Trane Voyager TS, Voyager YS, Voyager WS Catalogue

0 (0)
Trane Voyager TS, Voyager YS, Voyager WS Catalogue

Product Catalog

Voyager™ — TS*/YS*/WS*

Packaged Cooling, Gas/Electric & Heat Pump

15–25 Tons, 50 Hz

August 2012

RT-PRC034-EN

Introduction

Packaged Gas/Electric

Packaged Cooling/Heat Pump

Packaged Rooftop Air Conditioners

Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionize this design concept.

The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility.

Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.

Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager.

Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner you can be certain Voyager Products are built to meet your needs.

Trademarks

and the logo, Frostat, Integrated Comfort, ReliaTel, Tracer, are trademarks of in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.

Revision Summary

RT-PRC034-EN (20 August 2012)

New configurable model number

New optional features: Condensate Overflow Switch, MERV 8 and Filter Removal Tool, Stainless Steel Drain Pan

Updated Features/Benefits, Model Number Description, General Data, Electrical Data, Mechanical Specifications

© 2012 Trane All rights reserved

RT-PRC034-EN

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Selection Procedure (SI/IP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

SI Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

IP Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

19

Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

22

General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

59

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

62

Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

66

Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

80

Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

81

Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

87

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

93

Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

95

Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

96

Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

97

RT-PRC034-EN

3

Features and Benefits

Figure 1. Factory installed options

B

A

AFoil-Faced Insulation

BQuick Adjust Idler Pulley

CReliaTel™ Microprocessor Controls

D Colored and Numbered Wiring

ELow Ambient Cooling to Zero° F

FHigh and Low Pressure Switches

G Scroll Compressors (R-410A)

J

CE

 

F

 

 

D

 

 

 

K

 

G

 

 

I

 

 

H

M

 

Available in R-410A refrigerant

L

H

 

IHinged Access Doors

J

Single Side Service

N

 

 

Smoke Detector

 

K

 

LFan Failure Switch

M

Clogged Filter Switch

 

Through-the-Base Gas Piping

N

Standard Features

2” throwaway filters provided on 15–25 ton units

Anti-Short Cycle Timer

Belt Drive Motors

Colored and Numbered Wiring

Crankcase Heaters

Dedicated Airflow

Discharge Line Thermostat

Easy Access Low Voltage Terminal Board (LTB)

Foil-Faced and Edge Captured Insulation

High Efficiency Drum and Tube Heat Exchanger

High Efficiency Gas Heat with Hot Surface Ignition

High Pressure Cutout

IAQ Sloped Condensate Drain Pan

Liquid Line Refrigerant Drier

Low Ambient Cooling to 0°F

Microchannel Type Condenser Coils (Major Design Sequence F, T and Y Units Only)

Operating Charge of R-410A

Patented Hybrid Condenser Coil for Easy cleaning

Phase Monitor

Provisions for Through-the-Base Gas and Condensate Drain Connections

Quick Access Panels

Quick Adjust Idler Arm Pulley

ReliaTel™ Microprocessor Controls

4

RT-PRC034-EN

Features and Benefits

Single Point Power

Single Side Service

Standardized Components

Trane Built Scroll Compressors

U-shaped Airflow Pattern

Options

Factory Installed Options*10

2" MERV 8 or MERV 13 Filters with Filter Removal Tool

Black Epoxy Pre-Coated Coils4, 11

CO2 Sensor Wiring (Wiring Only)

Complete Coat™ Microchannel Condenser Coil

Condensate Overflow Switch

Hinged Access Doors

Stainless Steel Drain Pan

Stainless Steel Heat Exchanger with 10 year warranty4

Through the Base Electrical Access

Through the Base Electrical with Circuit Breaker8, 9

Through the Base Electrical with Disconnect Switch5, 8, 9

Factory* or Field Installed Options10

Note: *Some Factory Installed Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.

Explanation of Notes 1–10 located on page 23 following Model Number Description.

Clogged Filter/Fan Failure Switch2, 4

Discharge Air Sensing Kit2, 4

Economizer - Downflow

Electric Heaters4, 6, 9

Frostat2, 4

LonTalk® Communications Interface (LCI)4

ReliaTel™ Options Module7

Trane Communications Interface (TCI)1, 4

Field Installed Options

Barometric Relief

CO2 Sensor

Digital Display Zone Sensor

Economizer - Horizontal

High and Low Static Drive Kits

LP Conversion Kit

Manual Outside Air Damper

Motorized Outside Air Dampers

Oversized Motors

Reference or Comparative Enthalpy3, 4

Remote Potentiometer

Roof Curb (Downflow Only)

Thermostat

Tool-less Hail Guards

Ventilation Override Accessory2

Zone Sensors and Remote Zone Sensors

RT-PRC034-EN

5

Features and Benefits

Other Benefits

Cabinet Design Ensures Water Integrity

Ease of Service, Installation and Maintenance

Mixed Model Build Enables “Fastest in the Industry” Ship Cycle Times

Outstanding Airflow Distribution

ReliaTel™ Controls benefits

Rigorous Testing

Unmatched Product Support

Varitrac

Standard Features

Anti-Short Cycle Timer (Standard with ReliaTel™)

Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance compressor reliability by assuring proper oil return.

Colored And Numbered Wiring

Save time and money tracing wires and diagnosing the unit.

Compressors

Microchannel Condenser Coil

 

Microchannel Flat Tube

 

Header

 

(top removed)

 

Ribbon Fin

Voyager contains the best compressor technology available to achieve the highest possible performance.

Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models.

Microchannel coils have better heat transfer performance due to flat streamlined tubes with small ports, and metallurgical tube-to-fin bond.

Microchannel condenser coil can reduce system refrigerant charge by up to 50% (potential LEED credit) because of smaller internal volume, which can lead to better compressor reliability. Compact all aluminum microchannel coils also help to reduce the unit weight. All-aluminum construction improves recyclability. Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum brazed structure provides better fin protection.

6

RT-PRC034-EN

Features and Benefits

Condenser Coil

Voyager boasts a patentpending 1+1+1 condenser coil, permanently gapped for easy cleaning.

Controls—ReliaTel

ReliaTel™ microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel also provides outputs for building automation systems and expanded diagnostics.

For a complete list of ReliaTel offerings, refer to “Other Benefits,” p. 12.

Conversionless Units

The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field—a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.

Crankcase Heaters

These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.

Discharge Line Thermostat

A bi-metal element discharge line thermostats installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher.

Easy Access Low Voltage Terminal Board Foil Faced Insulation

Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature.

All panels in the evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream.

Heat Exchanger—Drum and Tube

The cabinet (pictured right) features a drum and tube heat exchanger that is manufactured using aluminized steel with stainless steel components for maximum durability.

The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both UL and AGA for cycle test requirements.

Forced Combustion Blower

Negative Pressure Gas Valve

Hot Surface Ignitor

RT-PRC034-EN

7

Features and Benefits

The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements. The negative pressure gas valve will not allow gas flow unless the combustion blower is operating. This is one of our unique safety features.

The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system.

The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability. Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NOx emission requirements.

Low Ambient Cooling

All Voyager microprocessor units have cooling capabilities down to 0°F as standard.

Low Voltage Connections

The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.

Motors

All indoor fan motors are belt drive as standard.

Pressure Cutouts

Low and high pressure cutouts are standard on all Voyager models.

Phase Monitor

The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.

Quick-Access Panels

Remove three or more screws for access to the standardized internal components and wiring.

Quick-Adjust Slider Plate

With the Quick-Adjust Slider Plate, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.

Single Point Power

A single electrical connection powers the unit.

Single Side Service

Single side service is standard on all units.

Sloped Drain Pans

Every Voyager unit has a non-corrosive, sloped drain pan made of pre-painted steel and standard on all units.

8

RT-PRC034-EN

Features and Benefits

Standardized Components

Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager.

Due to standardized components throughout the Voyager line, contractors/owners can stock fewer parts.

Through the Base Condensate

Every unit includes provisions for through the base condensate drain connections. This allows the drain to be connected through the roof curb instead of a roof penetration.

Variety of Options1

Factory Installed Options

Black Epoxy Pre-Coated Coils (W Units Only)

The pre-coated coils are an economical option for protection in mildly corrosive environments.

Circuit Breaker (Required with Through-the-Base Electrical)

This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. Available on all models.

CO2 Sensor Wiring

This is the unit wiring for field installed C02 sensors. Factory-installed C02 sensor wiring saves time and ensures proper unit connections for the field installed C02 sensor kits.

Complete Coat™ Condenser Coil (T/Y Units Only)

The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating shall be available on microchannel condenser coils.

Condensate Overflow Switch

A condensate overflow switch is available to shut the unit down in the event that the condensate drain line becomes clogged. This option protects the unit from water overflowing from the drain pan and entering the base of the units.

Disconnect Switch (Required with

Through-the-Base Electrical)

Factory installed three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. Available on all models.

Codes require a method of assured unit shutdown for servicing. Field-installed disconnects sometimes interfere with service access. Factory installation of unit disconnects reduces costs, assures proper mounting and provides the opportunity to upgrade to unit circuit breaker protection.

1 Refer to Model Number Description for option availability.

RT-PRC034-EN

9

Features and Benefits

High Efficiency Filtration

Voyager units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters provide additional filtration beyond the capabilities of typical 2” throwaway filters. Also, when MERV 8 or MERV 13 filters are ordered, units come equipped with a filter removal tool.

Hinged Access Doors

These doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.

Stainless Steel Drain Pan

For excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a cleanable surface that complement other IAQ solutions such as high efficiency filtration (MERV 8 or 13), or demand control ventilation (CO2).

Stainless Steel Heat Exchanger

The optional stainless steel heat exchanger is constructed of 304 stainless steel. It is resistant to corrosion and oxidation and easy to clean. The high strength to weight ratio allows for high ventilation rates with gas units. With this option, a 10-year stainless steel heat exchanger warranty is standard.

Through-the-Base Electrical Utility Access

An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of downflow units, and through the front of horizontal units. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.

Factory provided through the base openings simplify wiring and piping. Because these utility openings frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.

Factory or Field Installed Options1

Clogged Filter/Fan Failure Switch

A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication.

These sensors allow a zone sensor service light or Integrated Comfort System to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.

Discharge Air Sensing Kit

Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel™ Options Module.

Economizer - Downflow

Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings.

1 Refer to Model Number Description for option availability.

10

RT-PRC034-EN

Features and Benefits

Electric Heaters

Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.

Frostat™

This capillary bulb embedded in the face of the evaporator coil monitors coil temperature to prevent evaporator icing and protect the compressor. Recommended for applications with low leaving air temperatures, low airflow and or high latent load applications.

LonTalk® Communications Interface

The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building Automation System Controls.

Motors

Factory or field installed oversized motors available for high static applications are available.

Oversized Motors

Factory or field installed oversized motors available for high static applications.

Reference or Comparative Enthalpy

Measures and communicates humidity while maximizing comfort control.

Trane Communication Interface (TCI)

Available factory or field installed. This module when applied with the ReliaTel™ easily interfaces with Trane’s Integrated Comfort™ System.

*Refer to Model Number Description for option availability.

Field Installed Options1

Barometric Relief

Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.

CO2 Sensor - Demand Control Ventilation (DCV)

Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand (need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO2 sensor measures the concentration (parts per million, ppm) of CO2 (Carbon Dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone. The CO2 sensor kit is available as a field installed accessory.

Note: Choose factory-installed CO2 sensor wiring option to save time and ensure proper unit connections for the field installed CO2 sensor kits.

Dampers

0–25 percent manual or 0–50 percent motorized outside air dampers are available.

Digital Display Zone Sensor

The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor should be utilized with ReliaTel™ controls.

1 Refer to Model Number Description for option availability.

RT-PRC034-EN

11

Features and Benefits

Economizer - Horizontal

Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings.

High Static Drive

Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.

LP Conversion Kit

Provided for field conversion of gas/electric units from Natural gas to Propane.

Remote Potentiometer

When properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position.

Roof Curbs

Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.

Tool-less Hail Guards

Tool-less, hail protection quality coil guards shall be field-installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage.

Ventilation Override Accessory

With the Ventilation Override Accessory installed, the unit can be set to transition to up to three different preprogrammed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel.

Zone Sensors/Thermostats

Available in programmable, automatic and manual styles.

Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.

Other Benefits

Airflow Distribution

Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution. The U-shaped airflow allows for improved static capabilities.

Cabinet Integrity

For added water integrity, Voyager has a raised 1 1/8” lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.

12

RT-PRC034-EN

Features and Benefits

Easy to Install, Service and Maintain

Because today’s owners are very cost-conscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering outstanding standard features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support.

Outstanding Airflow Distribution

Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.

ReliaTel Controls Benefits

ReliaTel™ controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature.

ReliaTel Control Logic Enhances Quality and Reliability

prevents the unit from short cycling, considerably improving compressor life.

ensures that the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.

Voyager with ReliaTel™ reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.

ReliaTel Makes Installing and Servicing Easy

ReliaTel™ eliminates the need for field installed antishortcycle timer and time delay relays. ReliaTel™ controls provide these functions as an integral part of the unit. The

contractor no longer has to purchase these controls as options and pay to install them. The wiring of the low voltage

connections to the unit and the zone sensors is as easy as 1-1,

ReliaTel™

2-2, and 3-3. This simplified system makes wiring easier for the installer.

ReliaTel Makes Testing Easy

ReliaTel™ requires no special tools to run the Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically.

The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.

As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly.

ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™ Systems.

Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).

Other ReliaTel Benefits

The ReliaTel™ built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation.

RT-PRC034-EN

13

Features and Benefits

ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.

Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.

Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.

The same ReliaTel Board fits all Voyager Packaged Gas/Electrics, Cooling, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.

Rigorous Testing

All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress.

The evaporator and condenser coils are leak tested at 225 psig and pressure tested to 450 psig. All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately.

Every unit receives a 100 percent unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements. Voyager units incorporate either a one piece top or the Trane-Tite-Top (T3). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.

Unmatched Support

Trane Sales Representatives are a Support Group that can assist you with:

Product

Application

Service

Training

Special Applications

Specifications

Computer Programs and much more

VariTrac—Building Automation

System

When Trane’s changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac.

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

RT-PRC034-EN

Application Considerations

Application of this product should be within the cataloged airflow and cooling considerations.

Barometric Relief

This product line offers an optional barometric relief damper for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.

Notes:

The effectiveness of barometric relief damper during economizing operation is system related.

Pressure drop of the return air system should be considered to control building pressurization.

Black Epoxy Coil

The coils are manufactured with a thermoset, vinyl coating that is bonded to the aluminum fin stock prior to the fin stamping process. These coils are an economical option for protection in mildly corrosive environments.

Note: Not to be used where seacoast applications exist.

Clearance Requirements

The recommended clearances identified with unit dimensions should be maintained to ensure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel.

Complete Coat™ Microchannel Condenser Coil

The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salty air and other corrosive environments. This coating shall be available on microchannel condenser coils.

Condensate Trap

The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle.

Heating Operation

The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50 percent outside air or a minimum mixed air temperature of 40°F.

Optional Stainless Steel Heat Exchanger

The optional stainless steel heat exchanger is manufactured with 304 stainless steel. To prevent corrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowed across the heat exchanger is 20°F.

Low Ambient Cooling

The Voyager™ line features, with ReliaTel™ microprocessor controls, low ambient cooling down to 0°F. The following options need to be included/considered when low ambient applications are required: continuous fan operation, crankcase heaters (standard), thermal expansion valves, frostat.

Contact your local Trane Representative for more assistance with low ambient cooling applications.

Unit Pitch

These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be toward access side of the unit.

RT-PRC034-EN

15

Selection Procedure (SI/IP)

SI Selection Procedure

Cooling Capacity

Note: Cooling Capacity Procedure is the same for cooling (TS*), gas/electric (YS*) and heat pump (WS*) units.

Step 1.

Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane calculation methods or any other standard accepted method.

Factors used in unit selection:

Total Cooling Load: 40.0 kW

Sensible Cooling Load: 29.0 kW

Airflow: 8500 m3/h

Electrical Characteristics: 380-415/50/3

Summer Design Conditions:

Entering Evaporator Coil: 27°C DB, 22°C WB,

35°C Outdoor Ambient

External Static Pressure: 127 Pa

Rooftop—downflow configuration accessories

Roof Curb

Economizer

Electric Heat

Step 2.

Size the equipment using Table 4, p. 30. Match the cooling loads at design conditions.

Table 4, p. 30 shows that a TSD155F has a gross cooling capacity of 47.5 kW and 35.6 kW sensible capacity at 8500 m3/h and 35°C DB outdoor ambient with 27°C DB, 19°C WB air entering the evaporator.

To Find Capacity at Intermediate Conditions Not in the Table:

When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.

Note: Extrapolation outside of the table conditions is not recommended.

16

RT-PRC034-EN

Selection Procedure (SI/IP)

Step 3.

In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor, airflow and static pressure. To determine the total unit static pressure (see Table 48, p. 56 for Static Pressure Drops Through Accessories):

External Static Duct System

127 Pa

Standard Filter 25mm

19 Pa

Economizer (100% OA)

12 Pa

Electric Heater Size 27 kW

11Pa

Total Static Pressure

169 Pa

Notes:

1.Reference “Heating Capacity” section on this page for determination of heater size.

2.No additional static add for gas/heat exchanger.

Note: The Evaporator Fan Performance (see Table 20, p. 44) has already accounted for the pressure drop for standard filters and wet coils (see note below Table 20, p. 44). Therefore, the actual total static pressure is 169 - 19 (from Table 48, p. 56) = 150 Pa.

With 8500 m3/h and 150 Pa. Table 20, p. 44 shows 1.12 kW for this unit. The formula below can be used to calculate Fan Motor Heat:

Fan Motor Heat = 1.23 * Fan Power (kW) 1.23 * 1.12 kW = 1.3776 kW

Now subtract the fan motor heat from the gross cooling capacity of the unit:

Net Total Cooling Capacity = 47.5 - 1.37 = 46.12

Net Sensible Cooling Capacity = 35.6 - 1.37 = 34.22

Step 4.

If the performance will not meet the required load of the building, total or sensible cooling load, try a selection at the next higher size unit.

Heating Capacity

Note: Heating capacity procedures DIFFER for cooling (TS*), gas/electric (YS*) and heat pump (WS*) units.

Step 1.

Calculate the building heating load using the Trane calculation form or other standard accepted method.

Step 2.

Size the system heating capacity to match the calculated building heating load. The following are building heating requirements:

TS* cooling units:

380 volt/three-phase Power Supply

Total heating load of 20.5 kW

Airflow of 8500 m3/h

The electric heat accessory capacities are listed in Table 52, p. 62. From the table, a 26.9 kW heater at 415 volts is selected. In order to determine capacity at 380 volts, the heater voltage correction

RT-PRC034-EN

17

Selection Procedure (SI/IP)

factor from Table 53, p. 62 must be used. Therefore, 26.9 kW x 0.84 (voltage correction factor) = 22.59 kW.

YS* gas/electric:

The fuel used is natural gas with a total heating load of 30 kW. Table 2, p. 26 shows 61.1 kW and 85.5 kW input models. The output capacities of these furnaces are 49.6 kW and 69.4 kW, respectively. The low heat model with 49.6 kW output best matches the building requirements.

WS* heat pumps:

Total heating load of 30.0 kW. Outdoor ambient (Winter) of -9°C DB and indoor return of 21°C DB and an airflow of 8500 m3/h. The unit is using a 380 V power supply. Use the integrated portion of Table 16, p. 42 for the WC*155 to determine capacity at winter design conditions. The mechanical heating portion of the heat pump will provide 20.9 kW.

Step 3.

Note: This step does not apply to TS* and YS* units.

WS* heat pumps:

Because 22.1 kW is less than the building's required heating capacity at winter design condition, a supplementary heater must be selected.

30.0 - 20.9 = 9.1 kW

From Table 62, p. 64, a 13.4 kW heater at 415 V is selected. To find the capacity at 380 V, the heater voltage correction factor from Table 63, p. 64 must be used. Therefore, 13.4 kW x 0.84 (voltage correction factor) = 11.26 kW. This heater will be adequate to do the job.

Air Delivery Selection

Note: Air Deliver procedures is the same for cooling (TS*), gas/electric (YS*) and heat pump (WS*) units.

External static pressure drop through the air distribution system has been calculated to be 150 Pa. From Table 48, p. 56, static pressure drop through the economizer is 12 Pa and the 27 kW heater is 12 Pa (127 + 12 + 12). Enter (Table 20, p. 44) for a TSD155F at 8500 m3/h and 150 Pa static pressure.

The standard motor at 566 rpm will give the desired airflow at a rated kW of 1.12.

18

RT-PRC034-EN

Selection Procedure (SI/IP)

IP Selection Procedure

Cooling Capacity

Note: Cooling Capacity Procedure is the same for cooling (TS*), gas/electric (YS*) and heat pump (WS*) units.

Step 1.

Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane calculation methods or any other standard accepted method.

Factors used in unit selection:

Total Cooling Load: 140 MBh

Sensible Cooling Load: 100 MBh

Airflow: 5000 cfm

Electrical Characteristics: 380-415/50/3

Summer Design conditions:

Entering Evaporator Coil: 80 DB, 73 WB

Outdoor Ambient: 95 DB

External Static pressure: 0.50 in. wg

Rooftop - downflow configuration

Accessories

Roof Curb

Economizer

Electric Heat

Step 2.

As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal Btu/h per ton (12 MBh per ton); then round up to the nearest unit size.

140 MBh / 12 MBh = 11.6 tons

Step 3.

Table 5, p. 31 shows that a TSD155F has a gross cooling capacity of 162.2 MBh and 121.4 MBh sensible capacity at 5000 cfm and 95 DB outdoor ambient with 80 DB, 73 WB air entering the evaporator.

To Find Capacity at Intermediate Conditions Not in the Table:

When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.

Note: Extrapolation outside of the table conditions is not recommended.

RT-PRC034-EN

19

Selection Procedure (SI/IP)

Step 4.

In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor, cfm and static pressure. To determine the total unit static pressure you add the external static pressure to the additional static related by the added features (see Table 49, p. 57 for Static Pressure Drops Through Accessories):

External Static Duct System

0.50 wg

Standard Filter 1in.

0.08 wg

Economizer (100% OA)

0.05 wg

Electric Heater Size 27 kW

0.05 wg

Total Static Pressure

0.68 wg

Notes:

1.Reference “Heating Capacity” section on this page for determination of heater size.

2.No additional static add for gas/heat exchanger.

Note: The Evaporator Fan Performance Table 21, p. 44 has already accounted for the pressure drop for standard filters and wet coils (see note below Table 21, p. 44). Therefore, the actual total static pressure is 0.68 - 0.08 (from Table 49, p. 57) = 0.60 wg.

With 5000 cfm and 0.60 wg, Table 21, p. 44 shows 1.50 bhp for this unit. The formula below can be used to calculate Fan Motor Heat:

Fan Motor Heat = 3.15 * Fan bhp 3.15 * 1.50 = 4.725 MBh

Now subtract the fan motor heat from the gross cooling capacity of the unit:

Net Total Cooling Capacity =

162.2 - 4.725 = 157.475 MBh

Net Sensible Cooling Capacity =

121.4 - 4.725 = 116.675 MBh

Step 5.

If the performance will not meet the required load of the building, total or sensible cooling load, try a selection at the next higher size unit.

20

RT-PRC034-EN

Selection Procedure (SI/IP)

Heating Capacity

Note: Heating capacity procedures DIFFER for cooling (TS*), gas/electric (YS*) and heat pump (WS*) units.

Step 1.

Calculate the building heating load using the Trane calculation form or other standard accepted method.

Step 2.

Size the system heating capacity to match the calculated building heating load. The following are building heating requirements:

TS* cooling units:

380 volt/3 phase Power Supply

Total heating load of 75.0 MBh 5000 cfm

The electric heat accessory capacities are listed in Table 52, p. 62. From the table, a 26.9 kW heater will deliver 91.73 MBh at 415 volts. In order to determine capacity at 380 volts, the heater voltage correction factor from Table 53, p. 62 must be used. Therefore, 91.73 MBh x 0.84 (voltage correction factor) = 77.05 MBh.

YS* gas/electric:

Fuel natural gas and a total heating load of 115 MBh. Table 2, p. 26 shows 208.3 MBh and 291.7 MBh input models. The output capacities of these furnaces are 169.2 MBh and 236.7 MBh respectively. The low heat model with 169.2 MBh output best matches the building requirements.

WS* heat pumps:

Total heating load of 100 MBh. Outdoor ambient (Winter) of 17 DB and Indoor Return of 70 DB and an airflow of 5000 cfm. The unit is using a 380 V power supply. Use the integrated portion of Table 17, p. 42 for the WC*155 to determine capacity at winter design conditions. The mechanical heating portion of the heat pump will provide 71.2 MBh.

Step 3.

Note: This step does not apply to TS* and YS* units.

WS* heat pumps:

Because 71.2 MBh is less than the building’s required heating capacity at winter design conditions, a supplementary heater must be selected.

100 MBh - 71.2 MBh = 28.8 MBh

From Table 62, p. 64, a 13.4 kW heater at 415 V is selected. To find the capacity at 380 V, the heater voltage correction factor from Table 63, p. 64 must be used. Therefore, 13.4 kW x 0.84 (voltage correction factor) = 11.26 kW. This heater will be adequate to do the job. 38.3 MBh.

Air Delivery Selection

Note: Air Delivery procedures is the same for cooling (TS*), gas/electric (YS*) and heat pump (WS*) units.

External static pressure drop through the air distribution system has been calculated to by

0.60 inches of water. From Table 49, p. 57, static pressure drop through the economizer is 0.05 and the 26.9 kW heater is 0.05 inches of water (0.50 + 0.05 + 0.05). Enter (Table 21, p. 44) for a TSD155 at 5000 cfm and 0.60 static pressure. The standard motor at 566 rpm will give the desired airflow at a rated bhp of 1.50.

RT-PRC034-EN

21

Model Number Descriptions

T

 

S

 

D

1

5

5

 

F

 

D

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

Digit 1 — Unit Type

T

=

Packaged Cooling, Electric Heat

Y

=

Packaged Gas/Electric

W= Packaged Heat Pump, Electric Heat

Digit 2 — Efficiency

S = Standard

Digit 3 — Airflow Configuration

D

=

Downflow

H

=

Horizontal

Digit 4, 5, 6 — Nominal Gross Cooling Capacity (MBh)

155 = 15 Tons Standard Efficiency

175 = 17½ Tons Standard Efficiency

200 = 20 Tons Standard Efficiency

250 = 25 Tons Standard Efficiency

Digit 7 — Major Design

Sequence

E= Round Tube Plate Fin Type Condenser Coils

F= Microchannel Type Condenser Coils

Digit 8 — Voltage Selection

D

=

380-415/50/3

T

=

200/50/311

Digit 9 — Unit Controls

R = Reliatel

Digit 10 — Heating Capacity

Note:

(Applicable to Digit 1 T/W models

 

 

only)

0

=

No Heat

G

=

18 kW Electric Heat

K

=

27 kW Electric Heat

N

=

36 kW Electric Heat

P

=

54 kW Electric Heat

R

=

72 kW Electric Heat

Note:

(Applicable to Digit 1 Y models

 

 

only)

H

=

Gas Heat - High

L

=

Gas Heat - Low

X

=

Gas Heat - SS Ht Ex - Low

Z

=

Gas Heat - SS Ht Ex - High

Digit 11 — Minor Design

Sequence

Digit 12, 13 — Service Sequence

Digit 14 — Fresh Air Selection

0 = No Fresh Air

A= Manual Damper

B= Motorized Damper

D

=

Econ Dry Bulb w/ Barometric

 

 

Relief

F

=

Econ Reference Enthaply w/

 

 

Barometric Relief

H= Econ Comparative Enthaply w/ Barometric Relief

22

Digit 15 — Supply Fan/Drive

Type/Motor

0= Standard Motor

1= Oversized Motor

3 = High Efficiency Motor

6= Single Zone Variable Air Volume Standard Motor

7= Multi-Speed Standard Motor

8= Single Zone Variable Air Volume Oversized Motor

9= Multi-Speed Oversized Motor

A= Single Zone Variable Air Volume Standard Motor w/ Shaft Ground Ring

B= Multi-Speed Standard Motor w/ Shaft Ground Ring

C= Single Zone Variable Air Volume Oversized Motor w/ Shaft Ground Ring

D= Multi-Speed Oversized Motor w/ Shaft Ground Ring

Digit 16 — Hinged Service

Access / Filters

0

=

Standard Panels/Standard Filters

A

=

Hinged Access/Standard Filters

Digit 17 — Condenser Coil

Protection

0= Standard Coil

1= Standard Coil With Hail Guard

2= Black Epoxy Pre-Coated Coil

3= Black Epoxy Pre-Coated Coil With Hail guard

4= CompleteCoat™Condenser Coil

5= CompleteCoat™Condenser Coil with Hail Guard

Digit 18 — Through The Base

Provisions

0 = No Through The Base Provisions

A= Through The Base Electric

B= Through The Base Gas

C= Through The Base Electric/Gas

D= Through The Base Access

Digit 19 — Disconnect Switch/

Circuit Breaker

0= No Disconnect/circuit break

1= Unit Mounted Non-Fused Disconnect Switch

2= Unit Mounted Circuit Breaker

Digit 20 — Convenience Outlet

Option

0 = Without Convenience Outlet

A= Unpowered Convenience Outlet

B= Powered Convenience Outlet

0

 

A

 

A

 

 

 

 

 

10

11

12

Digit 21 — Communications

Options

0= Without Communications Options

6= Building Automation Control Network Communications Interface

Digit 22 — Refrigeration System Option

0 = Standard refrigeration system

Digit 23 — Refrigeration

Controls

0= Without Refrigeration Controls

1= Frostat

Digit 24 — Smoke Detector

0 = Without Smoke Detector

A= Return Air Smoke Detector

B= Supply Air Smoke Detector

C= Return/Supply Air Smoke Detector

D= Plenum Smoke Detector

Digit 25 — System Monitoring

Controls

0= No Monitoring Controls

1= Clogged Filter Switch

2= Fan Failure Switch

3= Discharge Air Sensing

4= Clogged Filter Switch and Fan Failure

5= Clogged Switch and Discharge Air Sensing

6= Fan Failure Switch and Discharge Air Sensing

7= Clogged Filter Switch, Fan Failure

Switch and Discharge Air Sensing

A= Condensate Drain Pan Overflow Switch

B= Clogged Filter Switch and Condensate Drain Pan Overflow Switch

C= Fan Failure Switch and Condensate Drain Pan Overflow Switch

D= Discharge Air Sensing and Condensate Drain Pan Overflow Switch

E= Clogged Filter Switch, Fan Failure Switch and Condensate Drain Pan Overflow Switch

F= Clogged Filter Switch, Discharge Air Sensing Tube and Condensate Drain Pan Overflow Switch

G= Fan Failure Switch, Discharge Air Sensing Tube and Condensate Drain Pan Overflow Switch

H= Clogged Filter Switch, Fan Failure Switch, Discharge Air Sensing and Condensate Drain Pan Overflow Switch

RT-PRC034-EN

Model Number Descriptions

Digit 26 - System Monitoring

Controls

0 No Monitoring Controls

A Demand Control Ventilation (CO2)12

Digit 27 - Unit Hardware

Enhancements

0No Enhancements

1Stainless Steel Drain Pan

Options

Factory Installed Options*10

Black Epoxy Pre-Coated Coils4

CO2 Sensor Wiring (Wiring Only)

Complete Coat Microchannel Coil

Condensate Overflow Switch

Hinged Access Doors

MERV 8 or 13 with Filter Removal Tool

Stainless Steel Drain Pan

Stainless Steel Heat Exchanger with 10 year warranty4

Through the Base Electrical Access

Through the Base Electrical with Circuit Breaker8, 9

Through the Base Electrical with Disconnect Switch5, 8, 9

Factory* or Field Installed Options10

Clogged Filter/Fan Failure Switch2, 4

Discharge Air Sensing Kit2, 4

Economizer - Downflow

Electric Heaters4, 6, 9

Frostat2, 4

LonTalk® Communications Interface (LCI)4

ReliaTel Options Module7

Field Installed Options

Barometric Relief

CO2 Sensing

Digital Display Zone Sensor

Dual Thermistor Remote Zone Sensor

Economizer - Horizontal

High and Low Static Drive Kits

LP Conversion Kit

Manual Outside Air Damper

Motorized Outside Air Dampers

Oversized Motors

Reference or Comparative Enthalpy3, 4

Remote Potentiometer

Roof Curb (Downflow Only)

Thermostat

Tool-less Hail Guards

Trane Communications Interface (TCI)1, 4

Ventilation Override Accessory2

Zone and Remote Zone Sensors

Model Number Notes

1.TCI is for use with non-VariTrac systems and VariTrac systems.

2.Requires ReliaTel options module.

3.Requires Economizer.

4.Available factory installed on downflow AND horizontal units. Verify with ordering system.

5.Cannot be fused.

6.Must be factory installed when using Through-the-Base Options.

7.ReliaTel Options Module is required when ordering the following accessories (Factoryor Field-Installed Options): Clogged Filter Switch, Fan Fail Switch, Discharge Air Sensing Kit, Frostat, Ventilation Override.

8.Unit mounted disconnect and circuit breakers are mutually exclusive of each other.

9.Through-the-base electrical option or Horizontal Side Access must be ordered with either unit mounted disconnect or circuit breaker. When adding heat, must order Trane Electric Heat.

10.All Factory Installed Options are Built-to-Order. Check order services for estimated production cycle.

11.Available on Heat Pump (W) units only.

12.Demand Control Ventilation Option includes wiring only. The C02 sensor is a field-installed only option.

Note: *Some Factory Installed Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.

RT-PRC034-EN

23

General Data

Table 1. TS* general data

 

 

15–25 Tons Downflow and Horizontal Units

 

 

 

 

 

 

Model

TS*155FD

TS*175FD

TS*200FD

TS*250FD

 

 

 

 

 

Cooling Performance(a)

 

 

 

 

ARI Gross Capacity kW (MBh)

44.8 (153)

51.2 (174.8)

62.7 (214.1)

68.3 (233.0)

COP/EER(b)

3.47 / 11.8

3.51 / 12.0

3.14 / 10.7

3.10 / 10.8

Nominal Airflow - m3/h (cfm)

7480 (4400)

9000 (5300)

10400 (6125)

12240 (7200)

ARI Airflow - m3/h (cfm)

44.0 (150)

49.8 (170.0)

61.0 (208.2)

66.0 (225.3)

ARI Net Capacity - kW (MBh)

13

14.6

20.0

21.6

System Power - kW

12.9

14.5

19.6

21.0

 

 

 

 

 

Compressor

 

 

 

 

No./Type

2/Scroll

2/Scroll

2/Scroll

2/Scroll

 

 

 

 

 

Sound Rating dB(c)

9.0

9.2

9.2

9.2

Outdoor Coil - Type

Microchannel

Microchannel

Microchannel

Microchannel

Coil Width mm (in.)

25.4 (1)

25.4 (1)

25.4 (1)

25.4 (1)

Face Area - m2 (sq. ft.)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

Rows/Fins per inch

1 / 20

1 / 20

1 / 20

1 / 20

 

 

 

 

 

Indoor Coil - Type

Hi-Performance

Hi-Performance

Hi-Performance

Hi-Performance

Tube Size OD - in.

0.3125

0.3125

0.3125

0.3125

Face Area - m2 (sq. ft.)

(2.42) 26

(2.42) 26

(2.42) 26

(2.42) 26

Rows/Fins per inch

3/ 15

4 / 15

4 / 15

4 / 15

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Drain Connection No./Size - in.

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

 

 

 

 

 

Outdoor Fan - Type

Propeller

Propeller

Propeller

Propeller

No. Used/Diameter - mm (in.)

2 / 660 (26)

2 / 660 (26)

2 / 660 (26)

2 / 710(28)

Drive Type/No. Speeds

Direct / 1

Direct / 1

Direct / 1

Direct / 1

Airflow - m3/h (cfm)

15630 (9200)

18860 (11100)

18000 (10600)

19880 (11700)

No. Motors/Power - W (HP)

2 / 250(0.33)

2 / 560(0.75)

2 / 560(0.75)

2 / 560(0.75)

Motor RPM

925

950

950

950

 

 

 

 

 

Indoor Fan - Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

1

Diameter x Width - mm (in.)

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

Drive Type/No. Speeds

Belt / 1

Belt / 1

Belt / 1

Belt / 1

No. Motors

1

1

1

1

Standard/Oversized Motor Power —

1500(2.0) / 2200(3.0)

2200(3.0) / 3700(5.0)

2200(3.0) / 3700(5.0)

3700(5.0) / N/A

W (HP)

 

 

 

 

Motor RPM - Standard/Oversized

1450 / 2850

2850 / 2920

2850 / 2920

2920/N/A

 

 

 

 

 

24

RT-PRC034-EN

General Data

TS* General Data

Table 1. TS* general data (continued)

 

 

15–25 Tons Downflow and Horizontal Units

 

 

 

 

 

 

Model

TS*155FD

TS*175FD

TS*200FD

TS*250FD

 

 

 

 

 

Filters—Type/Furnished

 

 

 

 

Type Furnished

Throwaway

Throwaway

Throwaway

Throwaway

Number Size Recommended

 

 

 

 

Downflow—mm

(4)508x508x50

(4)508x508x50

(4)508x508x50

(4)508x508x50

(4)508x635x50

(4)508x635x50

(4)508x635x50

(4)508x635x50

 

Downflow—in

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

Horizontal—mm

(8)508x635x50

(8)508x635x50

(8)508x635x50

(8)508x635x50

Horizontal—in

(8)20x25x2

(8)20x25x2

(8)20x25x2

(8)20x25x2

 

 

 

 

 

Refrigerant Charge

5.2/2.7 (11.4/6)

6.5/3.4 (14.4/7.6)

6.1/3.2 (13.5/7)

4.8/4.8 (10.5/10.5)

R-410A kg (lb)(d)

 

 

 

 

(a)Cooling Performance is rated at 35°C (95°F) ambient, 26.7°C (80°F) entering dry bulb, 19.4°C (67°F) entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation ±20% of nominal airflow. Ratings shown are tested and certified in accordance with ARI Standard 210/240 or 340/360 certification program.

(b)EER is rated at ARI conditions and in accordance with DOE test procedures.

(c)Sound Ratings shown are tested in accordance with ARI Standard 270 or 370.

(d)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC034-EN

25

General Data

 

 

 

 

 

 

 

YS* General Data

Table 2. YS* general data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15–25 Tons Downflow and Horizontal Units

 

 

 

 

 

 

 

Model

YS*155FD

YS*175FD

YS*200FD

YS*250FD

 

 

 

 

 

 

 

 

 

Cooling Performance(a)

 

 

 

 

 

 

 

 

ARI Gross Capacity—kw (MBh))

44.8 (153)

51.2 (174.8)

62.7 (214.1)

68.3 (233.0)

COP/EER(b)

3.47 / 11.8

3.51 / 12.0

3.14 / 10.7

3.10 / 10.8

Nominal Airflow—m3/h (cfm)

7480 (4400)

5300

6125

7175

ARI Airflow—m3/h (cfm)

44.0 (150)

49.8 (170.0)

61.0 (208.2)

66.0 (225.3)

System Power—kW

13

14.6

20.0

21.6

 

 

 

 

 

 

 

 

 

Heating Performance(c)

 

 

 

 

 

 

 

 

Heating Models

Low

High

Low

High

Low

High

Low

High

Heating Input—(MBh)

61.1(208.3)

85.5(291.7)

61.1(208.3)

85.5(291.7)

61.1(208.3)

97.7(333.3)

61.1(208.3)

97.7(333.3)

1st Stage (2 Stage Only)—(MBh)

42.7(145.8)

61.1(208.3)

42.7(145.8)

61.1(208.3)

42.7(145.8)

73.3(250.0)

42.7(145.8)

73.3(250.0)

Heating Output—(MBh)

49.6(169.2)

69.4(236.7)

49.6(169.2)

69.4(236.7)

49.6(169.2)

79.1(270.0)

49.6(169.2)

79.1(270.0)

1st Stage (2 Stage Only)—(MBh)

34.7(118.3)

49.6(169.2)

34.7(118.3)

49.6(169.2)

34.7(118.3)

59.3(202.5)

34.7(118.3)

59.3(202.5)

Steady State Efficiency %

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

23.7(81.0)

 

 

 

 

 

 

 

 

 

Numbers of Gas Heat

 

 

 

 

 

 

 

 

Stages

 

 

 

 

 

 

 

 

Number of Gas Burners

1

1

1

1

1

1

1

1

Gas Connection Pipe Size—in.

1/2

3/4

1/2

3/4

1/2

3/4

1/2

3/4

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

Number/Type

2/Scroll

2/Scroll

2/Scroll

2/Scroll

 

 

 

 

 

Sound Rating dB(d)

9.0

9.2

9.2

9.2

Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

Microchannel

Microchannel

Microchannel

Microchannel

Coil Width—mm (in.)

25.4 (1)

25.4 (1)

25.4 (1)

25.4 (1)

Face Area—m3 (sq. ft.)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

3.27 (35.2)

Rows / Fins per inch

1 / 20

1 / 20

1 / 20

1 / 20

 

 

 

 

 

 

 

 

 

Indoor Coil

 

 

 

 

 

 

 

 

Type

Hi-Performance

Hi-Performance

Hi-Performance

Hi-Performance

Tube Size (in.) ID

0.3125

0.3125

0.3125

0.3125

Face Area—m3 (sq. ft.)

(2.42) 26

(2.42) 26

(2.42) 26

(2.42) 26

Rows/Fins per inch

3/15

4/15

4/15

4/15

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Drain Connection Number/

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

Size—in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Fan

 

 

 

 

 

 

 

 

Type

Propeller

Propeller

Propeller

Propeller

Number Used/Diameter—mm

2/660 (26)

2/660 (26)

2/660 (26)

2/710 (28)

(in.)

 

 

 

 

 

 

 

 

Drive Type/No. Speeds

Direct/1

Direct/1

Direct/1

Direct/1

Airflow—m3/h (CFM)

15630 (9200)

18860 (11100)

18000 (10600)

19880 (11700)

Number Motors/W (HP)

2/250(0.33)

2/560(0.75)

2/560(0.75)

2/560(0.75)

Motor RPM

925

950

950

950

 

 

 

 

 

 

 

 

 

26

RT-PRC034-EN

General Data

YS* General Data

Table 2. YS* general data (continued)

 

 

 

 

15–25 Tons Downflow and Horizontal Units

 

 

 

 

 

 

 

 

 

Model

YS*155FD

YS*175FD

YS*200FD

YS*250FD

 

 

 

 

 

 

 

 

Indoor Fan

 

 

 

 

 

 

 

Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

Number Used

1

 

1

 

1

 

1

Diameter x Width—mm (in.)

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

457x457 (18x18)

Drive Type/No. Speeds

Belt / 1

Belt / 1

Belt / 1

Belt / 1

Number Motors

1

 

1

 

1

 

1

Motor W (HP)

1500 (2.0) / 2200 (3.0)

 

2200 (3.0) / 3700 (5.0)

 

2200 (3.0) / 3700 (5.0)

 

3700 (5.0) / N/A

(Standard/Oversized)

 

 

 

 

 

 

 

 

 

 

Motor RPM

1450 / 2850

 

2850 / 2920

 

2850 / 2920

 

2920/N/A

(Standard/Oversized)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Filters

 

 

 

 

 

 

 

Type Furnished

Throwaway

Throwaway

Throwaway

Throwaway

Number Size Recommended

 

 

 

 

 

 

 

Downflow—mm

(4)508x508x50

(4)508x508x50

(4)508x508x50

(4)508x508x50

(4)508x635x50

(4)508x635x50

(4)508x635x50

(4)508x635x50

 

 

Downflow—in.

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

(4)20x20x2 (4)20x25x2

Horizontal—mm

(8)508x635x50

(8)508x635x50

(8)508x635x50

(8)508x635x50

Horizontal—in.

(8)20x25x2

(8)20x25x2

(8)20x25x2

(8)20x25x2

 

 

 

 

 

 

 

 

Refrigerant Charge

 

 

 

 

 

 

 

R-410A kg (lb)(e)

 

5.2/2.7 (11.4/6)

 

6.5/3.4 (14.4/7.6)

 

6.1/3.2 (13.5/7)

 

4.8/4.8 (10.5/10.5)

 

 

 

 

(a)Cooling Performance is rated at 35°C (95°F) ambient, 26.7°C (80°F) entering dry bulb, 19.4°C (67°F) entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation ±20% of nominal airflow. Ratings shown are tested and certified in accordance with ARI Standard 210/240 or 340/360 certification program.

(b)EER is rated at ARI conditions and in accordance with DOE test procedures.

(c)Heating performance unit settings and data were established under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 610 meters (2000 ft.). For elevations above 610 meters (2000 ft.), ratings should be reduced at the rate of 4% for each 305 meters (1000 ft.) above sea level.

(d)Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(e)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC034-EN

27

General Data

WS* General Data

Table 3. WS* general data

 

15–20 Tons Downflow and Horizontal Units

 

 

 

Model

WS*155ED, ET

WS*200ED, ET

 

 

 

Cooling Performance(a)

 

 

ARI Gross Capacity—kW (MBh)

44.1 (150.7)

62.9 (214.8)

COP/EER(b)

3.3 (11.3)

2.9 (9.9)

Nominal Airflow—m3/h (cfm)

8500 (5000)

(11890) 7000

ARI Airflow—m3/h (cfm)

8500 (5000)

(11890) 7000

ARI Net Capacity—kW (MBh)

43.2 (147.5)

61.0 (208.5)

System Power—kW

13.1

21.0

 

 

 

Heating Performance(a)

 

 

High Temperature Capacity—kW (MBh)

41.8 (142.7)

61.4 (209.6)

COP

3.8

3.6

System Power—kW

11.0

17.2

 

 

 

Compressor

 

 

Number/Type

2 / Scrolls

2 / Scrolls

 

 

 

Sound Rating dB(c)

9.0

9.2

Outdoor Coil

 

 

Type

Hi-Performance

Hi-Performance

Refrigerant Control

Expansion Valve

Expansion Valve

Tube Size (in.) OD

0.3125

0.3125

Face Area-m3 (sq. ft.)

3.3 (35.2)

4.0 (42.53)

Rows / Fins per inch

3 / 16

3 / 16

 

 

 

Indoor Coil

 

 

Type

Hi-Performance

Hi-Performance

Tube Size (in.) ID

0.3125

0.3125

Face Area-m3 (sq. ft.)

2.4 (26)

2.9 (31.42)

Rows / Fins per inch

4 / 15

4 / 15

Refrigerant Control

Short Orifice

Short Orifice

Drain Connection Number/Size (in.)

1/1.00 NPT

1/1.00 NPT

 

 

 

Outdoor Fan

 

 

Type

Propeller

Propeller

Number Used/Diameter—mm (in.)

2 / 660 (26)

2 / 710(28)

Drive Type/No. Speeds

Direct / 1

Direct / 1

Airflow—m3/h (CFM)

15300 (9000)

20900 (12300)

Number Motors/W (HP)

2 / 250 (0.33)

2 / 560 (0.75)

Motor RPM

925

950

 

 

 

28

RT-PRC034-EN

General Data

WS* General Data

Table 3. WS* general data (continued)

 

15–20 Tons Downflow and Horizontal Units

 

 

 

Model

WS*155ED, ET

WS*200ED, ET

 

 

 

Indoor Fan

 

 

Type

FC Centrifugal

FC Centrifugal

Number Used

1

1

Diameter x Width—mm (in.)

457x457 (18x18)

457x457 (18x18)

Drive Type/No. Speeds

Belt / 1

Belt / 1

Number Motors

1

1

Motor W (HP) (Standard/Oversized)

1500 (2.0) / 2200 (3.0)

2200 (3.0) / 3700 (5.0)

Motor RPM (Standard/Oversized)

1450 / 2850

2850 / 2920

 

 

 

Filters

 

 

Type Furnished

Throwaway

Throwaway

Number Size Recommended

 

 

Downflow—mm

(4)508x508x50

(8)20x20x2 (4)20x16x2

Downflow

(4)508x635x50

(8)508x508x50

Downflow—in

(4)20x20x2 (4)20x25x2

(4)508x406x50

Horizontal—mm

(8)508x635x50

(12)508x508x50

Horizontal—in

(8)20x25x2

(12)20x20x2

 

 

 

Refrigerant Charge

 

 

R-410A kg (lb)(d)

6.6 / 6.4 (14.5 / 14.2)

9.0 / 8.2 (19.75 / 18)

(a)Cooling Performance is rated at 35°C (95°F) ambient, 26.7°C (80°F) entering dry bulb, 19.4°C (67°F) entering wet bulb. Heating Performance is rated at 20°C (68°F) ambient, 8.3°C (47°F) entering dry bulb, 6.1°C (43°F) entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal airflow. Rated in accordance with ARI Standard 210/240 or 340/360.

(b)EER is rated at ARI conditions and in accordance with DOE test procedures.

(c)Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(d)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC034-EN

29

Performance Data

Table 4. Gross cooling capacities T/YS*155FD (SI)

 

 

 

 

 

 

 

 

 

Ambient Temperature (°C)

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

35

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter

 

 

 

 

 

 

 

Entering Wet Bulb Temperature (°C)

 

 

 

 

 

 

 

 

16

19

22

 

16

19

22

 

16

19

22

Airflow

DB

 

 

m3/h

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

 

TGC SHC TGC SHC TGC SHC

 

TGC

SHC

TGC

SHC

TGC

SHC

 

24

42.3

34.8

46.1

25.1

51.3

17.9

 

38.7

32.6

42.6

23.7

47.7

16.7

 

34.7

30.2

38.6

22.0

43.8

15.3

7140

27

44.2

41.1

47.1

33.6

51.3

20.4

 

41.0

38.8

43.9

32.1

48.1

19.6

 

37.4

36.3

40.3

30.2

44.5

18.5

30

46.3

46.3

48.2

41.0

51.4

29.9

 

43.4

43.4

45.4

39.3

48.6

28.9

 

40.1

40.1

42.1

37.3

45.3

27.7

 

 

 

 

33

48.5

48.5

49.4

47.2

51.7

38.3

 

45.9

45.9

46.9

45.4

49.2

37.2

 

43.0

43.0

44.0

43.3

46.3

35.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

43.5

36.1

47.0

26.4

51.9

18.2

 

39.9

34.0

43.5

25.0

48.4

16.9

 

35.9

31.6

39.6

23.3

44.5

15.6

7820

27

45.5

42.6

48.1

35.0

52.0

21.7

 

42.3

40.3

44.9

33.5

48.9

20.9

 

38.7

37.8

41.3

31.6

45.3

19.8

30

47.7

47.7

49.3

42.4

52.2

31.3

 

44.8

44.8

46.5

40.8

49.4

30.3

 

41.5

41.5

43.2

38.8

46.2

29.1

 

 

 

 

33

49.9

49.9

50.6

48.7

52.6

39.7

 

47.4

47.4

48.1

46.9

50.1

38.6

 

44.7

44.5

45.2

44.8

47.2

37.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

44.5

37.4

47.8

27.6

52.4

18.3

 

41.0

35.3

44.3

26.2

48.9

17.1

 

37.0

32.9

40.4

24.5

45.0

15.8

8500

27

46.6

43.9

49.0

36.3

52.6

22.9

 

43.4

41.7

45.8

34.7

49.4

22.1

 

39.8

39.1

42.2

32.9

45.9

21.0

30

48.9

48.9

50.2

43.8

52.9

32.5

 

46.0

46.0

47.4

42.1

50.1

31.6

 

42.7

42.7

44.2

40.1

46.9

30.3

 

 

 

 

33

51.2

51.2

51.6

50.1

53.3

41.0

 

48.7

48.7

49.1

48.3

50.8

40.0

 

46.2

46.2

46.2

46.2

48.0

38.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

45.4

38.6

48.4

28.7

52.7

18.4

 

41.8

36.4

44.9

27.3

49.2

17.2

 

37.9

34.0

41.0

25.6

45.4

15.9

9180

27

47.6

45.2

49.7

37.4

53.0

24.0

 

44.4

42.9

46.5

35.9

49.9

23.1

 

40.8

40.4

42.9

34.1

46.3

22.0

30

49.9

49.9

51.0

45.0

53.4

33.7

 

47.1

47.1

48.2

43.4

50.6

32.7

 

43.8

43.8

45.0

41.4

47.4

31.5

 

 

 

 

33

52.3

52.3

52.4

51.5

53.9

42.3

 

49.5

49.5

50.0

49.7

51.4

41.2

 

47.1

47.1

47.1

47.1

48.6

39.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient Temperature (°C)

 

 

 

 

 

 

 

 

 

 

 

45

 

 

 

 

 

49

 

 

 

 

 

52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter

 

 

 

 

 

 

 

Entering Wet Bulb Temperature (°C)

 

 

 

 

 

 

 

 

16

19

22

 

16

19

22

 

16

19

22

Airflow

DB

 

 

m3/h

(°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TGC

SHC

TGC

SHC

TGC

SHC

 

TGC SHC TGC SHC TGC SHC

 

TGC

SHC

TGC

SHC

TGC

SHC

 

24

30.3

27.5

34.3

20.0

39.5

13.8

 

28.0

26.0

31.9

18.9

37.1

13.0

 

25.5

24.5

29.5

17.7

34.7

12.1

7140

27

33.3

33.3

36.3

28.1

40.5

17.1

 

31.1

31.1

34.1

26.9

38.4

16.2

 

28.9

28.9

31.8

25.7

36.1

15.3

30

36.4

36.4

38.4

35.1

41.7

26.1

 

34.4

34.4

36.4

33.8

39.7

25.3

 

32.3

32.3

34.3

32.5

37.6

24.3

 

 

 

 

33

40.6

40.6

40.6

40.6

43.0

34.1

 

38.8

38.8

38.8

38.8

41.1

33.1

 

36.9

36.9

36.9

36.9

39.2

32.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

31.6

28.9

35.2

21.3

40.2

14.1

 

29.2

27.4

32.9

20.2

37.8

13.2

 

26.8

25.9

30.5

19.0

35.4

12.4

7820

27

34.6

34.6

37.3

29.5

41.3

18.4

 

32.5

32.5

35.2

28.3

39.2

17.5

 

30.2

30.2

32.9

27.1

36.9

16.6

30

37.8

37.8

39.6

36.5

42.6

27.5

 

35.8

35.8

37.6

35.3

40.6

26.6

 

33.7

33.7

35.5

34.0

38.5

25.7

 

 

 

 

33

41.9

41.9

41.9

41.9

43.9

35.5

 

40.0

40.0

40.0

40.0

42.1

34.6

 

38.1

38.1

38.1

38.1

40.2

33.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

32.6

30.2

36.0

22.5

40.7

14.2

 

30.3

28.7

33.7

21.4

38.4

13.4

 

27.9

27.2

31.3

20.2

36.0

12.6

8500

27

35.8

35.8

38.2

30.8

41.9

19.6

 

33.6

33.6

36.1

29.6

39.8

18.7

 

31.4

31.4

33.8

28.4

37.5

17.8

30

39.1

39.1

40.5

37.9

43.3

28.8

 

37.1

37.1

38.5

36.7

41.3

27.9

 

35.0

35.0

36.5

35.3

39.2

27.0

 

 

 

 

33

42.9

42.9

42.9

42.9

44.7

36.9

 

41.1

41.1

41.1

41.1

42.9

36.0

 

39.2

39.2

39.2

39.2

41.0

34.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.6

31.3

36.7

23.6

41.1

14.4

 

31.2

29.9

34.4

22.5

38.8

13.6

 

28.8

28.3

31.9

21.3

36.4

12.7

 

24

 

 

9180

27

36.8

36.8

39.0

32.0

42.4

20.6

 

34.7

34.7

36.8

30.8

40.3

19.8

 

32.4

32.4

34.6

29.5

38.0

18.9

30

40.2

40.2

41.3

39.2

43.8

30.0

 

38.2

38.2

39.4

37.9

41.8

29.1

 

36.1

36.1

37.3

36.6

39.8

28.2

 

 

 

 

33

43.8

43.8

43.8

43.8

45.3

38.2

 

42.0

42.0

42.0

42.0

43.5

37.2

 

40.1

40.1

40.1

40.1

41.6

36.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

1.All capacities shown are gross and have not considered indoor fan heat.

2.TGC = Total gross capacity (kW)

3.SHC = Sensible heat capacity (kW)

30

RT-PRC034-EN

Loading...
+ 70 hidden pages