FILE NO. A02-014
Revised 3/June/2004
SERVICE MANUAL
SPLIT TYPE
RAV-SM560AT-E/RAV-SM800AT-E RAV-SM560UT-E/RAV-SM800UT-E RAV-SM560BT-E/RAV-SM800BT-E RAV-SM560KRT-E/RAV-SM800KRT-E RAV-SM560XT-E/RAV-SM800XT-E
R410A
PRINTED IN JAPAN, June,2004 ToMo
|
CONTENTS |
|
1. |
SPECIFICATIONS ................................................................................................ |
3 |
2. |
AIR DUCTING WORK ........................................................................................ |
12 |
3. |
CONSTRUCTION VIEWS (EXTERNAL VIEWS) ............................................... |
13 |
4. |
SYSTEMATIC REFRIGERATING CYCLE DIAGRAM ....................................... |
20 |
5. |
WIRING DIAGRAM ............................................................................................ |
22 |
6. |
SPECIFICATIONS OF ELECTRICAL PARTS ................................................... |
28 |
7. |
REFRIGERANT R410A ..................................................................................... |
30 |
8. |
CONTROL BLOCK DIAGRAM .......................................................................... |
38 |
9. |
CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS .................... |
48 |
10. |
TROUBLESHOOTING ....................................................................................... |
65 |
11. |
REPLACEMENT OF SERVICE INDOOR P.C. BOARD ..................................... |
88 |
12. |
SETUP AT LOCAL SITE AND OTHERS ........................................................... |
92 |
13. |
ADDRESS SETUP ........................................................................................... |
103 |
14. |
TROUBLESHOOTING <WALL TYPE> ............................................................ |
108 |
15. |
DETACHMENTS............................................................................................... |
135 |
16. |
EXPLODED VIEWS AND PARTS LIST ........................................................... |
168 |
– 2 –
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Air Discharge Cassette Type
Model name |
|
|
|
|
|
RAV-SM560UT-E |
RAV-SM800UT-E |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
|
Heating |
|
Average |
Cooling |
Heating |
Average |
Standard capacity (Note 1) |
|
(kW) |
|
|
|
|
|
|
|
|
|||
|
5.3 |
|
5.6 |
|
|
7.1 |
8.0 |
|
|||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
(1.5 – 5.6) |
|
(1.5 – 6.3) |
|
|
(2.2 – 8.0) |
(2.2–9.0) |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Heating low temp. capacity (Note 1) (kW) |
|
|
4.9 |
|
|
|
7 |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
||
Energy consumption effect ratio (Cooling) |
|
3.01 [B] |
|
3.90 [A] |
|
3.46 |
3.03 [B] |
3.45 [B] |
3.24 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Running current |
|
(A) |
8.42–7.72 |
|
6.78–6.29 |
|
|
11.32–10.37 |
11.22–10.28 |
|
|
Electrical |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.76 |
|
1.435 |
|
|
2.34 |
2.32 |
|
|||
characteristics |
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Low temp.) |
|
(kW) |
1.89 |
|
|
2.73 |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power factor |
|
(%) |
95 |
|
95 |
|
|
94 |
94 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
|
|
|
Zinc hot dipping steel plate |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Appearance |
|
Ceiling Panel |
|
Model |
|
|
|
|
RBC-U21PG (W) E |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Sold separately) |
|
Panel color |
|
|
|
Moon-white (Muncel 2.5GY 9.0/0.5) |
|
||||
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
|
|
|
256 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
Width |
(mm) |
|
|
|
840 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Outer |
|
|
|
Depth |
(mm) |
|
|
|
840 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
dimension |
|
|
|
Height |
(mm) |
|
|
|
53 |
|
|
||
|
|
|
|
|
|
|
|
|
|||||
|
|
Ceiling panel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Width |
(mm) |
|
|
|
950 |
|
|
|||
|
|
(Sold separately) |
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
|
|
|
950 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
|
21 |
|
|
|
22 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ceiling panel |
|
|
|
|
|
4.5 |
|
|
||||
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
|
|
|
|
Finned tubu |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|||
Soundproof/Heat-insulating material |
|
|
Inflammable polyethylene foam |
Foamed polyethylen |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
|
Turbo fan |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow High (Mid./Low) |
(m³/h) |
|
1050 |
|
|
|
1200 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
|
|
60 |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
|
|
|
|
Attached ceiling panel |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Controller (Sold separately) |
|
|
|
|
|
|
RBC-AMT21E |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas side |
|
(mm) |
|
Ø12.7 (1/2”) |
|
|
Ø15.9 (5/8”) |
|
|||
Connecting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid side |
|
(mm) |
|
Ø6.4 (1/4”) |
|
|
Ø9.5 (3/8”) |
|
||||
pipe |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(Nominal dia.) |
|
|
25 (Polyvinyl chloride tube) |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound level |
High (Mid./Low) (Note 2) |
(dB•A) |
32 |
|
29 |
|
27 |
34 |
31 |
28 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 3 –
• Operation characteristic curve
<Cooling> |
|
|
|
|
|
|
<Heating> |
|
|
|
|
|
|
||
|
14 |
|
|
|
|
|
|
|
16 |
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
14 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RAV-SM800UT-E |
|
|
|
||
|
|
RAV-SM800UT-E |
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|||
|
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(A) |
|
|
|
|
|
|
|
(A) |
10 |
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Current |
|
|
|
|
|
|
|
Current |
8 |
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|
|
RAV-SM560UT-E |
|
|
|
|
|
RAV-SM560UT-E |
|||||
|
|
|
|
|
|
|
|
4 |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
• Conditions |
|
|
|
|
|
• Conditions |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
2 |
|
|
Indoor : DB27 C/WB19 C |
|
|
|
|
|
Indoor : DB20 C |
|
|
|||
|
|
|
Outdoor : DB35 C |
|
|
2 |
|
|
Outdoor : DB7 C/WB6 C |
|
|||||
|
|
|
|
Air flow : High |
|
|
|
|
|
|
Air flow : High |
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
|
|
Pipe length : 7.5m |
|
|
|||
|
00 |
|
|
230V |
|
|
|
|
00 |
|
|
230V |
|
|
|
|
15 20 |
40 |
60 |
70 |
80 |
100 |
|
1520 |
40 |
60 |
80 |
90 |
100 |
Compressor speed (rps) |
Compressor speed (rps) |
• Capacity variation ratio according to temperature
<Cooling> |
<Heating> |
|
105 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(%) |
90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ratio |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Conditions |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
55 |
|
|
|
|
|
|
Indoor : DB27 C/WB19 C |
|
|
|||||
|
|
|
|
|
|
|
Indoor air flow : High |
|
|
|
|||||
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
||||
|
50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
32 |
33 |
34 |
35 |
36 |
37 |
38 |
39 |
40 |
41 |
42 |
43 |
Outsoor temp. ( C)
Capacity ratio (%)
120 |
|
|
|
|
110 |
|
|
|
|
100 |
|
|
|
|
90 |
|
|
|
|
80 |
|
|
|
|
70 |
|
|
|
|
60 |
|
|
|
|
50 |
|
|
|
|
40 |
|
|
|
|
30 |
|
|
|
|
20 |
|
|
|
|
|
• Conditions |
|
||
|
|
|
||
10 |
|
Indoor : DB20 C |
|
|
|
Indoor air flow : High |
|
||
|
|
Pipe length : 7.5m |
|
|
0 |
|
|
|
|
-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 |
||||
|
||||
|
Outsoor temp. ( C) |
– 4 –
1-1-2. Concealed Duct Type
Model name |
|
|
|
|
|
RAV-SM560BT-E |
|
RAV-SM800BT-E |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
|
Heating |
Average |
|
Cooling |
Heating |
Average |
Standard capacity (Note 1) |
|
(kW) |
|
|
|
|
|
|
|
|
|||
|
5 |
|
5.6 |
|
|
7.1 |
8 |
|
|||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
(1.5 – 5.6) |
|
(1.5 – 6.3) |
|
|
(2.2 – 8.0) |
(2.2–9.0) |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Heating low temp. capacity (Note 1) (kW) |
|
|
4.6 |
|
|
|
6.2 |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
||
Energy consumption effect ratio (Cooling) |
|
2.60 [D] |
|
3.27 [C] |
2.94 |
|
2.73 [D] |
3.21 [C] |
2.97 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Running current |
|
(A) |
9.19–8.42 |
|
8.18–7.50 |
|
|
12.57–11.52 |
12.04–11.04 |
|
|
Electrical |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.92 |
|
1.71 |
|
|
2.6 |
2.49 |
|
|||
characteristics |
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Low temp.) |
|
(kW) |
1.78 |
|
|
2.62 |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power factor |
|
(%) |
95 |
|
95 |
|
|
94 |
94 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
|
|
|
Zinc hot dipping steel plate |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Appearance |
|
Ceiling Panel |
|
Model |
|
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Sold separately) |
|
Panel color |
|
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
|
|
|
320 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
Width |
(mm) |
|
|
|
700 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Outer |
|
|
|
Depth |
(mm) |
|
|
|
800 (+7.5) |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
dimension |
|
|
|
Height |
(mm) |
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
Ceiling panel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Width |
(mm) |
|
|
|
—— |
|
|
|
||
|
|
(Sold separately) |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
|
39 |
|
|
|
53 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ceiling panel |
|
|
|
|
|
—— |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
|
|
|
Finned tubu |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||
Soundproof/Heat-insulating material |
|
|
Inflammable polyethylene foam |
|
Foamed polyethylen |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
Turbo fan |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow High (Mid./Low) |
(m³/h) |
|
840 |
|
|
|
1140 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
60 |
|
|
|
100 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
|
|
|
|
Attached main unit |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||
Controller (Sold separately) |
|
|
|
|
|
RBC-AMT21E |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas side |
|
(mm) |
|
Ø12.7 (1/2”) |
|
|
Ø15.9 (5/8”) |
|
|||
Connecting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid side |
|
(mm) |
|
Ø6.4 (1/4”) |
|
|
Ø9.5 (3/8”) |
|
||||
pipe |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(Nominal dia.) |
|
|
25 (Polyvinyl chloride tube) |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound level |
High (Mid./Low) (Note 2) |
(dB•A) |
42 |
|
39 |
36 |
|
43 |
40 |
37 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 5 –
• Operation characteristic curve
<Cooling> |
|
|
|
|
|
|
<Heating> |
|
|
|
|
|
|
||
|
14 |
|
|
|
|
|
|
|
16 |
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
14 |
|
|
|
|
|
|
|
RAV-SM800BT-E |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
RAV-SM800BT-E |
|
|
|
||||
|
|
|
|
|
|
|
|
|
12 |
|
|
|
|
||
|
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(A) |
|
|
|
|
|
|
|
(A) |
10 |
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Current |
|
|
|
|
|
|
|
Current |
8 |
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|
|
RAV-SM560BT-E |
|
|
|
|
|
RAV-SM560BT-E |
|||||
|
|
|
|
|
|
|
|
4 |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
• Conditions |
|
|
|
|
|
• Conditions |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
2 |
|
|
Indoor : DB27 C/WB19 C |
|
|
|
|
|
Indoor : DB20 C |
|
|
|||
|
|
|
Outdoor : DB35 C |
|
|
2 |
|
|
Outdoor : DB7 C/WB6 C |
|
|||||
|
|
|
|
Air flow : High |
|
|
|
|
|
|
Air flow : High |
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
|
|
Pipe length : 7.5m |
|
|
|||
|
00 |
|
|
230V |
|
|
|
|
00 |
|
|
230V |
|
|
|
|
15 20 |
40 |
60 |
70 |
80 |
100 |
|
1520 |
40 |
60 |
80 |
90 |
100 |
Compressor speed (rps) |
Compressor speed (rps) |
• Capacity variation ratio according to temperature
<Cooling> |
<Heating> |
|
105 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(%) |
90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ratio |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Conditions |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
55 |
|
|
|
|
|
|
Indoor : DB27 C/WB19 C |
|
|
|||||
|
|
|
|
|
|
|
Indoor air flow : High |
|
|
|
|||||
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
||||
|
50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
32 |
33 |
34 |
35 |
36 |
37 |
38 |
39 |
40 |
41 |
42 |
43 |
Outsoor temp. ( C)
Capacity ratio (%)
120 |
|
|
|
|
110 |
|
|
|
|
100 |
|
|
|
|
90 |
|
|
|
|
80 |
|
|
|
|
70 |
|
|
|
|
60 |
|
|
|
|
50 |
|
|
|
|
40 |
|
|
|
|
30 |
|
|
|
|
20 |
|
|
|
|
|
• Conditions |
|
||
|
|
|
||
10 |
|
Indoor : DB20 C |
|
|
|
Indoor air flow : High |
|
||
|
|
Pipe length : 7.5m |
|
|
0 |
|
|
|
|
-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 |
||||
|
||||
|
Outsoor temp. ( C) |
– 6 –
1-1-3. High-Wall Type
Model name |
|
|
|
|
RAV-SM560KRT-E |
|
RAV-SM800KRT-E |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
|
Heating |
Average |
|
Cooling |
Heating |
Average |
Standard capacity (Note 1) |
|
(kW) |
|
|
|
|
|
|
|
|
|||
|
5.1 |
|
5.6 |
|
|
6.7 |
8 |
|
|||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
(1.5 – 5.6) |
|
(1.5 – 6.3) |
|
|
(2.2 – 8.0) |
(2.2–9.0) |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Heating low temp. capacity (Note 1) (kW) |
|
|
4.9 |
|
|
|
5.8 |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
||
Energy consumption effect ratio (Cooling) |
|
2.93 [D] |
|
3.29 [C] |
3.11 |
|
2.46 [E] |
3.00 [D] |
3.24 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Running current |
|
(A) |
8.33–7.63 |
|
8.138–7.46 |
|
|
13.15–12.05 |
12.91–11.84 |
|
|
Electrical |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.74 |
|
1.7 |
|
|
2.72 |
2.67 |
|
|||
characteristics |
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Low temp.) |
|
(kW) |
1.95 |
|
|
2.21 |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power factor |
|
(%) |
95 |
|
95 |
|
|
94 |
94 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
|
|
|
|
Pure white |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Appearance |
|
Ceiling Panel |
|
Model |
|
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Sold separately) |
|
Panel color |
|
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
|
|
|
298 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
Width |
(mm) |
|
|
|
998 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Outer |
|
|
|
Depth |
(mm) |
|
|
|
208 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
dimension |
|
|
|
Height |
(mm) |
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
Ceiling panel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Width |
(mm) |
|
|
|
—— |
|
|
|
||
|
|
(Sold separately) |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
|
|
|
12 |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ceiling panel |
|
|
|
|
|
—— |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
|
|
|
Finned tubu |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||
Soundproof/Heat-insulating material |
|
|
Inflammable polyethylene foam |
|
Foamed polyethylen |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
Turbo fan |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow High (Mid./Low) |
(m³/h) |
|
840 |
|
|
|
1110 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
|
|
30 |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
|
|
|
|
Attached main unit |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||
Controller (Sold separately) |
|
|
|
|
Wired remote controller RBC-AMT21E |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas side |
|
(mm) |
|
Ø12.7 (1/2”) |
|
|
Ø15.9 (5/8”) |
|
|||
Connecting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid side |
|
(mm) |
|
Ø6.4 (1/4”) |
|
|
Ø9.5 (3/8”) |
|
||||
pipe |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(Nominal dia.) |
|
|
25 (Polyvinyl chloride tube) |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound level |
High (Mid./Low) (Note 2) |
(dB•A) |
45 |
|
41 |
36 |
|
45 |
41 |
36 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 7 –
• Operation characteristic curve |
|
|
|
|
|
|
|
|
|
|
|
||||
<Cooling> |
|
|
|
|
|
|
<Heating> |
|
|
|
|
|
|
||
|
14 |
|
|
|
|
|
|
|
16 |
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
14 |
|
|
|
|
|
|
|
RAV-SM800KRT-E |
|
|
|
|
|
|
RAV-SM800KRT-E |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
10 |
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(A) |
|
|
|
|
|
|
|
(A) |
10 |
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Current |
|
|
|
|
|
|
Current |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
4 |
|
|
RAV-SM560KRT-E |
|
|
|
|
RAV-SM560KRT-E |
||||||
|
|
|
|
|
|
|
|
4 |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
• Conditions |
|
|
|
|
|
• Conditions |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
2 |
|
|
Indoor : DB27 C/WB19 C |
|
|
|
|
|
Indoor : DB20 C |
|
|
|||
|
|
|
Outdoor : DB35 C |
|
|
2 |
|
|
Outdoor : DB7 C/WB6 C |
|
|||||
|
|
|
|
Air flow : High |
|
|
|
|
|
|
Air flow : High |
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
|
|
Pipe length : 7.5m |
|
|
|||
|
00 |
|
|
230V |
|
|
|
|
00 |
|
|
230V |
|
|
|
|
15 20 |
40 |
60 |
70 |
80 |
100 |
|
1520 |
40 |
60 |
80 |
90 |
100 |
Compressor speed (rps) |
Compressor speed (rps) |
• Capacity variation ratio according to temperature
<Cooling> |
<Heating> |
|
105 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(%) |
90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ratio |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Conditions |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
55 |
|
|
|
|
|
|
Indoor : DB27 C/WB19 C |
|
|
|||||
|
|
|
|
|
|
|
Indoor air flow : High |
|
|
|
|||||
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
||||
|
50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
32 |
33 |
34 |
35 |
36 |
37 |
38 |
39 |
40 |
41 |
42 |
43 |
Outsoor temp. ( C)
Capacity ratio (%)
120 |
|
|
|
|
110 |
|
|
|
|
100 |
|
|
|
|
90 |
|
|
|
|
80 |
|
|
|
|
70 |
|
|
|
|
60 |
|
|
|
|
50 |
|
|
|
|
40 |
|
|
|
|
30 |
|
|
|
|
20 |
|
|
|
|
|
• Conditions |
|
||
|
|
|
||
10 |
|
Indoor : DB20 C |
|
|
|
Indoor air flow : High |
|
||
|
|
Pipe length : 7.5m |
|
|
0 |
|
|
|
|
-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 |
||||
|
||||
|
Outsoor temp. ( C) |
– 8 –
1-1-4. Flexible Type
Model name |
|
|
|
|
|
RAV-SM560XT-E |
|
RAV-SM800XT-E |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
|
Heating |
Average |
|
Cooling |
Heating |
Average |
Standard capacity (Note 1) |
|
(kW) |
|
|
|
|
|
|
|
|
|||
|
5.1 |
|
5.6 |
|
|
6.7 |
8 |
|
|||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
(1.5 – 5.6) |
|
(1.5 – 6.3) |
|
|
(2.2 – 8.0) |
(2.2–9.0) |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Heating low temp. capacity (Note 1) (kW) |
|
|
4.9 |
|
|
|
5.8 |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
||
Energy consumption effect ratio (Cooling) |
|
2.93 [D] |
|
3.29 [C] |
3.11 |
|
2.46 [E] |
3.00 [D] |
3.24 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Running current |
|
(A) |
8.33–7.63 |
|
8.138–7.46 |
|
|
13.15–12.05 |
12.91–11.84 |
|
|
Electrical |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.74 |
|
1.7 |
|
|
2.72 |
2.67 |
|
|||
characteristics |
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Low temp.) |
|
(kW) |
1.95 |
|
|
2.21 |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power factor |
|
(%) |
95 |
|
95 |
|
|
94 |
94 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
|
|
|
|
Pure white |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Appearance |
|
Ceiling Panel |
|
Model |
|
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Sold separately) |
|
Panel color |
|
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
|
|
|
298 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
Width |
(mm) |
|
|
|
998 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Outer |
|
|
|
Depth |
(mm) |
|
|
|
208 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
dimension |
|
|
|
Height |
(mm) |
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
Ceiling panel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Width |
(mm) |
|
|
|
—— |
|
|
|
||
|
|
(Sold separately) |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
|
|
|
—— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
|
|
|
12 |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ceiling panel |
|
|
|
|
|
—— |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
|
|
|
Finned tubu |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||
Soundproof/Heat-insulating material |
|
|
Inflammable polyethylene foam |
|
Foamed polyethylen |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
Cross flow fan |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow High (Mid./Low) |
(m³/h) |
|
840 |
|
|
|
1110 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
|
|
30 |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
|
|
|
|
Attached main unit |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||
Controller (Sold separately) |
|
|
|
|
Wired remote controller RBC-AMT21E |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas side |
|
(mm) |
|
Ø12.7 (1/2”) |
|
|
Ø15.9 (5/8”) |
|
|||
Connecting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid side |
|
(mm) |
|
Ø6.4 (1/4”) |
|
|
Ø9.5 (3/8”) |
|
||||
pipe |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(Nominal dia.) |
|
|
25 (Polyvinyl chloride tube) |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound level |
High (Mid./Low) (Note 2) |
(dB•A) |
39 |
|
36 |
36 |
|
45 |
41 |
36 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 9 –
• Operation characteristic curve
<Cooling> |
|
|
|
|
|
|
<Heating> |
|
|
|
|
|
|
||
|
14 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
14 |
|
|
|
|
|
|
|
RAV-SM800XT-E |
|
|
|
|
|
|
RAV-SM800XT-E |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
10 |
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(A) |
|
|
|
|
|
|
|
(A) |
10 |
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Current |
|
|
|
|
|
|
|
Current |
8 |
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|
|
RAV-SM560XT-E |
|
|
|
|
|
RAV-SM560XT-E |
|
||||
|
|
|
|
|
|
|
|
4 |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
• Conditions |
|
|
|
|
|
• Conditions |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
2 |
|
|
Indoor : DB27 C/WB19 C |
|
|
|
|
|
Indoor : DB20 C |
|
|
|||
|
|
|
Outdoor : DB35 C |
|
|
2 |
|
|
Outdoor : DB7 C/WB6 C |
|
|||||
|
|
|
|
Air flow : High |
|
|
|
|
|
|
Air flow : High |
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
|
|
Pipe length : 7.5m |
|
|
|||
|
00 |
|
|
230V |
|
|
|
|
00 |
|
|
230V |
|
|
|
|
15 20 |
40 |
60 |
70 |
80 |
100 |
|
1520 |
40 |
60 |
80 |
90 |
100 |
Compressor speed (rps) |
Compressor speed (rps) |
• Capacity variation ratio according to temperature |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
<Cooling> |
|
|
|
|
|
<Heating> |
|
|
|
|
|
|
|
|
|
|
|
||||
|
105 |
|
|
|
|
|
|
|
120 |
|
|
|
|
|
|
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
110 |
|
|
|
|
|
|
|
|
|
|
|
|
|
95 |
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
90 |
|
|
|
|
|
|
|
90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(%) |
85 |
|
|
|
|
|
|
(%) |
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ratio |
80 |
|
|
|
|
|
|
ratio |
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Capacity |
|
|
|
|
|
|
|
Capacity |
|
|
|
|
|
|
|
|
|
|
|
|
|
75 |
|
|
|
|
|
|
40 |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65 |
|
|
|
|
|
|
|
30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 |
|
|
|
• Conditions |
|
|
|
20 |
|
|
|
|
|
|
• Conditions |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
55 |
|
|
|
Indoor : DB27 C/WB19 C |
|
|
10 |
|
|
|
|
|
|
Indoor : DB20 C |
|
|
||||
|
|
|
|
Indoor air flow : High |
|
|
|
|
|
|
|
|
|
Indoor air flow : High |
|
||||||
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|||
|
50 |
|
|
|
|
|
|
|
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
32 |
33 |
34 35 |
36 |
37 38 39 40 41 |
42 |
43 |
|
-14 |
-12 |
-10 |
-8 |
-6 |
-4 |
-2 |
0 |
2 |
4 |
6 |
8 |
10 |
Outsoor temp. ( C) |
Outsoor temp. ( C) |
– 10 –
1-2. Outdoor Unit
Model name |
|
|
|
RAV-SM560AT-E |
|
|
RAV-SM800AT-E |
|
|
|
|
|
|
|
|
|
|
Appearance |
|
|
|
Silky shade (Muncel 1Y8.5/0.5) |
||||
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
1 phase 230V (220 – 240V) 50Hz |
||||
|
|
|
(Power exclusive to outdoor is required.) |
|||||
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
Type |
|
Hermetic compressor |
||||
|
|
|
|
|
|
|
|
|
Compressor |
|
Motor |
(kW) |
1.1 |
|
1.6 |
||
|
|
|
|
|
|
|
|
|
|
|
Pole |
|
|
4 poles |
|||
|
|
|
|
|
|
|
|
|
Refrigerant charged |
(kg) |
R410A 0.9 |
|
|
R410A 1.5 |
|||
|
|
|
|
|
|
|
||
Refrigerant control |
|
Pulse motor valve |
||||||
|
|
|
|
|
|
|
|
|
|
|
Standard length |
|
20 (without additional charge) |
||||
|
|
|
|
|
|
|
|
|
|
|
Max. total length |
(m) |
30 |
|
50 |
||
|
|
|
|
|
|
|
|
|
Pipe |
|
Over 20m |
|
Add 20g/m (Max. 200g) |
|
|
Add 40g/m (Max. 1200g) |
|
|
|
|
|
|
|
|
|
|
|
|
Height difference |
Outdoor lower |
(m) |
|
30 |
||
|
|
|
|
|
|
|
|
|
|
|
Outdoor higher |
(m) |
|
50 |
|||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
595 |
|
795 |
||
Outer |
|
|
|
|
|
|
|
|
|
Width |
(mm) |
780 |
|
780 |
|||
dimension |
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
270 |
|
270 |
||
|
|
|
|
|
|
|
|
|
Total weight |
|
|
(kg) |
35 |
|
55 |
||
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
Finned tube |
|||
|
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
Propeller fan |
|||
|
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow High |
(m³/h) |
2400 |
|
3400 |
||
|
|
|
|
|
|
|
|
|
|
|
Motor |
(W) |
43 |
|
63 |
||
|
|
|
|
|
|
|
|
|
Connecting |
|
Gas side |
(mm) |
Ø12.7 (1/2”) |
|
|
Ø15.9 (5/8”) |
|
|
|
|
|
|
|
|
|
|
pipe |
|
Liquid side |
(mm) |
Ø6.4 (1/4”) |
|
|
Ø9.5 (3/8”) |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Discharge temp. sensor |
|||
Protection device |
|
Over-current sensor |
||||||
|
|
|
|
|
Compressor thermo. |
|||
|
|
|
|
|
|
|
|
|
Sound level |
|
High (Mid./Low) |
(dB•A) |
46/48 |
|
45/50 |
||
(Note 2) |
|
(Cooling/Heating) |
|
|||||
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 11 –
2. AIR DUCTING WORK
2-1. Static Pressure Characteristics of Each Model
Fig. 1 RAV-SM560BT-E
External static pressure (mmAq)
External static pressure (mmAq)
12
11
10
9
8
7
6
5
4
3
2
1
0
500
12
11
10
9
8
7
6
5
4
3
2
1
0700
70% (570m³/h) Standard air volume : 840m³/h |
110% (925m³/h) |
Extra High tap
High tap
Middleoletaptap
Low tap
570 600 |
700 |
800 |
900 |
925 |
1000 |
|
Air volume (m³/hr.) |
|
|
|
Fig. 2 RAV-SM800BT-E
70% (800m³/h) Standard air volume : 1140m³/h |
110% (1255m³/h) |
Extra High tap |
|
High tap
Middleoletaptap
Low tap
800 |
900 |
1000 |
1100 |
1200 |
1255 |
1300 |
|
|
Air volume (m³/hr.) |
|
|
|
– 12 –
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
3-1. Indoor Unit
4-Way Air Discharge Cassette Type
RAV-SM560UT-E/RAV-SM800UT-E
200 |
|
860 to 910 Recommended external size |
|
|
|
Check port (450)
200 |
|
Check port |
|
|
|
( 450) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
45 |
Cable draw-in port |
|
30 |
|
|
|
|
||
|
|
|
|
|
|
173 |
113 |
|
|
|
105 |
|
|
Refrigerant pipe |
|
|
|
|
|
connecting port A |
|
270 |
|
|
|
|
Refrigerant pipe |
|
|
|
|
|
70 |
250 |
|
|
|
|
connecting port B |
||
|
|
|
|
|
|
130 |
|
|
|
950 Panel external dimension |
|
|
|
|
|
|
790 Hanging bolt pitch |
|
|
|
|
|
346.5 |
Surface |
|
|
Electric |
|
|
|
|
parts box |
|
|
|
under ceiling |
|
|
|
|
|
dimensionexternal |
80 |
240 |
105 |
415.0 |
|
150 |
|
|
|
840 Unit |
|
|
105 |
|
|
105 |
|
|
|
Ø162
254.5
840 Hanging bolt
480
227
|
A |
B |
120 |
|
|
||
SM560 |
Ø6.4 |
Ø12.7 |
97 |
SM800 |
Ø9.5 |
Ø15.9 |
Surface under ceiling |
860 to 910 Recommended external size |
|
|
|
|
|
|
Standing |
||
|
|
850 or less |
||
Surface |
|
Standing |
||
under ceiling |
||||
640 or less |
||||
|
|
|||
130 |
210 360 |
|
Surface |
|
|
|
|
under ceiling |
|
|
Indoor unit |
Drain up standing size |
||
|
|
|
Hanging bolt M10 or W3/8
Procured locally
|
|
|
|
256 |
|
|
|
|
|
|
|
88 |
|
381.6 |
|
Panelexternal dimension |
|
|
|
Knockout |
Hangingbolt pitch |
|
227 |
|
for |
||
|
|
humidifier |
||||
480 |
|
Ceiling |
||||
|
723 |
950 |
|
|
|
|
|
|
|
|
panel |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
(Sold |
35 |
|
|
|
|
separately) |
|
|
|
|
|
120 |
97 |
Surface |
|
|
|
|
under ceiling |
||
|
|
|
|
|
|
|
|
|
|
|
|
35 |
|
|
|
57 |
|
64 |
|
|
|
5 |
|
|
|
|
|
|
. |
|
|
|
|
|
57 |
25 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Z view |
|
|
188 |
|
|
|
|
Surface under ceiling
– 13 –
Concealed Duct Type
RAV-SM560BT-E
2-Ø200 |
750 |
± 7.5 Hanging bolt pitch |
|
170 |
|||
700 |
Dimension of main unit |
||||||
|
|||||||
Discharge port flange |
|
|
|
|
|
|
|
|
|
20 |
|
|
120 |
||
|
|
|
|
|
4-M10 |
|
|
|
Drain up kit |
Hanging bolt |
280 |
252 |
70 |
(Sold separately) |
(Procured locally) |
|
|
|
|
150 |
|
|
|
to457637 |
160~640 |
|
|
60 |
|
|
|
|
|
|
For hanging bolt M10 |
|
|
80 |
|
|
|
|
|
|
(4-12 x 25 long hole) |
|
|
|
|
5 |
|
|
|
|
|
730 |
|
|
|
|
780 Ceiling opening size |
|
|
75
|
|
|
|
|
|
|
|
|
|
|
|
800 Dimension of main unit |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
Drain pipe connecting port |
|
25 |
|
|
|
|
|
|
|
|
565 Hanging bolt pitch |
210 |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
at drain up kit side |
|
|
720 |
|
|
|
|
|||||||||||
(For polyvinyl chloride pipe |
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
(Inner dia. 32, Nominal dia. 25)) |
|
|
240 |
|
|
|
314.5 |
|||||||||||
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
211 |
|
|
|
|
|
509 |
Refrigerant pipe |
|
|
630 |
|
Ø125 knockout hole (Only rear side) |
|||
connecting port |
|
|
|
|
(For air suction) |
|||
(Gas side Ø12.7) |
|
45 |
300 |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
130 |
80 |
|
6-Ø4 tapping screw lower hole Ø160 |
|
|
25 |
|
35 |
30 |
|
|
||
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
||
305 |
90 120 |
|
|
|
100 |
170 |
210 |
320 |
|
|
|
|
|
|
|
70 |
|
Refrigerant pipe |
|
80 |
|
|
|
|
|
30 |
connecting port |
|
170 |
|
|
|
|
|
|
(Liquid side Ø6.4) |
|
|
|
|
Suction port canvas |
|||
|
|
|
335 |
|
|
|
||
Drain pipe connecting port |
Panel |
|
|
|
|
|||
at main unit side |
|
to |
|
Suction panel |
||||
(For polyvinyl chloride pipe |
155 |
|
|
|||||
(Inner dia. 32, Nominal dia. 25)) |
450 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
2-Ø26 power supply remote |
470 Ceiling opening size |
|
|
|||||
|
|
|
|
|
|
|
|
|
controller cord draw-out port |
|
|
|
|
|
|
Check port A |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
||
|
|
Plane view of main unit |
450 |
|
||||
|
|
|
|
|||||
NOTE 1 : |
|
|
|
|
|
|
150 |
|
|
|
|
|
|
|
|
|
|
For maintenance of the equipment, be sure to install |
|
|
|
|
(Pipe side) |
|
|
|
|
|
|
|
|
|
|||
a check port A at the position as shown below. |
|
|
|
|
|
|
|
|
NOTE 2 : |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Using the drain up kit sold separately, drain-up by 300 (mm) |
|
|
|
|
|
|
|
|
from drain pipe draw-out port of the main unit is necessary. |
|
|
|
|
|
|
|
|
The drain-up over 300mm or more is impossible. |
|
|
Discharge side |
|
|
– 14 –
RAV-SM800BT-E |
|
|
|
|
|
2-Ø200 |
1050 ± 7.5 Hanging bolt pitch |
|
|
|
|
1000 Dimension of main unit |
|
170 |
|
||
Discharge port flange |
|
|
|||
|
|
|
|
|
|
4-M10 |
|
|
20 |
120 |
Drain up kit |
Hanging bolt |
|
|
|
|
(Sold separately) |
(Procured locally) |
290 |
290 |
252 |
|
70 |
|
|
||||
150 |
|
|
|
|
457to 637 |
460~640 |
|
|
|
|
|
|
|
|
|
|
60 |
For hanging bolt M10 |
|
|
|
|
80 |
|
|
|
|
|
|
(4-12 x 25 long hole) |
|
|
|
|
|
5 |
|
|
|
|
|
|
|
1030 |
|
|
|
|
1050 Ceiling opening size |
|
|
|
75
|
|
|
|
|
|
|
|
|
|
|
|
800 Dimension of main unit |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||
Drain pipe connecting port |
|
25 |
|
|
|
|
|
|
|
|
565 Hanging bolt pitch |
210 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
at drain up kit side |
|
|
720 |
|
|
|
||||||||||
(For polyvinyl chloride pipe |
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
(Inner dia. 32, Nominal dia. 25)) |
|
|
|
240 |
|
|
314.5 |
|||||||||
|
|
|
|
|
|
|
|
211 |
|
|
509 |
|
|
|
|
Refrigerant pipe |
|
|
|
630 |
|
Ø125 knockout hole (Only rear side) |
|||
connecting port |
|
|
|
|
|
(For air suction) |
|||
(Gas side Ø12.7) |
|
|
45 |
300 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
130 |
80 |
|
6-Ø4 tapping screw lower hole Ø160 |
|
|
25 |
|
|
35 |
30 |
|
|
||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
||
305 |
90 120 |
|
|
|
|
100 |
170 |
210 |
320 |
|
|
|
|
|
|
|
|
70 |
|
Refrigerant pipe |
80 |
|
|
|
|
|
|
30 |
|
connecting port |
170 |
|
|
|
|
|
|
|
|
(Liquid side Ø6.4) |
|
|
|
|
|
Suction port canvas |
|||
|
|
|
|
|
|
|
|
||
Drain pipe connecting port |
335 |
|
Panel |
|
|
|
|
||
at main unit side |
|
to |
|
|
Suction panel |
||||
(For polyvinyl chloride pipe |
|
|
|
||||||
155 |
|
|
|
||||||
(Inner dia. 32, Nominal dia. 25)) |
|
450 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
2-Ø26 power supply remote |
470 Ceiling opening size |
|
|
|
||||
|
|
|
|
|
|
|
|||
|
controller cord draw-out port |
|
|
|
|
|
Check port A |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Plane view of main unit |
450 |
|||
|
|
|
|
|
|
NOTE 1 : |
150 |
|||||
|
|
|
|
|
|
|
For maintenance of the equipment, be sure to install |
|
|
|
(Pipe side) |
|
|
|
|
|
|
|||
a check port A at the position as shown below. |
|
|
|
|
|
|
NOTE 2 : |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Using the drain up kit sold separately, drain-up by 300 (mm) |
|
|
|
|
|
|
from drain pipe draw-out port of the main unit is necessary. |
|
|
|
|
|
|
The drain-up over 300mm or more is impossible. |
|
Discharge side |
– 15 –
High-Wall Type
RAV-SM560KRT-E/RAV-SM800KRT-E
7 75
|
298 |
|
51 |
Pipe port from left |
Discharge port |
|
|
|
|
(Knockout hole) |
|
Z views
998
Suction port
Pipe port from lower side 75 56 (Knockout hole)
50
Pipe port from right (Knockout hole)
50
Z
8 75
110 |
390 |
Drain hose |
|
Refrigerant pipe connecting port B |
|||
|
490 |
||
|
540 |
|
|
|
|
Refrigerant pipe connecting port A |
|
|
|
998 |
|
|
|
|
|
|
|
763.5 |
|
|
|
|
|
20 |
48 |
450 |
20 |
29 48 |
|
|
|
10 |
41 |
|
||||
|
|
|
|
||||
|
|
|
|
|
|
55 |
|
|
|
|
|
|
|
55 55 |
298 |
40 |
|
|
|
|
40 |
|
|
115 |
100 |
|
|
100 |
115 |
|
|
Position of installation plate
|
A |
B |
|
more |
|
Liquid Side |
Gas Side |
|
55 or |
SM560 |
Ø6.4 |
Ø12.7 |
|
|
|
|
|||
|
|
|
53 or more |
53 or more |
SM800 |
Ø9.5 |
Ø15.9 |
Space required for service |
– 16 –
Under Ceiling/Console Type
RAV-SM560XT-E/RAV-SM800XT-E
Front panel |
1093 |
208 |
|
||
|
|
633
Knock out system
Grille air inlet
Back body
For stud bolt |
200 Min |
1093 |
(Ø8 – Ø10) |
|
1015 |
For stud bolt (Ø6) |
|
742 |
|
450 |
|
|
|
|
|
20 |
20 |
330 |
|
|
165 |
74 |
|
Ø |
||
|
UNDER CEILING & CONSOLE INSTALLATION
Installation plate
Mount plate
M10 Suspention bolt
633 |
|
|
460 |
|
|
|
|
160 |
Min |
57 |
18 |
70 |
Wireless remote control |
|
|
Knock out system
– 17 –
3-2. Outdoor Unit
RAV-SM560AT-E
Drain hole (Ø25) |
Drain hole (2-Ø20 x 88 long hole) |
|
|
|
|
83 |
600 |
97 |
|
|
|
|
|
A legs |
|
115.3 |
125 |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
29 |
|
|
|
|||
308 |
pitchhole(Long bolt)anchorFor |
302 |
pitchholeØ6 |
153 |
150 |
11 |
|
76 |
|
|
30 |
|
330 |
|
|
|
30 |
|
|
|
|
270 |
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B legs |
21 |
780 |
|
|
31 |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
49.5 |
147 |
|
|
|
|
(49.3) |
|
|
115.3 |
|
Discharge guide mounting hole |
|
216 |
|||
21 |
|
|
|
|
|
Discharge guard |
|
|
(4-Ø4 embossing) |
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
21 |
|
|
Valve cover |
|
|
|
|
|
|
center dividing) |
|
|
|
|
|
|
|
|
|
|
521 |
|
|
|
593 598 |
|
|
|
|
|
31 |
|
|
|
|
||
|
|
|
|
|
|
(Fan |
|
|
|
|
|
23 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Earth |
|
|
|
|
|
|
|
500 |
|
|
|
|
|
|
|
|
|
terminal |
|
|
|
|
|
|
|
|
|
|
|
|
132 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
90.6 |
|
|
|
|
25 |
220 |
|
|
|
|
|
|
500 (Fan center dividing) |
Charge port |
31 |
134 |
Protective net mounting hole (2-Ø4 embossing)
43 |
707 |
Protective net mounting hole |
|
(4-Ø4 embossing) |
|
30
60
475
Refrigerant pipe connecting port
(Ø12.7 flare at gas side) Refrigerant pipe connecting port (Ø6.4 flare at liquid side)
Space required for service
|
|
600 |
|
|
|
52 |
|
|
|
36 |
|
11 |
R15 |
2-Ø6 hole |
|
308 |
302 |
Product |
|
external line |
|||
|
|
||
|
Ø11 x 14 U-shape hole |
Details of A legs
|
Ø11 x 14 U- |
|
2-Ø11 x 14 U-shape holes |
|
||
|
shape holes 2-Ø6 hole |
|
||||
|
(For Ø8–Ø10 anchor bolt) |
more |
||||
308 302 |
Product |
|||||
|
|
|||||
external |
|
|
150 or |
|||
|
|
line |
|
|
|
|
11 |
|
R15 |
365 |
150 |
|
|
36 |
or more |
|
||||
|
|
|
||||
|
|
|
|
|||
|
52 |
|
|
|
|
|
|
|
600 |
|
|
|
|
Details of B legs |
|
|
500 |
|
||
|
|
or more |
600
Suction port |
|
|
300 |
|
or more |
Discharge |
(Minimum |
port |
distance up to wall) |
Discharge |
2-Ø11 x 14 long hole |
|
port |
||
(For Ø8–Ø10 anchor bolt) |
||
|
– 18 –
RAV-SM800AT-E
Knockout
(For draining) Drain hole (Ø20 x 88 burring hole)
17.5 |
|
|
|
21 |
|
|
|
|
|
|
|
|
pitch bolt) 70 |
|
365 |
(Long hole for anchor 40 |
29 |
90 |
191 |
20 Drain hole (Ø25 burring hole) |
|
|
Suction |
Part B |
|
|
port |
|
|
|
43 |
40 |
Suction |
Knockout |
|
port |
||
(For draining) |
||
|
17.5
Installation bolt hole (Ø12 x 17 U-shape holes)
40
Details of B part
Details of A part
17.5 |
21 |
26 |
60 |
Discharge |
|
|
port |
Part A |
|
||||
|
150 |
300 |
95 |
|||
|
|
|
|
900 |
|
|
|
|
|
|
314 |
|
|
|
101 |
|
|
|
|
|
|
565 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 |
|
Discharge guide |
|
|
|
|
|
|
|
Z |
|
|||||
|
|
300 |
|
|
|
|
|
|
|
96 |
|
|||
mounting hole |
|
|
307 |
|
||||||||||
(4-Ø4 embossing) |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
43 |
39 47 |
|
40 |
|
17.5 |
|
|
|
|
Installation bolt hole |
|
|
|
|
|
|
|
|
(Ø12 x 17 U-shape holes) |
Handles (Both sides)
Refrigerant pipe connecting port (Ø9.5 flare at liquid side)
Refrigerant pipe connecting port (Ø15.9 flare at gas side)
2
60 67 |
|
|
154 |
|
264 |
|
|
|
|||||
|
|
|
||||
|
|
|
|
|||
|
|
|
||||
27 |
|
|
1 |
|
|
Knockout for lower piping
28 320
Z views
86 |
7 |
|
7 |
|
58 |
|
|
|
|
|
|
|
Space required for service |
|
|
|
|
795 |
|
|
|
2-Ø12 x 17 U-shape holes |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
(For Ø8–Ø10 anchor bolt) |
|
|
|
|
|
|
2 |
46 |
|
more |
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
150 or |
9060 |
|
25 |
85 |
165 |
8060 |
|
365 |
150 |
|
|
|
|
|
|
|
|
or more |
27 |
58 |
2 |
|
|
1 30 |
|
45 |
500 |
|
161 |
|
|
|
|
|
||
|
|
400 |
|
|
|
|
|
or more |
600
Suction port |
|
|
150 |
|
or more |
Discharge |
(Minimum |
port |
distance up to wall) |
Discharge |
2-Ø12 x 17 long hole |
|
port |
||
(For Ø8–Ø10 anchor bolt) |
||
|
– 19 –
4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
Indoor Unit/Outdoor Unit
RAV-SM560UT-E, RAV-SM560BT-E, RAV-SM560KRT-E/RAV-SM560AT-E
Indoor unit
TCJ sensor
Air heat exchanger
TC sensor
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
12.7mm 6.4mm
TS sensor
TD sensor
4-way valve (VT7101D)
Muffler
Ø19 × L160
Rotary compressor (DA130A1F-23F)
Refrigerant pipe |
Refrigerant pipe |
at liquid side |
at gas side |
Outer dia. ØB |
Outer dia. ØA |
Max 30m
Packed valve |
|
Packed valve |
Outer dia. ØB |
Outdoor unit |
Outer dia. ØA |
|
|
|
|
|
PMV |
|
|
(SKV-18D26) |
TO sensor |
|
|
|
|
Strainer |
|
TE |
|
|
sensor |
|
Heat exchanger Ø8 multiple thread
ripple 1 row 22 stages FP1.3 flat fin
Distributor
R410A 0.9 kg
Cooling
Heating
|
|
|
Pressure |
|
Pipe surface temperature (°C) |
Compressor |
|
Indoor/Outdoor |
|||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
Indoor heat |
Outdoor heat |
Indoor |
temp. conditions |
||
|
|
(MPa) |
(kg/cm²G) |
|
|
revolutions per |
|||||||
|
|
Discharge |
Suction |
(DB/WB) (°C) |
|||||||||
|
|
|
|
|
|
|
|
exchanger |
exchanger |
second (rps) |
fan |
|
|
|
|
Pd |
Ps |
Pd |
Ps |
(TD) |
(TS) |
(TC) |
(TE) |
* |
|
Indoor |
Outdoor |
|
Standard |
3.1 |
0.9 |
31.9 |
8.9 |
85 |
15 |
10 |
50 |
74 |
HIGH |
27/19 |
35/– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Overload |
3.6 |
1.0 |
37.1 |
10.4 |
93 |
20 |
15 |
57 |
72 |
HIGH |
32/24 |
43/– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
0.9 |
0.7 |
9.1 |
7.1 |
20 |
7 |
3 |
5 |
28 |
LOW |
18/15.5 |
–5/– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.3 |
0.6 |
23.6 |
6.2 |
71 |
1 |
39 |
3 |
84 |
HIGH |
20/– |
7/6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Overload |
3.3 |
1.2 |
33.2 |
11.8 |
78 |
20 |
54 |
19 |
47 |
LOW |
30.– |
24/18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
1.7 |
0.2 |
16.4 |
1.8 |
110 |
–20 |
26 |
–22 |
110 |
HIGH |
15/– |
–20/(70%) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
–20 –
Indoor Unit/Outdoor Unit
RAV-SM800UT-E, RAV-SM800BT-E, RAV-SM800KRT-E/RAV-SM800AT-E
Indoor unit
TCJ sensor
Air heat exchanger
TC sensor
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
15.9mm 9.5mm
|
Refrigerant pipe |
|
Refrigerant pipe |
|
|
at liquid side |
|
at gas side |
|
|
Outer dia. ØB |
|
Outer dia. ØA |
|
|
|
|
|
Max |
|
|
|
|
50m |
Pd |
Packed valve |
|
Packed valve |
Ps |
|
Outer dia. ØB |
Outdoor unit |
Outer dia. ØA |
|
|
|
|
|
|
TS sensor |
Strainer |
|
Modulating (PMV) |
|
|
(SKV-18D26) |
|
||
|
|
|
|
|
|
TO sensor |
|
|
|
TD sensor
Strainer
4-way valve
Accumulator |
Muffler (STF-0213Z) |
(1500cc) |
Ø25 × L210 |
|
|
|
Ø25 × L160 |
|
Rotary compressor |
|
(DA220A2F-20L) |
TE sensor
Heat exchangerØ8 1 row 30 stages FP1.3 flat fin
Capillary Ø3×Ø2× L530
R410A 1.5 kg
Cooling
Heating
|
|
|
Pressure |
|
Pipe surface temperature (°C) |
Compressor |
|
Indoor/Outdoor |
|||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
Indoor heat Outdoor heat |
Indoor |
temp. conditions |
|||
|
|
(MPa) |
(kg/cm²G) |
|
|
revolutions per |
|||||||
|
|
Discharge |
Suction |
(DB/WB) (°C) |
|||||||||
|
|
|
|
|
|
|
|
exchanger |
exchanger |
second (rps) |
fan |
|
|
|
|
Pd |
Ps |
Pd |
Ps |
(TD) |
(TS) |
(TC) |
(TE) |
* |
|
Indoor |
Outdoor |
|
Standard |
3.3 |
0.9 |
33.4 |
8.8 |
86 |
11 |
9 |
44 |
64 |
HIGH |
27/19 |
35/– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Overload |
3.7 |
1.1 |
37.8 |
11.4 |
90 |
21 |
18 |
54 |
52 |
HIGH |
32/24 |
43/– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
1.0 |
0.8 |
10.0 |
7.9 |
19 |
4 |
4 |
8 |
27 |
LOW |
18/15.5 |
–5/– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.5 |
0.6 |
25.8 |
6.3 |
67 |
6 |
42 |
2 |
65 |
HIGH |
20/– |
7/6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Overload |
3.4 |
1.1 |
34.7 |
11.5 |
85 |
23 |
55 |
16 |
31 |
LOW |
30.– |
24/18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
2.0 |
0.2 |
20.3 |
2.3 |
89 |
–16 |
34 |
–18 |
90 |
HIGH |
15/– |
–20/(70%) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
–21 –
5. WIRING DIAGRAM
5-1. Indoor Unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
4-Way Air Discharge Cassette Type |
|
|
|
|
|
|
|
|
|
|
|
|
||||
RAV-SM560UT-E/RAV-SM800UT-E |
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
TA |
TCJ |
|
TC |
|
|
|
|
|
|
|
|
|
|
|
|
|
1 2 |
1 2 |
1 |
2 |
|
|
|
|
(EXCT) |
|
|
|
|
|
|
|
CN34 |
1 2 |
1 2 |
1 |
2 |
|
1 2 3 |
1 2 |
12 |
|
|
|
|
||
|
FS |
CN104 |
CN102 |
|
CN101 |
|
CN80 |
CN73 |
CN70 |
|
|
|
|
|||
|
(RED) |
|
|
|
|
|
|
|||||||||
|
|
3 3 |
(YEL) |
(RED) |
|
(BLK) |
|
(GRN) |
(RED) |
(WHI) |
5 |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
2 2 |
|
|
|
|
|
|
|
|
|
|
4 |
CN620 |
|
|
|
|
1 1 |
|
MCC-1402 |
|
|
|
|
3 |
|
||||||
|
5 5 |
|
|
|
|
|
|
2 |
(BLU) |
|
||||||
LM1 |
4 4 |
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
3 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 2 |
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
1 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN33 |
|
|
|
|
|
|
|
|
|
|
5 |
|
|
|
|
|
|
Control P.C. Board for |
|
|
CN60 |
|
||||||||||
|
|
|
|
4 |
|
|||||||||||
|
|
(WHI) |
|
|
|
|||||||||||
|
5 5 |
5 5 |
|
|
3 |
(WHI) |
|
|||||||||
|
|
Indoor Unit |
|
|
|
2 |
|
|
|
|||||||
|
4 4 |
4 4 |
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
1 |
|
|
|
||||||||
|
3 3 |
3 3 |
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
2 2 |
2 2 |
|
|
|
|
|
|
|
|
|
|
2 |
CN32 |
|
|
|
1 1 |
1 1 |
|
|
|
|
|
|
DC20V |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
DC15V |
|
|
|
1 |
(WHI) |
|
|
|
|
|
|
|
|
|
|
|
DC12V |
|
|
|
(FAN DRIVE) |
|
||
|
|
|
|
|
|
|
|
|
DC7V |
|
|
|
6 |
|
|
|
|
5 5 |
|
|
|
|
|
Power |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
5 |
|
|
|
|||
LM2 |
4 4 |
|
|
|
|
|
supply |
|
|
|
|
4 |
CN61 |
|
||
3 3 |
|
|
|
|
|
circuit |
|
|
|
|
3 |
(YEL) |
|
|||
|
2 2 |
|
|
|
|
Fuse |
|
|
|
|
|
|
2 |
|
|
|
|
1 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
F302 |
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
T3.15A |
|
|
|
|
|
|
|
|
|
|
|
|
CN333 |
|
|
|
250V~ |
|
|
|
|
|
|
5 |
|
|
|
|
|
(WHI) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|
|
|
|
|
|
5 5 |
|
|
|
|
|
|
|
|
|
|
CN50 |
|
||
|
|
4 4 |
|
Motor |
|
|
|
|
|
|
|
|
3 |
(WHI) |
|
|
|
|
3 3 |
|
drive |
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
||
|
|
2 2 |
|
circuit |
|
|
|
|
|
|
|
|
|
|
|
|
FM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
1 1 |
|
|
|
|
Motor |
|
|
|
|
|
|
|
|
||
|
|
CN334 |
|
|
|
|
drive |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
circuit |
|
|
|
|
3 |
|
|
|
||
|
|
(WHI) |
|
|
|
|
|
|
|
|
CN309(YEL) |
|
||||
|
|
1 1 |
|
|
|
|
|
|
|
|
|
|
2 |
|
||
|
|
2 2 |
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
3 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 4 |
|
|
|
|
|
|
|
|
|
|
|
3 BLK |
B |
|
|
|
5 5 |
|
|
|
Fuse |
|
|
|
|
|
|
3 |
|||
|
|
|
RY |
RY |
|
|
|
|
|
|
|
2 |
2 |
BLK |
|
|
|
|
|
302 |
303 |
|
F301 |
|
|
|
|
|
|
1 |
1 |
A |
|
|
|
|
|
250V~ |
|
|
P301 |
|
|
|
||||||
|
|
|
|
|
|
T6.3A |
|
|
|
|
|
CN41 |
|
|||
|
|
CN68 |
1 2 3 |
1 2 3 |
|
CN67 |
1 2 3 4 5 |
BLK |
1 2 |
|
(BLU) |
|
||||
|
|
|
|
|
|
|
|
|||||||||
|
|
(BLU) |
1 2 3 |
CN304 |
|
(BLK) |
1 2 3 4 5 |
|
CN66 |
|
|
|
|
|
||
|
|
|
|
(GRY) |
|
|
|
|
|
|
(WHI) |
|
|
|
|
|
|
|
|
|
|
|
RED WHI BLK |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
RED |
Closed-end |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
DP |
|
|
|
|
|
|
|
connector |
|
|
|
|
|
|
|
|
|
|
|
|
|
WHI |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
1 |
2 |
3 |
|
|
|
|
|
|
|
|
|
|
|
|
Indoor unit |
|
NOTE |
|
|
|
earth screw |
|
|
|
|
|
|
FM |
: Fan motor |
1 |
2 |
3 |
|
TA |
: Indoor temp. sensor |
|
|||
|
|
|
Outdoor unit |
||
TC |
: Temp. sensor |
|
|
|
|
L |
N |
signalSerial |
earth screw |
||
TCJ |
: Temp. sensor |
|
|||
Single phase |
|
||||
LM1,LM2 |
: Louver motor |
|
|||
220 to 240V |
|
||||
DP : Drain pump motor |
50Hz |
|
|
|
|
|
|
|
|
||
FS : Float switch |
|
|
|
|
|
RY302 : Drain control relay |
|
|
|
|
BLK
2 2 CN001
1 1 (WHI)
WHI
Adapter for Wireless Remote Controller
BLK |
|
2 2 |
CN1 |
1 1 (WHI) |
|
WHI |
|
Wired Renote
Controller
Color
Identification
BLK : BLACK BLU : BLUE RED : RED GRY : GRAY PNK : PINK GRN : GREEN WHI : WHITE BRW : BROWN ORN : ORANGE YEL : YELLOW
– 22 –
Concealed Duct Type |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
RAV-SM560BT-E/RAV-SM800BT-E |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
TA |
TCJ |
TC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 2 |
1 2 |
|
1 2 |
PNL |
EXCT |
1 2 |
|
|
|
|
|
|
|
|
|
|
|
1 2 |
1 2 |
|
1 2 |
1 2 3 |
1 2 |
1 2 |
|
|
|
|
|
|
|
|
|
FS |
CN104 CN102 CN101 |
CN080 |
CN073 CN070 |
|
6 |
|
|
|
|||||
|
|
|
|
CN030 |
(YEL) (RED) |
(BLK) |
(GRN) |
(RED) |
(WHI) |
|
5 |
|
|
|
|||
|
|
|
|
(RED) |
|
|
|
|
|
|
CN060 |
4 |
OPTION |
|
|||
|
|
|
|
|
3 3 |
|
|
|
|
|
|
(WHI) |
3 |
|
|
|
|
|
|
|
|
|
2 2 |
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
1 1 |
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
LM |
|
|
|
|
|
|
CN032 |
2 |
FAN |
|
|||
|
|
|
|
|
|
|
|
|
|
(WHI) |
1 |
DRIVE |
|
||||
|
|
|
|
CN033 |
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
(GRN) |
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
|
5 |
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
CN061 |
4 |
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
(YEL) |
3 |
|
|
|
|
|
|
|
|
CN068 |
|
RY001 |
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
||
|
|
|
|
(BLU) |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
DP |
|
|
3 3 |
|
|
|
|
|
|
|
|
3 |
3 |
|
|
|
|
|
|
2 2 |
|
|
|
|
|
|
|
|
2 |
2 |
|
|
|
|
|
|
|
|
1 1 |
|
|
|
|
|
|
|
|
1 |
1 |
|
|
|
|
|
|
|
|
|
RY002 |
|
|
|
|
|
|
CN074 |
|
||
|
|
1 1 |
1 1 |
YEL 1 1 |
UL |
|
|
|
|
|
|
|
(WHI) |
TR |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
6 |
6 |
|
|
|||||
|
RED |
2 2 |
2 2 |
BLU |
2 2 |
L |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
Power |
|
5 |
5 |
|
|
||||||
|
3 3 |
3 3 |
3 3 |
|
|
|
RY005 |
|
|
|
|
||||||
FM |
YEL |
4 4 |
4 4 |
|
4 4 |
M |
|
|
|
|
supply |
|
4 |
4 |
|
|
|
BLU |
5 5 |
5 5 |
|
5 5 |
|
|
RY006 |
|
|
circuit |
|
3 |
3 |
|
|
||
|
OPN |
|
|
|
|
|
|
|
|
|
2 |
2 |
|
|
|||
|
BLK |
6 6 |
6 6 |
ORN |
6 6 |
H |
|
|
|
|
|
|
|
1 |
1 |
|
|
|
|
7 7 |
7 7 |
BLK |
7 7 |
|
|
|
|
|
|
|
|
CN075 |
|
|
|
RC |
BRW |
8 8 |
|
|
8 8 |
|
|
|
|
|
|
|
|
(WHI) |
|
|
|
|
9 9 |
|
RED 9 9 |
RY007 |
|
|
|
|
|
|
6 |
|
|
|
|||
|
|
|
|
CN083 |
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
(WHI) |
|
|
|
|
|
|
|
|
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
|
|
|
|
|
1 1 |
1 1 |
|
1 |
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|||
|
|
2 2 |
2 2 |
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
RED |
|
|
|
|
|
|
|
|
|
CN050 |
|
|||||
|
3 3 |
3 3 |
|
3 |
|
|
|
|
|
|
|
|
|
||||
FM |
YEL |
4 4 |
4 4 |
|
4 |
|
RY |
|
|
|
Fuse |
|
|
(WHI) |
|
|
|
BLU |
|
|
|
|
|
|
|
|
|
||||||||
|
OPN |
5 5 |
5 5 |
|
5 |
|
004 |
|
|
|
F001 |
|
|
3 |
3 |
B |
2 2 |
|
6 6 |
6 6 |
|
6 |
|
|
|
|
|
T5A |
|
|
|||||
|
BLK |
7 7 |
7 7 |
|
7 |
|
|
|
|
|
250V~ |
|
|
2 |
2 |
A |
1 1 CN1 |
|
BRW |
8 8 |
|
|
8 |
|
|
|
|
|
|
|
|
1 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
CN041 |
|
|||||
|
9 9 |
|
|
9 |
|
|
|
|
|
|
|
|
Remote |
||||
|
|
|
|
|
|
|
1 2 3 |
|
1 2 3 |
|
1 2 3 4 5 |
1 2 |
(BLU) |
||||
|
|
|
|
|
|
|
|
|
Controller |
||||||||
|
(When selecting |
|
|
|
|
CN304 |
|
CN309 |
1 2 3 4 5 CN067 CN066 |
|
|
|
|||||
|
|
|
|
|
(GRY) |
|
(YEL) |
|
|
(BLK) |
(WHI) |
|
|
|
|||
|
high-static pressure) |
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
RED WHI BLK |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
RED |
Closed-end |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
WHI |
connector |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Indoor unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
|
|
|
|
|
||||
|
|
|
earth screw |
|
|
|
|
|
||||||
|
NOTE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FM : Fan motor |
|
1 |
2 |
3 |
|
|
|
Color |
||||||
|
|
|
|
|
|
|
||||||||
RC : Runing capacitor |
|
|
|
Identification |
|
|||||||||
|
|
|
|
|||||||||||
TR : Transformer |
|
|
|
|
|
|
|
|
BLK |
: BLACK |
||||
LM : Louver motor |
|
L |
N |
|
|
|
BLU |
: BLUE |
||||||
TA : Indoor temp. sensor |
|
|
|
|
|
|
|
|
RED : RED |
|||||
Outdoor unit |
|
|
|
|
|
GRY : GRAY |
||||||||
TC, TCJ : Indoor heat exchanger sensor |
earth screw |
|
|
|
|
|
PNK |
: PINK |
||||||
RY001 : Louver control relay |
|
|
|
|
|
|
|
|
GRN : GREEN |
|||||
|
|
|
|
|
|
|
|
WHI : WHITE |
||||||
RY002 : Drain control relay |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
BRW : BROWN |
||||||
RY005~007 : Air volume control relay |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
ORN : ORANGE |
||||||
DP : Drain pump motor |
|
|
|
|
|
|
|
|
YEL |
: YELLOW |
– 23 –
High-Wall Type
RAV-SM560KRT-E/RAV-SM800KRT-E
|
|
|
|
|
SUB-CONTROL P.C. BOARD |
|
CN12 |
2 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
CN01 |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
WHI |
2 1 |
|
TR |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BLK |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 1 |
|
|
|
|
Indoor unit |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 CN63 6 |
5 |
4 |
3 |
2 |
1 CN62 |
CN16 1 |
2 |
3 |
|
|
|
|
|||||
|
|
|
|
|
|
CN |
1 2 |
WHI 6 5 4 3 2 1 |
WHI |
BLU |
1 2 3 |
GRN&YEL |
|
||||||||||||
|
|
|
|
|
|
240 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Remote Controller |
|
BLK |
1 2 |
CN64 6 5 4 3 2 1 CN61 |
|
|
|
|
|
RED |
1 |
||||||||||||||
|
P03 |
P02 |
|
|
|
F201 |
CN230 |
||||||||||||||||||
|
|
|
|
|
|||||||||||||||||||||
(Option) |
|
|
|
|
|
1 2 |
|
6 5 4 3 2 1 |
WHI |
|
|
|
T3,15A |
|
WHI |
2 |
|||||||||
|
|
ORG |
|
|
|
|
|
|
|
|
|||||||||||||||
A |
A |
|
1 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
250V~ |
CN231 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
B |
B |
YEL |
|
2 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BLK |
3 |
||
C |
C |
BLU |
|
3 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN223 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
CN02 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN11 |
|
||
|
|
|
|
|
WHI |
|
1 1 |
1 1 |
|
|
|
MCC-1370A |
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
2 |
2 |
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHI |
|
|||||
Central Centroller |
|
|
|
2 |
2 |
2 |
2 |
|
|
|
|
|
|
|
|
|
|
|
1 |
1 |
|
|
|||
|
|
|
3 3 |
3 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
Connection (Option) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
X |
|
1 1 |
|
|
|
4 |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
CN207 |
|
||
|
|
|
|
|
5 |
5 |
5 |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
Y |
|
2 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHI |
|
|||||
|
|
|
|
|
6 |
6 |
6 |
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
CN01 |
|
AI-NET |
|
|
|
|
|
|
|
|
|
|
|
|
6 |
6 |
BLU |
|
||||
|
|
|
|
|
7 7 |
7 7 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
RED |
|
|
|
|
|
|
|
|
|
|
|
|
|
PNK |
|
|||||||
|
|
|
|
P.C. BOARD |
8 |
8 |
8 |
8 |
|
|
|
|
|
|
|
|
|
|
|
5 |
5 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
4 |
YEL |
|
|||||||
|
|
|
|
9 |
9 |
9 |
9 |
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
MCC-1337 |
|
|
|
|
|
|
|
|
|
|
|
3 |
3 |
OPG |
|
||||||
|
|
|
|
10 10 |
10 10 |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
11 11 |
11 11 |
|
|
|
|
|
|
|
|
|
|
|
2 |
2 |
RED |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
1 |
BRN |
|
||||
|
|
|
|
|
|
|
12 12 |
12 12 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
13 13 |
13 13 |
|
|
|
|
|
|
|
|
|
|
|
6 |
6 |
BLU |
|
||
|
|
|
|
|
|
|
14 14 |
14 14 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
5 |
YEL |
|
||||
|
|
|
|
|
|
|
15 15 |
15 15 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
4 |
WHI |
|
||||
|
|
|
|
|
|
|
16 16 |
16 16 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
3 |
BLK |
|
||||
|
|
|
|
|
|
|
CN02 |
CN31 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
2 |
|
|
||||
|
|
|
|
|
|
|
WHI |
WHI |
|
|
|
|
|
|
|
|
|
|
|
RED |
|
||||
|
|
|
|
BLU |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
1 |
|
|
|
|
|
1 1 |
1 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN210 |
|
|||
|
|
Receiver |
2 2 |
BLU |
2 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHI |
|
|
|
|
3 3 |
BLU |
3 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
5 5 |
BLU |
5 5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
4 4 |
BLU |
4 4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Infra-Red |
6 6 |
BLU |
6 6 |
|
Control P.C. Board for |
2 |
CN14 |
|
|||||||||||||||
|
|
8 8 |
BLU |
8 8 |
|
4 |
|
||||||||||||||||||
|
|
|
7 7 |
BLU |
7 7 |
|
3 |
|
|
|
|||||||||||||||
|
|
|
9 9 |
BLU |
9 9 |
|
|
|
|
|
Indoor Unit |
|
|
|
5 |
WHI |
|
||||||||
|
|
|
10 10 |
WHI |
10 10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
CN25 |
|
CN213 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7 |
|
|
|
|
|
|
|
|
WHI |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
|
|
|
Outdoor unit
(1 Phase model)
Earth
Screw
1 F2 L Power Supply
2N 220/240 50Hz
3Serial Signal
LM
FM
2 1 |
|
|
2 1 |
|
|
2 1 |
6 5 4 3 2 1 |
||||
2 |
1 CN04 |
2 |
1 CN05 |
2 |
1 CN20 |
CN13 |
|||||
BLK BLK |
WHI |
BLK BLK |
WHI |
BLK BLK |
YEL |
WHI |
|||||
|
|
|
|
2 |
1 |
4 |
3 |
2 |
1 |
2 |
1 CN50 |
CN06 |
|
||
GRY PNK |
WHI |
WHI |
|
||
|
|
|
|
2 1
CN21 WHI
TA
NOTE
F : Fuse (PCB) FM : Fan motor LM : Louver motor
TA : Temperature sensor TC : Temperature sensor TCJ : Temperature sensor TR : Transformer
O/D : Outdoor
R/C : Remote Contoller
TC TCJ
|
|
LED Detall |
D05 |
Orange |
O/D Serial Signal Input |
D02 |
Green |
O/D Serial Signal Output |
D13 |
Orange |
R/C Serial Signal Input |
D11 |
Green |
R/C Serial Signal Output |
Chack Code |
Diagnosis |
04 |
Serial Signal Error |
08 |
4-Way Valve Error |
09 |
I/D Heart Exchange Error |
0C |
TA Sensor Error |
0d |
TC Sensor Error |
0F |
TCJ Sensor Error |
11 |
Indoor Fan Error |
12 |
Indoor unit Error |
97 |
LAN Comms Circuit Error |
98 |
LAN Adress Setting |
99 |
R/C Mis-Wiring |
– 24 –
RAV-SM560XT-E/RAV-SM800XT-E
|
HEAT |
|
SWITCH PCB |
EXCHANGER |
|
MCC-1428B |
SENSOR |
|
(TCJ) |
|
|
|
|
|
CN101 1 2 3 |
FOR FLOAT SWITCH |
1 2 |
|
||
WHI GRY GRY |
(OPTION) |
|
When you use float |
1 2 |
|
|
switch you should cut J401 |
|
|
|
|
|
|
|
1 2 3 |
CN402 |
|
|
|
|
|
|
|
|
|
|
|
|||
RECEIVERAYSINFRARED PARTSINDICATIONAND |
|
|
|
|
CN100 1 2 3 |
1 2 |
|
CN05 |
1 2 |
CN03 |
BLK |
|
THERMO |
|
|||||||
|
WHI |
|
|
|
|
|
|
|
|
|
J401 |
|
|
2 |
2 |
|
SENSOR |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
10 10 |
10 10 |
|
|
|
|
|
|
|
|
|
BLK |
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
(TA) |
|
|||||||||
|
9 9 |
BLU |
9 |
9 |
4 |
|
|
POWER |
|
|
DC12V |
|
|
1 |
1 |
BLK |
|
|
|
||
|
8 8 |
BLU |
8 |
8 |
|
|
SUPPLY |
|
|
DC5V |
IC03 |
|
2 2 |
|
HEAT |
|
|||||
|
7 7 |
BLU |
7 |
7 |
|
|
|
CIRCUIT |
|
|
|
|
|
|
1 |
1 |
BLK |
|
EXCHANGER |
|
|
2 |
6 6 |
BLU |
6 |
6 |
|
|
C02 |
|
|
|
|
|
|
|
CN01 |
|
|
SENSOR |
|
||
5 5 |
BLU |
5 |
5 |
|
|
|
|
|
|
|
|
R506 |
|
|
|
|
(TC) |
|
|||
|
4 4 |
BLU |
4 |
4 |
|
|
DB01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 3 |
BLU |
3 |
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
2 2 |
BLU |
2 |
2 |
|
|
|
|
|
|
|
CR502 |
|
|
1 1 |
|
|
|
|
||
|
1 1 |
BLU |
1 |
1 |
|
|
R01 |
|
|
|
|
|
|
CR501 |
WHI 1 1 WHI |
|
|||||
|
CN25 |
|
CN13 |
|
|
|
C01 |
|
|
|
|
|
|
|
2 |
2 |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
3 |
|
2 2 |
|
|
|
|
BRW |
1 |
1 |
5 |
|
|
|
|
|
|
RY501 |
|
|
4 |
4 |
RED |
3 3 |
RED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
5 |
|
4 4 |
|
|
||||
|
|
RED |
2 |
2 |
|
|
|
|
|
|
|
|
|
C501 |
CN10 |
BLK |
5 5 |
BLK |
|
||
|
|
ORN |
3 |
3 |
|
|
|
|
|
|
|
MCC-1428A |
|
|
|
|
|
6 6 |
|
|
|
|
|
YEL |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PNK |
5 |
5 |
|
|
|
|
|
|
|
|
|
|
|
3 |
3 |
BRW |
3 3 |
BLU |
|
|
|
BLU |
6 |
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
CN07 |
IC04 |
|
C15 |
|
|
|
|
R405 |
CR401 |
2 |
2 |
GRY |
2 2 |
PUR |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
1 1 |
YEL |
1 1 |
GRY |
FAN-MOTOR |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN11 |
|
|
|
||
LOUVER |
|
|
|
|
|
|
|
|
|
|
|
RY401 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100”C |
|
|
MOTOR |
|
|
|
|
R507 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R09 |
|
|
R21 |
|
|
|
|
|
|
|
23 |
FOR DRAIN PUMP |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
(OPTION) |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R22 |
|
FUSE |
|
|
|
|
|
|
|
|
CN401 |
|
|
|
||
|
|
|
|
|
250VAC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
SG01 |
|
F01 |
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
T6.3A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BLK |
P04 |
|
CN30 |
|
|
CN31 |
CN23 |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BLK |
WHI |
RED |
INDOOR |
|
GRN&YEL |
|
|
|
|
|
||
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
|
INDOOR |
|
|
|
|
|
|
|
|
|
|
1 2 3 |
TERMINAL |
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
BLOCK |
|
|
|
|
|
|
UNIT |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OUTDOOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UNIT |
|
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS
Check items |
Diagnosis result |
|||
|
|
|
||
1 |
OPERATION |
Check to see if OPERATION indicator goes on and off when the main switch |
||
indicator |
or breaker is turned on. |
|
|
|
|
|
|
|
|
2 |
Terminal |
Check the power supply voltage between |
1 |
- 2 (Refer to the name plate.) |
block |
Chack the fluctuate voltage between 2 - |
3 |
(DC15 to 60V) |
|
|
|
|
||
3 |
Fuse |
Check to see if the fuse blows out. (Check the varistor. : R22, R21) |
||
6.3A |
|
|
|
|
|
|
|
||
4 |
DC 5V |
Check the voltage at the No.8 pin on CN13 connector of the infrared receiver. |
||
(Check the transformer and the power supply circuit of the rated voltage.) |
||||
|
|
|
||
5 |
DC 12V |
Check the voltage at the brown lead of the louver motor. |
||
(Check the transformer and the power supply circuit of the rated voltage.) |
||||
|
|
|
|
|
Color
Identification
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE
GRN&YEL : GREEN& YELLOW
GRN : GREEN
PUR : PURPLE
– 25 –
5-2. Outdoor Unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
RAV-SM560AT-E |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
Q200 |
|
|
|
|
|
|
|
|
DB01 |
|
|
|
REACTOR |
|
|
THERMOSTAT |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
CONVERTER |
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
IGBT MODULE |
|
|
|
|
|
|
|
|
|
FOR |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
MODULE |
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COMPRESSOR |
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
BLU |
BZ BY BX EW BW EV BV EU BU |
BRW |
|
|
|
|
ORN |
2 |
1 |
2 |
1 CN500 |
|
|
||||||||||||
|
|
|
|
|
|
+ ~ |
|
|
|
|
|
2 |
1 |
|
|
||||||||||||
|
|
|
|
|
|
– |
~ A E G |
P10 |
P09 |
2 |
1 |
|
|
TE |
|||||||||||||
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
P17 P18 |
|
|
|
|
|
|
|
P20 |
P19 |
|
|
|
|
P08 |
P07 |
CN600 |
1 |
1 |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
1 |
TD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ELECTRONIC |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CT |
|
|
|
CN601 2 |
2 |
|
|
|||||
|
P23 |
P22 |
P21 |
|
|
|
|
|
|
|
|
STARTER |
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
POWER |
|
|
|
|
|
3 |
3 |
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
BLK |
WHI |
RED |
|
|
|
|
|
|
|
|
|
|
|
RELAY |
|
|
|
|
|
1 |
1 |
TO |
||||
|
|
P.C. BOARD |
|
|
|
|
|
|
|
|
|
|
|
CN602 |
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
2 |
|
|
|||||||||||
4 |
3 |
2 |
1 |
|
(MCC-813) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TS |
||||||
3 |
2 |
1 |
|
|
|
|
|
|
|
|
|
– |
+ |
C12 |
|
|
|
|
|
|
1 |
1 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
|
|
|
|
CN603 2 |
2 |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– |
+ |
C13 |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
3 |
|
|
||||
|
|
CM |
|
|
|
|
|
|
|
|
|
– |
+ |
C14 |
|
|
|
RELAY |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
Q300 |
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
1 |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
COMPRESSOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN701 2 |
2 |
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
3 |
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COIL FOR |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P06 |
|
BLK |
4-WAY VALVE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F04 |
|
|
|
|
|
|
SURGE |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FUSE |
2 |
|
|
|
|
ABSORBER |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
T3. 15A |
|
|
|
|
|
|
1 |
1 |
BLK |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
250V~ |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VARISTOR |
|
2 |
2 |
YEL |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
3 |
RED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
4 |
ORN PMV |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FUSE |
|
|
2 |
|
5 |
5 |
RED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
T25A |
F01 |
|
6 |
6 |
GRY |
PULSE |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
250V~ |
|
|
|
|
CN703 |
MODULATING |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VALVE |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P14 |
P13 |
|
|
P02 |
P03 P01 |
|
|
|
|
|
|
|||
|
|
|
|
|
CN301 5 |
4 |
3 |
2 |
1 |
3 |
2 |
1 |
CN300 |
P12 |
P11 |
WHI |
ORN BLK |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
5 |
4 |
3 |
2 |
1 |
3 |
2 |
1 |
|
|
2 |
1 |
|
|
|
|
|
TERMINAL OF COMPRESSOR |
|||||
|
|
|
|
|
|
PUR |
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
GRY PNK |
|
YEL |
BLK WHI RED |
|
2 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHITE (S) |
|
BLACK (C) |
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
FM |
|
|
|
|
|
1 |
2 3 L N |
|
1 |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
REACTOR |
|
|
|
|
|
|
|
|
|
|
|
RED (R) |
FAN MOTOR |
TO |
POWER |
The sign in ( ) is displayed |
|
INDOOR |
SUPPLY |
|
|
in the terminalcover |
||
|
UNIT |
220 to 240 |
|
|
|
||
|
|
50Hz |
|
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS
Check |
Diagnosis result |
|||
items |
||||
|
|
|
||
1 |
TERMINAL BLOCK |
|
|
|
There is no supply voltage |
|
Power supply and connecting |
||
(AC220 to 240V) between L - N , 1 - 2 |
|
cable check |
||
|
There is no voltage (DC15 to 25V) 2 - 3 |
|
|
|
|
|
|
|
|
|
FUSE |
|
|
|
2 |
T25A 250V to fuse (F01) blown |
|
Converter module (DB01) and |
|
|
|
electrolytic capacitor (C12 to C14) check |
||
T3.15A 250V to fuse (F04) blown |
|
IGBT module (Q200) check |
||
|
|
|
Fan motor check |
|
|
|
|
||
3 |
ELECTROLYTIC CAPACITOR VOLTAGE (C12, C13, C14) |
|||
DC320V not available between |
|
T25A fuse (F01) check |
||
+ – terminal of electrolytic capacitor |
|
P.C. board and converter |
||
|
||||
|
|
|
module (DB01) check |
|
|
|
|
||
|
INVERTER OUTPUT (Inverter and compressor connector out of position) |
|||
4 |
(Please confirm within six minutes after instructing in the drive.) |
|||
Voltage between each line of inverter side |
|
IGBT module and |
||
|
conector pins are not equal. |
|
P.C. board check |
|
|
|
|
|
Color Identification
BLK : BLACK |
WHI : WHITE |
BLU : BLUE |
BRW : BROWN |
RED : RED |
ORN : ORANGE |
GRY : GRAY |
YEL : YELLOW |
PNK : PINK |
PUR : PURPLE |
GRN : GREEN |
|
|
|
NOTE |
|
|
|
|
|
CM |
: Compressor |
||
PMV |
: Pulse modulating valve |
||
FM |
: Fan motor |
||
TE |
: Heat exchanger Temp. Sensor |
||
TD |
: Discharge Temp. Sensor |
||
TO |
: Outdoor Temp. Sensor |
||
TS |
: Suction Temp. Sensor |
||
IGBT |
: Insulated Gate Bipolar Transistor |
||
DB01 |
: Converter module |
||
CT |
: Curreut Transformer |
||
Q300 |
: Fan motor driver module |
||
|
|
|
|
– 26 –
RAV-SM800AT-E |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
T03 |
+ |
|
|
|
|
|
|
|
|
|
RED |
|
CN09 |
|
BU |
|
|
||
|
|
|
|
|
|
|
|
|
CT |
|
|
||||
|
|
|
|
|
|
|
|
|
EU |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CM |
WHI |
|
CN10 |
|
|
BV |
|
|
|
|
|
|
|
|
Compressor |
|
|
T04 |
EV |
|
IGBT |
||||
THERMOSTAT |
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
BLK |
|
CN11 |
|
CT |
BW |
|
module |
|||
FOR |
|
|
|
|
|
|
|
|
|
|
|
|
EW |
|
|
COMPRESSOR |
|
CN604 2 2 |
|
TE |
|
|
|
|
|
4 |
BX |
|
|
||
ORN |
2 2 |
CN500 |
|
1 1 |
|
|
POWER SUPPLY CIRCUIT |
BY |
|
|
|||||
|
|
|
|
|
|
|
BZ |
|
|
||||||
ORN |
1 1 |
|
CN605 2 2 |
|
|
|
(FOR P.C. BOARD) |
|
|
|
|
|
|||
|
|
GRN |
TS |
|
|
|
|
|
|
|
|
Q200 |
|||
|
|
|
|
|
|
|
|
|
|
|
|||||
4-WAY VALVE COIL |
|
|
1 1 |
|
|
F04 |
2 |
|
|
|
|
||||
|
|
|
|
|
|
|
FUSE |
|
|
|
|
|
|||
3 3 |
3 |
|
|
3 3 |
|
|
|
|
3.15A |
|
|
|
|
|
|
|
|
|
TD |
|
|
|
|
|
|
|
|
|
|||
|
|
CN700 |
CN600 2 |
|
|
|
|
|
|
|
P20 |
|
|
||
1 1 |
1 |
|
|
1 1 |
|
|
|
|
|
C13 |
3 |
|
P19 |
|
YEL |
FAN MOTOR |
|
|
CN601 2 2 |
|
TO |
|
|
|
C12 |
|
P18 |
|
BLU |
||
5 5 |
|
|
1 1 |
|
|
|
|
C11 |
|
|
P17 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
FM |
4 4 |
|
Fan |
|
|
|
|
|
|
C10 |
2 |
F02 |
|
|
|
3 3 CN300 |
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
FUSE |
G |
|
|
|||||
|
2 2 |
|
circuit |
|
BLU |
|
|
|
|
|
|
15A |
|
|
|
|
1 1 |
|
|
3 3 |
|
3 3 |
|
|
|
|
|
E |
|
|
|
|
|
2 |
CN302 |
|
|
CN04 |
|
|
|
|
A |
Converter |
|||
|
3 3 |
|
YEL |
|
|
|
|
|
|
||||||
|
|
|
1 1 |
|
1 1 |
|
|
|
|
|
~ |
|
module |
||
|
2 2 CN301 |
F300 |
|
|
|
|
POWER |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
~ |
|
|
||||
|
1 1 |
|
FUSE |
5 5 |
BLK |
|
5 5 |
|
|
RELAY |
|
|
|
|
|
|
|
|
T5A |
WHI |
|
|
|
|
|
|
+ |
|
DB01 |
||
|
6 6 |
|
CN800 |
4 4 |
BLU |
|
4 4 |
CN06 |
|
RY01 |
|
P10 |
|
|
|
|
|
3 3 |
|
3 3 |
|
|
|
|
|
||||||
|
5 5 |
|
RED |
|
|
|
|
|
|
|
ORN |
||||
|
|
|
2 2 |
|
2 2 |
P.C. BOARD |
R05 |
|
|
|
|
||||
PMV |
4 4 |
|
|
1 1 |
PNK |
|
1 1 |
|
P11 |
REACTOR |
|||||
3 3 CN702 |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
(MCC-1359) |
R06 |
|
P13 |
2 2 |
|
|
|||
|
2 2 |
|
|
2 2 |
|
|
2 2 |
|
|
|
|
||||
|
|
CN04 |
|
|
|
|
|
|
1 1 |
|
|
||||
|
1 1 |
|
ORN |
|
CN05 |
|
|
|
P12 |
|
|
||||
|
|
1 1 |
|
1 1 |
|
T02 |
|
REACTOR |
|||||||
|
|
|
|
|
BLK |
|
|
|
|
CT |
|
P09 |
2 2 |
|
|
|
|
|
|
5 5 |
|
5 5 |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
1 1 |
|
|
|||
|
|
PHOTO COUPLER |
|
|
|
|
|
|
P08 |
|
|
||||
|
|
4 4 |
WHI |
|
4 4 |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
P15 |
|
|
|
|||
|
|
|
|
3 3 |
|
3 3 |
|
|
|
|
|
|
BRN |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
CN01 2 2 |
RED |
|
2 2 |
|
|
|
|
P14 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
1 1 |
|
1 1 |
CN13 |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
SUB |
|
2 |
F01 |
|
|
|
|
|
|
|
|
|
|
|
|
P.C. BOARD |
|
FUSE |
|
|
|
|
|
F01 |
VARISTOR |
SURGE |
|
|
|
||
(MCC-1398) |
|
T3.15A |
|
|
|
|
2 |
25AFUSE |
|
|
|
||||
|
|
|
|
|
|
ABSORBER |
|
|
|
||||||
|
|
CN02 |
1 2 3 |
|
|
REACTOR |
|
CN01 |
CN02 |
|
CN03 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
RED |
WHI |
|
BLK |
|
|
|
|
|
|
|
1 2 3 GRY |
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHI |
RED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
1 |
|
1 |
|
|
2 |
3 |
|
|
L |
|
|
|
|
N |
|
|
|
|
|
|
|
|
|
|
|
|
|
TERMINAL OF COMPRESSOR |
|
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TO |
POWER |
WHITE(S) |
|
BLACK(C) |
The sign in ( ) |
||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
INDOOR SUPPLY |
|
|
|
|
||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
UNIT |
220-240V |
|
|
|
|
|
|
|
is displayed |
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
~50Hz |
|
|
|
|
|
|
|
in the terminal |
|||||||||||||||||
|
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS |
|
|
|
|
|
RED(R) |
cover |
|||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Check |
|
|
|
|
Diagnosis result |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
items |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
TERMINAL BLOCK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
There is no supply voltage |
Connecting cable check |
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
(AC220 to 240V) between L - N , 1 - 2 |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
|
There is no voltage (DC15 to 25V) 2 - 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FUSE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
2 |
25A fuse (F01) blown, 15A fuse (F02) blown |
Converter module (DB01) and electrolytic |
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
3.15A fuse (F04) blown, |
capacitor (C10 to C13) check IGBT |
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
T5A fuse (F300) blown (SUB P.C. board) |
|
|
module (Q200) check, Fan motor check |
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
|
T3.15A fuse (F01) blown (SUB P.C. board) |
SUB P.C. board check |
|
|
|
Color Identification |
|
||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
ELECTROLYTIC CAPACITOR VOLTAGE (C10, C11, C12, C13) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BLK |
: BLACK |
WHI |
: WHITE |
|||||||||||||||||||||||||||
DC320V not available between |
25A fuse (F01) check |
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
+ terminal of electrolytic capacitor |
|
|
P.C. board and coverter |
|
|
BLU |
: BLUE |
BRN : BROWN |
|||||||||||||||||||||||||||||||||||||||||||
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
module (DB01) check |
|
|
RED : RED |
ORN : ORANGE |
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
INVERTER OUTPUT (CN09, CN10, CN11) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GRY |
: GRAY |
YEL |
: YELLOW |
|||||||||
4 |
(Please confirm within six minutes after instructing in the drive.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PNK |
: PINK |
PUR : PURPLE |
|||||||||||||||||||||||||||
Voltage between each line of inverterside |
IGBT module and |
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
|
conector pins are not equal. |
|
|
P.C. board check |
|
|
GRN : GREEN |
|
|
|
|
– 27 –
6. SPECIFICATIONS OF ELECTRICAL PARTS
6-1. Indoor Unit
4-Way Air Discharge Cassette Type
RAV-SM560UT-E/RAV-SM800UT-E
No. |
Parts name |
Type |
|
Specifications |
|
|
|
|
|
1 |
Fan motor (for indoor) |
SWF-230-60-1 |
Output (Rated) 60 W, 220–240 V |
|
|
|
|
|
|
2 |
Thermo. sensor (TA-sensor) |
155 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
3 |
Heat exchanger sensor (TCJ-sensor) |
Ø6 mm, 1200 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
4 |
Heat exchanger sensor (TC-sensor) |
Ø6 mm, 1200 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
5 |
Float switch |
FS-0218-106 |
|
|
|
|
|
|
|
6 |
Drain pump motor |
ADP-1406 |
|
|
|
|
|
|
|
Concealed Duct Type
RAV-SM560BT-E/RAV-SM800BT-E
No. |
Parts name |
Type |
|
Specifications |
|
|
|
|
|
1 |
Fan motor (RAV-SM800BT-E) |
STF-230-80-4C |
Output (Rated) 80 W, 220–240 V, 4P |
|
|
|
|
|
|
2 |
Fan motor (RAV-SM560BT-E) |
STF-220-80-4C |
Output (Rated) 80 W, 220–240 V, 4P |
|
|
|
|
|
|
3 |
Capacitor (RAV-SM800BT-E) |
EAG40M805UF1 |
400WV, 5µF |
|
|
|
|
|
|
4 |
Capacitor (RAV-SM560BT-E) |
CMPS400-4.0 |
400WV, 4.0µF |
|
|
|
|
|
|
5 |
Thermo. sensor (TA-sensor) |
818 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
6 |
Heat exchanger sensor (TC-sensor) |
Ø6 mm, 1200 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
7 |
Heat exchanger sensor (TCJ-sensor) |
Ø6 mm, 1200 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
High-Wall Type
RAV-SM560KRT-E/RAV-SM800KRT-E
No. |
Parts name |
Type |
|
Specifications |
|
|
|
|
|
1 |
Fan motor (for indoor) |
ICF340-30-1 |
Output (Rated) 30 W, 220–240 V |
|
|
|
|
|
|
2 |
Grille motor |
MP35EA12 |
|
|
|
|
|
|
|
3 |
Thermo. sensor (TA-sensor) |
268 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
4 |
Heat exchanger sensor (TC-sensor) |
Ø6 mm, 400 mm |
10 kΩ |
at 25°C |
|
|
|
|
|
5 |
Heat exchanger sensor (TCJ-sensor) |
Ø6 mm, 400 mm |
|
|
|
|
|
|
|
RAV-SM560XT-E/RAV-SM800XT-E
No. |
Parts name |
Type |
|
|
Specifications |
|
|
|
|
||
1 |
Fan motor (for indoor) |
AFP-220-50-4A |
Output (Rated) 50 W, 220–240 V |
||
|
|
|
|
||
2 |
Grille motor |
MP35EA |
DC 12 V |
||
|
|
|
|
|
|
3 |
Thermo. sensor (TA-sensor) |
mm |
|
10 kΩ |
at 25°C |
|
|
|
|
|
|
4 |
Heat exchanger sensor (TC-sensor) |
Ø6 mm, |
mm |
10 kΩ |
at 25°C |
|
|
|
|
|
|
5 |
Heat exchanger sensor (TCJ-sensor) |
Ø6 mm, |
mm |
|
|
|
|
|
|
|
|
– 28 –
6-2. Outdoor Unit
RAV-SM560AT-E
No. |
Parts name |
Type |
|
Specifications |
|
|
|
|
|
1 |
Fan motor |
ICF-140-43-1 |
Output (Rated) 40 W |
|
|
|
|
|
|
2 |
Compressor |
DA130A1F-23F |
3 phase, 4P, 1100 W |
|
|
|
|
|
|
3 |
Reactor |
CH-57 |
1=10 mH, 16A |
|
|
|
|
|
|
4 |
Outdoor temp. sensor (To-sensor) |
— |
10 kΩ |
at 25°C |
|
|
|
|
|
5 |
Heat exchanger sensor (Te-sensor) |
— |
10 kΩ |
at 25°C |
|
|
|
|
|
6 |
Suction temp. sensor (Ts-sensor) |
— |
10 kΩ |
at 25°C |
|
|
|
|
|
7 |
Discharge temp. sensor (Td-sensor) |
— |
50 kΩ |
at 25°C |
|
|
|
|
|
8 |
Fuse (Switching power (Protect)) |
|
T3.15 A, AC 250 V |
|
|
|
|
|
|
9 |
Fuse (Inverter, input (Current protect) |
|
25 A, AC 250 V |
|
|
|
|
|
|
10 |
4-way valve solenoid coil |
STF-0108G |
|
|
|
|
|
|
|
11 |
Compressor thermo. (Protection) |
US-622 |
ON : 90 ± 5°C, OFF : 125 ± 4°C |
|
|
|
|
|
|
RAV-SM800AT-E
No. |
Parts name |
Type |
|
|
Specifications |
|
|
|
|
||
1 |
Fan motor |
ICF-140-63-1 |
Output (Rated) 63 W, 220–240 V |
||
|
|
|
|
||
2 |
Compressor |
DA220A2F-20L |
3 phase, 4P, 1600 W |
||
|
|
|
|
|
|
3 |
Reactor |
CH-47 |
mH, |
A |
|
|
|
|
|
|
|
4 |
Outdoor temp. sensor (To-sensor) |
— |
10 kΩ |
at 25°C |
|
|
|
|
|
|
|
5 |
Heat exchanger sensor (Te-sensor) |
— |
10 kΩ |
at 25°C |
|
|
|
|
|
|
|
6 |
Suction temp. sensor (Ts-sensor) |
— |
10 kΩ |
at 25°C |
|
|
|
|
|
|
|
7 |
Discharge temp. sensor (Td-sensor) |
— |
50 kΩ |
at 25°C |
|
|
|
|
|
||
8 |
Fuse (Switching power (Protect)) |
|
T3.15 A, AC 250 V |
||
|
|
|
|
||
9 |
Fuse (Inverter, input (Current protect)) |
|
25 A, AC 250 V |
||
|
|
|
|
|
|
10 |
4-way valve solenoid coil |
DKV-M0ZS743B0 |
|
|
|
|
|
|
|
||
11 |
Compressor thermo. (Protection) |
|
ON : 90 ± 5°C, OFF : 125 ± 4°C |
||
|
|
|
|
|
|
6-3. Accessory Separate Sold Parts
RBC-U21PG (W) E (Ceiling panel)
No. |
Parts name |
Type |
Specifications |
|
|
|
|
1 |
Motor-louver |
MP24GA |
DC 12 V |
|
|
|
|
2 |
|
|
|
|
|
|
|
TCB-DP11E (Drain up pump)
No. |
Parts name |
Type |
Specifications |
|
|
|
|
1 |
Pump-drain |
PJD-05230TF-1 |
AC 220–240 V |
|
|
|
|
2 |
|
|
|
|
|
|
|
– 29 –
7. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
7-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1)Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
(2)Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3)If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
(4)When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5)After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6)When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7)Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
(8)Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
7-2. Refrigerant Piping Installation
7-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1)Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 7-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 30 –