Trane TSH 060, TSD User Manual

5 (1)

Installation

Operation

Maintenance

Voyager™ I Rooftop Units Cooling-only TSD/TSH 060 072 102 120 Reversible WSD/WSH 060 072 090 Gas-fired YSD/YSH 060 072 090 102 120

RT-SVX20A-E4

General information

Foreword

These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane TSD/TSH, WSKD/WSH and YSD/YSH units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.

TSD/TSH units are designed to operate in cooling mode only, with optional auxiliary heat (electric heater or hot water coil).

WSD/WSH can operate in cooling mode or heating mode by reversing the refrigeration cycle with or without auxiliary heat.

YSD/YSH units are designed to operate In cooling mode and equipped with a gas fired heating module.

TSD/TSH, WSD/WSH and YSD/YSH units are assembled, pressure tested, dehydrated, charged and run tested before shipment.

Warnings and cautions

Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.

WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.

2

RT-SVX20A-E4

General information

Reception

On arrival, inspect the unit before signing the delivery note. In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery.

Reception in France only:

Concealed damage must be looked for at delivery and immediately treated as visible damage.

Reception in all countries except France:

In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.

Warranty

Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.

Refrigerant

The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled.

Storage

Take precautions to prevent condensate formation inside the unit's electrical components and motors when:

1.The unit is stored before it is installed; or,

2.The unit is set on the roof curb and temporary auxiliary heat is provided in the building.

Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for start-up.

Do not use the unit's heater as temporary heat without completing the start-up procedures detailed under "Unit Start-Up".

The Trane Company will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components.

Maintenance contract

It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.

Training

To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.

RT-SVX20A-E4

3

Contents

 

 

 

General information

2

 

 

Foreword

 

2

 

 

Warnings and Cautions

 

2

 

 

Reception

 

3

 

 

Warranty

 

3

 

 

Refrigerant

 

3

 

 

Maintenance contract

 

3

 

 

Storage

 

3

 

 

Training

 

3

Installation

6

 

 

Reception of units

 

6

 

 

Roof curb installation

 

6

 

 

Dimensions/Weights/Clearances

 

7

 

 

Installing the unit

 

9

 

 

Connection of duct network

 

10

 

 

Condensate drain piping

 

12

 

 

Gas pipework installation

 

13

 

 

Filter installation

 

14

 

 

Supply fan adjustment

 

14

 

 

Component air pressure drops

 

16

 

 

Supply fan performances

 

17

 

 

Electrical connection

 

30

Controls

33

 

 

Control wiring

 

33

 

 

CO2 sensors

 

35

 

 

Remote potentiometer

 

39

 

 

Fire thermostat

 

40

 

 

Clogged filter detector

 

41

 

 

Smoke detector

 

41

 

 

High temperature safety thermostat

 

41

 

 

Remote fault relay

 

41

 

 

Thermostats

 

42

 

 

Communication Interfaces

 

43

4

RT-SVX20A-E4

Contents

 

 

 

Unit Options

44

 

 

Hot water coil

 

44

 

 

Electric Heater

 

45

 

 

Soft Starter

 

45

 

 

0 - 25% fresh air hood

 

46

 

 

Barometric relief

 

47

Operation

48

 

 

Operation with a conventional thermostat

 

48

 

 

Setting the economizer

 

50

 

 

Test procedures

 

52

 

 

Test modes

 

53

 

 

Unit Start-up

 

54

 

 

Cooling without an Economizer

 

56

 

 

Low Ambient Operation

 

57

 

 

Cooling with an Economizer

 

57

 

 

Economizer Set-Up

 

58

 

 

ReliaTel™ Control Heating Operation

 

58

 

 

Ignition Module

 

58

 

 

Final installation checklist

 

59

Maintenance

60

 

 

End user routine maintenance

 

60

 

 

Service technician maintenance

 

61

 

 

Troubleshooting

 

62

RT-SVX20A-E4

5

Installation

General information: The installation must conform to all local standards and regulations.

Reception of units

Rooftop unit

There are two ways to handle the unit:

1.Use the openings in the base to handle the machine using a forklift, in accordance with applicable safety regulations.

2.Use a lifting beam correctly adjusted to fit the unit (Figure 1).

Unit handling

The units are supplied on the truck but are not unloaded. An opening is provided on each corner of the unit base to facilitate handling. Four shackles and four slings are required. Use a lifting beam to prevent the cables pressing too hard on top of the unit during lifting.The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. (Refer to Figures 1 and

2 and Tables 2 and 3.)

Important: For unit to fit on the roof curb the fork lift pockets must be removed.

Figure 1 - Unit handing

Roof curb (accessory)

Roof curbs are available as an accessory for downflow units. The curbs can be adjustable and supplied pre-assembled on wooden pallets, packed under plastic film. Two types of self-adhesive seals are provided to ensure the roof curb seal is leak-tight (40 mm wide for the perimeter, 20 mm wide for the crosspieces).

Roof curb Installation (TSD-WSD-YSD accessories)

Roof curbs are available as an accessory for "downflow" units to support the unit and ensure the water tightness between the rooftop and the roof.

The curbs can be adjustable and supplied pre-assembled on wooden pallets, packed under plastic film. Two types of self-adhesive seals are provided separate. (40 mm wide for the perimeter, 20 mm wide for the cross pieces). Make sure they are properly installed where indicated to assure an adequate curb to unit seal.

Instructions for the roof curb assembly and installation with curb dimensions are provided with each roof curb kit.

Figure 2 - Rigging

1

2

1 = Remove 2 fork lift brackets

2 = Remove 2 metal runners and 3 wooden boards

Lift the unit enough to allow the removal of two Fork Lift brackets and hardware. Remove the two Fork Lift brackets, two metal runners and three wooden boards as shown in Figure 2.

6

RT-SVX20A-E4

Installation

Dimensions/Weights/

Clearances

Figure 3 - Minimum clearances

The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. Refer to Table 2 and the space requirement plan.

Table 1 - Minimum recommended clearances

Unit size

 

 

Mimum clearances (mm)

 

 

 

1

2

3

4

5

 

 

 

 

 

 

TSD/TSH 060

1829

1219

914

914

914

TSD/TSH 072

1829

1219

914

914

914

TSD/TSH 090

1829

1219

914

914

914

TSD/TSH 102

1829

1219

914

914

914

TSD/TSH 120

1829

1219

914

914

914

 

 

 

 

 

 

YSD/YSH 060

1829

1219

914

914

914

YSD/YSH 072

1829

1219

914

914

914

YSD/YSH 090

1829

1219

914

914

914

YSD/YSH 102

1829

1219

914

914

914

YSD/YSH 120

1829

1219

914

914

914

 

 

 

 

 

 

WSD/WSH 060

1829

1219

914

914

914

WSD/WSH 072

1829

1219

914

914

914

WSD/WSH 090

1829

1219

914

914

914

 

 

 

 

 

 

Table 2 - Unit weights and center of gravity

 

Maximum weight

 

Corner weight (1)

 

Center of gravity

Unit Size

 

 

 

 

 

 

 

 

Shipping

Net

A

B

C

D

Length

Width

 

 

(kg)

(kg)

(kg)

(kg)

(kg)

(kg)

(mm)

(mm)

 

 

 

 

 

 

 

 

 

TSD/TSH 060

259

235

75

56

48

56

790

480

TSD/TSH 072

365

326

107

83

58

78

970

560

TSD/TSH 090

428

389

131

101

67

89

970

530

TSD/TSH 102

445

405

133

106

72

94

990

560

TSD/TSH 120

485

445

147

115

81

104

990

560

 

 

 

 

 

 

 

 

 

YSD/YSH 060

285

260

81

64

54

62

810

510

YSD/YSH 072

390

350

113

90

64

83

990

560

YSD/YSH 090

458

419

139

110

75

95

970

530

YSD/YSH 102

474

434

141

114

79

100

1020

560

YSD/YSH 120

520

481

155

126

89

111

1020

560

 

 

 

 

 

 

 

 

 

WSD/WSH 060

266

241

77

58

49

58

790

480

WSD/WSH 072

408

368

122

93

66

87

970

560

WSD/WSH 090

418

378

128

95

67

88

970

530

Notes:

(1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.

RT-SVX20A-E4

7

Installation

Figure 4

A

 

 

Center of

 

 

 

 

 

B

 

gravity length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Center of gravity width

D C

Center of

gravity

Table 3 - Factory-installed options and accessories net weights (kg)

 

 

Barometric

Motorized

Manual

 

Oversized

Electric

Hot water

Unit size

Economizer

Outside Air

Outside Air

Roof Curb

Relief

Motor

Heaters

coil

 

 

Damper

Damper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TSD/TSH 060

11,8

3,2

9,1

7,3

31,8

-

6,8

14,0

 

 

 

 

 

 

 

 

 

TSD/TSH 072

16,3

4,5

13,6

11,8

52,2

3,6

13,6

17,0

 

 

 

 

 

 

 

 

 

TSD/TSH 090

16,3

4,5

13,6

11,8

52,2

3,6

13,6

17,0

 

 

 

 

 

 

 

 

 

TSD/TSH 1020

16,3

4,5

13,6

11,8

52,2

3,6

13,6

19,0

 

 

 

 

 

 

 

 

 

TSD/TSH 120

16,3

4,5

13,6

11,8

52,2

3,6

13,6

19,0

 

 

 

 

 

 

 

 

 

YSD/YSH 060

11,8

3,2

9,1

7,3

31,8

-

6,8

 

 

 

 

 

 

 

 

 

 

YSD/YSH 072

16,3

4,5

13,6

11,8

52,2

3,6

13,6

 

 

 

 

 

 

 

 

 

 

YSD/YSH 090

16,3

4,5

13,6

11,8

52,2

3,6

13,6

 

 

 

 

 

 

 

 

 

 

YSD/YSH 102

16,3

4,5

13,6

11,8

52,2

3,6

13,6

 

 

 

 

 

 

 

 

 

 

YSD/YSH 120

16,3

4,5

13,6

11,8

52,2

3,6

13,6

 

 

 

 

 

 

 

 

 

 

WSD/WSH 060

11,8

3,2

9,1

7,3

31,8

-

6,8

14,0

 

 

 

 

 

 

 

 

 

WSD/WSH 072

16,3

4,5

13,6

11,8

52,2

3,6

13,6

17,0

 

 

 

 

 

 

 

 

 

WSD/WSH 090

16,3

4,5

13,6

11,8

52,2

3,6

13,6

17,0

 

 

 

 

 

 

 

 

 

Notes:

(1)Weights for options not listed are < 3 kg.

(2)Net weight should be added to unit weight when ordering factory-installed accessories.

(3)Some accessories are not available on all units.

8

RT-SVX20A-E4

Trane TSH 060, TSD User Manual

Installation

Installing the unit

Discharge Conversion

If a unit is to be converted to Vertical discharge, a panel must be acquired from Trane.

If a unit is to be converted to Horizontal discharge, the following conversion must be performed:

1.Remove the return and supply duct covers.

2.Apply gasket to the return duct cover.

Figure 6 - Unit mounting on roof

1

1 = Frame

3.Position duct covers as shown in Figure 4. The supply duct cover is installed (insulation side down) over the downflow return opening by engaging one side of the panel under a retaining angle and securing the other side with 3 screws.

4.Slide return duct cover (insulation side up) into supply openings until outer edge of the duct cover engages with the two retaining clips on the duct flanges. Secure the outer edge of the each duct cover with two screws.

Figure 5 - Conversion to horizontal discharge

3

1

2

1 = Supply duct cover, insulation side down

2 = Return duct cover with gasket installed, insulation side up

3 = Edge of duct cover goes under retaining angle

Unit mounting on roof

Fix the rooftop curb on the joint beam of the building's structure. Make the rooftop curb's sealing surface level using angle brackets adjusted by screw bolts, located around its perimeter. Place the adhesive seals on the curb's sealing surface (perimeter and cross pieces). Make the rooftop leak-tight around the curbs before installing the unit, in compliance with current construction standards.

Note: The unit must be installed perfectly level to ensure condensates flow from the condensate tray.

The rooftop unit nests into the curb and is supported by it. Position the unit, taking care to comply with the indicated directions: the unit's discharge and intake openings must match those of the curb.

RT-SVX20A-E4

9

Installation

Installing the unit on the ground

To install the unit on the ground, its base must be level and supported securely. For horizontal discharge units, a support is required such as a metal or concrete slab whose height must be determined according to the amount of snow cover, to prevent problems with condensation drainage and obstruction of the external coil. If necessary use an anti-vibration material between the rooftop unit's base and the support.

Note: Unit installation must comply to local codes

Connection of duct network

1) Downflow discharge units (TSD,WSD,YSD)

Using the rooftop curb

The rooftop curb must be insulated on the outside walls at the discharge and intake openings to prevent condensation in the ducts.

The rims around the discharge and intake openings make it possible to attach the flanges on the ends of the ducts. If you are using rigid duct ends recommended on the rooftop curb plan, it is essential to fix these components before installing the unit.

Figure 7 - Unit installation on the ground

1 = Concrete slab

For the design of the duct network, comply with recommendations currently applicable on the market, in particular:

. Installation of a section of flexible ducts to limit transmission of the unit's vibrations

. Use of movable vanes or deflectors to reduce the sound level.

2) Horizontal discharge units (TSH,WSH,YSH)

The intake and discharge ducts must be insulated (thermal insulation).

The duct section located outside must be leak-tight.

Provide a flexible connector to prevent transmission of the unit vibrations. This flexible duct must be installed inside the building.

Note: In case of use of units with economizer option, temperature and humidity sensors must be installed in return duct.

Economizer linkage is factory mounted but the damper position must be adjusted on site.

10

RT-SVX20A-E4

Installation

Table 4 - Duct dimensions for downflow units (mm)

Unit size

A

B

C

D

E

Flanges

 

 

 

 

 

 

 

TSD 060

619

357

411

459

356

32

 

 

 

 

 

 

 

YSD 060

610

356

394

457

356

32

 

 

 

 

 

 

 

WSD 060

819

357

411

459

356

32

 

 

 

 

 

 

 

TSD/WSD 072/090

875

451

451

875

356

31

 

 

 

 

 

 

 

TSD 102/120

875

451

451

875

356

31

 

 

 

 

 

 

 

YSD 072/090/102/120

816

444

444

838

356

31

 

 

 

 

 

 

 

Table 5 - Duct dimensions for downflow units (mm)

Unit size

A

B

C

D

 

 

 

 

 

TSH/WSH 060

591

337

375

438

 

 

 

 

 

YSH 060

591

337

375

438

 

 

 

 

 

TSH/WSH/YSH 072/090

832

425

606

489

 

 

 

 

 

TSH/YSH 102/120

832

425

606

489

 

 

 

 

 

Figure 8 - Duct dimensions for downflow units

Figure 9 - Duct dimensions for horizontal units

 

 

B

 

 

A

C

 

 

 

 

 

 

 

D

 

 

 

R

A

S

R

 

S C

 

 

 

B

E

 

D

 

 

 

S = Supply

 

S = Supply

 

R = Return

 

R = Return

 

RT-SVX20A-E4

11

Installation

Condensate drain piping

A 3/4" condensate drain connection with P-trap is provided. Follow local codes and standard piping practices when running the drain line. Install a trap and be sure to fill with water before starting the unit. Pitch the line downward, away from the unit to avoid long, level, horizontal runs. Refer to Figure 11.

The condensate drain is reversible to allow installation of a drain tap on either side of the unit.

Figure 10 - Condensate drain location

1

1 = Main condensate drain location

Figure 11 - Condensate drain line location

1 = Static pressure drain pan

2 = Panel enclosure

3 = ¾ " drain

4 = Cleanout plug

12

RT-SVX20A-E4

Installation

Gas pipework installation

The installation must conform to all standards and regulations.

The gas supply pipework and gas stop valve to be installed near the unit must be sized so as to ensure the gas pressure is sufficient at the unit inlet when operating at full load.

CAUTION! Should the pressure at the unit valve gas inlet be higher than 0.035 bar, an expansion valve must be installed.

The pipework must be selfsupporting and the final connection to the burner must be made by a flexible pipe. Provide a dust protection (filter) upstream the unit connection.

Figure 12 - Typical gas supply pipework

CAUTION! The gas pipework must not exert any stress on the burner gas connection.

Note: Expansion valve must be adapted to the type of gas used:

G 20: 20 mb

G 25: 25 mb

G 31 (Propane): 37 or 50 mb

Table 6 - Gas burner models

Unit

Burner size

 

 

YSD/YSH 060

G120

 

 

YSD/YSH 072

G200

 

 

YSD/YSH 090

G200

 

 

YSD/YSH 102

G250

 

 

YSD/YSH 120

G250

 

 

See Table 51 for burner performance.

Gas leak check procedure

1.Vent the gas line

2.Gas supply line pressure test: close valve 4 and open valve 2

3.Leak-check the gas pipe.

Look for gas pipe leaks using "Typol", "1000 bulles" or a similar product. Do not use soapy water.

WARNING! Never use an open flame to check for gas leaks.

Required gas pressure at the unit inlet connection are given in Table 50.

Note: To operate with propane gas, the burner is fitted with a pressure limiter (supplied by Trane)

1 = Evaporator section

2 = Gas burner section

3 = Condenser section

4 = Gas supply connection

5 = Gas supply line

6, 8 = Gas stop valve (Field supplied) 7 = Expansion valve (Field supplied) 9 = Filter (Field supplied)

RT-SVX20A-E4

13

Installation

Filter installation

To gain access to filters, remove the supply fan access panel on downflow units and the filter access panel on the end for horizontal units.

Number and size of filters is determined by size and configuration of the unit. If disposable filters were chosen as an option, they are shipped in the supply fan section.

CAUTION! Do not operate unit without filters in place.

The maximum pressure drops allowable on filters are:

EU2/G2: 120 Pa

EU4/G4: 150 Pa

Supply fan adjustment

Use the following procedure to determine the proper adjustment of the supply fan for a specific application.

1.Determine total external static pressure about system and accessories.

Obtain the design airflow rate and the design external static pressure drop through the distribution system.

Add static pressure drop of the accessories installed on the unit. (Table 9)

Add the total accessory static pressure drop (from step 1b) to the design external static pressure (from step 1a). The sum of these two values is the total system external static pressure.

2.Using the Tables 10 through 35 to find the external static pressure that most closely approximates total system external static pressure. Then locate the appropriate airflow rate for your unit. The value obtained represents the brake horsepower for the supply fan motor and the fan RPM.

3.Adjust motor sheave according to Table 8.

Table 7 - Filter arrangement

Unit

 

EU2/G2

 

EU4/G4

 

 

 

 

Quantity

Size

Quantity

Size

 

 

 

 

 

 

TSD/TSH/YSD/YSH/WSD/WSH 060

2

(508x762x25)

2

(500x750x25)

 

 

 

 

 

TSD/TSH/YSD/YSH/WSD/WSH 072

4

(406x635x50)

4

(395x625x50)

 

 

 

 

 

TSD/TSH/YSD/YSH/WSD/WSH 090

4

(406x635x50)

4

(395x625x50)

 

 

 

 

 

TSD/TSH/YSD/YSH 102

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

TSD/TSH/YSD/YSH 120

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

14

RT-SVX20A-E4

Installation

To increase airflow

Loosen variable sheave set screw and turn sheave clockwise.

To decrease airflow

Loosen variable sheave set screw and turn sheave counter-clockwise.

To adjust belt

The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn.

Units with dual belts require a matched set of belts to ensure equal belt length.

When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.

Once the new belts are installed, adjust the belt tension.

Table 8 - Motor sheave / Fan speed

 

 

 

 

Fan speed (RPM)

 

 

 

 

 

 

 

Standard drive & motor

 

 

 

 

 

 

 

 

 

 

 

Unit

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

Closed

Open

Open

Open

Open

Open

Open

 

 

 

 

 

 

 

 

 

 

TSD/TSH 060

N/A

898

967

1036

1105

1174

1243

 

 

 

 

 

 

 

 

TSD/TSH 072

N/A

698

751

806

859

913

967

 

 

 

 

 

 

 

 

TSD/TSH 090

N/A

752

806

860

914

968

1020

 

 

 

 

 

 

 

 

TSD/TSH 102

N/A

688

737

786

835

885

934

 

 

 

 

 

 

 

 

TSD/TSH 120

N/A

782

838

894

950

1006

1062

 

 

 

 

 

 

 

 

YSD/YSH 060

N/A

1036

1105

1174

1243

1312

1381

 

 

 

 

 

 

 

 

YSD/YSH 072

N/A

806

860

913

968

1022

1074

 

 

 

 

 

 

 

 

YSD/YSH 090

859

913

967

1021

1075

1129

N/A

 

 

 

 

 

 

 

 

YSD/YSH 102

786

836

885

934

982

1032

N/A

 

 

 

 

 

 

 

 

YSD/YSH 120

894

950

1006

1062

1118

1174

N/A

 

 

 

 

 

 

 

 

WSD/WSH 060

N/A

898

967

1036

1105

1174

1243

 

 

 

 

 

 

 

 

WSD/WSH 072

N/A

698

751

806

859

913

967

 

 

 

 

 

 

 

 

WSD/WSH 090

N/A

752

806

860

914

968

1020

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed (RPM)

 

 

 

 

 

 

 

Oversized drive & motor

 

 

 

 

 

 

 

 

 

 

 

Unit

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

Closed

Open

Open

Open

Open

Open

Open

 

 

 

 

 

 

 

 

 

 

TSD/TSH 060

N/A

1243

1311

1379

1450

1515

1588

 

 

 

 

 

 

 

 

TSD/TSH 072

N/A

967

1021

1075

1128

1183

1235

 

 

 

 

 

 

 

 

TSD/TSH 090

1112

1182

1252

1322

1392

1460

N/A

 

 

 

 

 

 

 

 

TSD/TSH 102

N/A

971

1041

1111

1181

1251

1321

 

 

 

 

 

 

 

 

TSD/TSH 120

1062

1118

1174

1229

1285

1341

N/A

 

 

 

 

 

 

 

 

YSD/YSH 060

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

YSD/YSH 072

N/A

967

1021

1075

1128

1183

1235

 

 

 

 

 

 

 

 

YSD/YSH 090

1112

1182

1252

1322

1392

1460

N/A

 

 

 

 

 

 

 

 

YSD/YSH 102

N/A

971

1041

1111

1181

1251

1321

 

 

 

 

 

 

 

 

YSD/YSH 120

1062

1118

1174

1229

1285

1341

N/A

 

 

 

 

 

 

 

 

WSD/WSH 060

N/A

1243

1311

1379

1450

1515

1588

 

 

 

 

 

 

 

 

WSD/WSH 072

N/A

967

1021

1075

1128

1183

1235

 

 

 

 

 

 

 

 

WSD/WSH 090

1112

1182

1252

1322

1392

1460

N/A

 

 

 

 

 

 

 

 

RT-SVX20A-E4

15

Installation

Component air pressure drops

Table 9 - Pressure drop through accessories

Unit

Airflow

Filter

Filter

Economizer

Electric

Hot water

100%

size

(m3/h)

EU2/G2

EU4/G4

heater

coil

 

 

 

 

outside air

 

 

 

 

 

 

 

 

 

 

3060

31

50

38

17

49

 

 

 

 

 

 

 

060

3400

38

55

46

21

55

 

 

 

 

 

 

3740

46

61

55

25

62

 

 

 

 

 

 

 

 

 

4080

55

66

64

30

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3670

13

37

27

7

46

 

 

 

 

 

 

 

072

4080

16

42

29

9

52

 

 

 

 

 

 

4490

19

46

31

11

58

 

 

 

 

 

 

 

 

 

4900

23

50

33

13

64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4590

19

47

33

12

66

 

 

 

 

 

 

 

090

5100

24

52

39

15

74

 

 

 

 

 

 

5610

29

57

45

20

83

 

 

 

 

 

 

 

 

 

6120

35

62

52

25

92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5200

16

42

40

8

64

 

 

 

 

 

 

 

102

5780

20

47

50

10

72

 

 

 

 

 

 

6360

25

52

62

12

81

 

 

 

 

 

 

 

 

 

6940

30

57

75

15

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6120

22

50

52

11

84

 

 

 

 

 

 

 

120

6800

27

55

62

14

95

 

 

 

 

 

 

7480

33

61

73

17

106

 

 

 

 

 

 

 

 

 

8160

40

66

85

20

117

 

 

 

 

 

 

 

16

RT-SVX20A-E4

Installation

Supply fan performances

Table 10 - TSD 060 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2720

-

-

-

-

-

-

-

-

-

-

899

0.43

944

0.49

985

0.54

1023

0.59

1060

0.64

1093

0.69

1126

0.74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3060

-

-

-

-

-

-

-

-

904

0.49

947

0.54

988

0.58

1028

0.64

1067

0.70

1104

0.76

1138

0.82

1171

0.87

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3400

-

-

-

-

-

-

918

0.57

958

0.62

998

0.67

1036

0.71

1073

0.76

1111

0.82

1147

0.89

1182

0.96

1215

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3740

-

-

-

-

930

0.65

977

0.71

1016

0.77

1053

0.82

1089

0.88

1124

0.93

1158

0.98

1191

1.03

1226

1.10

1258

1.17

4080

909

0.71

950

0.76

990

0.80

1034

0.87

1074

0.93

1110

1.00

1143

1.06

1177

1.12

1209

1.17

1241

1.23

1272

1.29

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

2720

1160

0.79

1190

0.84

1222

0.90

 

 

 

 

 

 

 

 

 

3060

1203

0.93

1232

0.98

1262

1.04

 

3400

1246

1.09

1276

1.15

1306

1.21

 

3740

1290

1.25

-

-

-

-

 

4080

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

Table 11 - TSH 060 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2720

-

-

-

-

-

-

898

0.43

953

0.48

1001

0.54

1045

0.59

1087

0.65

1129

0.71

1168

0.77

1206

0.83

1241

0.89

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3060

-

-

-

-

897

0.48

953

0.54

1008

0.60

1058

0.67

1102

0.73

1143

0.79

1181

0.85

1219

0.92

1256

0.99

1291

1.05

3400

-

-

908

0.54

961

0.60

1012

0.67

1062

0.74

1111

0.81

1157

0.88

1198

0.95

1237

1.02

1274

1.09

1309

1.16

1343

1.24

3740

923

0.63

978

0.69

1028

0.76

1075

0.83

1120

0.91

1166

0.99

1211

1.06

1254

1.14

1294

1.22

1330

1.29

-

-

-

-

4080

997

0.80

1049

0.87

1096

0.94

1140

1.02

1183

1.10

1223

1.18

1266

1.27

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

2720

1275

0.96

1306

1.02

1338

1.09

 

3060

1326

1.12

1359

1.19

1390

1.26

 

3400

1376

1.31

-

-

-

-

 

3740

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

4080

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

Standard drive

Oversize drive Note : Data includes pressure drops for standard filters and wet coils

RT-SVX20A-E4

17

Installation

Table 12 - TSD 072 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3260

-

-

-

-

-

-

-

-

-

-

726

0.41

769

0.47

811

0.52

851

0.58

889

0.65

925

0.71

960

0.77

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3670

-

-

-

-

-

-

-

-

706

0.43

751

0.49

792

0.55

832

0.61

871

0.67

908

0.74

944

0.81

978

0.87

4080

-

-

-

-

-

-

-

-

732

0.51

777

0.58

818

0.64

856

0.71

893

0.77

930

0.84

964

0.91

998

0.99

4490

-

-

-

-

-

-

715

0.54

758

0.60

802

0.68

845

0.75

883

0.82

919

0.89

953

0.96

986

1.04

1019

1.11

4890

-

-

-

-

706

0.58

749

0.64

789

0.71

830

0.79

870

0.87

909

0.95

945

1.02

979

1.10

1011

1.18

1043

1.26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

3260

994

0.83

1026

0.89

1057

0.95

 

3670

1010

0.94

1043

1.01

1073

1.08

 

4080

1030

1.06

1063

1.14

1092

1.21

 

4490

1051

1.19

1082

1.27

1112

1.35

 

4890

1073

1.34

1103

1.42

1133

1.51

 

 

 

 

 

 

 

 

 

Table 13 - TSH 072 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3260

-

-

-

-

-

-

-

-

726

0.39

771

0.45

814

0.51

857

0.57

899

0.63

939

0.70

978

0.76

1015

0.83

3670

-

-

-

-

-

-

716

0.42

762

0.48

804

0.54

843

0.60

883

0.67

922

0.74

960

0.81

996

0.87

1034

0.95

4080

-

-

-

-

701

0.45

751

0.51

798

0.59

839

0.65

877

0.71

914

0.78

950

0.85

984

0.93

1020

1.00

1055

1.08

4490

-

-

710

0.51

745

0.56

788

0.62

833

0.69

875

0.77

914

0.85

949

0.91

984

0.98

1016

1.06

1049

1.14

1081

1.23

4890

726

0.58

762

0.64

795

0.70

828

0.76

869

0.82

911

0.91

950

0.99

986

1.07

1019

1.14

1051

1.22

1081

1.30

1112

1.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

3260

1051

0.90

1086

0.97

1118

1.04

 

3670

1069

1.02

1103

1.09

1136

1.17

 

4080

1089

1.16

1122

1.23

1154

1.31

 

4490

1113

1.31

1144

1.40

1176

1.48

 

4890

1141

1.47

1170

1.57

1199

1.66

 

 

 

 

 

 

 

 

 

Standard drive

 

Oversize drive

Note : Data includes pressure drops for standard filters and wet coils

18

RT-SVX20A-E4

Installation

Table 14 - TSD 090 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4080

-

-

-

-

-

-

-

-

750

0.54

794

0.60

834

0.67

873

0.73

909

0.80

945

0.87

980

0.95

1013

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4590

-

-

-

-

-

-

-

-

787

0.66

830

0.74

871

0.82

908

0.89

943

0.96

977

1.04

1010

1.11

1043

1.19

5100

-

-

-

-

747

0.68

789

0.74

827

0.82

867

0.90

906

0.98

944

1.06

980

1.15

1013

1.23

1045

1.31

1076

1.39

5610

-

-

755

0.77

797

0.85

836

0.92

873

1.00

908

1.08

944

1.17

980

1.26

1016

1.35

1050

1.45

1081

1.54

1111

1.63

6120

771

0.88

809

0.96

848

1.06

885

1.14

921

1.22

954

1.30

986

1.39

1019

1.49

1052

1.58

1085

1.69

1116

1.79

1148

1.89

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

4080

1046

1.10

1076

1.17

1106

1.25

 

4590

1074

1.27

1105

1.36

1134

1.44

 

5100

1105

1.47

1134

1.56

1163

1.65

 

5610

1141

1.72

1168

1.80

1197

1.90

 

6120

1177

1.99

1204

2.08

1232

2.18

 

 

 

 

 

 

 

 

 

Table 15 - TSH 090 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4080

-

-

-

-

-

-

769

0.54

814

0.61

855

0.67

893

0.73

929

0.81

965

0.88

999

0.96

1035

1.04

1070

1.12

4590

-

-

-

-

773

0.62

817

0.68

862

0.76

904

0.85

941

0.92

975

0.98

1009

1.06

1041

1.14

1073

1.22

1104

1.31

5100

771

0.68

805

0.74

837

0.81

870

0.87

912

0.94

951

1.03

989

1.12

1025

1.21

1056

1.28

1088

1.36

1117

1.44

1146

1.53

5610

842

0.89

873

0.96

903

1.03

930

1.10

963

1.17

1000

1.25

1037

1.34

1073

1.45

1106

1.55

1136

1.63

1165

1.72

1194

1.80

6120

913

1.14

942

1.22

970

1.30

996

1.37

1021

1.45

1052

1.52

1086

1.61

1121

1.71

1153

1.82

1184

1.93

1215

2.04

1242

2.13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

4080

1104

1.19

1137

1.27

1168

1.35

 

4590

1136

1.40

1167

1.48

1198

1.57

 

5100

1176

1.62

1205

1.72

1233

1.82

 

5610

1220

1.88

1248

1.98

1275

2.08

 

6120

1269

2.22

1295

2.31

1319

2.40

 

 

 

 

 

 

 

 

 

Standard drive

 

Oversize drive

Note : Data includes pressure drops for standard filters and wet coils

RT-SVX20A-E4

19

Installation

Table 16 - TSD 102 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4620

-

-

-

-

-

-

-

-

-

-

695

0.62

733

0.71

769

0.81

802

0.90

833

1.00

863

1.11

892

1.21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5200

-

-

-

-

-

-

-

-

688

0.64

725

0.73

761

0.83

796

0.93

828

1.03

861

1.13

891

1.24

919

1.35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5780

-

-

-

-

-

-

689

0.68

724

0.76

759

0.86

792

0.96

825

1.07

856

1.18

887

1.28

917

1.40

946

1.51

6350

-

-

-

-

693

0.72

729

0.82

764

0.92

795

1.01

826

1.11

857

1.22

887

1.34

916

1.46

945

1.58

974

1.70

6930

-

-

706

0.80

738

0.89

770

0.98

804

1.09

834

1.19

864

1.30

892

1.40

920

1.52

948

1.64

976

1.78

1002

1.91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

400

425

450

475

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4620

920

1.33

946

1.44

973

1.55

999

1.67

1025

1.79

1050

1.90

1073

2.02

1098

2.14

 

5200

946

1.46

973

1.58

999

1.71

1024

1.83

1048

1.96

1072

2.09

1096

2.22

1119

2.34

 

5780

974

1.63

1001

1.75

1026

1.88

1051

2.01

1074

2.14

1099

2.27

1121

2.41

1143

2.55

 

6350

1001

1.82

1028

1.95

1054

2.08

1079

2.20

1103

2.34

1126

2.48

1148

2.62

1170

2.76

 

6930

1029

2.04

1055

2.17

1081

2.30

1105

2.43

1130

2.58

1154

2.72

1176

2.85

1199

3.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 17 - TSH 102 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4620

-

-

-

-

-

-

689

0.58

734

0.67

781

0.77

826

0.88

865

0.98

898

1.07

928

1.16

956

1.25

982

1.33

5200

-

-

-

-

693

0.64

735

0.73

773

0.82

812

0.92

855

1.03

897

1.15

934

1.27

969

1.38

999

1.49

1026

1.58

5780

-

-

711

0.75

743

0.82

781

0.91

819

1.01

853

1.11

886

1.21

925

1.34

964

1.47

1000

1.60

1034

1.73

1067

1.86

6350

735

0.89

770

0.97

799

1.04

830

1.12

865

1.23

899

1.34

930

1.45

960

1.56

994

1.68

1028

1.82

1063

1.96

1098

2.11

6930

796

1.14

828

1.23

857

1.31

883

1.39

913

1.48

945

1.60

977

1.72

1006

1.84

1034

1.96

1061

2.08

1093

2.23

1125

2.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

400

425

450

475

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4620

1008

1.42

1033

1.51

1056

1.60

1079

1.69

1102

1.78

1125

1.87

1146

1.95

1168

2.04

 

5200

1052

1.68

1078

1.78

1101

1.88

1124

1.98

1146

2.08

1168

2.18

1188

2.27

1209

2.37

 

5780

1094

1.97

1120

2.08

1145

2.20

1168

2.31

1191

2.42

1213

2.53

1234

2.63

1254

2.74

 

6350

1129

2.26

1158

2.40

1185

2.53

1210

2.66

1234

2.78

1256

2.90

1278

3.03

1299

3.15

 

6930

1157

2.53

1188

2.70

1218

2.86

1245

3.01

1273

3.16

1297

3.31

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard drive

 

Oversize drive

Note : Data includes pressure drops for standard filters and wet coils

20

RT-SVX20A-E4

Installation

Table 18 - TSD 120 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5440

-

-

-

-

-

-

-

-

-

-

-

-

789

0.93

822

1.03

856

1.14

887

1.25

917

1.36

945

1.47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6120

-

-

-

-

-

-

-

-

-

-

797

0.99

829

1.10

860

1.22

892

1.34

922

1.46

951

1.57

979

1.69

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6800

-

-

-

-

-

-

782

1.01

814

1.11

844

1.21

874

1.32

903

1.44

932

1.56

960

1.69

988

1.82

1015

1.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7480

-

-

-

-

803

1.14

834

1.24

864

1.36

894

1.48

922

1.59

948

1.70

975

1.82

1001

1.95

1028

2.09

1053

2.23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8160

803

1.21

833

1.31

861

1.42

887

1.52

916

1.64

945

1.77

972

1.90

997

2.02

1022

2.14

1046

2.27

1071

2.41

1095

2.55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

400

425

450

475

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5440

973

1.60

999

1.72

1024

1.84

1048

1.97

1072

2.10

1095

2.23

1117

2.37

1140

2.51

 

6120

1007

1.82

1033

1.94

1059

2.07

1082

2.20

1107

2.34

1130

2.49

1152

2.63

1173

2.77

 

6800

1042

2.08

1068

2.21

1093

2.35

1117

2.48

1142

2.63

1164

2.76

1187

2.91

1209

3.06

 

7480

1078

2.38

1103

2.52

1128

2.66

1152

2.81

1176

2.95

1198

3.10

1221

3.25

-

-

 

8160

1119

2.70

1142

2.86

1166

3.02

1189

3.17

1212

3.33

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 19 - TSH 120 Available static pressure

External Static Pressure (Pa)

 

25

 

50

 

75

 

100

125

150

175

200

225

250

275

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

Fan

kW

Fan

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5440

-

-

-

-

-

-

-

-

807

0.94

844

1.04

886

1.16

926

1.28

965

1.41

1000

1.53

1029

1.64

1057

1.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6120

-

-

-

-

792

0.99

829

1.08

865

1.19

898

1.30

930

1.41

965

1.53

1002

1.67

1038

1.81

1072

1.95

1106

2.10

6800

802

1.13

833

1.22

860

1.29

890

1.38

923

1.50

956

1.62

986

1.73

1015

1.85

1044

1.98

1077

2.12

1111

2.28

1143

2.43

7480

876

1.49

905

1.58

931

1.67

955

1.75

983

1.86

1014

1.99

1045

2.12

1072

2.25

1098

2.37

1125

2.51

1152

2.65

1182

2.81

8160

950

1.91

977

2.02

1002

2.11

1025

2.20

1048

2.30

1074

2.42

1102

2.56

1131

2.71

1156

2.84

1181

2.98

1205

3.12

1229

3.27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

350

375

400

425

450

475

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

Fan

kW

 

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5440

1084

1.86

1108

1.96

1132

2.06

1155

2.17

1177

2.27

1198

2.37

1219

2.48

1239

2.58

 

6120

1134

2.22

1160

2.35

1185

2.47

1209

2.59

1231

2.70

1252

2.82

1274

2.94

1295

3.06

 

6800

1174

2.58

1204

2.74

1232

2.90

1260

3.05

1283

3.18

1306

3.32

-

-

-

-

 

7480

1211

2.97

1241

3.14

1270

3.31

-

-

-

-

-

-

-

-

-

-

 

8160

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard drive

 

Oversize drive

Note : Data includes pressure drops for standard filters and wet coils

RT-SVX20A-E4

21

Loading...
+ 47 hidden pages