Voyager™ II Rooftop units
Cooling only TKD/TKH 155 175 200 250 Reversible WKD/WKH 125 155 200 Gas-Fired YKD/YKH 155 175 200 250 R22 - R407C Refrigerant
RT-SVX19A-E4
General information
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane TKD/TKH, WKD/WKH and YKD/YKH units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.
TKD/TKH units are designed to operate in cooling mode only, with optional auxiliary heat (electric heater or hot water coil).
WKD/WKH can operate in cooling mode or heating mode by reversing the refrigeration cycle with or without auxiliary heat.
YKD/YKH units are designed to operate In cooling mode and equipped with a gas fired heating module.
TKD/TKH, WKD/WKH and YKD/YKH units are assembled, pressure tested, dehydrated, charged and run tested before shipment.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
Safety recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:
1.The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter "Installation". Always provide a pressure regulator.
2.Disconnect the main power supply before any servicing on the unit.
3.Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel.
Reception
On arrival, inspect the unit before signing the delivery note.
In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery.
Reception in France only:
Concealed damage must be looked for at delivery and immediately treated as visible damage.
Reception in all countries except France:
In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.
2 |
RT-SVX19A-E4 |
General information
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
Refrigerant
The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Storage
Take precautions to prevent condensate formation inside the unit's electrical components and motors when:
1.The unit is stored before it is installed; or,
2.The unit is set on the roof curb and temporary auxiliary heat is provided in the building.
Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for start-up.
Do not use the unit's heater as temporary heat without completing the start-up procedures detailed under "Unit Start-Up".
The Trane Company will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
RT-SVX19A-E4 |
3 |
Contents
|
|
|
|
Foreword |
2 |
|
|
Warnings and Cautions |
2 |
|
|
Safety recommendations |
2 |
|
|
Reception |
2 |
|
|
Warranty |
3 |
|
|
Refrigerant |
3 |
|
|
Maintenance contract |
3 |
|
|
Storage |
3 |
|
|
Training |
3 |
Installation |
6 |
|
|
Reception of units |
6 |
|
|
Roof curb installation |
7 |
|
|
Dimensions/Weights/Clearances |
8 |
|
|
Installing the unit |
10 |
|
|
Connection of duct network |
11 |
|
|
Condensate drain piping |
12 |
|
|
Gas pipework installation |
13 |
|
|
Filter installation |
14 |
|
|
Supply fan adjustment |
15 |
|
|
Component air pressure drops |
17 |
|
|
Supply fan performances |
20 |
|
|
Electrical connection |
26 |
Controls |
31 |
|
|
|
|
Control wiring |
|
31 |
|
|
|
CO2 sensors |
|
33 |
|
|
|
Remote potentiometer |
|
36 |
|
|
|
Fire thermostat |
|
37 |
|
|
|
Clogged filter detector |
|
38 |
|
|
|
Smoke detector |
|
38 |
|
|
|
High temperature safety thermostat |
|
38 |
|
|
|
Remote fault relay |
|
38 |
|
|
|
Thermostats |
|
38 |
|
|
|
Communication Interfaces |
|
39 |
4 |
RT-SVX19A-E4 |
Contents
|
|
|
Unit Options |
40 |
|
|
|
|
Hot water coil |
|
40 |
|
|
|
Electric Heater |
|
41 |
|
|
|
Soft Starter |
|
41 |
|
|
|
0 - 25% fresh air hood |
|
42 |
|
|
|
Barometric relief |
|
43 |
Operation |
44 |
|
|
|
|
Operation with a conventional thermostat |
|
44 |
|
|
|
Setting the economizer |
|
47 |
|
|
|
Test procedures |
|
49 |
|
|
|
Test modes |
|
50 |
|
|
|
Unit start-up |
|
51 |
|
|
|
Cooling without an Economizer |
|
54 |
|
|
|
Low Ambient Operation |
|
55 |
|
|
|
Cooling with an Economizer |
|
55 |
|
|
|
Economizer Set-Up |
|
56 |
|
|
|
ReliaTel™ Control Heating Operation |
|
56 |
|
|
|
Ignition Module |
|
56 |
|
|
|
Final installation checklist |
|
57 |
Maintenance |
58 |
|
|
|
|
End user routine maintenance |
|
58 |
|
|
|
Service technician maintenance |
|
59 |
|
|
|
Troubleshooting |
|
60 |
RT-SVX19A-E4 |
5 |
Installation
General information : The installation must conform to all local standards and regulations.
Reception of units
Rooftop unit
The unit is supplied on a wooden frame. It is recommended to check the machine's condition upon reception.
Figure 1a - Unit handling
B
A
1 = Clevis
2 = Base Rail
3 = Spreader Bar
L = Length (Center of Gravity)
W = Width (Center of Gravity)
Refer to Table 2 for weights and center of gravity.
There are two ways to handle the unit:
1.Use the openings in the wooden frame to handle the machine using a fork lift, in accordance with applicable safety regulations.
2.Use a lifting beam correctly adjusted to fit the unit (Figure 1a).
Unit handling
The units are supplied on the truck but are not unloaded. An opening is provided on each corner of the unit base to facilitate handling.
4 shackles and 4 slings are required. Use a lifting beam to prevent the cables pressing too hard on top of the unit during lifting.
Figure 1a indicates the position of the center of gravity and the lifting recommendations.
Important: For unit to fit on the roof curb the fork lift pockets must be removed.
6 |
RT-SVX19A-E4 |
Installation
Table 1 - Sling lengths and maximum unit weight
Unit size |
A (mm) |
B (mm) |
Maximm weight |
|
kg |
||||
|
|
|
||
|
|
|
|
|
125 |
3000 |
1900 |
644 |
|
|
|
|
|
|
155 |
3000 |
1900 |
773 |
|
|
|
|
|
|
175 |
3000 |
1900 |
810 |
|
|
|
|
|
|
400 |
3500 |
2200 |
1001 |
|
|
|
|
|
|
500 |
3500 |
2200 |
1027 |
|
|
|
|
|
Figure 1b - Maximum slope correction of adjustable roof curb.
Figure 2 - Waterproofing
Roof curb Installation (TKD-WKD-YKD accessories)
Roof curbs are available as an accessory for "downflow" units to support the unit and ensure the water tightness between the rooftop and the roof. Two types of roof curbs are available: The standard version to allow the installation of the unit on a flat roof and the adjustable version for a sloped roof installation. (See Figure 1b for the maximum slope correction of adjustable roofcurb.)
The adjustable roof curbs are supplied pre-assembled on a skid.
Two types of self-adhesive seals are provided separately. (40 mm wide for the perimeter, 20 mm wide for the cross pieces). Make sure they are properly installed where indicated to assure an adequate curb to unit seal.
Instructions for the roof curb assembly and installation with curb dimensions are provided with each roof curb kit.
4
3
1
2
1 = Roofcurb
2 = Roof membrane
3 = Seal
4 = Rooftop
RT-SVX19A-E4 |
7 |
Installation
Dimensions/Weights/Clearances
Figure 3 - Minimum clearances
Table 2 - Minimum clearances (mm)
|
|
|
Minimum clearance |
|
|
UNIT |
1 |
2 |
3 |
4 |
5 |
|
|
|
|
|
|
YKD/YKH 155 |
1900 |
1800 |
1220 |
1000 |
1300 |
YKD/YKH 175 |
1900 |
1800 |
1220 |
1000 |
1300 |
YKD/YKH 200 |
1900 |
1800 |
1220 |
1000 |
1300 |
YKD/YKH 250 |
1900 |
1800 |
1220 |
1000 |
1300 |
|
|
|
|
|
|
TKD/TKH 155 |
1900 |
1800 |
1220 |
1000 |
1300 |
TKD/TKH 175 |
1900 |
1800 |
1220 |
1000 |
1300 |
TKD/TKH 200 |
1900 |
1800 |
1220 |
1000 |
1300 |
TKD/TKH 250 |
1900 |
1800 |
1220 |
1000 |
1300 |
|
|
|
|
|
|
WKD/WKH 125 |
1900 |
1800 |
1220 |
1000 |
1300 |
WKD/WKH 155 |
1900 |
1800 |
1220 |
1000 |
1300 |
WKD/WKH 200 |
1900 |
1800 |
1220 |
1000 |
1300 |
|
|
|
|
|
|
The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. Refer to Table 3a and the space requirement plan.
8 |
RT-SVX19A-E4 |
Installation
Table 3a - Weigths & center of gravity (Figure 1)
|
Maximum weight |
|
Corner Weight (1) |
|
Center of Gravity |
|||
|
|
|
|
|
|
|
|
|
|
Shipping |
Net |
A |
B |
C |
D |
Length (L) |
Width (W) |
UNIT |
(kg) |
(kg) |
(kg) |
(kg) |
(kg) |
(kg) |
(mm) |
(mm) |
|
|
|
|
|
|
|
|
|
YKD/YKH 155 |
866 |
698 |
243 |
176 |
118 |
162 |
1143 |
737 |
YKD/YKH 175 |
902 |
735 |
251 |
188 |
127 |
169 |
1168 |
737 |
YKD/YKH 200 |
1128 |
920 |
324 |
242 |
151 |
203 |
1321 |
838 |
YKD/YKH 250 |
1154 |
946 |
327 |
251 |
159 |
208 |
1346 |
838 |
|
|
|
|
|
|
|
|
|
TKD/TKH 155 |
790 |
623 |
219 |
159 |
103 |
142 |
1143 |
711 |
TKD/TKH 175 |
827 |
660 |
227 |
172 |
112 |
149 |
1168 |
711 |
TKD/TKH 200 |
1050 |
841 |
297 |
221 |
138 |
185 |
1321 |
838 |
TKD/TKH 250 |
1075 |
866 |
300 |
230 |
145 |
206 |
1346 |
838 |
|
|
|
|
|
|
|
|
|
WKD/WKH 125 |
792 |
625 |
218 |
159 |
105 |
144 |
1143 |
711 |
WKD/WKH 155 |
809 |
642 |
228 |
162 |
105 |
147 |
1143 |
711 |
WKD/WKH 200 |
1080 |
871 |
291 |
226 |
155 |
199 |
1346 |
889 |
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
Table 3b - Weights of Options & accessories
|
|
|
|
|
Motorized |
|
|
|
Standard Roof |
Adjustable Roof |
|
Manual Outside |
Outside Air |
|
|
UNIT |
Curb |
Curb |
Economizer |
Air Damper |
Damper |
Electric heater |
Hot water coil |
|
|
|
|
|
|
|
|
YKD 155 |
93 |
220 |
30 |
15 |
27 |
|
|
YKD 175 |
93 |
220 |
30 |
15 |
27 |
|
|
YKD 200 |
107 |
260 |
37 |
15 |
34 |
|
|
YKD 250 |
107 |
260 |
37 |
15 |
34 |
|
|
YKH 155 |
|
|
30 |
15 |
27 |
|
|
YKH 175 |
|
|
30 |
15 |
27 |
|
|
YKH 200 |
|
|
37 |
15 |
34 |
|
|
YKH 250 |
|
|
37 |
15 |
34 |
|
|
|
|
|
|
|
|
|
|
TKD 155 |
93 |
220 |
30 |
15 |
27 |
14 |
85 |
TKD 175 |
93 |
220 |
30 |
15 |
27 |
14 |
85 |
TKD 200 |
107 |
260 |
37 |
15 |
34 |
18 |
110 |
TKD 250 |
107 |
260 |
37 |
15 |
34 |
18 |
110 |
TKH 155 |
|
|
30 |
15 |
27 |
14 |
|
TKH 175 |
|
|
30 |
15 |
27 |
14 |
|
TKH 200 |
|
|
37 |
15 |
34 |
18 |
|
TKH 250 |
|
|
37 |
15 |
34 |
18 |
|
|
|
|
|
|
|
|
|
WKD 125 |
93 |
180 |
20 |
15 |
27 |
18 |
85 |
WKD 155 |
93 |
220 |
30 |
15 |
27 |
18 |
85 |
WKD 200 |
107 |
260 |
37 |
15 |
34 |
18 |
110 |
WKH 125 |
|
|
20 |
15 |
27 |
18 |
|
WKH 155 |
|
|
30 |
15 |
27 |
18 |
|
WKH 200 |
|
|
37 |
15 |
34 |
18 |
|
Notes :
Net weight should be added to unit weight when ordering factory installed accessories.
To estimate shipping weight add 2.3 kg to net weight.
RT-SVX19A-E4 |
9 |
Installation
Figure 4
1 = Frame |
Figure 5
Installing the unit
1) Unit mounting on roof
Fix the rooftop curb on the joint beam of the building's structure. Make the rooftop curb's sealing surface level using angle brackets adjusted by screw bolts, located around its perimeter. Place the adhesive seals on the curb's sealing surface (perimeter and cross pieces). Make the rooftop leak-tight around the curbs before installing the unit, in compliance with current construction standards.
Note: The unit must be installed perfectly level to ensure condensates flow from the condensate tray.
The rooftop unit nests into the curb and is supported by it. Position the unit, taking care to comply with the indicated directions: the unit's discharge and intake openings must match those of the curb.
2) Installing the unit on the ground
To install the unit on the ground, its base must be level and supported securely.
For horizontal discharge units, a support is required such as a metal or concrete slab whose height must be determined according to the amount of snow cover, to prevent problems with condensation drainage and obstruction of the external coil. If necessary use an anti-vibration material between the rooftop unit's base and the support.
Note: Unit installation must comply to local codes
1 = Concrete slab
10 RT-SVX19A-E4 |
RT-SVX19A-E4 |
Installation
Connection of duct network
1) Downflow discharge units (TKD,WKD,YKD)
Using the rooftop curb
•The rooftop curb must be insulated on the outside walls at the discharge and intake openings to prevent condensation in the ducts.
•The rims around the discharge and intake openings make it possible to attach the flanges on the ends of the ducts. If you are using rigid duct ends recommended on the rooftop curb plan, it is essential to fix these components before installing the unit.
•For the design of the duct network, comply with recommendations currently applicable on the market, in particular:
. Installation of a section of flexible ducts to limit transmission of the unit's vibrations
. Use of movable vanes or deflectors to reduce the sound level.
2) Horizontal discharge units (TKH,WKH,YKH)
•The intake and discharge ducts must be insulated (thermal insulation).
•The duct section located outside must be leak-tight.
•Provide a flexible connector to prevent transmission of the unit vibrations. This flexible duct must be installed inside the building.
Note: In case of use of TKH, WKH or YKH units with economizer option, temperature and humidity sensors must be installed in return duct.
Economizer linkage is factory mounted but the damper position must be adjusted on site.
Figure 6 - Condensate Drain location
1 = Condensate drain connection
A = TKH/YKH 155, 175, 200, 250 - WKH 125,155, 200 B = TKD/YKD 155, 175, 200, 250 - WKD 125,155,200
RT-SVX19A-E4 |
11 |
Installation
Condensate drain piping
A 42mm PVC condensate drain connection with P-trap is provided.
Follow local codes and standard piping practices when running the drain line. Install a trap and be sure to fill with water before starting the unit. Pitch the line downward, away from the unit to avoid long, level, horizontal runs. Refer to Figure 7.
Figure 7 - Condensate drain line connection
1 = Static pressure drain pan
2 = Panel enclosure
3 = 42mm PVC drain
4 = Cleanout plug
12 |
RT-SVX19A-E4 |
Installation
Gas pipework installation
The installation must conform to all standards and regulations.
The gas supply pipework and gas stop valve to be installed near the unit must be sized so as to assure the gas pressure is sufficient at the unit inlet when operating at full load.
CAUTION! Should the pressure at the unit valve gas inlet be higher than 0.035 bar, an expansion valve must be installed.
The pipework must be selfsupporting and the final connection to the burner must be made by a flexible pipe. Provide a dust protection (filter) upstream the unit connection.
CAUTION! The gas pipework must not exert any stress on the burner gas connection.
Note: Expansion valve must be adapted to the type of gas used:
•G 20 : 20 mb
•G 25 : 25 mb
•G 31 : (Propane): 37 or 50 mb
Table 4 - Gas burner models
Unit |
|
Burner size |
YKD/H |
155 |
G350A |
YKD/H |
175 |
G350A |
YKD/H |
200 |
G350A |
YKD/H |
250 |
G350A |
|
|
|
|
See Table 38 for burner |
|
performance. |
|
Gas leak check procedure |
|
1. Vent the gas line |
|
2. Gas supply line pressure test: |
Figure 8 - Typical gas supply Pipework |
close valve 4 and open valve 2 |
|
3. Leak-check the gas pipe |
|
Look for gas pipe leaks using |
|
"Typol", "1000 bulles" or a similar |
|
product. Do not use soapy water. |
|
WARNING! Never use an open |
|
flame to check for gas leaks. |
|
Required gas pressure at the unit |
|
inlet connection are given in |
|
Table 37. |
|
Note: To operate with propane gas, |
|
the burner is fitted with a pressure |
|
limiter (supplied by Trane) |
1 |
= Evaporator section |
5 |
= Gas supply line |
2 |
= Gas burner section |
6,8 = Gas stop valve (Field supplied) |
|
3 |
= Condenser section |
7 |
= Expansion valve (Field supplied) |
4 |
= Gas supply connection |
9 |
= Filter (Field supplied) |
RT-SVX19A-E4 |
13 |
Installation
Filter installation
To gain access to filters, remove the supply fan access panel on downflow units and the filter access panel on the end for horizontal units.
Each unit ships with 40 or 50 mm thick filters. Number and size of filters is determined by size and configuration of the unit.
CAUTION! Do not operate unit without filters in place.
The maximum pressure drops allowable on filters are:
EU2/G2: 120 Pa
EU4/G4: 150 Pa
Table 5 - Filter arrangement
UNIT |
|
EU2/G2 |
|
EU4/G4 |
|
Qty |
Size |
Qty |
Size |
||
|
|||||
|
|
|
|
|
|
YKH/YKD 155 |
2 |
(508x508x50) |
2 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
YKH/YKD 175 |
2 |
(508x508x50) |
2 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
YKH 200 |
8 |
(508x635x50) |
8 |
(500x625x50) |
|
|
|
|
|
|
|
YKD 200 |
4 |
(508x508x50) |
4 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
YKH 250 |
8 |
(508x635x50) |
8 |
(500x625x50) |
|
|
|
|
|
|
|
YKD 250 |
4 |
(508x508x50) |
4 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
TKH/TKD 155 |
2 |
(508x508x50) |
2 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
TKH/TKD 175 |
2 |
(508x508x50) |
2 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
TKH 200 |
8 |
(508x635x50) |
8 |
(500x625x50) |
|
|
|
|
|
|
|
TKD 200 |
4 |
(508x508x50) |
4 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
TKH 250 |
8 |
(508x635x50) |
8 |
(500x625x50) |
|
|
|
|
|
|
|
TKD 250 |
4 |
(508x508x50) |
4 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
WKH/WKD 125 |
2 |
(508x508x50) |
2 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
WKH/WKD 155 |
2 |
(508x508x50) |
2 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
|
WKH 200 |
8 |
(508x635x50) |
8 |
(500x625x50) |
|
|
|
|
|
|
|
WKD 200 |
4 |
(508x508x50) |
4 |
(498x498x40) |
|
|
|
|
|
||
4 |
(508x635x50) |
4 |
(500x625x50) |
||
|
|||||
|
|
|
|
|
14 |
RT-SVX19A-E4 |
Installation
Supply fan adjustment
Use the following procedure to determine the proper adjustment of the supply fan for a specific application.
1.Determine total external static pressure about system and accessories.
a.Obtain the design airflow rate and the design external static pressure drop through the distribution system.
b.Add static pressure drop of the accessories installed on the unit. (Table 7,8 & 9)
c.Add the total accessory static pressure drop (from step 1b) to the design external static pressure (from step 1a).The sum of these two values is the total system external static pressure.
2.Using the Tables 10 through 20 to find the external static pressure that most closely approximates total system external static pressure. Then locate the appropriate airflow rate for your unit. The value obtained represents the brake horsepower for the supply fan motor and the fan RPM.
3.Adjust motor sheave according to Table 6.
Table 6 - Motor sheave / Fan speed
Fan Speed (RPM)
Standard Drive
|
6 turns |
5 turns |
4 turns |
3 turns |
2 turns |
1 turns |
|
UNIT |
Open |
Open |
Open |
Open |
Open |
Open |
Closed |
|
|
|
|
|
|
|
|
YKD/YKH 155 |
566 |
601 |
637 |
672 |
708 |
743 |
N/A |
YKD/YKH 175 |
724 |
769 |
815 |
860 |
906 |
951 |
N/A |
YKD/YKH 200 |
513 |
550 |
586 |
623 |
659 |
696 |
N/A |
YKD/YKH 250 |
588 |
619 |
650 |
681 |
712 |
743 |
N/A |
|
|
|
|
|
|
|
|
TKD/TKH 155 |
566 |
601 |
637 |
672 |
708 |
743 |
N/A |
TKD/TKH 175 |
724 |
769 |
815 |
860 |
906 |
951 |
N/A |
TKD/TKH 200 |
513 |
550 |
586 |
623 |
659 |
696 |
N/A |
TKD/TKH 250 |
588 |
619 |
650 |
681 |
712 |
743 |
N/A |
|
|
|
|
|
|
|
|
WKD/WKH 125 |
533 |
566 |
600 |
633 |
667 |
700 |
N/A |
WKD/WKH 155 |
566 |
601 |
637 |
672 |
708 |
743 |
N/A |
WKD/WKH 200 |
513 |
550 |
586 |
623 |
659 |
696 |
N/A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan Speed (RPM) |
|
|
|
|
|
|
|
Oversized Drive |
|
|
|
|
|
|
|
|
|
|
|
|
6 turns |
5 turns |
4 turns |
3 turns |
2 turns |
1 turns |
|
UNIT |
Open |
Open |
Open |
Open |
Open |
Open |
Closed |
|
|
|
|
|
|
|
|
YKD/YKH 155 |
672 |
714 |
756 |
798 |
840 |
882 |
N/A |
YKD/YKH 175 |
791 |
840 |
890 |
939 |
989 |
1038 |
N/A |
YKD/YKH 200 |
680 |
711 |
742 |
773 |
804 |
835 |
N/A |
YKD/YKH 250 |
690 |
722 |
754 |
786 |
818 |
850 |
N/A |
|
|
|
|
|
|
|
|
TKD/TKH 155 |
672 |
714 |
756 |
798 |
840 |
882 |
N/A |
TKD/TKH 175 |
791 |
840 |
890 |
939 |
989 |
1038 |
N/A |
TKD/TKH 200 |
680 |
711 |
742 |
773 |
804 |
835 |
N/A |
TKD/TKH 250 |
690 |
722 |
754 |
786 |
818 |
850 |
N/A |
|
|
|
|
|
|
|
|
WKD/WKH 125 |
724 |
769 |
815 |
860 |
906 |
951 |
N/A |
WKD/WKH 155 |
513 |
550 |
586 |
623 |
659 |
696 |
N/A |
WKD/WKH 200 |
588 |
619 |
650 |
681 |
712 |
743 |
N/A |
|
|
|
|
|
|
|
|
RT-SVX19A-E4 |
15 |
Installation
To increase airflow
Loosen variable sheave set screw and turn sheave clockwise.
To decrease airflow
Loosen variable sheave set screw and turn sheave counter-clockwise.
To increase belt tension
Loosen the nut (next to the idler sheave) that secures the sheave in place. With a wrench, apply pressure clockwise on the outside nut (round headed one), until tension desired is reached. While holding pressure with the tension nut, retighten the nut next to the idler sheave.
Figure 9 - Typical fan, motor, and sheave assembly
A = Fan Housing
B= Terminal Block
C= Fan Sheave
D= Plastic Bushing
E= Belt Tension Adjustment Bolt
F= Idler Pulley
Table 6b - Belt tensioning
TK* / YK* / |
|
Fan pulley |
Fan pulley |
Belt type |
Belt |
Deflexion |
Deflexion |
Belt tensionBelt tension |
|
Motor kW |
Type / |
Type / |
deflexion |
effort |
effort |
mini |
maxi |
||
WK* |
|
diam. (mm) |
diam. (mm) |
/ lengh (mm) |
(mm) |
mini kg |
maxi kg |
N |
N |
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
125 |
1,5 |
BK90 / 222 |
1VP44 / 105 |
BX68 / 1727 |
5,89 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
155 |
1,5 |
BK85 / 210 |
1VP44 / 105 |
BX68 / 1727 |
6 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
175 |
3 |
BK130 / 324 |
1VP44 / 105 |
BX75 / 1905 |
6,05 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
200 |
3 |
BK160 / 400 |
1VL40 / 95 |
BX90 / 2286 |
6,96 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
250 |
4,6 |
BK190 / 476 |
1VP50 / 121 |
BX96 / 2438 |
6,91 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
125 |
3 |
BK130 / 324 |
1VP44 / 105 |
BX75 / 1905 |
5,85 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
155 |
3 |
BK140 / 349 |
1VP44 / 105 |
BX77 / 1955 |
6,17 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
175 |
4,6 |
BK140 / 349 |
1VP56 / 136 |
BX75 / 1905 |
5,45 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
200 |
4,6 |
BK190 / 476 |
1VP56 / 136 |
BX96 / 2438 |
6,87 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
250 |
4,6 |
BK190 / 476 |
1VP56 / 136 |
BX96 / 2438 |
6,32 |
2,4 |
2,9 |
400 |
500 |
|
|
|
|
|
|
|
|
|
|
16 |
RT-SVX19A-E4 |
Installation
Component air pressure drops
Table 7 - YKD/YKH Pressure drop through accessories
|
|
Filter |
Filter |
Economizer |
Economizer |
|
Airflow |
EU2/G2 |
EU4/G4 |
100% |
100% |
|
outside air |
return air |
|||
|
|
|
|
||
|
|
|
|
|
|
|
6800 |
13 |
27 |
8 |
6 |
|
|
|
|
|
|
|
7650 |
16 |
30 |
10 |
7 |
|
|
|
|
|
|
YKD/YKH 155 |
8500 |
19 |
34 |
12 |
8 |
|
9350 |
22 |
37 |
14 |
9 |
|
|
|
|
|
|
|
10200 |
26 |
40 |
16 |
10 |
|
|
|
|
|
|
|
7870 |
17 |
30 |
10 |
7 |
|
|
|
|
|
|
|
8860 |
21 |
34 |
12 |
8 |
|
|
|
|
|
|
YKD/YKH 175 |
9850 |
25 |
38 |
15 |
9 |
|
10840 |
30 |
43 |
17 |
11 |
|
|
|
|
|
|
|
11830 |
35 |
47 |
20 |
12 |
|
|
|
|
|
|
|
8970 |
12 |
26 |
29 |
6 |
|
|
|
|
|
|
|
10090 |
15 |
30 |
37 |
8 |
|
|
|
|
|
|
YKD 200 |
11210 |
19 |
33 |
45 |
9 |
|
12330 |
23 |
37 |
55 |
11 |
|
|
|
|
|
|
|
13450 |
27 |
41 |
65 |
13 |
|
|
|
|
|
|
|
8970 |
11 |
23 |
33 |
6 |
|
|
|
|
|
|
|
10090 |
14 |
26 |
41 |
8 |
|
|
|
|
|
|
YKH 200 |
11210 |
17 |
29 |
51 |
9 |
|
12330 |
20 |
33 |
61 |
11 |
|
|
|
|
|
|
|
13450 |
23 |
36 |
72 |
13 |
|
|
|
|
|
|
|
11280 |
18 |
32 |
46 |
10 |
|
|
|
|
|
|
|
12690 |
24 |
36 |
58 |
12 |
|
|
|
|
|
|
YKD 250 |
14100 |
29 |
41 |
71 |
14 |
|
15510 |
36 |
46 |
86 |
17 |
|
|
|
|
|
|
|
16920 |
43 |
51 |
102 |
19 |
|
|
|
|
|
|
|
11280 |
17 |
30 |
52 |
10 |
|
|
|
|
|
|
|
12690 |
21 |
34 |
65 |
12 |
|
|
|
|
|
|
YKH 250 |
14100 |
26 |
38 |
80 |
14 |
|
15510 |
31 |
43 |
96 |
17 |
|
|
|
|
|
|
|
16920 |
36 |
47 |
114 |
19 |
|
|
|
|
|
|
RT-SVX19A-E4 |
17 |
Installation
Table 8 - TKD/TKH Pressure drop through accessories
|
|
Filter |
Filter |
Economizer |
Economizer |
Electric |
Hot water coil |
|
Airflow |
EU2/G2 |
EU4/G4 |
100% |
100% |
heater |
Downflow only |
|
outside air |
return air |
|||||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
6800 |
13 |
27 |
8 |
6 |
7 |
33 |
|
|
|
|
|
|
|
|
|
7650 |
16 |
30 |
10 |
7 |
9 |
40 |
|
|
|
|
|
|
|
|
TKD/TKH 155 |
8500 |
19 |
34 |
12 |
8 |
11 |
48 |
|
9350 |
22 |
37 |
14 |
9 |
13 |
56 |
|
|
|
|
|
|
|
|
|
10200 |
26 |
40 |
16 |
10 |
16 |
65 |
|
|
|
|
|
|
|
|
|
7870 |
17 |
30 |
10 |
7 |
10 |
42 |
|
|
|
|
|
|
|
|
|
8860 |
21 |
34 |
12 |
8 |
13 |
51 |
|
|
|
|
|
|
|
|
TKD/TKH 175 |
9850 |
25 |
38 |
15 |
9 |
16 |
61 |
|
10840 |
30 |
43 |
17 |
11 |
19 |
72 |
|
|
|
|
|
|
|
|
|
11830 |
35 |
47 |
20 |
12 |
23 |
83 |
|
|
|
|
|
|
|
|
|
8970 |
12 |
26 |
29 |
6 |
13 |
33 |
|
|
|
|
|
|
|
|
|
10090 |
15 |
30 |
37 |
8 |
17 |
40 |
|
|
|
|
|
|
|
|
TKD 200 |
11210 |
19 |
33 |
45 |
9 |
21 |
48 |
|
12330 |
23 |
37 |
55 |
11 |
25 |
56 |
|
|
|
|
|
|
|
|
|
13450 |
27 |
41 |
65 |
13 |
30 |
65 |
|
|
|
|
|
|
|
|
|
8970 |
11 |
23 |
33 |
6 |
13 |
- |
|
|
|
|
|
|
|
|
|
10090 |
14 |
26 |
41 |
8 |
17 |
- |
|
|
|
|
|
|
|
|
TKH 200 |
11210 |
17 |
29 |
51 |
9 |
21 |
- |
|
12330 |
20 |
33 |
61 |
11 |
25 |
- |
|
|
|
|
|
|
|
|
|
13450 |
23 |
36 |
72 |
13 |
30 |
- |
|
|
|
|
|
|
|
|
|
11280 |
18 |
32 |
46 |
10 |
20 |
49 |
|
|
|
|
|
|
|
|
|
12690 |
24 |
36 |
58 |
12 |
25 |
59 |
|
|
|
|
|
|
|
|
TKD 250 |
14100 |
29 |
41 |
71 |
14 |
32 |
71 |
|
15510 |
36 |
46 |
86 |
17 |
38 |
82 |
|
|
|
|
|
|
|
|
|
16920 |
43 |
51 |
102 |
19 |
46 |
95 |
|
|
|
|
|
|
|
|
|
11280 |
17 |
30 |
52 |
10 |
19 |
- |
|
|
|
|
|
|
|
|
|
12690 |
21 |
34 |
65 |
12 |
24 |
- |
|
|
|
|
|
|
|
|
TKH 250 |
14100 |
26 |
38 |
80 |
14 |
29 |
- |
|
15510 |
31 |
43 |
96 |
17 |
35 |
- |
|
|
|
|
|
|
|
|
|
16920 |
36 |
47 |
114 |
19 |
42 |
- |
|
|
|
|
|
|
|
|
18 |
RT-SVX19A-E4 |
Installation
Table 9 - WKD/WKH Pressure drop through accessories
|
|
|
|
Economizer |
Economizer |
|
|
|
|
Filter |
Filter |
100% |
100% |
Electric |
Hot water coil |
|
Airflow |
EU2/G2 |
EU4/G4 |
outside air |
return air |
heater |
Downflow only |
|
|
|
|
|
|
|
|
|
5720 |
9 |
21 |
6 |
5 |
4 |
37 |
|
|
|
|
|
|
|
|
|
6430 |
11 |
24 |
7 |
6 |
6 |
45 |
|
|
|
|
|
|
|
|
WKD/WKH 125 |
7140 |
14 |
27 |
9 |
6 |
7 |
53 |
|
7850 |
17 |
30 |
10 |
7 |
9 |
62 |
|
|
|
|
|
|
|
|
|
8560 |
20 |
33 |
12 |
8 |
12 |
72 |
|
|
|
|
|
|
|
|
|
6800 |
13 |
27 |
8 |
6 |
7 |
33 |
|
|
|
|
|
|
|
|
|
7650 |
16 |
30 |
10 |
7 |
9 |
40 |
|
|
|
|
|
|
|
|
WKD/WKH 155 |
8500 |
19 |
34 |
12 |
8 |
11 |
48 |
|
9350 |
22 |
37 |
14 |
9 |
13 |
56 |
|
|
|
|
|
|
|
|
|
10200 |
26 |
40 |
16 |
10 |
16 |
65 |
|
|
|
|
|
|
|
|
|
8970 |
12 |
26 |
29 |
6 |
13 |
33 |
|
|
|
|
|
|
|
|
|
10090 |
15 |
30 |
37 |
8 |
17 |
40 |
|
|
|
|
|
|
|
|
WKD 200 |
11210 |
19 |
33 |
45 |
9 |
21 |
48 |
|
12330 |
23 |
37 |
55 |
11 |
25 |
56 |
|
|
|
|
|
|
|
|
|
13450 |
27 |
41 |
65 |
13 |
30 |
65 |
|
|
|
|
|
|
|
|
|
8970 |
11 |
23 |
33 |
6 |
13 |
- |
|
|
|
|
|
|
|
|
|
10090 |
14 |
26 |
41 |
8 |
17 |
- |
|
|
|
|
|
|
|
|
WKH 200 |
11210 |
17 |
29 |
51 |
9 |
21 |
- |
|
12330 |
20 |
33 |
61 |
11 |
25 |
- |
|
|
|
|
|
|
|
|
|
13450 |
23 |
36 |
72 |
13 |
30 |
- |
|
|
|
|
|
|
|
|
RT-SVX19A-E4 |
19 |
Installation
Supply fan performances
Table 10 - YK 155 External static pressure
External Static Pressure (Pa)
|
|
25 |
50 |
75 |
100 |
125 |
150 |
175 |
200 |
225 |
250 |
|||||||||
m3/h |
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) |
|||||||||||||||||||
6800 |
|
|
|
|
|
|
|
|
564 |
1 |
587 |
1.07 |
610 |
1.15 |
633 |
1.23 |
655 |
1.31 |
677 |
1.39 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7650 |
|
|
|
|
560 |
1.14 |
583 |
1.23 |
605 |
1.31 |
627 |
1.39 |
648 |
1.48 |
669 |
1.56 |
690 |
1.65 |
710 |
1.74 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8500 |
559 |
1.31 |
584 |
1.41 |
606 |
1.5 |
628 |
1.6 |
649 |
1.69 |
669 |
1.78 |
689 |
1.87 |
708 |
1.97 |
727 |
2.06 |
746 |
2.16 |
9350 |
610 |
1.72 |
633 |
1.83 |
654 |
1.94 |
675 |
2.04 |
694 |
2.14 |
713 |
2.24 |
732 |
2.34 |
750 |
2.45 |
767 |
2.55 |
785 |
2.65 |
10200 |
661 |
2.21 |
683 |
2.33 |
703 |
2.45 |
722 |
2.56 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
External Static Pressure (Pa)
|
275 |
300 |
325 |
350 |
375 |
400 |
425 |
450 |
475 |
500 |
|||||||||||
m3/h |
|
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) |
|||||||||||||||||||
6800 |
699 |
1.47 |
719 |
1.55 |
739 |
1.63 |
758 |
1.71 |
777 |
1.79 |
795 |
1.86 |
813 |
1.94 |
830 |
2.01 |
847 |
2.09 |
863 |
2.16 |
|
7650 |
|
729 |
1.82 |
749 |
1.92 |
768 |
2.01 |
787 |
2.1 |
806 |
2.19 |
824 |
2.28 |
841 |
2.37 |
858 |
2.46 |
875 |
2.55 |
|
|
8500 |
|
764 |
2.25 |
782 |
2.35 |
800 |
2.45 |
818 |
2.55 |
|
|
|
|
|
|
|
|
|
|
|
|
9350 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard drive |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
Oversized drive |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20 |
RT-SVX19A-E4 |