transmitter Power:

min: -5.0 dBm

max: 0.0 dBm

Fiber-optic Receiver Sensitivity:

min: -34.0 dBm

max: -7.0 dBm

Link Budget:

29.0 dB

 

This device is certified by the manufacturer to comply with DHHS Rule 21/CFR, Subchapter J applicable at the date of manufacture.

CAUTION: Visible and invisible laser radiation when open. Do not stare into beam or view directly with optical instruments.

CAUTION: Use of controls, adjustments or the performance of procedures other than those specified herein may result in hazardous radiation exposure.

The fiber optic transmitters on this device meet Class I Laser safety requirements per IEC-825/CDRH standards and comply with 21 CFR1040.10 and 21CFR1040.11.

20

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

21

SIBTF10xx-1xx-Mx

Technical Specifications

For use with Transition Networks Model SIBTF10xx-1xx-Mx or equivalent.

Standards:

IEEE 802.3™ 2000, IEEE 802.3x™

Data Rate:

10 Mb/s, 100 Mb/s (copper), 100 Mb/s (fiber)

Dimensions:

Models 130- & 140-Mx

 

(W x H x D) 4.125" x 6" x 5" (104.77 x 152.4 x 127 mm)

Dimensions:

Model 110-Mx

 

(W x H x D) 3.375" x 6" x 5" (85.73x 152.4 x 127 mm)

Weight:

3.2 lb. (1.5 kg) approximately

Input Voltage:

48170VDC +/-15%

 

90125VAC +/-15%, 50/60 Hz

Power:

15 W (maximum)

 

Aux input standby power, 200 mW typically

Fuse:

2.5 A/250 VDC

Alarm Relay:

Three-position screw terminal block for the dry contact relay

 

0.5 A @ 125 VAC / 2.0 A @ 30 VDC (maximum)

 

switching capacity: 60 W (maximum)

Packet Size:

Memory: 64K Bytes

 

Unicast MAC addresses: 1000

 

Maximum packet size: 1536 Bytes

MTBF*:

51,115 MIL-HDBK-217F Hours

 

153,038 Bellcore Hours

Environment

-40 to 75°C (-40 to 167°F)

Operating Temp:

Storage Temp:

-40 to 85°C (-40 to 185°F)

Humidity:

5 to 95%, non-condensing

Altitude:

3000 m (10,000 ft.)

Warranty:

Lifetime

The industrial switch is designed for installation in restricted access locations. Installing the industrial switch into other equipment or facility control rooms must comply with the fire-enclosure requirements of IEC60950/EN60950/UL60950, along with other local, national fire and safety codes.

IMPORTANT: Copper based media ports: e.g., Twisted Pair (TP) Ethernet, USB, RS232, RS422, RS485, DS1, DS3, Video Coax, etc. are intended for connecting to intra-building (inside plant) link segments, not subject to lightening transients or power faults. Copper based media ports: e.g., Twisted Pair (TP) Ethernet, USB, RS232, RS422, RS485, DS1, DS3, Video Coax, etc. are NOT for connecting to interbuilding (outside plant) link segments subject to lightening transients or power faults.

*MTBF is estimated using the predictability method. This method is based on MIL217F at 25°C ambient temperature, typical enclosure heat rise of 10°C, and nominal operating conditions and parameters. Installation and configuration specific MTBF estimates are available upon request. Contact Technical Support.

Technical Specification -- continued

220–240VAC, 50/60Hz installation

CAUTION: If the main power source is 220-240VAC @50/60Hz, use a 2:1, 50VA or greater step-down transformer between the main power source and the industrial switch. Failure to observe this caution could result in a damaged switch.

EMC Type Tests (all test were performed using unshielded cables)

Standard

Description

Compliance Level

Remarks

 

 

 

 

EN55022/FCC Part15

ITE Emissions

Class A

Conducted and radiated

 

 

 

 

EN55024/EN61000-6-2:

ITE Emissions

 

 

 

 

 

 

IEC61000-4-2

 

Level 2

ESD contact discharge

 

 

 

 

IEC61000-4-3

 

Level 4

Radiated fields

 

 

 

 

IEC61000-4-4

 

Level 3

Fast transients - power port

 

 

 

2 meter cable AC

 

 

 

1 meter cable DC

 

 

 

 

 

 

Level 2

Fast transient – Ethernet port

 

 

 

3 meter cable length

 

 

 

 

IEC6100-4-5

 

Level 3 CM

Surge – power port

 

 

Level 2 DM

2 meter cable AC

 

 

Level 1 DC

1 meter cable DC

 

 

 

 

 

 

Level 2

Surge – relay port

 

 

 

1 meter cable length

 

 

 

 

 

 

Level 2

Surge – Ethernet port

 

 

 

3 meter cable length

 

 

 

 

IEC61000-4-5

 

EN61000-6-2 Level 3

Conducted – power port

 

 

EN55024 Level 2

2 meter cable AC,

 

 

 

1 meter cable DC

 

 

 

 

 

 

EN61000-6-2 Level 3

Conducted – relay port

 

 

EN55024 Level 2

1 meter cable length

 

 

 

 

 

 

EN61000-6-2 Level 3

Conducted – PE Studs

 

 

EN55024 Level 2

2 meter cable length

 

 

 

 

 

 

EN61000-6-2 Level 3

Conducted – Ethernet port

 

 

EN55024 Level 2

10 meter cable length

 

 

 

 

IEC61000-4-8

 

Level 1

Power freq. mag. field

 

 

 

 

IEC61000-4-11

 

N/A

VoltageDIPs and variations

 

 

 

 

IEEE1613, Power Substation Testing

 

 

 

 

 

 

IEEE1613, Clause 6.2

 

Not rated

Dielectric power freq.

 

 

 

 

IEEE1613, Clause 6.3

 

Compliant

Impulse voltage all ports

 

 

 

 

IEEE1613, Clause 7.3.1

 

Class 2 transverse and

Surge oscillatory waveform

 

 

common Mode

–power AC

 

 

 

 

 

 

Class 2 transverse and

Surge oscillatory waveform

 

 

common Mode

–power DC

 

 

 

 

 

 

Class 2 common mode

Surge oscillatory waveform

 

 

 

–relay port

 

 

 

 

 

 

Class 2 common mode

Surge oscillatory waveform

 

 

 

–Ethernet 10 Mbps

 

 

 

 

 

 

Class 1 common mode

Surge oscillatory waveform

 

 

 

– Ethernet 100 Mbps

 

 

 

 

22

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

23

SIBTF10xx-1xx-Mx

Technical Specification -- continued

EMC Type Tests -- Continued

Standard

Description

Compliance Level

Remarks

 

 

 

 

IEEE1613, Power Substation Testing -- Continued

 

 

 

 

 

 

IEEE1613, Clause 7.3.2

 

Class 2 transverse mode

Surge fast transient

 

 

Class 1 common mode

waveform – power AC

 

 

 

 

 

 

Class 2 transverse mode

Surge fast transient

 

 

Class 1 common mode

waveform – power DC

 

 

 

 

 

 

Class 1 common mode

Surge fast transient

 

 

 

waveform – relay port

 

 

 

 

 

 

Class 1 common mode

Surge fast transient

 

 

 

waveform – Ethernet 10

 

 

 

Mbps

 

 

 

 

 

 

Class 1 common mode

Surge fast transient

 

 

 

waveform – Ethernet 100

 

 

 

Mbps

 

 

 

 

IEEE1613, Clause 8

 

Class 2

Radio frequency

 

 

 

susceptibility

 

 

 

 

IEEE1613, Clause 9

 

Class 1

ESD contact discharge 8kV

 

 

 

 

Troubleshooting

If the industrial switch fails, isolate and correct the failure by determining the answers to the following questions and then taking the indicated action:

1.

Is the “PRI” (primary power) LED illuminated?

 

NO

Ensure the power source is the proper voltage (48–170 VDC or 90–125

 

 

 

VAC, 50/60Hz).

 

 

Ensure that the positive, negative, and ground wires from the power

 

 

source are properly connected to the primary inputs.

 

Contact Technical Support:

US/Canada: 1-800-260-1312,

 

 

 

International: 00-1-952-941-7600.

 

YES

 

 

Proceed to step 2.

2.(SIBTF10xx10x-MR models only) is the “AUX” (auxiliary power) LED illuminated?

NO

If the device does not have an auxiliary power source, proceed to step 3.

Ensure the power source is the proper voltage (48–170 VDC or 90–125 VAC, 50/60Hz).

Ensure that the positive, negative, and ground wires from the power source are properly connected to the auxiliary inputs.

Contact Technical Support: US/Canada: 1-800-260-1312, International: 00-1-952-941-7600.

YES

Proceed to step 3.

Troubleshooting -- continued

3.Is the “FAULT” LED illuminated?

NO

Proceed to step 4.

YES

Contact Technical Support: US/Canada: 1-800-260-1312, International: 00-1-952-941-7600.

4.For each port with a cable installed is either the “10MB” or the “100MB” LED illuminated?

YES

Proceed to step 5.

NO

For each port with a cable installed and its LED is OFF, check the cable for proper connection.

For the fiber ports, verify that the TX and RX cables on the SIBTF10xx10x are connected to the RX and TX ports, respectively, on the device at the other end of the fiber cables.

Contact Technical Support: US/Canada: 1-800-260-1312, International: 00-1-952-941-7600

5.For each RJ-45 port with a cable installed (ports 1, 2, 3, and 4), check to see if the 10MB or 100MB LED is illuminated.

10MB is ON = The industrial switch has selected 10Mb/s operation.

100MB is ON = The industrial switch has selected 100Mb/s operation.

If the speed is not correct, disconnect and reconnect the cable to restart the initialization process.

Proceed to step 6.

6.For each fiber port with a cable installed, is the “FD” (full-duplex) LED illuminated?

NO

The industrial switch has selected half-duplex mode.

If the mode is not correct, disconnect and reconnect cable to restart the initialization process.

Check the cable for proper connection.

Contact Tech Support: 1-800-260-1312, Int’l: 00-1-952-941-7600.

YES

The industrial switch has selected full-duplex mode.

If the mode is not correct, disconnect and reconnect cable to restart the initialization process.

Check the cable for proper connection.

Contact Tech Support: 1-800-260-1312, Int’l: 00-1-952-941-7600.

24

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

25

SIBTF10xx-1xx-Mx

Contact Us

Technical support

Technical support is available 24 hours a day.

US and Canada: 1-800-260-1312

International: 00-1-952-941-7600

Transition now

Chat live via the Web with Transition Networks Technical Support. Log onto www.transition.com and click the Transition Now link.

Web-Based seminars

Transition Networks provides seminars via live web-based training. Log onto www.transition.com and click the Learning Center link.

E-Mail

Ask a question anytime by sending an e-mail to our technical support staff. techsupport@transition.com

Address

Transition Networks

6475 City West Parkway

Minneapolis, MN 55344, U.S.A.

telephone:

952-941-7600

toll free:

800-526-9267

fax:

952-941-2322

 

 

 

Declaration of Conformity

Name of Mfg:

Transition Networks

 

6475 City West Pkwy, Minneapolis MN 55344 U.S.A.

Model:

SIBTF10xx-1xx Industrial switches

Part Number(s):

SIBTF1011-1xx-MR, SIBTF1013-1xx-MR, SIBTF1014-1xx-MR,

 

SIBTF1015-1xx-MR, SIBTF1016-1xx-MR, SIBTF1017-1xx-MR,

 

SIBTF1011-1xx-MS, SIBTF1013-1xx-MS, SIBTF1014-1xx-MS,

 

SIBTF1015-1xx-MS, SIBTF1016-1xx-MS, SIBTF1017-1xx-MS,

Regulation:

EMC Directive 89/336/EEC

Purpose:

To declare that the SIBTF10xx-1xx-Mx to which this declaration

 

refers is in conformity with the following standards:

CISPR 22:1993; EN 55022:1994+A1:1995+A2:1997 Class A; EN 55024:1998; EN 61000-6-2:2001; EN61000-4-2:1995; -4-3:2002; -4-4:1995; -4-5:1995; -4-6:1995

I, the undersigned, hereby declare that the equipment specified above conforms to the above Directive(s) and Standard(s).

 

June 30, 2006

Stephen Anderson, Vice-President of Engineering

Date

Compliance Information

EN55022, EN55024, EN61000-6-2:2001 & IEEE1613

FCC Regulations This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at the user's own expense.

Canadian Regulations This digital apparatus does not exceed the Class A limits for radio noise for digital apparatus set out on the radio interference regulations of the Canadian Department of Communications.

Le présent appareil numérique n'émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la Class A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.

European Regulations

Warning: This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

Achtung ! Dieses ist ein Gerät der Funkstörgrenzwertklasse A. In Wohnbereichen können bei Betrieb dieses Gerätes Rundfunkstörungen auftreten. In diesem Fäll ist der Benutzer für Gegenmaßnahmen verantwortlich.

Attention ! Ceci est un produit de Classe A. Dans un environment domestique, ce produit risque de créer des interférences radioélectriques, il appartiendra alors à l'utilsateur de prende les measures spécifiques appropriées.

CAUTION: RJ connectors are NOT INTENDED FOR CONNECTION TO THE PUBLIC TELEPHONE NETWORK. Failure to observe this caution could result in damage to the public telephone network. Der Anschluss dieses Gerätes an ein öffentlickes Telekommunikationsnetz in den EG-Mitgliedstaaten verstösst gegen die

jeweligen einzelstaatlichen Gesetze zur Anwendung der Richtlinie 91/263/EWG zur Angleichung der Rechtsvorschriften der Mitgliedstaaten über Telekommunikationsendeinrichtungen einschliesslich der gegenseitigen Anerkennung ihrer Konformität.

In accordance with European Union Directive 2002/96/EC of the European Parliament and of the Council of 27 January 2003, Transition Networks will accept post usage returns of this product for proper disposal. The contact information for this activity can be found in the 'Contact Us' portion of this document.

26

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.

27

SIBTF10xx-1xx-Mx

Trademark Notice

All trademarks and registered trademarks are the property of their respective owners.

Copyright Restrictions © 2005 Transition Networks. All rights reserved. No part of this work may be reproduced or used in any form or means (graphic, electronic, mechanical) without written permission from Transition Networks.

28

Printed in the U.S.A.

33323.A