Trane RT-SVX19A-E4 User Manual

0 (0)

Installation

Operation

Maintenance

Voyager™ II Rooftop units

Cooling only TKD/TKH 155 175 200 250 Reversible WKD/WKH 125 155 200 Gas-Fired YKD/YKH 155 175 200 250 R22 - R407C Refrigerant

RT-SVX19A-E4

General information

Foreword

These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane TKD/TKH, WKD/WKH and YKD/YKH units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.

TKD/TKH units are designed to operate in cooling mode only, with optional auxiliary heat (electric heater or hot water coil).

WKD/WKH can operate in cooling mode or heating mode by reversing the refrigeration cycle with or without auxiliary heat.

YKD/YKH units are designed to operate In cooling mode and equipped with a gas fired heating module.

TKD/TKH, WKD/WKH and YKD/YKH units are assembled, pressure tested, dehydrated, charged and run tested before shipment.

Warnings and cautions

Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.

WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.

Safety recommendations

To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:

1.The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter "Installation". Always provide a pressure regulator.

2.Disconnect the main power supply before any servicing on the unit.

3.Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel.

Reception

On arrival, inspect the unit before signing the delivery note.

In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery.

Reception in France only:

Concealed damage must be looked for at delivery and immediately treated as visible damage.

Reception in all countries except France:

In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.

2

RT-SVX19A-E4

General information

Warranty

Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.

Refrigerant

The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled.

Maintenance contract

It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.

Storage

Take precautions to prevent condensate formation inside the unit's electrical components and motors when:

1.The unit is stored before it is installed; or,

2.The unit is set on the roof curb and temporary auxiliary heat is provided in the building.

Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for start-up.

Do not use the unit's heater as temporary heat without completing the start-up procedures detailed under "Unit Start-Up".

The Trane Company will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components.

Training

To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.

RT-SVX19A-E4

3

Contents

 

 

 

 

Foreword

2

 

 

Warnings and Cautions

2

 

 

Safety recommendations

2

 

 

Reception

2

 

 

Warranty

3

 

 

Refrigerant

3

 

 

Maintenance contract

3

 

 

Storage

3

 

 

Training

3

Installation

6

 

 

Reception of units

6

 

 

Roof curb installation

7

 

 

Dimensions/Weights/Clearances

8

 

 

Installing the unit

10

 

 

Connection of duct network

11

 

 

Condensate drain piping

12

 

 

Gas pipework installation

13

 

 

Filter installation

14

 

 

Supply fan adjustment

15

 

 

Component air pressure drops

17

 

 

Supply fan performances

20

 

 

Electrical connection

26

Controls

31

 

 

Control wiring

 

31

 

 

CO2 sensors

 

33

 

 

Remote potentiometer

 

36

 

 

Fire thermostat

 

37

 

 

Clogged filter detector

 

38

 

 

Smoke detector

 

38

 

 

High temperature safety thermostat

 

38

 

 

Remote fault relay

 

38

 

 

Thermostats

 

38

 

 

Communication Interfaces

 

39

4

RT-SVX19A-E4

Contents

 

 

 

Unit Options

40

 

 

Hot water coil

 

40

 

 

Electric Heater

 

41

 

 

Soft Starter

 

41

 

 

0 - 25% fresh air hood

 

42

 

 

Barometric relief

 

43

Operation

44

 

 

Operation with a conventional thermostat

 

44

 

 

Setting the economizer

 

47

 

 

Test procedures

 

49

 

 

Test modes

 

50

 

 

Unit start-up

 

51

 

 

Cooling without an Economizer

 

54

 

 

Low Ambient Operation

 

55

 

 

Cooling with an Economizer

 

55

 

 

Economizer Set-Up

 

56

 

 

ReliaTel™ Control Heating Operation

 

56

 

 

Ignition Module

 

56

 

 

Final installation checklist

 

57

Maintenance

58

 

 

End user routine maintenance

 

58

 

 

Service technician maintenance

 

59

 

 

Troubleshooting

 

60

RT-SVX19A-E4

5

Installation

General information : The installation must conform to all local standards and regulations.

Reception of units

Rooftop unit

The unit is supplied on a wooden frame. It is recommended to check the machine's condition upon reception.

Figure 1a - Unit handling

B

A

1 = Clevis

2 = Base Rail

3 = Spreader Bar

L = Length (Center of Gravity)

W = Width (Center of Gravity)

Refer to Table 2 for weights and center of gravity.

There are two ways to handle the unit:

1.Use the openings in the wooden frame to handle the machine using a fork lift, in accordance with applicable safety regulations.

2.Use a lifting beam correctly adjusted to fit the unit (Figure 1a).

Unit handling

The units are supplied on the truck but are not unloaded. An opening is provided on each corner of the unit base to facilitate handling.

4 shackles and 4 slings are required. Use a lifting beam to prevent the cables pressing too hard on top of the unit during lifting.

Figure 1a indicates the position of the center of gravity and the lifting recommendations.

Important: For unit to fit on the roof curb the fork lift pockets must be removed.

6

RT-SVX19A-E4

Installation

Table 1 - Sling lengths and maximum unit weight

Unit size

A (mm)

B (mm)

Maximm weight

kg

 

 

 

 

 

 

 

125

3000

1900

644

 

 

 

 

155

3000

1900

773

 

 

 

 

175

3000

1900

810

 

 

 

 

400

3500

2200

1001

 

 

 

 

500

3500

2200

1027

 

 

 

 

Figure 1b - Maximum slope correction of adjustable roof curb.

Figure 2 - Waterproofing

Roof curb Installation (TKD-WKD-YKD accessories)

Roof curbs are available as an accessory for "downflow" units to support the unit and ensure the water tightness between the rooftop and the roof. Two types of roof curbs are available: The standard version to allow the installation of the unit on a flat roof and the adjustable version for a sloped roof installation. (See Figure 1b for the maximum slope correction of adjustable roofcurb.)

The adjustable roof curbs are supplied pre-assembled on a skid.

Two types of self-adhesive seals are provided separately. (40 mm wide for the perimeter, 20 mm wide for the cross pieces). Make sure they are properly installed where indicated to assure an adequate curb to unit seal.

Instructions for the roof curb assembly and installation with curb dimensions are provided with each roof curb kit.

4

3

1

2

1 = Roofcurb

2 = Roof membrane

3 = Seal

4 = Rooftop

RT-SVX19A-E4

7

Installation

Dimensions/Weights/Clearances

Figure 3 - Minimum clearances

Table 2 - Minimum clearances (mm)

 

 

 

Minimum clearance

 

 

UNIT

1

2

3

4

5

 

 

 

 

 

 

YKD/YKH 155

1900

1800

1220

1000

1300

YKD/YKH 175

1900

1800

1220

1000

1300

YKD/YKH 200

1900

1800

1220

1000

1300

YKD/YKH 250

1900

1800

1220

1000

1300

 

 

 

 

 

 

TKD/TKH 155

1900

1800

1220

1000

1300

TKD/TKH 175

1900

1800

1220

1000

1300

TKD/TKH 200

1900

1800

1220

1000

1300

TKD/TKH 250

1900

1800

1220

1000

1300

 

 

 

 

 

 

WKD/WKH 125

1900

1800

1220

1000

1300

WKD/WKH 155

1900

1800

1220

1000

1300

WKD/WKH 200

1900

1800

1220

1000

1300

 

 

 

 

 

 

The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. Refer to Table 3a and the space requirement plan.

8

RT-SVX19A-E4

Installation

Table 3a - Weigths & center of gravity (Figure 1)

 

Maximum weight

 

Corner Weight (1)

 

Center of Gravity

 

 

 

 

 

 

 

 

 

 

Shipping

Net

A

B

C

D

Length (L)

Width (W)

UNIT

(kg)

(kg)

(kg)

(kg)

(kg)

(kg)

(mm)

(mm)

 

 

 

 

 

 

 

 

 

YKD/YKH 155

866

698

243

176

118

162

1143

737

YKD/YKH 175

902

735

251

188

127

169

1168

737

YKD/YKH 200

1128

920

324

242

151

203

1321

838

YKD/YKH 250

1154

946

327

251

159

208

1346

838

 

 

 

 

 

 

 

 

 

TKD/TKH 155

790

623

219

159

103

142

1143

711

TKD/TKH 175

827

660

227

172

112

149

1168

711

TKD/TKH 200

1050

841

297

221

138

185

1321

838

TKD/TKH 250

1075

866

300

230

145

206

1346

838

 

 

 

 

 

 

 

 

 

WKD/WKH 125

792

625

218

159

105

144

1143

711

WKD/WKH 155

809

642

228

162

105

147

1143

711

WKD/WKH 200

1080

871

291

226

155

199

1346

889

1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.

Table 3b - Weights of Options & accessories

 

 

 

 

 

Motorized

 

 

 

Standard Roof

Adjustable Roof

 

Manual Outside

Outside Air

 

 

UNIT

Curb

Curb

Economizer

Air Damper

Damper

Electric heater

Hot water coil

 

 

 

 

 

 

 

 

YKD 155

93

220

30

15

27

 

 

YKD 175

93

220

30

15

27

 

 

YKD 200

107

260

37

15

34

 

 

YKD 250

107

260

37

15

34

 

 

YKH 155

 

 

30

15

27

 

 

YKH 175

 

 

30

15

27

 

 

YKH 200

 

 

37

15

34

 

 

YKH 250

 

 

37

15

34

 

 

 

 

 

 

 

 

 

 

TKD 155

93

220

30

15

27

14

85

TKD 175

93

220

30

15

27

14

85

TKD 200

107

260

37

15

34

18

110

TKD 250

107

260

37

15

34

18

110

TKH 155

 

 

30

15

27

14

 

TKH 175

 

 

30

15

27

14

 

TKH 200

 

 

37

15

34

18

 

TKH 250

 

 

37

15

34

18

 

 

 

 

 

 

 

 

 

WKD 125

93

180

20

15

27

18

85

WKD 155

93

220

30

15

27

18

85

WKD 200

107

260

37

15

34

18

110

WKH 125

 

 

20

15

27

18

 

WKH 155

 

 

30

15

27

18

 

WKH 200

 

 

37

15

34

18

 

Notes :

Net weight should be added to unit weight when ordering factory installed accessories.

To estimate shipping weight add 2.3 kg to net weight.

RT-SVX19A-E4

9

Trane RT-SVX19A-E4 User Manual

Installation

Figure 4

1 = Frame

Figure 5

Installing the unit

1) Unit mounting on roof

Fix the rooftop curb on the joint beam of the building's structure. Make the rooftop curb's sealing surface level using angle brackets adjusted by screw bolts, located around its perimeter. Place the adhesive seals on the curb's sealing surface (perimeter and cross pieces). Make the rooftop leak-tight around the curbs before installing the unit, in compliance with current construction standards.

Note: The unit must be installed perfectly level to ensure condensates flow from the condensate tray.

The rooftop unit nests into the curb and is supported by it. Position the unit, taking care to comply with the indicated directions: the unit's discharge and intake openings must match those of the curb.

2) Installing the unit on the ground

To install the unit on the ground, its base must be level and supported securely.

For horizontal discharge units, a support is required such as a metal or concrete slab whose height must be determined according to the amount of snow cover, to prevent problems with condensation drainage and obstruction of the external coil. If necessary use an anti-vibration material between the rooftop unit's base and the support.

Note: Unit installation must comply to local codes

1 = Concrete slab

10 RT-SVX19A-E4

RT-SVX19A-E4

Installation

Connection of duct network

1) Downflow discharge units (TKD,WKD,YKD)

Using the rooftop curb

The rooftop curb must be insulated on the outside walls at the discharge and intake openings to prevent condensation in the ducts.

The rims around the discharge and intake openings make it possible to attach the flanges on the ends of the ducts. If you are using rigid duct ends recommended on the rooftop curb plan, it is essential to fix these components before installing the unit.

For the design of the duct network, comply with recommendations currently applicable on the market, in particular:

. Installation of a section of flexible ducts to limit transmission of the unit's vibrations

. Use of movable vanes or deflectors to reduce the sound level.

2) Horizontal discharge units (TKH,WKH,YKH)

The intake and discharge ducts must be insulated (thermal insulation).

The duct section located outside must be leak-tight.

Provide a flexible connector to prevent transmission of the unit vibrations. This flexible duct must be installed inside the building.

Note: In case of use of TKH, WKH or YKH units with economizer option, temperature and humidity sensors must be installed in return duct.

Economizer linkage is factory mounted but the damper position must be adjusted on site.

Figure 6 - Condensate Drain location

1 = Condensate drain connection

A = TKH/YKH 155, 175, 200, 250 - WKH 125,155, 200 B = TKD/YKD 155, 175, 200, 250 - WKD 125,155,200

RT-SVX19A-E4

11

Installation

Condensate drain piping

A 42mm PVC condensate drain connection with P-trap is provided.

Follow local codes and standard piping practices when running the drain line. Install a trap and be sure to fill with water before starting the unit. Pitch the line downward, away from the unit to avoid long, level, horizontal runs. Refer to Figure 7.

Figure 7 - Condensate drain line connection

1 = Static pressure drain pan

2 = Panel enclosure

3 = 42mm PVC drain

4 = Cleanout plug

12

RT-SVX19A-E4

Installation

Gas pipework installation

The installation must conform to all standards and regulations.

The gas supply pipework and gas stop valve to be installed near the unit must be sized so as to assure the gas pressure is sufficient at the unit inlet when operating at full load.

CAUTION! Should the pressure at the unit valve gas inlet be higher than 0.035 bar, an expansion valve must be installed.

The pipework must be selfsupporting and the final connection to the burner must be made by a flexible pipe. Provide a dust protection (filter) upstream the unit connection.

CAUTION! The gas pipework must not exert any stress on the burner gas connection.

Note: Expansion valve must be adapted to the type of gas used:

G 20 : 20 mb

G 25 : 25 mb

G 31 : (Propane): 37 or 50 mb

Table 4 - Gas burner models

Unit

 

Burner size

YKD/H

155

G350A

YKD/H

175

G350A

YKD/H

200

G350A

YKD/H

250

G350A

 

 

 

 

See Table 38 for burner

 

performance.

 

Gas leak check procedure

 

1. Vent the gas line

 

2. Gas supply line pressure test:

Figure 8 - Typical gas supply Pipework

close valve 4 and open valve 2

 

3. Leak-check the gas pipe

 

Look for gas pipe leaks using

 

"Typol", "1000 bulles" or a similar

 

product. Do not use soapy water.

 

WARNING! Never use an open

 

flame to check for gas leaks.

 

Required gas pressure at the unit

 

inlet connection are given in

 

Table 37.

 

Note: To operate with propane gas,

 

the burner is fitted with a pressure

 

limiter (supplied by Trane)

1

= Evaporator section

5

= Gas supply line

2

= Gas burner section

6,8 = Gas stop valve (Field supplied)

3

= Condenser section

7

= Expansion valve (Field supplied)

4

= Gas supply connection

9

= Filter (Field supplied)

RT-SVX19A-E4

13

Installation

Filter installation

To gain access to filters, remove the supply fan access panel on downflow units and the filter access panel on the end for horizontal units.

Each unit ships with 40 or 50 mm thick filters. Number and size of filters is determined by size and configuration of the unit.

CAUTION! Do not operate unit without filters in place.

The maximum pressure drops allowable on filters are:

EU2/G2: 120 Pa

EU4/G4: 150 Pa

Table 5 - Filter arrangement

UNIT

 

EU2/G2

 

EU4/G4

Qty

Size

Qty

Size

 

 

 

 

 

 

YKH/YKD 155

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

YKH/YKD 175

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

YKH 200

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

YKD 200

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

YKH 250

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

YKD 250

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH/TKD 155

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH/TKD 175

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH 200

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

TKD 200

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

TKH 250

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

TKD 250

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

WKH/WKD 125

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

WKH/WKD 155

2

(508x508x50)

2

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

WKH 200

8

(508x635x50)

8

(500x625x50)

 

 

 

 

 

WKD 200

4

(508x508x50)

4

(498x498x40)

 

 

 

 

4

(508x635x50)

4

(500x625x50)

 

 

 

 

 

 

14

RT-SVX19A-E4

Installation

Supply fan adjustment

Use the following procedure to determine the proper adjustment of the supply fan for a specific application.

1.Determine total external static pressure about system and accessories.

a.Obtain the design airflow rate and the design external static pressure drop through the distribution system.

b.Add static pressure drop of the accessories installed on the unit. (Table 7,8 & 9)

c.Add the total accessory static pressure drop (from step 1b) to the design external static pressure (from step 1a).The sum of these two values is the total system external static pressure.

2.Using the Tables 10 through 20 to find the external static pressure that most closely approximates total system external static pressure. Then locate the appropriate airflow rate for your unit. The value obtained represents the brake horsepower for the supply fan motor and the fan RPM.

3.Adjust motor sheave according to Table 6.

Table 6 - Motor sheave / Fan speed

Fan Speed (RPM)

Standard Drive

 

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

 

UNIT

Open

Open

Open

Open

Open

Open

Closed

 

 

 

 

 

 

 

 

YKD/YKH 155

566

601

637

672

708

743

N/A

YKD/YKH 175

724

769

815

860

906

951

N/A

YKD/YKH 200

513

550

586

623

659

696

N/A

YKD/YKH 250

588

619

650

681

712

743

N/A

 

 

 

 

 

 

 

 

TKD/TKH 155

566

601

637

672

708

743

N/A

TKD/TKH 175

724

769

815

860

906

951

N/A

TKD/TKH 200

513

550

586

623

659

696

N/A

TKD/TKH 250

588

619

650

681

712

743

N/A

 

 

 

 

 

 

 

 

WKD/WKH 125

533

566

600

633

667

700

N/A

WKD/WKH 155

566

601

637

672

708

743

N/A

WKD/WKH 200

513

550

586

623

659

696

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Speed (RPM)

 

 

 

 

 

 

 

Oversized Drive

 

 

 

 

 

 

 

 

 

 

 

 

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

 

UNIT

Open

Open

Open

Open

Open

Open

Closed

 

 

 

 

 

 

 

 

YKD/YKH 155

672

714

756

798

840

882

N/A

YKD/YKH 175

791

840

890

939

989

1038

N/A

YKD/YKH 200

680

711

742

773

804

835

N/A

YKD/YKH 250

690

722

754

786

818

850

N/A

 

 

 

 

 

 

 

 

TKD/TKH 155

672

714

756

798

840

882

N/A

TKD/TKH 175

791

840

890

939

989

1038

N/A

TKD/TKH 200

680

711

742

773

804

835

N/A

TKD/TKH 250

690

722

754

786

818

850

N/A

 

 

 

 

 

 

 

 

WKD/WKH 125

724

769

815

860

906

951

N/A

WKD/WKH 155

513

550

586

623

659

696

N/A

WKD/WKH 200

588

619

650

681

712

743

N/A

 

 

 

 

 

 

 

 

RT-SVX19A-E4

15

Installation

To increase airflow

Loosen variable sheave set screw and turn sheave clockwise.

To decrease airflow

Loosen variable sheave set screw and turn sheave counter-clockwise.

To increase belt tension

Loosen the nut (next to the idler sheave) that secures the sheave in place. With a wrench, apply pressure clockwise on the outside nut (round headed one), until tension desired is reached. While holding pressure with the tension nut, retighten the nut next to the idler sheave.

Figure 9 - Typical fan, motor, and sheave assembly

A = Fan Housing

B= Terminal Block

C= Fan Sheave

D= Plastic Bushing

E= Belt Tension Adjustment Bolt

F= Idler Pulley

Table 6b - Belt tensioning

TK* / YK* /

 

Fan pulley

Fan pulley

Belt type

Belt

Deflexion

Deflexion

Belt tensionBelt tension

Motor kW

Type /

Type /

deflexion

effort

effort

mini

maxi

WK*

 

diam. (mm)

diam. (mm)

/ lengh (mm)

(mm)

mini kg

maxi kg

N

N

 

 

 

 

 

 

 

 

 

 

 

 

 

125

1,5

BK90 / 222

1VP44 / 105

BX68 / 1727

5,89

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

155

1,5

BK85 / 210

1VP44 / 105

BX68 / 1727

6

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

175

3

BK130 / 324

1VP44 / 105

BX75 / 1905

6,05

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

200

3

BK160 / 400

1VL40 / 95

BX90 / 2286

6,96

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

250

4,6

BK190 / 476

1VP50 / 121

BX96 / 2438

6,91

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

125

3

BK130 / 324

1VP44 / 105

BX75 / 1905

5,85

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

155

3

BK140 / 349

1VP44 / 105

BX77 / 1955

6,17

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

175

4,6

BK140 / 349

1VP56 / 136

BX75 / 1905

5,45

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

200

4,6

BK190 / 476

1VP56 / 136

BX96 / 2438

6,87

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

250

4,6

BK190 / 476

1VP56 / 136

BX96 / 2438

6,32

2,4

2,9

400

500

 

 

 

 

 

 

 

 

 

 

16

RT-SVX19A-E4

Installation

Component air pressure drops

Table 7 - YKD/YKH Pressure drop through accessories

 

 

Filter

Filter

Economizer

Economizer

 

Airflow

EU2/G2

EU4/G4

100%

100%

 

outside air

return air

 

 

 

 

 

 

 

 

 

 

 

6800

13

27

8

6

 

 

 

 

 

 

 

7650

16

30

10

7

 

 

 

 

 

 

YKD/YKH 155

8500

19

34

12

8

 

9350

22

37

14

9

 

 

 

 

 

 

 

10200

26

40

16

10

 

 

 

 

 

 

 

7870

17

30

10

7

 

 

 

 

 

 

 

8860

21

34

12

8

 

 

 

 

 

 

YKD/YKH 175

9850

25

38

15

9

 

10840

30

43

17

11

 

 

 

 

 

 

 

11830

35

47

20

12

 

 

 

 

 

 

 

8970

12

26

29

6

 

 

 

 

 

 

 

10090

15

30

37

8

 

 

 

 

 

 

YKD 200

11210

19

33

45

9

 

12330

23

37

55

11

 

 

 

 

 

 

 

13450

27

41

65

13

 

 

 

 

 

 

 

8970

11

23

33

6

 

 

 

 

 

 

 

10090

14

26

41

8

 

 

 

 

 

 

YKH 200

11210

17

29

51

9

 

12330

20

33

61

11

 

 

 

 

 

 

 

13450

23

36

72

13

 

 

 

 

 

 

 

11280

18

32

46

10

 

 

 

 

 

 

 

12690

24

36

58

12

 

 

 

 

 

 

YKD 250

14100

29

41

71

14

 

15510

36

46

86

17

 

 

 

 

 

 

 

16920

43

51

102

19

 

 

 

 

 

 

 

11280

17

30

52

10

 

 

 

 

 

 

 

12690

21

34

65

12

 

 

 

 

 

 

YKH 250

14100

26

38

80

14

 

15510

31

43

96

17

 

 

 

 

 

 

 

16920

36

47

114

19

 

 

 

 

 

 

RT-SVX19A-E4

17

Installation

Table 8 - TKD/TKH Pressure drop through accessories

 

 

Filter

Filter

Economizer

Economizer

Electric

Hot water coil

 

Airflow

EU2/G2

EU4/G4

100%

100%

heater

Downflow only

 

outside air

return air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6800

13

27

8

6

7

33

 

 

 

 

 

 

 

 

 

7650

16

30

10

7

9

40

 

 

 

 

 

 

 

 

TKD/TKH 155

8500

19

34

12

8

11

48

 

9350

22

37

14

9

13

56

 

 

 

 

 

 

 

 

 

10200

26

40

16

10

16

65

 

 

 

 

 

 

 

 

 

7870

17

30

10

7

10

42

 

 

 

 

 

 

 

 

 

8860

21

34

12

8

13

51

 

 

 

 

 

 

 

 

TKD/TKH 175

9850

25

38

15

9

16

61

 

10840

30

43

17

11

19

72

 

 

 

 

 

 

 

 

 

11830

35

47

20

12

23

83

 

 

 

 

 

 

 

 

 

8970

12

26

29

6

13

33

 

 

 

 

 

 

 

 

 

10090

15

30

37

8

17

40

 

 

 

 

 

 

 

 

TKD 200

11210

19

33

45

9

21

48

 

12330

23

37

55

11

25

56

 

 

 

 

 

 

 

 

 

13450

27

41

65

13

30

65

 

 

 

 

 

 

 

 

 

8970

11

23

33

6

13

-

 

 

 

 

 

 

 

 

 

10090

14

26

41

8

17

-

 

 

 

 

 

 

 

 

TKH 200

11210

17

29

51

9

21

-

 

12330

20

33

61

11

25

-

 

 

 

 

 

 

 

 

 

13450

23

36

72

13

30

-

 

 

 

 

 

 

 

 

 

11280

18

32

46

10

20

49

 

 

 

 

 

 

 

 

 

12690

24

36

58

12

25

59

 

 

 

 

 

 

 

 

TKD 250

14100

29

41

71

14

32

71

 

15510

36

46

86

17

38

82

 

 

 

 

 

 

 

 

 

16920

43

51

102

19

46

95

 

 

 

 

 

 

 

 

 

11280

17

30

52

10

19

-

 

 

 

 

 

 

 

 

 

12690

21

34

65

12

24

-

 

 

 

 

 

 

 

 

TKH 250

14100

26

38

80

14

29

-

 

15510

31

43

96

17

35

-

 

 

 

 

 

 

 

 

 

16920

36

47

114

19

42

-

 

 

 

 

 

 

 

 

18

RT-SVX19A-E4

Installation

Table 9 - WKD/WKH Pressure drop through accessories

 

 

 

 

Economizer

Economizer

 

 

 

 

Filter

Filter

100%

100%

Electric

Hot water coil

 

Airflow

EU2/G2

EU4/G4

outside air

return air

heater

Downflow only

 

 

 

 

 

 

 

 

 

5720

9

21

6

5

4

37

 

 

 

 

 

 

 

 

 

6430

11

24

7

6

6

45

 

 

 

 

 

 

 

 

WKD/WKH 125

7140

14

27

9

6

7

53

 

7850

17

30

10

7

9

62

 

 

 

 

 

 

 

 

 

8560

20

33

12

8

12

72

 

 

 

 

 

 

 

 

 

6800

13

27

8

6

7

33

 

 

 

 

 

 

 

 

 

7650

16

30

10

7

9

40

 

 

 

 

 

 

 

 

WKD/WKH 155

8500

19

34

12

8

11

48

 

9350

22

37

14

9

13

56

 

 

 

 

 

 

 

 

 

10200

26

40

16

10

16

65

 

 

 

 

 

 

 

 

 

8970

12

26

29

6

13

33

 

 

 

 

 

 

 

 

 

10090

15

30

37

8

17

40

 

 

 

 

 

 

 

 

WKD 200

11210

19

33

45

9

21

48

 

12330

23

37

55

11

25

56

 

 

 

 

 

 

 

 

 

13450

27

41

65

13

30

65

 

 

 

 

 

 

 

 

 

8970

11

23

33

6

13

-

 

 

 

 

 

 

 

 

 

10090

14

26

41

8

17

-

 

 

 

 

 

 

 

 

WKH 200

11210

17

29

51

9

21

-

 

12330

20

33

61

11

25

-

 

 

 

 

 

 

 

 

 

13450

23

36

72

13

30

-

 

 

 

 

 

 

 

 

RT-SVX19A-E4

19

Installation

Supply fan performances

Table 10 - YK 155 External static pressure

External Static Pressure (Pa)

 

 

25

50

75

100

125

150

175

200

225

250

m3/h

RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)

6800

 

 

 

 

 

 

 

 

564

1

587

1.07

610

1.15

633

1.23

655

1.31

677

1.39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7650

 

 

 

 

560

1.14

583

1.23

605

1.31

627

1.39

648

1.48

669

1.56

690

1.65

710

1.74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8500

559

1.31

584

1.41

606

1.5

628

1.6

649

1.69

669

1.78

689

1.87

708

1.97

727

2.06

746

2.16

9350

610

1.72

633

1.83

654

1.94

675

2.04

694

2.14

713

2.24

732

2.34

750

2.45

767

2.55

785

2.65

10200

661

2.21

683

2.33

703

2.45

722

2.56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pa)

 

275

300

325

350

375

400

425

450

475

500

m3/h

 

RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)

6800

699

1.47

719

1.55

739

1.63

758

1.71

777

1.79

795

1.86

813

1.94

830

2.01

847

2.09

863

2.16

7650

 

729

1.82

749

1.92

768

2.01

787

2.1

806

2.19

824

2.28

841

2.37

858

2.46

875

2.55

 

 

8500

 

764

2.25

782

2.35

800

2.45

818

2.55

 

 

 

 

 

 

 

 

 

 

 

 

9350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Oversized drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

RT-SVX19A-E4