Trane FADA, FAHA Installation and Maintenance Manual

5 (1)

Installation, Operation, and Maintenance

Packaged Fresh Air Unit

For 100% Outdoor Air Applications

Models FADA and FAHA

“BO” and later design sequence

April 2003

FAXA-SVX01B-EN

general information

About This Manual

Literature Change History

Use this manual for Packaged Fresh Air units, models FADA and FAHA. This is the “B” issue of this manual, revised to include the total energy wheel option. It provides specific installation, operation, and maintenance instructions for “BO” and later design sequences.

These units have modular DDC controls that provide operating functions significantly different than conventional air conditioning units. Refer to the startup and test mode procedures within this manual. Also, reference the Trane publication, Packaged Fresh Air Unit Programming Guide, FAXA-SVP01B-EN.

For units with gas heat, also reference the Reznor Installation Form RGM 401 Installation/Operation/Service Manual.

Overview of Manual

This manual describes proper installation, startup, operation, and maintenance procedures for the Packaged Fresh Air unit. Carefully review the information within this manual and follow the instructions to minimize risk of improper operation and/or component damage.

The roof curb specifically designed for the Packaged Fresh Air unit is available in 14” or 24” height from Trane. The curb must be mounted on a permanent roof structure before attempting to install the unit. Reference the roof curb installation instructions in the Trane publication,

“Accessory Roof Curb Kit” Installation Manual, FAXA-SVN01B-EN. Dimensional data for use with curbs other than Trane, can be found on pages 15-32 of this manual.

Note: One copy of this manual ships inside the control panel of each unit.

It is important that you perform periodic maintenance to help ensure trouble free operation. Should equipment failure occur, contact a qualified Trane service organization for an experienced HVAC technician to properly diagnose and repair this equipment.

Note: Do not release refrigerant to the atmosphere!

If adding or removing refrigerant, the service technician must comply with all federal, state, and local laws.

Warnings and Cautions

WARNING

Warnings indicate potential hazardous situations, which if not avoided, can cause death or serious injury.

CAUTION

Cautions indicate a potentially hazardous situation, which if not avoided, may cause minor or moderate injury. Also, cautions may alert against unsafe practices.

CAUTION

Cautions indicate a situation that may cause equipment or property-damage only.

Examples follow below.

WARNING

Hazardous voltage!

Disconnect all electrical power including remote disconnects before servicing unit. Follow proper lockout/ tagout procedures to ensure power cannot be inadvertently energized. Failure to do so can cause death or serious injury.

cfm = cubic-feet-per-minute CKT. = circuit

CV = constant volume CW = clockwise

CCW = counterclockwise E/A = exhaust air

ECEM = exhaust/comparative enthalpy module

F/A = fresh air FAU = fresh air unit

GBAS = generic building automation system

HI = human interface I/O = inputs/outputs

IOM= installation/operation/maintenance manual

IPC = interprocessor communications LCI = LonTalk™ communication interface LH = left-hand

MCM = multiple compressor module MWU = morning warmup

NSB = night setback O/A = outside air

psig = pounds-per-square-inch, gage pressure

R/A = return air RH = right-hand

RPM = revolutions-per-minute RTM = rooftop module

S/A = supply air

SCM = single circuit module SZ = single-zone (unit airflow)

TCI = Tracer communications module UCM = unit control modules

VAV = variable air volume

VCM = ventilation control module VOM = ventilation override module ZSM = zone sensor module

CAUTION

Use copper conductors only!

Unit terminals are not designed to accept other type conductors. Failure to use copper conductors may cause equipment damage.

Common HVAC Acronyms

For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.

BAS = building automation systems

Special Note on Refrigeration Emissions

World environmental scientists have concluded that ozone in our upper atmosphere is being reduced due to the release of CFC fully halogenated compounds. Trane urges all HVAC service personnel to make every effort to prevent any refrigerant emissions while installing, operating, or servicing equipment. Always conserve refrigerants for continued use and follow all warnings and cautions in this manual.

©2003 American Standard Inc.

FAXA-SVX01B-EN

contents

Cross reference to related publications:

Packaged Fresh Air Unit Programming Guide, FAXA-SVP01B-EN

Accessory Roof Curb Installation Manual, FAXA-SVN01B-EN

Reznor Installation Form RGM 401, Installation/Operation/Service for units with gas heat

Installation ……………………………………………………………2

General Information……………………………………………2

Pre-installation Considerations ………………………………8

Dimensions/Weights …………………………………………15

Mechanical Requirements …………………………………33

Electrical Requirements………………………………………36

Installation Procedure ………………………………………40

Pre-Startup Requirements …………………………………51

Startup …………………………………………………………52

Operation ……………………………………………………………54

General Information …………………………………………54

Sequence of Operation ………………………………………62

Maintenance………………………………………………………… 67

General Information …………………………………………67

Maintenance Procedures ……………………………………71

Periodic Checklists ……………………………………………77

Index ………………………………………………………………… 79

Note: This document is customer property and must be retained by the unit’s owner for use by maintenance personnel.

FAXA-SVX01B-EN

3

general Installation information

Packaged Fresh Air unit Model Number Description

Following is a complete description of the Packaged FAU model number. Each digit in the model number has a corresponding code that identifies specific unit options.

F

A D A 040

6 G A,0 0,8,4 0 1 A 0 1 A 0,5,7 0,7 A 0 0 0 E F 0 1 0,0,0

0,0 A A A A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4 5,6,7

8 9 10,11 12,13,141516171819 20 21,22,23 24,25 26 27 28 29 30 31 32 33 34,35,36 37,38 39 40 41 42

Digit 1 – Unit model

F = fresh air unit

Digit 2 – Unit configuration

A= air cooled

Digit 3 – Unit discharge direction

D= downflow H= horizontal

Digit 4 – Development sequence

A = development sequence ‘A’

Digits 5, 6, 7 – Unit size

031 = 3100 cfm

040 = 4000 cfm

051 = 5100 cfm

066 = 6600 cfm

Digit 8 – Unit voltage

3 = 230 volt/60 hz/3 ph

4 = 460 volt/60 hz/3 ph

6 = 208 volt/60 hz/3 ph

Digit 9 – Heating system

0 = none

A= gas low rise, single bank, 2-stage B = gas low rise, single bank, 2:1

modulate

C = gas high rise, single bank, 2-stage D= gas high rise, single banks, 2:1

modulate

E = gas dual bank, 4-stage

F = gas dual bank 4:1 modulate G= electric heat, 3-stage

H= electric heat, 7-stage

K = hydronic interface only

Digits 10, 11 – Design sequence

** = factory assigned

Digits 12, 13, 14 – Heat input

000 = none

020 = 20 kW

026 = 26 kW

032 = 32 kW

042 = 42 kW

056 = 56 kW

070 = 70 kW

084 = 84 kW

100 = 100 kW

122 = 122 kW

125 = 125 MBh

150 = 150 MBh

200 = 200 MBh

250 = 250 MBh

300 = 300 MBh

 

107

= 1075

160 = 1600

350 = 350 MBh

 

110

= 1100

162 = 1625

400 = 400 MBh

 

112

= 1125

165 = 1650

500 = 500 MBh

 

115

= 1150

167 = 1675

600 = 600 MBh

 

117 = 1175

170 = 1700

700 = 700 MBh

 

120 = 1200

172 = 1725

800= 800 MBh

 

122 = 1225

175 = 1750

 

 

 

 

125 = 1250

177 = 1775

Digit 15 – Heat exchanger material

127 = 1275

180 = 1800

0

= none

 

 

130 = 1300

182 = 1825

1

= 409 stainless steel, 409 stainless Burner

132 = 1325

185 = 1850

2

= 321 stainless steel, 409 stainless burner

135 = 1350

187 = 1875

 

 

 

 

137 = 1375

190 = 1900

Digit 16 – Condenser reheat coil

140 = 1400

192 = 1925

0

= none

 

 

142 = 1425

195 = 1950

1

= condenser hot gas reheat coil

145 = 1450

197 = 1975

 

 

 

 

147 = 1475

200 = 2000

Digit 17 – Ventilation damper type

150 = 1500

202 = 2025

0

= parallel blade damper

152 = 1525

205 = 2050

1

= TRAQ™ damper with air flow

155 = 1550

207 = 2075

 

measurement

157 = 1575

210 = 2100

Digit 18 – Energy recovery

Digits 24, 25 – Supply fan horsepower

0

= none

 

 

1

= total energy wheel w/occupancy

01 = 1

 

 

control

 

 

02 = 2

 

2

= total energy wheel w/dry bulb control

03 = 3

 

 

 

 

 

05 = 5

 

Digit 19 – Return air damper

07

= 7.5

 

0

= none

 

 

10 = 10

 

1

= bottom

return/reference enthalpy

15 = 15

 

2

= bottom

return/comparative enthalpy

Digit 26 – Fan motor type

 

 

 

 

Digit 20 – Supply fan type1

A= standard efficiency ODP fan motor

A= 12 - 9 centrifugal fan

B = high efficiency ODP fan motor

B = 15 - 11 centrifugal fan

Digit 27 – Coil protection

C = 18 - 13 centrifugal fan

 

 

 

 

0 = none

 

Digits 21, 22, 23 – Supply fan rpm

A= corrosion

inhibiting coating

037 = 375

072

= 725

Digit 28 – Unit cabinet protection

040 = 400

075

= 750

042 = 425

077

= 775

0 = standard prepainted steel finish

045 = 450

080

= 800

A= corrosion

inhibiting coating

047 = 475

082

= 825

Digit 29 – Filter type

050 = 500

085

= 850

052 = 525

087

= 875

0 = field-provided filter

055 = 550

090

= 900

1 = dirty filter switch (DFS) with field-

057 = 575

092

= 925

 

provided

filter

060 = 600

095

= 950

2 = 2” pleated media filters

062 = 625

097

= 975

3 = 2” pleated media filters & DFS

065 = 650

100

= 1000

Digit 30 – System control

067 = 675

102

= 1025

070 = 700

105

= 1050

A= supply air dehumidification

 

 

 

 

B = supply air dehimidification with zone

Note1: The first number in this description indicates the

 

RH reference

 

fan wheel diameter (in.). The second number

E = zone dehumidification

 

indicates the fan wheel width.

 

 

 

4

FAXA-SVX01B-EN

general Installation information

F = zone dehumidification with OA RH reference

G= supply air temperature control (no dehumidification)

J = zone temperature control (no dehumidification)

Digit 31 – Control interface options

0 = none

A= LonTalk® communications interface (LCI ) (comm5)

B = LCI (comm5) & generic building automation system (GBAS) (0-5 VDC)

C = LCI (comm5) & GBAS (0-5 VDC) & ventilation override module (VOM)

D= LCI (comm5) & VOM E = GBAS (0-5 VDC)

F = GBAS (0-5 VDC) & VOM G= VOM

Digit 32 – Miscellaneous system control options

0 = none

1 = interface for remote human interface

Digit 33 – Exhaust option

0 = none

1 = exhaust interface

Digits 34, 35, 36 – Exhaust air fan rpm

000

= none

127 = 1275

045

= 450

130 = 1300

047

= 475

132 = 1325

050

= 500

135 = 1350

052

= 525

137 = 1375

055

= 550

140 = 1400

057

= 575

142 = 1425

060

= 600

145 = 1450

062

= 625

147 = 1475

065

= 650

150 = 1500

067

= 675

152 = 1525

070

= 700

155 = 1550

072

= 725

157 = 1575

075

= 750

160 = 1600

077

= 775

162 = 1625

080

= 800

165 = 1650

082

= 825

167 = 1675

085

= 850

170 = 1700

087

= 875

172 = 1725

090

= 900

175 = 1750

092

= 925

177 = 1775

095

= 950

180 = 1800

097

= 975

182 = 1825

100

= 1000

185 = 1850

102

= 1025

187 = 1875

105

= 1050

190 = 1900

107

= 1075

192 = 1925

110

= 1100

195 = 1950

112

= 1125

197 = 1975

115

= 1150

200 = 2000

117 = 1175

202 = 2025

120 = 1200

205 = 2050

122 = 1225

207 = 2075

125 = 1250

210 = 2100

Digits 37, 38 – Exhaust air fan horsepower

00 = none

01 = 1

02 = 2

03 = 3

05 = 5

07 = 7.5

10 = 10

Digit 39 – Unit connection type

A= terminal block

B = non-fused disconnect switch

Digit 40 – Convenience outlet

0 = none

A= 115V, factory wired B = 115V, field wired

Digit 41 – Extended grease lines

0 = none

A= extended grease lines

Digit 42 – Agency approval

0 = no agency approval A= UL approval

Digit 43 – Roof curb

A= 14” curb

B = 24” curb

FAXA-SVX01B-EN

5

general Installation information

Packaged Fresh Air unit Accessory Model Number Description

Following is a complete description of the Packaged FAU accessory model number. Each digit in the model number has a corresponding code that identifies specific accessory options.

 

P

F

K

A

031

3

A

A0

B

C

0

A

A

 

0

A

0

A

0

A

0

A

 

1

2

3

4

5, 6, 7

8

9

10,11

12

13

14

15

16

17

18

19

20

21

22

23

24

Digit 1 – Parts/accessories

 

 

C = 2” pleated media total energy wheel

Digit 17 – Zone sensor with timed override

P = parts/accessories

 

 

 

only

 

 

 

 

 

 

0

= none

 

 

 

 

Digit 2 – Unit type

 

 

 

 

D = 2” cleanable total energy wheel only

A = zone temperature densor with timed

 

 

 

 

E = 2” pleated media unit & total energy

 

override BAYSENS013*

 

F

= fresh air unit

 

 

 

 

wheel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F = 2” cleanable unit & total energy wheel

Digit 18 – Zone sensor with timed override

Digit 3 – Field installed kits

 

 

 

 

 

 

 

 

 

 

 

and local setpoint adjustment

K = field installed kits

 

 

 

Digit 13 – Control interface kits

 

 

 

0

= none

 

 

 

 

 

 

 

 

 

 

 

 

0 = none

 

 

 

 

 

 

A = zone temperature sensor with timed

Digit 4 – Development sequence

 

 

A= LonTalk® communications

interface

 

override buttons and local setpoint

A = development sequence

 

 

(LCI) (comm5)

 

 

 

 

 

 

adjustment BAYSENS014*

 

Digits 5, 6, 7 – Nominal size

 

 

B = LCI (comm5) & generic building

 

 

Digit 19 – Remote minimum position

 

 

automation system (GBAS) (0-5 VDC)

031= 3100 cfm

 

 

 

 

C = LCI (comm5) & GBAS (0-5 VDC) &

 

 

potentiometer control

 

 

040= 4000 cfm

 

 

 

 

ventilation override module (VOM)

 

0 = none

 

 

 

 

051= 5100 cfm

 

 

 

 

D= LCI (comm5) & VOM

 

 

 

 

A = remote minimum position

 

066= 6600 cfm

 

 

 

 

E = GBAS (0-5 VDC)

 

 

 

 

 

 

potentiomenter control BAYSTAT023*

Digit 8 – Unit voltage

 

 

 

F = GBAS (0-5 VDC) & VOM

 

 

 

Digit 20 – Dual setpoint sensor

 

 

 

 

G= VOM

 

 

 

 

 

 

 

3 = 230/60/3

 

 

 

 

 

 

 

 

 

 

 

 

0 = none

 

 

 

 

4

= 460/60/3

 

 

 

 

Digit 14 – Time clock

 

 

 

 

A = dual setpoint sensor

 

 

6

= 208/60/3

 

 

 

 

0 = none

 

 

 

 

 

 

Digit 21 – Dual setpoint sensor with system

 

 

 

 

 

 

 

 

A = time clock

 

 

 

 

 

Digit 9 – Roof curb

 

 

 

 

 

 

 

 

 

 

 

 

 

function

lights

 

 

 

0 = none

 

 

 

 

 

Digit 15 – Remote mounted human

 

 

0 = none

 

 

 

 

A = 14”

 

 

 

 

 

 

interface

 

 

 

 

 

 

A = dual setpoint sensor with system

B = 24”

 

 

 

 

 

0 = none

 

 

 

 

 

 

 

function

lights

 

 

 

C = acoustical

 

 

 

 

A = remote mounted human interface

 

 

 

 

 

 

 

 

D = 14” curb for unit w/ERV

 

 

B = remote mounted human interface with

Digits 22 – Space relative humidity kit

E = 24” extended for unit w/ERV

 

 

interprocessor

communication

bridge

0 = none

 

 

 

 

F

= 24” extended, acoustical for unit w/

 

module board kit

 

 

 

 

A = space relative humidity kit

 

 

 

ERV

 

 

 

 

 

C = interprocessor

communication

bridge

Digit 23 – Carbon dioxide sensor

 

 

 

 

 

 

 

 

module board kit

 

 

 

 

Digits 10, 11 – Design sequence

 

 

Digit 16 – Zone sensor

 

 

 

 

0 = none

 

 

 

 

A0 = design sequence

 

 

 

 

 

 

 

A = carbon dioxide sensor

 

 

 

 

 

 

 

 

 

 

0 = none

 

 

 

 

 

 

 

 

 

 

 

 

 

Digit 12 – Filter type

 

 

 

A = zone temperature sensor

 

 

 

Digit 24 – Dry-bulb duct sensor

 

0 = none

 

 

 

 

 

BAYSENS017*

 

 

 

 

 

0 = none

 

 

 

 

A = 2” pleated media

 

 

 

 

 

 

 

 

 

 

 

A = dry-bulb duct sensor

 

 

B = 2” cleanable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

FAXA-SVX01B-EN

general Installation information

Unit Nameplate

The unit nameplate identifies the unit model number, appropriate service literature, and wiring diagram numbers. It is mounted on the control panel door. Reference this information when making inquiries or ordering parts or literature for the fresh air unit.

Unit mounted IntelliPak® microprocessor control with easy-to-read human interface

Horizontal or vertical discharge openings

Hi-rise electric (or gas) heat

1’’ Solid double-wall panels of foamed- in-place construction

Non-corrosive IAQ drain pan sloped in two directions

Optional condenser

Quiet FC fan reheat coil with modulating control

Figure I-GI-1. Packaged fresh air unit components

2’’ Pleated filter section with adjustable rack to 4’’

Standard protective bird screen on inlet hood

Traq® damper available for airflow measurement

Optional return air damper for unoccupied recirculation

All ship-with items are inside this compartment

FAXA-SVX01B-EN

7

pre-installation Installation considerations

Pre-Installation Considerations

Checklist

The following checklist is provided to give an overview of the factoryrecommended pre-installation considerations. Follow the procedures in this section to ensure the installation is complete and adequate for proper unit operation. Verify this checklist is complete before beginning unit installation.

οVerify the unit size and tagging with the unit nameplate to ensure the correct unit is received.

οInspect the unit for possible shipping damage and make any necessary claims with the freight delivery company immediately.

οBefore installing the roof curb, remember to allow minimum recommended clearances for routine maintenance and service. Refer to unit dimensions and clearances on submittals or in Dimensions and Weights section on page 15.

οVerify the unit roof curb is installed properly prior to beginning unit installation. See the Roof Curb Installation Manual, FAXA-SVN01B-EN.

οMake proper acoustic considerations before installing unit. Do not install unit above sound-senstive locations.

οAllow adequate space for service and operating clearances. Reference page 10.

οMake provisions for correct supply power and note electrical connection knockouts locations on the unit submittals or in the Dimensions and Weights section on page 15. This includes main power and dual power connections for electric heat.

Note: Verify electric stub-out within roof curb assembly, if using bottom electrical knockouts.

οElectrical supply power must meet specific balance and voltage requirements as described in the “Electrical Requirements” section on page 36.

οUnits with gas heat, ensure adequate gas service and piping is available at unit installation location.

οEnsure the unit installation location is level.

Receiving and Handling

Shipping Package

Packaged Fresh Air units ship fully assembled.

Ship-Separate Accessories

Field-installed sensors ship separately inside the unit’s filter/return air section. Units with gas heat have temporary panels in place for shipping. The permanent panels are located in this compartment and must be field-installed. Units with the total energy wheel option have an exhaust louver that ships inside the exhaust compartment. Install the louvers after installing the unit in its final position.

WARNING

No step surface!

Do not walk on the sheet metal drain pan. Walking on the drain pan can cause the supporting metal to collapse, causing death or serious injury.

8

FAXA-SVX01B-EN

pre-installation Installation considerations

Receiving Checklist

Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage. If entry into the unit is necessary, bridge between the unit’s main supports using multiple 2 x 12 boards.

οVerify that the unit nameplate data corresponds to the sales order and bill of lading (including electrical data).

οVisually inspect the unit exterior for physical signs of shipping damage or material shortages.

οIf a unit appears damaged, inspect it immediately before accepting the shipment. Remove access panels and check for interiour component damage. Make specific notations concerning the damage on the freight bill. Do not refuse delivery.

οReport concealed damage to the freight line within the allotted time after delivery. Verify with the carrier what their allotted time is to submit a claim.

Note: Failure to follow these procedures may result in no reimbursement for damages from the freight company.

οDo not move damaged material from the receiving location. It is the receiver’s responsibility to provide reasonable evidence that concealed damage did not occur after delivery.

οDo not continue unpacking the shipment if it appears damaged. Retain all packaging. Take photos of damaged material if possible.

οNotify the carrier’s terminal of the damage immediately by phone and mail. Request an immediate joint inspection of the damage by the carrier and consignee.

οNotify your Trane representative of the damage and arrange for repair. Have the carrier inspect the damage before making any repairs to the unit.

Unit Storage

Isolate all side panel service entrances and base pan openings, such as conduit holes and supply and return air openings from the ambient air until the unit is ready for startup.

If relocating the unit is necessary after the initial delivery, position the unit on the open trailer so the inlet hood is facing the rear of the trailer.

FAXA-SVX01B-EN

9

pre-installation Installation considerations

Service Access

Maintain adequate clearances around and above the fresh air unit to ensure proper unit operation and allow sufficient service access. See Figure I-PC-1 for recommended clearances. If installing the unit higher than the typical curb elevation, field-construct a catwalk around it to provide safe, easy maintenance access.

WARNING!

Hazardous voltage!

Disconnect electrical power source and remote disconnects before servicing unit. Follow proper lockout/ tagout procedures to ensure power cannot be inadvertently energized. Failure to do so may cause death or injury.

WARNING!

Disconnect gas supply!

Before servicing unit, FIRST turn off the gas supply. Failure to turn off the gas supply can cause death or serious injury.

WARNING!

Combustible materials!

Maintain proper clearance between the unit heat exchanger, vent surfaces, and combustible materials. Refer to this manual for proper clearances. Improper clearances can cause a fire hazard. Failure to maintain proper clearances can cause death, serious injury, or property damage.

unit without TE wheel

service access for removal of gas or electric heaters

air path into unit

condenser airflow and compressor maintenance

unit with TE wheel

service access for removal of

air path into

condenser airflow

Figure I-PC-1. Top view of fresh air unit showing recommended service and code clearances.

10

FAXA-SVX01B-EN

pre-installation Installation considerations

Roof Curb

You must install the roof curb before beginning unit installation. Reference the

Roof Curb Installation Manual, FAXA- SVN01B-EN for complete installation instructions. For reference, installation instructions are provided below. Reference roof curb dimensions in the Dimensions and Weights section on pages 15–32.

Note: Do not tighten any of the screws used to assemble this section until the curb has been leveled and squared in its installed location.

Roof Curb and Ductwork

Ensure the unit curb encloses the entire unit base area. It is referred to as a “full perimeter” type curb. Fabricate and install the supply air and return air ductwork adjoining the roof curb before the unit is set into place. Note electrical stub-ups within the curb.

General

Set the roof curb and Packaged Fresh Air unit level to ensure proper operation. If providing a field-fabricated roof curb, see page 12 for roof curb details for units without the total energy wheel option. See page 13 for units with the total energy wheel option. All installations must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1.

Note: Trane has a roof curb specifically designed for the Packaged Fresh Air unit available in the following options: 14” or 24” height, and an acoustic curb. To install it, reference the Accessory Roof Curb Installation Manual, FAXA- SVN01B-EN.

Roof Support

The roof must be capable of adequately supporting the weight of the Packaged Fresh Air unit as well as the curb. See Figure I-IP-1 on page 40 for approximate unit four-corner weights.

Trane Roof Curb Installation

If the building is new, the curb may be assembled at any convenient location and installed as soon as the roof support members are in place. The curb must be mounted on the roof deck and support

provided directly below the flanges of the roof curb for further support and to minimize vibration. If the fresh air unit is to be installed on an existing building, hoist the curb shipping container to the roof, where the curb can be assembled more conveniently.

Standard Perimeter Curb Rail Assembly

Follow the procedure below as an example of how to field-assemble a field roof curb. This procedure also applies to the Trane standard 14” roof curb. Reference pages 12 & 13 for assembly drawings.

1.Attach corner angle (7) using 4 sheet metal screws to the end of end rail (1) adjacent to side rail (3). Place the clearance holes in the corner angle toward the top of the curb.

2.Attach end rail (1) to side rail (3) using 4 sheet metal screws.

3.Align side rail (4) next to side rail (3) and attach crossmember (11) perpendicular to both side rails at the joint using eight sheet metal screws.

4.Attach corner angle (8) using eight sheet metal screws to end rail (2) and side rail (4). Place the clearance holes in the corner angle toward the top of the curb.

5.Attach corner angle (9) using eight sheet metal screws to end rail (2) and side rail (5). Place the clearance holes in the corner angle toward the top of the curb.

6.Align side rail (6) next to side rail (5) and attach crossmember (11) perpendicular to both side rails at the joint using eight sheet metal screws.

7.Attach corner angle (10) using eight sheet metal screws to end rail (1) and side rail (6). Place the clearance holes in the corner angle toward the top of the curb.

Return and Exhaust Air Opening

Assembly

8.Place end rail (12) between side rail (3) and side rail (6) with flanges positioned away from the return air opening and attach it with two sheet metal screws at each end. Use rails (14), (15), (16), and (17) as spacers.

9.Place side rail (14) between end rail (1) and end rail (12) with flanges positioned away from the return air opening and attach it with two sheet metal screws at each end.

10.Place side rail (15) between end rail

(1)and end rail (12) with flanges positioned toward the return air opening and attach it with two sheet metal screws at each end.

11.Place side rail (16) between end rail

(1)and end rail (12) with flanges positioned away from side rail (15) and attach it with two sheet metal screws at each end.

12.Place side rail (17) between end rail

(1)and end rail (12) with flanges positioned away from the exhaust air opening and attach it with two sheet metal screws at each end.

Supply Air Opening Assembly

13.Place end rail (13) between side rail

(4)and side rail (5) with flanges positioned away from the supply air opening and attach it with two sheet metal screws at each end. Use rails (18) and (19) as spacers.

14.Place side rail (18) between end rail

(2)and end rail (13) with flanges positioned away from the supply air opening and attach it with two sheet metal screws at each end.

15.Place side rail (19) between end rail

(2)and end rail (13) with flanges positioned away from the supply air opening and attach it with two sheet metal screws at each end.

Units with the Total Energy Wheel Only

16.Attach corner angle (26) using five sheet metal scres to the side of duct support (25) without flanges. Place the clearance holes in the corner angle toward the top of the curb.

17.Align side rail (23) next to side rail (3) and attach crossmember assembly (25) and (26) perpendicular to both side rails at the joint using ten sheet metal screws.

FAXA-SVX01B-EN

11

pre-installation Installation considerations

Standard roof curb assembly, units without TE wheel option

7

1

23

15

R/A

14

E/A

17

16

10

6

 

Note: Center lines connect corresponding holes in the rails and crossmember. All screws are installed from outside the curb.

corner angle

end rail

Typical std. curb corner assembly for units without the total energy wheel option

Curb legend

 

 

(1) end rail (R/A end)

(13) duct support end rail

(2) end rail (S/A end)

(14) duct support end rail (R/A end)

(3) side rail

(15) duct support side rail (R/A end)

(4) side rail

(16) duct support side rail (E/A end)

(5) side rail

(17) duct support side rail (E/A end)

(6) side rail

(18) duct support side rail (S/A end)

(7) corner angle

(19) duct support side rail (S/A end)

(8) corner angle

(20)

6” wood nailer; side

(9) corner angle

(21)

6” wood nailer; side

(10) corner angle

(22)

6” wood nailer; end

(11) crossmember

(23) 6” wood nailer; end

(12) duct support end rail

 

 

20

 

 

8

 

3

 

 

12

 

 

4

 

 

 

 

 

 

13

 

11

 

S/A

 

 

 

 

 

5

18

 

 

 

 

 

 

19

22

21

2

9

side rails

side rail

return air end

 

supply air end supply air end

crossmember

Note: Center lines connect corresponding holes in the rails and crossmember. All screws are installed from outside the curb.

Typical std. curb rail and crossmember assembly for units without the total energy wheel option

12

FAXA-SVX01B-EN

pre-installation Installation considerations

Standard roof curb assembly, units with the TE wheel

Curb legend

 

 

(1) end rail (R/A, E/A end)

(15)

duct support end rail

(2) end rail (S/A end)

(16)

duct support side rail (R/A end)

(3) side rail

(17)

duct support side rail (R/A end)

(4) side rail

(18)

duct support side rail (E/A end)

(5) side rail

(19)

duct support side rail (E/A end)

(6) side rail

(20)

duct support side rail (S/A end)

(7) corner angle

(21)

duct support side rail (S/A end)

(8) corner angle

(22)

crossmember

(9) corner angle

(23) side rail

(10)

corner angle

(24) side rail

(11)

crossmember

(25) duct support end rail

(12)

crossmember

(26)

corner angle

(13)

crossmember

(27)

corner angle

(14)

duct support end rail

 

 

GEND

side rail

corner angle

side rail

duct support end rail

Typical standard roof curb assembly for units with the TE wheel

FAXA-SVX01B-EN

13

pre-installation Installation considerations

Acoustic Considerations

Before determining the final unit installation site, remember that proper unit placement is critical in reducing transmitting sound levels to the building. The ideal time to make provisions to reduce sound transmissions is during the design phase. The most economical means of avoiding a potential acoustical problem is to place units in areas that are not acoustically sensitive. Ideal locations are over over corridors, utility rooms, toilets, or other areas where higher sounds levels below the unit may be acceptable.

Follow these basic guidelines to help minimize sound transmission through the building structure:

Locate the unit’s center of gravity close to or over a column or main support beam.

If the roof structure is very light, replace roof joists using a structural shape in the critical areas described above.

Note: Cut applicable holes only for the supply, exhaust, and return duct penetration in the roof deck. To maintain roof integrity and prevent possible property damage, do not remove the roof decking from the inside perimeter of the curb.

Installation Preparation

Before installing the unit, perform the following procedures to ensure proper unit operation.

1.Verify the roof curb is level. To ensure proper unit operation, install the unit level (zero tolerance) in both horizontal axes. Failure to level the unit properly can result in condensate management problems, such as standing water inside the unit. Standing water and wet surfaces inside units can result in microbial growth (mold) in the drain pan that may cause unpleasant odors and serious health-related indoor air quality problem.

2.Allow adequate service and code clearances as recommended in “Service Access” section on page 10.

3.Position the unit and skid assembly in its final location. Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location. See Figure I-IP-2 on page 41 for typical rigging procedures, including cautions and proper uses of such equipment as fork lifts, spreader bars, and hooks.

14

FAXA-SVX01B-EN

Installation

dimensions

& weights

 

 

 

 

Typical exterior dimensions, ft./in.

outdoor side view, unit without total energy wheel

outdoor side view, unit with total energy wheel

detail B

lifting hole detail A

CONTROL PANEL

END VIEW

inlet hood end view

control panel end view

unit size

A

B

C

D

E

F

G

H

J

K

L

M

N

P

without TE wheel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

031, 041

18' - 10"

2' - 7" 4' - 2"

3' - 10"

3' - 2"

10"

9"

1' - 11 1/2"

1 1/4"

1' - 6 1’4"

ø 2

1/2"

051, 066

19' - 3"

3'

5' - 10"

4' - 1"

3' - 6"

1' - 3"

10 1’4"

2' - 4 1/2"

1 1/4"

3' - 6 3/4"

ø 3"

 

 

withTEwheel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

031, 041

24' - 2"

2' - 7" 4' - 2"

3' - 10"

9 1/4"

3' - 2"

10"

9"

1' - 11 1/2"

1' 6"

1' - 6 1’4"

ø 2 1/2"

7"

1' - 3/4"

051, 066

24' - 7"

3'

5' - 10"

4' - 1"

8"

3' - 6"

1' - 3"

10 - 1’4"

2' - 4 1/2"

1' 8"

3' - 6 3/4"

ø 3"

7"

11"

FAXA-SVX01B-EN

15

 

dimensions

Installation

& weights

 

 

 

 

unit without TE wheel - indoor side view (electric heat version shown)

unit with TE wheel - indoor side view (electric heat version shown)

single & dual gas heater options

16

FAXA-SVX01B-EN

Installation

dimensions

& weights

 

 

 

 

Unit base plan view, duct openings & thru-base power openings, unit sizes 031 & 040

unit without TE wheel

unit with TE wheel

FAXA-SVX01B-EN

17

 

dimensions

Installation

& weights

 

 

 

 

Unit base plan view, duct openings & thru-base power openings, unit sizes 051 & 066

unit without TE wheel

unit with TE wheel

18

FAXA-SVX01B-EN

Installation

dimensions

& weights

 

 

 

 

Fresh air unit control panel detail, all unit sizes

detail A

3x

THRU-BASE MAIN POWER WIRING ENTRANCE

HOLE Ø3.000’’

NOTE: DRILL OR PUNCH HOLE IN COVER PLATE FOR

SMALLER CONDUIT CONNECTION

top view

FAXA-SVX01B-EN

19

 

dimensions

Installation

& weights

 

 

 

 

Exterior features for unit sizes 031 & 040, without TE wheel

CONDENSER FANS

CONVENIENCE OUTLET (OPTION)

 

 

 

LIFTING HOLES

 

 

 

 

 

 

HORIZONTAL DISCHARGE

MAIN COMPRESSOR ACCESS PANEL

 

 

(OPTION)

(40x35)

MAIN CONDENSER

HUMAN INTERFACE

 

REHEAT COMPRESSOR/COIL ACCESS PANEL

COIL ACCESS

ACCESS DOOR

(34x36)

PANEL

(68x36)

 

 

 

 

UNIT CONTROL PANEL

 

 

MAIN POWER WIRING ENTRANCE

 

 

 

(CAN ALSO BE RUN THRU-

24 VOLT CONTROL CIRCUIT WIRING ENTRANCE

 

 

BASE)

 

 

(CAN ALSO BE RUN THRU-BASE)

 

 

 

DUAL GAS HEAT ACCESS PANEL (EACH HEATER HAS SEPARATE PANEL)

(16x23)

INLET HOOD

GAS CONNECTION–DUAL GAS HEAT (EACH HEATER HAS SEPARATE GAS CONNECTIONS)

NATURAL GAS 250–400 MBH: Æ.500 NPT INTERNAL

 

 

CONDENSATE

FILTER AND DAMPER ACCESS DOOR

 

 

DRAIN CONNECTION

 

 

(25x39)

 

ELECTRIC HEAT POWER WIRING ENTRANCE

 

 

 

 

 

(ALSO CAN BE RUN THRU-BASE)

 

EVAP COIL AND

 

ELECTRIC HEATER ELECTRICAL PANEL (24x30)

 

 

 

CONDENSATE DRAIN PAN

 

-OR-

 

ACCESS DOOR (18x34)

 

GAS HEAT PANEL (16x23)

 

 

 

-OR-

 

 

 

FIXED PANEL FOR NO-HEAT OPTION

 

 

 

OR HYDRONIC HEAT INTERFACE OPTION (24x47)

 

 

 

SUPPLY FAN ACCESS DOOR

 

 

20

(33X34)

 

FAXA-SVX01B-EN

 

 

Installation

dimensions

& weights

 

 

 

 

Exterior features, unit sizes 031 & 040 with TE wheel

FAXA-SVX01B-EN

21

 

dimensions

Installation

& weights

 

 

 

 

Exterior features for unit sizes 051 & 066, without TE wheel

CONDENSER FANS

LIFTING HOLES

REHEAT COMPRESSOR/

COIL ACCESS PANEL (40x52)

MAIN COMPRESSOR/

MAIN COMPRESSOR/

COIL ACCESS PANEL (34x52)

COIL ACCESS PANEL

 

(68x52)

CONVENIENCE OUTLET

(OPTION) MAIN POWER WIRING ENTRANCE (CAN ALSO BE RUN THRU-BASE)

HORIZONTAL DISCHARGE (OPTION)

HUMAN INTERFACE

ACCESS DOOR

UNIT CONTROL PANEL

24 VOLT CONTROL CIRCUIT WIRING ENTRANCE (CAN ALSO BE RUN THRU-BASE)

DUAL GAS HEAT ACCESS PANEL (EACH HEATER HAS SEPARATE PANEL)

(16x23)

GAS CONNECTION–DUAL GAS HEAT (EACH HEATER HAS SEPARATE GAS CONNECTIONS)

ELECTRIC HEAT POWER WIRING ENTRANCE FOR 208/230 V: 70, 84, 100, 122 kW (CAN ALSO BE RUN THRU-BASE)

ELECTRIC HEATER ELECTRICAL PANEL (24x49)

-OR-

SINGLE GAS HEAT ACCESS PANEL (16x23)

-OR-

FIXED PANEL FOR NO-HEAT OPTION

OR HYDRONIC HEAT INTERFACE OPTION (24x67)

GAS CONNECTION–SINGLE GAS HEATER

INLET HOOD

CONDENSATE DRAIN

CONNECTION

FILTER AND DAMPER ACCESS DOOR (25x59)

SUPPLY FAN ACCESS DOOR (33x54)

EVAP COIL & CONDENSATE DRAIN PAN ACCESS DOOR

(18x54)

22

FAXA-SVX01B-EN

Trane FADA, FAHA Installation and Maintenance Manual

Installation

dimensions

& weights

 

 

 

 

Exterior features for unit sizes 051 & 066 with TE wheel

FAXA-SVX01B-EN

23

 

dimensions

Installation

& weights

 

 

 

 

Standard curb, unit sizes 031 & 040 without TE wheel

6’’ WOOD NAILER

24

FAXA-SVX01B-EN

Installation

dimensions

& weights

 

 

 

 

Standard roof curb, unit sizes 031 & 040 with TE wheel

6" WOOD NAILER

FAXA-SVX01B-EN

25

 

dimensions

Installation

& weights

 

 

 

 

Standard curb , unit sizes 051 & 66 without TE wheel

6’’ WOOD NAILER

26

FAXA-SVX01B-EN

Loading...
+ 58 hidden pages