Trane UNT-SVX07A-EN User Manual

0 (0)

Installation, Operation, and Maintenance

UniTrane Fan-Coil & Force Flo Air Conditioners

200 to 1,200 cfm

Models FC & FF

“ZO” and later design sequence

Low vertical models FCKB & FCLB: “SO” and later design sequence

April 2005

UNT-SVX07A-EN

general information

About This Manual

Literature Change History

Use this manual for UniTrane fan-coils and Force Flo cabinet heaters. This is the seventh revision of this manual. It provides specific installation, operation, and maintenance instructions for “ZO” and later design sequences for all models except low vertical, which are “SO” and later design sequences. For previous design sequence information, contact your local Trane representative.

Warnings and Cautions

Warnings and cautions appear at appropriate sections throughout this manual. Read these carefully.

WARNING

Indicates a potentially hazardous situation, which could result in death or serious injury if not avoided.

CAUTION

Indicates a potentially hazardous situation, which may result in minor or moderate injury if not avoided. Also, it may alert against unsafe practices.

CAUTION

Indicates a situation that may result in equipment or property-damage- only accidents.

WARNING

Hazardous Voltage w/Capacitors!

Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

CAUTION

Use Copper Conductors Only!

Unit terminals are not designed to accept other type conductors. Failure to use copper conductors may result in equipment damage.

Common HVAC Acronyms

For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.

BAS = Building automation systems cfm = Cubic-feet-per-minute

ewt = entering water temperature F/A = Fresh air

HVAC = Heating, ventilation and air conditioning

I/O = Inputs/outputs

IOM= Installation, operation, and maintenace manual

LH = Left-hand O/A = Outside air R/A = Return air RH = Right-hand

rpm = Revolutions-per-minute S/A = Supply air

w.c. = Water column

ZSM = Zone sensor module

© 2005 American Standard Inc.

UNT-SVX07A-EN

contents

Cross reference to related publications/information for UniTrane™ fan-coil & Force Flo™ equipment:

RoverInstallation, Operation and Programming Guide, EMTX-SVX01D-EN

TracerZN510 Unit Controller, CNT-IOP-1

TracerZN520 Unit Controller, CNT-SVX04A-EN

UniTraneFan-Coil Catalog, UNT-PRC001-EN

Force FloCabinet Heater Catalog, CAB-PRC001-EN

Installation ……………………………………………………………2

general information ……………………………………………2

dimensions & weights ……………………………………… 10 pre-installation considerations ………………………………28

mechanical requirements ……………………………………30

electrical requirements ………………………………………36

installation procedure ………………………………………41

pre-startup requirements ……………………………………46

Operation ……………………………………………………………49

general information …………………………………………49

sequence of operation ………………………………………50

Maintenance…………………………………………………………60

diagnostics ……………………………………………………60

troubleshooting ………………………………………………64

maintenance procedures ……………………………………67

typical wiring diagrams ………………………………………71

UNT-SVX07A-EN

3

general information

General

UniTrane fan-coil and Force Flo units are intended for single zone applications. These units have load capabilities of 200 to 1200 cfm. See Figure I-GI-1 for unit components. Fan-coil units are available as two-pipe, with or without electric heat (one hydronic circuit) or four-pipe (two hydronic circuits). Force-Flo units feature two-pipe hydronic, electric heat only, or steam only. Also, these units feature a variety of factory mounted piping packages.

Units with the three-speed fan switch only, are available with the switch mounted on the unit, or shipped separately, to be mounted in the occupied space. The unit mounted three-speed

switch option, can be ordered with a low voltage(24 volts AC) transformer and three fan speed relays. The ship seperate three-speed switch option, only comes with a low voltage (24 volt AC) transformer and three fan speed relays.

The Tracer ZN010, ZN510, and ZN520 controllers are included inside the units control box assembly. These controllers utilize analog signals from a unit-mounted control device or from a control device mounted in the occupied space.

The controls interface option, includes a 24 volt AC transformer, and an interface terminal board. Controls provided by an external source, can be tied into the interface terminal board, utilizing 1/4" female spade connectors.

Model Number

Each UniTrane fan-coil and Force-Flo cabinet heater has a multiple character model number unique to that particular unit. To determine a unit’s specific options, reference the model number on the unit nameplate on the fan scroll. The unit nameplate also identifies the serial number, sales order number, and installation and operating specifications.

Following is a complete description of the fan-coil model number. Each digit in the model number has a corresponding code that identifies specific unit options.

Factory installed and tested controls

Removable, noncorrosive, positively-sloped drain pan that’s easy to clean

Easy to remove fan assembly

16-gage steel construction

Smallerunitfootprint

 

Factory assembled,

 

installed and tested piping

 

 

package with IAQ drain pan

 

Two, three or

to collect condensate

Quiet operation

 

four-row coils

 

Cleanable closedcellinsulation(nonfiberglass)

Easy filter access

Damper allows up

without front panel

to 100% fresh air

removal

 

Figure I-GI-1. UniTrane fan-coil unit components. Vertical cabinet model is shown.

4

UNT-SVX07A-EN

general Installation information

Model Number Description

FC B B 020 1 C

P0 A

0 G 1 0 A

A 2 M 000 0

0 1 0 0 0

A A 000

000 0

0 0 0 A 0 0

1

5

10

15

20

25

30

35

40

44

Digits 1, 2 — unit type

FC = fan-coil

FF = force flo

Digit 3 — cabinet type

A= vertical concealed

B= vertical cabinet

C= horizontal concealed

D=horizontalcabinet

E= horizontal recessed

F= vertical wall hung

H = vertical recessed

J= vertical cabinet slope top

K= low vertical concealed

L= low vertical cabinet

M= inverted vertical cabinet

N= inverted vertical recessed

Digit 4 — development sequence “B”

Digits 5, 6, 7 — unit size

020 040 080

030 060 100

120

Digit 8 — unit voltage

1 = 115/60/1

4 = 230/60/1

2 = 208/60/1

9 = 220/50/1

3 = 277/60/1

 

Digit 9 — piping system/placement

A = no piping, RH, w/o aux drn pan B = no piping, LH, w/o aux drn pan C = no piping, RH, w/ aux drn pan D = no piping, LH, w/ aux drn pan E = no piping, RH, w/o aux drn pan,

extended end pocket

F = no piping, LH, w/o aux drn pan, extended end pocket

G = no piping, RH, w/ aux drn pan, extended end pocket

H = no piping, LH, w/ aux drn pan, extended end pocket

J = piping package, RH K = piping package, LH

L = piping package, RH, extd end pkt M = piping package, LH, extd end pkt

Digits 10, 11 — design sequence

Digit 12 — inlets

A = front toe space

B= front bar grille

C= front stamped louver

D= bottom stamped louver

E= bottom toe space

F= back duct collar

G = back open return

H = back stamped louver

Digit 13 — fresh air damper

0 = none

A= manual,bottomopening

B= manual,backopening

C= manual,topopening

D= auto,2-position,bottomopening

E= auto,2-position,backopening

F= auto,2-position,topopening

G= auto,economizer,bottomopening

H= auto, economizer, back opening

J= auto,economizer,topopening

K= nodamper,bottomopening

L= no damper, back opening M= nodamper,topopening

Digit 14 — outlets

A = front duct collar

B= front bar grille

C= front stamped louver

D= front quad grille

G = top quad grille

H = top bar grille

J = top duct collar

Digit 15 — color

 

 

0

= no paint (concealed units only)

1

= deluxe beige

4

= driftwood grey

2

= soft dove

5

= stone grey

3

= cameo white

6

= rose mauve

Digit 16 — tamperproof locks/leveling feet

0 = none

A = locking panel

B= keylock access door

C= locking panel & keylock access door

D= leveling feet

F = locking panel w/ leveling feet G = keylock panel, keylock access door

w/ leveling feet

Digit 17 — motor

A = free discharge

B = high static

Digit 18 — coil

A= 2rowcooling/heating

B= 3rowcooling/heating

C= 4rowcooling/heating

D= 2 row cooling/1 row heating

E= 2 row cooling/2 row heating

F= 3 row cooling/1 row heating

G= 2 row cooling only

H= 3 row cooling only

J= 4 row cooling only

K= 2 row cooling/heating w/ elec heat

L = 3 row cooling/heating w/ elec heat M= 4 row cooling/heating w/ elec heat

P= 2 row cooling/heating w/1 row heat

Q= 2 row cooling/heating w/2 row heat

R= 3 row cooling/heating w/1 row heat

Digit 19 — coil series

2 = 144 FPF

Digit 20 — coil air vent

A = automatic air vent

M= manual air vent

Digits 21, 22, 23 — electric heat (208V derate)

000 = no electric heat

010 = 1.0 kW (0.75 kW)

015 = 1.5 kW (1.1 kW)

020 = 2.0 kW (1.5 kW)

025 = 2.5 kW (1.9 kW)

030 = 3.0 kW (2.3 kW)

040 = 4.0 kW (3.0 kW)

050 = 5.0 kW (3.8 kW)

060 = 6.0 kW (4.5 kW)

070 = 7.0 kW (5.3 kW)

08 0= 8.0 kW (6.0 kW)

100 = 10.0 kW

Digit 24 — reheat coil

0 = none B = hot water coil A = steam coil

Digit 25 — disconnect switch

0 = none

D = disconnect switch

Digit 26 — filter

0= none

1= 1” throwaway filter

2= 1” throwaway pleated media filter 3= 1” throwaway, qty 2

4= 1” throwaway pltd media, qty 2 5= 1” throwaway, qty 3

6= 1” throwaway pltd media, qty 3 7= 1” throwaway, qty 4

8= 1” throwaway pltd media, qty 4

Digit 27 — main control valve

0 = none

A= 2-way, 2-position, NO (30 psig)

B= 3-way, 2-position, NO (28 psig)

C= 2-way, 2-position, NC (30 psig)

D= 3-way, 2-position, NC (20 psig)

E= 2-way, 2-position, NO (50 psig)

F= 3-way, 2-position, NO (28 psig)

G= 2-way, 2-position, NC (50 psig)

H= 3-way, 2-position, NC (28 psig)

UNT-SVX07A-EN

5

general Installation information

J= 2-way, modulating, 0.7 Cv (50 psig)*

K= 3-way, modulating, 0.7 Cv (50 psig)* L = 2-way, modulating, 1.1 Cv (60 psig)*

M= 3-way, modulating, 1.1 Cv (60 psig)* N = 2-way, modulating, 2.3 Cv (60 psig)* P = 3-way, modulating, 2.7 Cv (60 psig)*

Q= 2-way, modulating, 3.3 Cv (60 psig)*

R= 3-way, modulating, 3.8 Cv (60 psig)*

X=field-supplied,NO

Y=field-supplied,NC

Z= field-supplied 3-wire modulating

Digit 28 — auxiliary control valve

0 = none

A= 2-way, 2-position, NO (30 psig)

B= 3-way, 2-position, NC (28 psig)

C= 2-way, 2-position, NC (30 psig)

D= 3-way, 2-position, NC (20 psig)

E= 2-way, 2-position, NO (50 psig)

F= 3-way, 2-position, NO (28 psig)

G= 2-way, 2-position, NC (50 psig)

H= 3-way, 2-position, NC (28 psig)

J= 2-way, modulating, 0.6 Cv (60 psig)

K= 3-way, modulating, 0.6 Cv (60 psig)

L= 2-way, modulating, 1.1 Cv (60 psig) M= 3-way, modulating, 1.1 Cv (60 psig)

N= 2-way, modulating, 2.3 Cv (60 psig)

P= 3-way, modulating, 2.7 Cv (60 psig)

Q= 2-way, modulating, 3.3 Cv (60 psig)

R= 3-way, modulating, 3.8 Cv (60 psig)

X=field-supplied,NO

Y=field-supplied,NC

Z= field-supplied 3-wire modulating

Digit 29 — piping packages

0 = none

A = basic ball valve S & R

B = basic ball valve S/man. crkt set

C = basic ball valve S & R w/auto crkt set D = deluxe ball valve S & R

E = deluxe ball valve S /man. crkt set R

F = deluxe ball valve S & R w/auto crkt set

Digit 30 — control type

0 = none

A = fan speed switch E = Tracer ZN010

F = Tracer ZN510

G = Tracer ZN520

H = CSTI

Digit 31 — control option

D = unit mtd fan mode, unit voltage, K = wall mtd fan mode

V = unit mtd fan sp w/ setpnt

X = unit mtd fan sp w/ wall mtd setpnt Y = unit mtd fan sp & wall mtd setpnt w/

comm.

Z = unit mtd fan sp, on/cancel, setpnt w/ comm.

1 = wall mtd on/cancel w/ comm.

2 = wall mtd fan speed, setpnt, on/cancel w/ comm.

3 = unit mtd fan speed switch, low voltage 4 = wall mtd digital zone sensor, fan sp w/

setpnt, on/cancel, comm.

5 = wall mtd digital zone sensor, setpnt, on/cancel,comm.

Digit 32 — IAQ options

0 = none

1=dehumidification

4 = dehumidification w/sensor

Digit 33 — cntrl function #1

0 = w/o exhaust fan/damper or alarm

Digit 34 — cntrl function #2

0 = w/o occupant call or IAQ status

Digit 35 — control function #3

0 = none

1 = occ/unocc control

2 = condensate overflow detection

3 = occ/unocc & condensate overflow

Digit 36 — cntrl function #4

0 = none

1 = smoke input

2 = low temperature detection

3 = smoke input & low limit sensor

Digits 37, 38 — future cntrl functions

Digit 39 — projection panel/falseback

0 = none

A = 5/8”standard vertical recessed panel B = 2” projection panel

C = 2.5” projection panel D = 3” projection panel E = 3.5” projection panel F = 4” projection panel G = 4.5” projection panel H = 5” projection panel J = 5.5”projection panel K = 6” projection panel L = 2”falseback

M = 3” falseback N = 4” falseback P = 5” falseback Q = 6” falseback R = 7” falseback T = 8” falseback

Digit 40 — main autoflow gpm

A = 0.5

G = 3.0

N = 7.0

B = 0.75

H = 3.5

P = 8.0

C = 1.0

J = 4.0

Q = 9.0

D = 1.5

K = 4.5

R = 10.0

E = 2.0

L = 5.0

T = 11.0

F = 2.5

M= 6.0

U = 12.0

Digit 41 — auxiliary autoflow gpm

A = 0.5

F = 2.5

L = 5.0

B = 0.75

G = 3.0

M= 6.0

C = 1.0

H = 3.5

N = 7.0

D = 1.5

J = 4.0

P = 8.0

E = 2.0

K = 4.5

 

Digit 42 — subbase

 

0 = none

 

 

A = 2” subbase

D =5” subbase

B = 3” subbase

E =6” subbase

C = 4” subbase

F =7” subbase

Digit 43 — recessed flange

0 = none

A = recessed flange

Digit 44 — wall boxes

0 = none

A = anodized wall box

6

UNT-SVX07A-EN

general Installation information

Table I-GI-1. Fan-coil component data

unit size

02

03

04

06

08

10

12

CoilData

 

 

 

 

 

 

 

Face Area — Ft2 (cm2)

0.8 (743)

0.8 (743)

1.1 (1020)

1.6 (1490)

2.1 (1950)

3.2 (2970)

3.2 (2970)

LxDxH — In. (cm)

 

 

 

 

 

 

 

2-Row

15x1.7x8

15x1.7x8

20x1.7x8

29.5x1.7x8

38x1.7x8

57x1.7x8

57x1.7x8

 

(38x4x20)

(38x4x20)

(51x4x20)

(75x4x20)

(97x4x20)

(145x4x20)

(145x4x20)

3-Row

15x2.6x8

15x2.6x8

20x2.6x8

29.5x2.6x8

38x2.6x8

57x2.6x8

57x2.6x8

 

(38x7x20)

(38x7x20)

(51x7x20)

(75x7x20)

(97x7x20)

(145x7x20)

(145x7x20)

4-Row

15x3.5x8

15x3.5x8

20x3.5x8

29.5x3.5x8

38x3.5x8

57x3.5x8

57x3.5x8

 

(38x9x20)

(38x9x20)

(51x9x20)

(75x9x20)

(97x9x20)

(145x9x20)

(145x9x20)

Volume — Gal. (Liters)

 

 

 

 

 

 

 

1-Row(Heat)

.06 (.23)

.06 (.23)

.08 (.30)

.11 (.42)

.14 (.53)

.21 (.79)

.21 (.79)

2-Row

.12 (.45)

.12 (.45)

.15 (.57)

.22 (.83)

.28 (1.06)

.42 (1.59)

.42 (1.59)

3-Row

.18 (.68)

.18 (.68)

.23 (.87)

.33 (1.25)

.42 (1.59)

.62 (2.35)

.62 (2.35)

4-Row

.24 (.91)

.24 (.91)

.30 (1.14)

.44 (1.67)

.56 (2.12)

.83 (3.14)

.83 (3.14)

Fins/Ft (cm)

 

 

 

 

 

 

 

2-Row

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

3-Row

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

4-Row

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

144 (4.7)

Reheat Coil Data (1-Row)

 

 

 

 

 

 

 

Hot Water or Steam

 

 

 

 

 

 

 

Face Area — Ft2 (cm2)

0.6

0.6

0.8

1.2

1.6

2.4

2.4

 

(557)

(557)

(743)

(1120)

(1490)

(2230)

(2230)

LxDxH — In. (cm)

15x1.5x6

15x1.5x6

20x1.5x6

29.5x1.5x6

38x1.5x6

57x1.5x6

57x1.5x6

 

(38x4x15)

(38x4x15)

(51x4x15)

(75x4x15)

(97x4x15)

(145x4x15)

(145x4x15)

Volume — Gal. (Liters)

.12 (.45)

.12 (.45)

.15 (.57)

.22 (.83)

.28 (1.06)

.42 (1.59)

.42 (1.59)

Fins/Ft (cm)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

48 (1.6)

Fan/MotorData

 

 

 

 

 

 

 

FanQuantity

1

1

1

2

2

3

3

Size — Dia” x Width” (cm)

6.31x4

6.31x6.5

6.31x7.5

6.31x6.5

6.31x7.5

(1) 6.31x7.5

6.31x7.5

 

(16x10)

(16x17)

(16x19)

(16x17)

(16x19)

(16x19)

(16x19)

Size — Dia” x Width” (cm)

 

 

 

 

 

(2) 6.31x6.5

 

 

 

 

 

 

 

(16x6.5)

 

MotorQuantity

1

1

1

1

1

2

2

Filter Data

 

 

 

 

 

 

 

1” (cm) TA and Pl. Media

 

 

 

 

 

 

 

Quantity

1

1

1

1

1

1

1

Size — In. (cm)

87/8 x 191/8

87/8 x 191/8

87/8 x 241/8

87/8 x 335/8

87/8 x 421/8

87/8 x 611/8

87/8 x 611/8

 

(23x49)

(23x49)

(23x61)

(23x85)

(23x107)

(23x155)

(23x155)

1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)

 

 

 

Quantity

1

1

1

1

1

1

1

Size — In. (cm)

51/2 x 191/8

51/2 x 191/8

51/2 x 241/8

51/2 x 335/8

51/2 x 421/8

51/2 x 611/8

51/2 x 611/8

(14 x 49)

(14 x 49)

(14 x 61)

(14 x 85)

(14 x 107)

(14 x 156)

(14 x 156)

 

Table I-GI-2. Low vertical fan-coil component data

unit size

03

04

06

Coil Data

 

 

 

Face Area — Ft2 (cm2)

1.1 (1020)

1.6 (1490)

2.1 (1950)

LxDxH — In. (cm)

 

 

 

2-Row

20x1.7x8 (51x4x20)

29.5x1.7x8 (75x4x20)

38x1.7x8 (97x4x20)

3-Row

20x2.6x8 (51x7x20)

29.5x2.6x8 (75x7x20)

38x2.6x8 (97x7x20)

Volume — Gal. (Liters)

 

 

 

1-Row(Heat)

.08 (.30)

.11 (.42)

.14 (.53)

2-Row

.15 (.57)

.22 (.83)

.28 (1.06)

3-Row

.23 (.87)

.33 (1.25)

.42 (1.59)

Fins/Ft

 

 

 

2-Row

144 (4.7)

144 (4.7)

144 (4.7)

3-Row

144 (4.7)

144 (4.7)

144 (4.7)

Fan/MotorData

 

 

 

FanQuantity

1

1

1

Size — Dia”x Width” (cm)

5x23 (13x59)

5x32 (13x83)

5x41(13x105)

MotorQuantity

1

1

1

Filter Data

 

 

 

1” (2.5 cm) TA

 

 

 

Quantity

1

1

1

Size — In. (cm)

87/8x241/8 (23x61)

87/8x335/8 (23x85)

87/8 x 421/8 (23x107)

UNT-SVX07A-EN

7

general Installation information

Available Models

model A vertical concealed

model B vertical cabinet

model C horizontal concealed

model D horizontal cabinet

model E horizontal recessed

model F wall hung cabinet

model K low vertical cabinet

model H vertical recessed

model L low vertical concealed

 

model J slope-top cabinet

model M inverted vertical cabinet

model N inverted vertical recessed

 

(Force Flo only)

(Force Flo only)

8

UNT-SVX07A-EN

Trane UNT-SVX07A-EN User Manual

general Installation information

Factory-Installed Piping Packages

Note: This figure shows piping package components and basic arrangement. It is not an accurate pictorial of what factory-installed piping packages look like.

UNT-SVX07A-EN

9

 

dimensions

Installation

& weights

 

 

 

 

Vertical Concealed, Model A

Vertical Concealed Unit Dimensions & weights, in-lbs.

Unit

 

 

 

 

 

Size

02-03

04

06

08

10-12

A

2’-8 11/16

3’-1 11/16

3’-11 3/16

4’-7 11/16” 6’-2 11/16

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

1’-10 13/16

2’-3 13/16

3’-1 5/16

3’-9 13/16” 5’-4 13/16

D

1’-5 5/16

1’-10 5/16

2’-7 13/16

3’-4 5/16

4’-11 5/16

E

1’-7 5/16” 2’-0 5/16” 2’-9 13/16” 3’-6 5/16” 5’-1 5/16

operating weight 81

109

139

147

200

shippingweight

68

96

123

131

182

Notes:

1.Coil connections are always on the drain pan side and opposite the control box.

2.Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.

3.All duct collar dimensions are to the outside of the collar.

4.See fresh air opening dimensions on pages 23-24.

10

UNT-SVX07A-EN

 

dimensions

Installation

& weights

 

 

 

 

Vertical Cabinet, Model B

Vertical Cabinet Unit Dimensions, in-lbs.

unit

 

 

 

 

 

size

02-03

04

06

08

10-12

A

2’-9 5/16

3’-2 5/16” 3’-11 3/16” 4’-8 5/16” 6’-3 5/16

B

1’-9 5/16

2’-2 5/16” 2’-11 3/16” 3’-8 5/16” 5’-3 5/16

C

7 5/8

7 1/8

8 7/8

7 1/8

7 5/8

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-7 5/16

2’-0 5/16” 2’-9 13/16

3’-6 5/16” 5’-1 5/16

F

3’-5 5/16

3’-10 5/16

4’-7 3/16

5’-4 5/16

6’-11 5/16

operatingweight 97

125

155

164

218

shippingweight

84

112

139

148

200

Notes:

1. Coil connections are always on the drain pan side and opposite the control box. 2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.

3. All duct collar dimensions are to the outside of the collar. 4. See pages 23-24 for fresh air opening dimensions.

UNT-SVX07A-EN

 

11

 

dimensions

Installation

& weights

 

 

 

 

Horizontal Concealed, Model C

Horizontal Concealed Unit Dimensions, in-lbs.

unit

 

 

 

 

 

 

size

 

02-03

04

06

08

10-12

A

2’-8 11/16

3’-1 11/16

3’-11 3/16

4’-7 11/16

6’-2 11/16

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

1’-10 13/16

2’-3 13/16

3’-1 5/16

3’-9 13/16

5’-4 13/16

D

 

1’-7 3/8

2’-0 3/8

2’-9 7/8

3’-6 3/8

5’-1 3/8

E

 

1’-6 1/8” 1’-11 1/8” 2’-8 5/8

3’-5 1/8

5’-0 1/8

F

1’-7 5/16” 2’-0 5/16” 2’-9 13/16” 3’-6 5/16” 5’-1 5/16

operatingweight

81

109

139

147

200

shippingweight

68

96

123

131

182

Notes:

1. Coil connections are always on the drain pan side and opposite the control box.

2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations. 3. All duct collar dimensions are to the outside of the collar.

4. See pages 23-24 for fresh air opening dimensions.

12

UNT-SVX07A-EN

 

dimensions

Installation

& weights

 

 

 

 

Horizontal Cabinet, Model D

Horizontal Cabinet Unit Dimensions, in-lbs.

unit

 

 

 

 

 

size

02-03

04

06

08

10-12

A

2’-9 5/16

3’-2 5/16” 3’-11 3/16” 4’-8 5/16” 6’-3 5/16

B

1’-9 5/16

2’-2 5/16

2’-11 13/16” 3’-8 5/16

5’-3 5/16

C

7 5/8

7 1/8

8 7/8

7 1/8

7 5/8

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-5 1/4

1’-10 1/4” 2’-7 3/4” 3’-4 1/4” 4’-11 1/4

F

3’-5 5/16

3’-10 5/16

4’-7 3/16

5’-4 5/16” 6’-11 5/16

G

8 5/8

8 1/8

9 7/8

8 1/8

8 5/8

H

1’ -4”

1’-10”

2’-4”

3’-4”

4’-10”

J

1’-7 3/4

1’-11 3/4” 2’-7 3/4” 3’-3 3/4” 4’-11 3/4

operatingweight

97

125

155

164

218

shippingweight

84

112

139

148

200

Notes:

1. Coil connections are always on the drain pan side and opposite the control box.

2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations. 3. All duct collar dimensions are to the outside of the collar.

4. See pages 23-24 for fresh air opening dimensions.

UNT-SVX07A-EN

13

Installation

dimensions

& weights

 

 

 

 

Horizontal Recessed, Model E

Horizontal Recessed Unit Dimensions, in-lbs.

unit

 

 

 

 

 

 

size

 

02-03

04

06

08

10-12

A

2’-11 13/16

3’-4 13/16

4’-2 5/16

4’-10 13/16

6’-5 13/16

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

1’-10 13/16

2’-3 13/16

3’-1 5/16

3’-9 13/16

5’-4 13/16

D

1’-7 3/8

2’-0 3/8

2’-9 7/8

3’-6 3/8

5’-1 3/8

E

1’-6 1/8

1’-11 1/8” 2’-8 5/8

3’-5 1/8

5’-0 1/8

F

2’-8 7/16

3’-1 7/16

3’-10 15/16

4’-7 7/16

6’-2 7/16

G

2’-10 5/16

3’-3 5/16

4’-0 13/16

4’-9 5/16

6’-4 5/16

H

1’-7 3/4

1’-11 3/4” 2’-7 3/4

3’-3 3/4” 4’-11 3/4

operatingweight

78

88

128

139

253

shippingweight

68

78

118

129

243

Notes:

1.Coil connections are always on the drain pan side and opposite the control box.

2.Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.

3.All duct collar dimensions are to the outside of the collar.

4.See pages 23-24 for fresh air opening dimensions.

14

UNT-SVX07A-EN

Installation

dimensions

& weights

 

 

 

 

Vertical Wall Hung Cabinet, Model F

Vertical wall hung cabinet unit dimensions & weights, in-lbs.

unit

 

 

 

 

 

size

02-03

04

06

08

10-12

A

2’-9 5/16

3’-2 5/16

3’-11 13/16

4’-8 5/16

6’-3 5/16

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

7 5/8

7 1/8

8 7/8

7 1/8

7 5/8

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-7 5/16

2’-0 5/16” 2’-9 13/16” 3’-6 5/16” 5’-1 5/16

F

1’-7 3/4

1’-11 3/4

2’-7 3/4

3’-3 3/4” 4’-11 3/4

operatingweight

97

125

155

164

218

shipping weight

84

112

139

148

200

Notes:

1. Coil connections are always on the side opposite the control box. 2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations. 3. All duct collar dimensions are to the outside of the collar.

4. See pages 23-24 for fresh air opening dimensions.

UNT-SVX07A-EN

15

Installation

dimensions

& weights

 

 

 

 

Vertical Recessed, Model H

Vertical Recessed Unit Dimensions, in-lbs.

unit

 

 

 

 

 

 

size

 

02-03

04

06

08

10-12

A

2’-8 11/16

3’-1 11/16

3’-11 3/16

4’-7 11/16

6’-2 11/16

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

1’-10 13/16

2’-3 13/16

3’-1 5/16

3’-9 13/16

5’-4 13/16

D

1’-5 5/16

1’-10 5/16

2’-7 13/16

3’-4 5/16

4’-11 5/16

E

 

3’-11”

4’-3”

5’-3”

5’-5 1/2

7’-5 1/2

F

 

2’-6”

2’-6”

2’-6”

2’-9 1/2

2’-9 1/2

G

 

2 3/8

2 3/8

2 3/8

4 1/8

4 1/8

H

 

3’-6”

4’-0”

4’-9”

5’-3”

7’-3”

J

 

2’-2 1/2

2’-2 1/2

2’-2 1/2

2’-3 1/2

2’-3 1/2

operatingweight

78

88

128

139

253

shipping weight

68

78

118

129

243

Notes:

1. Coil connections are always on the drain pan side and opposite the control box.

2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations. 3. All duct collar dimensions are to the outside of the collar.

4. See pages 23-24 for fresh air opening dimensions.

5. Dimension 'G' refers to the required minimum distance between the finished floor, and the bottom of the unit.

16

 

UNT-SVX07A-EN

Installation

dimensions

& weights

 

 

 

 

Vertical Slope Top, Model J

Vertical Slope Top Unit Dimensions, in-lbs.

unit

 

 

 

 

 

 

size

02-03

04

06

08

10-12

 

A

2’-9 5/16

3’-2 5/16

3’-11 13/16

4’-8 5/16

6’-3 5/16

 

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

7 5/8

7 1/8

8 7/8

7 1/8

7 5/8

 

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

 

E

1’-7 5/16

2’-0 5/16

2’-9 13/16

3’-6 5/16

5’-1 5/16

 

F

3’-5 5/16

3’-10 5/16

4’-7 13/16

5’-4 5/16

6’-11 5/16

operatingweight 97

125

155

164

218

 

shipping weight

84

112

139

148

200

 

Notes:

1. Coil connections are always on the drain pan side and opposite the control box. 2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.

3. All duct collar dimensions are to the outside of the collar. 4. See pages 23-24 for fresh air opening dimensions.

UNT-SVX07A-EN

17

Installation

dimensions

& weights

 

 

 

 

Low Vertical Concealed, Model K

Low Vertical Concealed Unit Dimensions, in-lbs.

unit size

03

04

06

A

3’-5 7/16

4’-2 15/16

4’-11 7/16

B

2’-2 1/4

2’-11 3/4

3’-8 1/4

C

2’-3 15/16

3’-0 13/16

3’-9 15/16

D

1’-10 5/16

2’-7 13/16

3’-4 5/16

E

2’-0 1/4

2’-9 3/4

3’-6 1/4

operatingweight

109

139

147

shipping weight

96

123

131

Notes:

1. Coil connections are always on the drain pan side and opposite the control box.

2. Coil connections are 5/8” O.D. sweat.

3. All duct collar dimensions are to the outside of the collar. 4. See pages 23-24 for fresh air opening dimensions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNT-SVX07A-EN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation

dimensions

& weights

 

 

 

 

Low Vertical Cabinet, Model L

Low Vertical Cabinet Unit Dimensions, in-lbs.

unit

 

 

 

size

03

04

06

A

3’-10 15/16

4’-8 7/16

5’-4 15/16

B

2’-2 1/4

2’-11 3/4

3’-8 1/4

C

11 7/16

1’-1 5/16

11 7/16

D

2’-0”

2’-6”

3’-6”

E

2’-0 1/4

2’-9 3/4

3’-6 1/4

operatingweight

125

155

164

shipping weight

112

139

148

Notes:

1. Coil connections are always on the drain pan side and opposite the control box.

2. Coil connections are 5/8” O.D. sweat.

3. All duct collar dimensions are to the outside of the collar. 4. See pages 23-24 for fresh air opening dimensions.

UNT-SVX07A-EN

19

Installation

dimensions

& weights

 

 

 

 

Inverted Vertical Cabinet, Model M

Inverted vertical cabinet unit dimensions & weights, in-lbs.

unit

 

 

 

 

 

size

02-03

04

06

08

10-12

A

2’-9 5/16

3’-2 5/16

3’-11 13/16

4’-8 5/16

6’-3 5/16

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

7 5/8

7 1/8

8 7/8

7 1/8

7 5/8

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-7”

2’-0”

2’-9 1/2

3’-6”

5’-1”

F

1’-7 3/4

1’-11 3/4

2’-7 3/4

3’-3 3/4

4’-11 3/4

G

8 5/8

8 1/8

9 7/8

8 1/8

8 5/8

H

1’-4”

1’-10”

2’-4”

3’-4”

4’-10”

operatingweight

97

125

155

164

218

shipping weight

84

112

139

148

200

Notes:

1. Coil connections are always on the side opposite the control box. 2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations. 3. All duct collar dimensions are to the outside of the collar.

4. See pages 23-24 for fresh air opening dimensions.

20

UNT-SVX07A-EN

Installation

dimensions

& weights

 

 

 

 

Inverted Vertical Recessed, Model N

Inverted vertical recessed unit dimensions & weights, in-lbs.

unit

 

 

 

 

 

size

02-03

04

06

08

10-12

A

2’-3 7/8

2’-8 7/8

3’-6 3/8

4’-2 7/8

5’-9 7/8

B

1’-9 5/16

2’-2 5/16

2’-11 13/16

3’-8 5/16

5’-3 5/16

C

1’-10 13/16

2’-3 13/16

3’-1 5/16

3’-9 13/16

5’-4 13/16

D

2 3/8

2 3/8

2 3/8

4 1/8

4 1/8

E

3’-11”

4’-3”

5’-3”

5’-5 1/2

7’-5 1/2

F

2’-6”

2’-6”

2’-6”

2’-9 1/2

2’-9 1/2

G

2’-2 1/2

2’-2 1/2

2’-2 1/2

2’-3 1/2

2’-3 1/2

H

3’-6”

4’-0”

4’-9”

5’-3”

7’-3”

operatingweight

78

88

128

139

253

shipping weight

68

78

118

129

243

Notes:

1.Coil connections are always on the side opposite the control box.

2.Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.

3.All duct collar dimensions are to the outside of the collar.

4.See pages 23-24 for fresh air opening dimensions.

Dimension 'D' refers to the required minimum distance between the finished floor, and the bottom of the unit.

UNT-SVX07A-EN

21

Installation

dimensions

& weights

 

 

 

 

Fan-Coil

Coil Connections

Vertical Units

Fan-Coil

Coil Connections

Horizontal Units

22

UNT-SVX07A-EN

Force Flo

Coil Connections,

Vertical Units

Force Flo

Coil Connections,

Horizontal Units

HR - Hot Water Return

HS - Hot Water Supply

 

 

 

 

Installation

 

dimensions

 

 

 

 

 

& weights

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Force Flo

Coil Connections,

Inverted Units

UNT-SVX07A-EN

23

Installation

dimensions

& weights

 

 

 

 

Fresh Air Opening Locations

Horizontal Units Models C, D, and E

Fresh Air Opening Dimensions, Horizontal Units

Unit

 

 

 

 

 

 

 

Size

02-03

04

06

 

08

 

10-12

A

1’-6”

1’-11”

2’-8

1/2

3’-5”

5’-0”

B

1’-9 5/16

2’-2 5/16

2’-11 13/16” 3’-8

5/16

5’-3 5/16

24

UNT-SVX07A-EN

Loading...