SERVICE MANUAL

SPLIT TYPE

RAV-SM560AT-E/RAV-SM800AT-E RAV-SM560UT-E/RAV-SM800UT-E RAV-SM560BT-E/RAV-SM800BT-E RAV-SM560KRT-E/RAV-SM800KRT-E RAV-SM560XT-E/RAV-SM800XT-E

R410A

PRINTED IN JAPAN, June,2004 ToMo

 

CONTENTS

 

1.

SPECIFICATIONS ................................................................................................

3

2.

AIR DUCTING WORK ........................................................................................

12

3.

CONSTRUCTION VIEWS (EXTERNAL VIEWS) ...............................................

13

4.

SYSTEMATIC REFRIGERATING CYCLE DIAGRAM .......................................

20

5.

WIRING DIAGRAM ............................................................................................

22

6.

SPECIFICATIONS OF ELECTRICAL PARTS ...................................................

28

7.

REFRIGERANT R410A .....................................................................................

30

8.

CONTROL BLOCK DIAGRAM ..........................................................................

38

9.

CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS ....................

48

10.

TROUBLESHOOTING .......................................................................................

65

11.

REPLACEMENT OF SERVICE INDOOR P.C. BOARD .....................................

88

12.

SETUP AT LOCAL SITE AND OTHERS ...........................................................

92

13.

ADDRESS SETUP ...........................................................................................

103

14.

TROUBLESHOOTING <WALL TYPE> ............................................................

108

15.

DETACHMENTS...............................................................................................

135

16.

EXPLODED VIEWS AND PARTS LIST ...........................................................

168

– 2 –

1. SPECIFICATIONS

1-1. Indoor Unit

1-1-1. 4-Way Air Discharge Cassette Type

Model name

 

 

 

 

 

RAV-SM560UT-E

RAV-SM800UT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

Heating

 

Average

Cooling

Heating

Average

Standard capacity (Note 1)

 

(kW)

 

 

 

 

 

 

 

 

 

5.3

 

5.6

 

 

7.1

8.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1.5 – 5.6)

 

(1.5 – 6.3)

 

 

(2.2 – 8.0)

(2.2–9.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating low temp. capacity (Note 1) (kW)

 

 

4.9

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy consumption effect ratio (Cooling)

 

3.01 [B]

 

3.90 [A]

 

3.46

3.03 [B]

3.45 [B]

3.24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

1 phase 230V (220 – 240V) 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

(A)

8.42–7.72

 

6.78–6.29

 

 

11.32–10.37

11.22–10.28

 

Electrical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

1.76

 

1.435

 

 

2.34

2.32

 

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Low temp.)

 

(kW)

1.89

 

 

2.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

 

(%)

95

 

95

 

 

94

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

 

Ceiling Panel

 

Model

 

 

 

 

RBC-U21PG (W) E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Sold separately)

 

Panel color

 

 

 

Moon-white (Muncel 2.5GY 9.0/0.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

 

 

 

256

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

Width

(mm)

 

 

 

840

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

 

Depth

(mm)

 

 

 

840

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dimension

 

 

 

Height

(mm)

 

 

 

53

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

(mm)

 

 

 

950

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

 

 

 

950

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

 

Main unit

 

(kg)

 

21

 

 

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

 

Finned tubu

 

 

 

 

 

 

 

 

 

 

 

 

 

Soundproof/Heat-insulating material

 

 

Inflammable polyethylene foam

Foamed polyethylen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Turbo fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

 

Standard air flow High (Mid./Low)

(m³/h)

 

1050

 

 

 

1200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

(W)

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

Attached ceiling panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller (Sold separately)

 

 

 

 

 

 

RBC-AMT21E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

 

(mm)

 

Ø12.7 (1/2”)

 

 

Ø15.9 (5/8”)

 

Connecting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

 

(mm)

 

Ø6.4 (1/4”)

 

 

Ø9.5 (3/8”)

 

pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain port

(Nominal dia.)

 

 

25 (Polyvinyl chloride tube)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound level

High (Mid./Low) (Note 2)

(dB•A)

32

 

29

 

27

34

31

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.

Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

– 3 –

• Operation characteristic curve

<Cooling>

 

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAV-SM800UT-E

 

 

 

 

 

RAV-SM800UT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

 

 

 

 

 

 

 

(A)

10

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

Current

8

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

RAV-SM560UT-E

 

 

 

 

 

RAV-SM560UT-E

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Indoor : DB27 C/WB19 C

 

 

 

 

 

Indoor : DB20 C

 

 

 

 

 

Outdoor : DB35 C

 

 

2

 

 

Outdoor : DB7 C/WB6 C

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

Pipe length : 7.5m

 

 

 

00

 

 

230V

 

 

 

 

00

 

 

230V

 

 

 

 

15 20

40

60

70

80

100

 

1520

40

60

80

90

100

Compressor speed (rps)

Compressor speed (rps)

• Capacity variation ratio according to temperature

<Cooling>

<Heating>

 

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(%)

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

Indoor : DB27 C/WB19 C

 

 

 

 

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

33

34

35

36

37

38

39

40

41

42

43

Outsoor temp. ( C)

Capacity ratio (%)

120

 

 

 

110

 

 

 

100

 

 

 

90

 

 

 

80

 

 

 

70

 

 

 

60

 

 

 

50

 

 

 

40

 

 

 

30

 

 

 

20

 

 

 

 

• Conditions

 

 

 

 

10

 

Indoor : DB20 C

 

 

Indoor air flow : High

 

 

 

Pipe length : 7.5m

 

0

 

 

 

-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10

 

 

Outsoor temp. ( C)

– 4 –

1-1-2. Concealed Duct Type

Model name

 

 

 

 

 

RAV-SM560BT-E

 

RAV-SM800BT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

Heating

Average

 

Cooling

Heating

Average

Standard capacity (Note 1)

 

(kW)

 

 

 

 

 

 

 

 

 

5

 

5.6

 

 

7.1

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1.5 – 5.6)

 

(1.5 – 6.3)

 

 

(2.2 – 8.0)

(2.2–9.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating low temp. capacity (Note 1) (kW)

 

 

4.6

 

 

 

6.2

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy consumption effect ratio (Cooling)

 

2.60 [D]

 

3.27 [C]

2.94

 

2.73 [D]

3.21 [C]

2.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

1 phase 230V (220 – 240V) 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

(A)

9.19–8.42

 

8.18–7.50

 

 

12.57–11.52

12.04–11.04

 

Electrical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

1.92

 

1.71

 

 

2.6

2.49

 

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Low temp.)

 

(kW)

1.78

 

 

2.62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

 

(%)

95

 

95

 

 

94

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

 

Ceiling Panel

 

Model

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Sold separately)

 

Panel color

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

 

 

 

320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

Width

(mm)

 

 

 

700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

 

Depth

(mm)

 

 

 

800 (+7.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dimension

 

 

 

Height

(mm)

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

(mm)

 

 

 

——

 

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

 

Main unit

 

(kg)

 

39

 

 

 

53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

Finned tubu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Soundproof/Heat-insulating material

 

 

Inflammable polyethylene foam

 

Foamed polyethylen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Turbo fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

 

Standard air flow High (Mid./Low)

(m³/h)

 

840

 

 

 

1140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

(W)

 

60

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

Attached main unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller (Sold separately)

 

 

 

 

 

RBC-AMT21E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

 

(mm)

 

Ø12.7 (1/2”)

 

 

Ø15.9 (5/8”)

 

Connecting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

 

(mm)

 

Ø6.4 (1/4”)

 

 

Ø9.5 (3/8”)

 

pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain port

(Nominal dia.)

 

 

25 (Polyvinyl chloride tube)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound level

High (Mid./Low) (Note 2)

(dB•A)

42

 

39

36

 

43

40

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.

Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

– 5 –

• Operation characteristic curve

<Cooling>

 

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

RAV-SM800BT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAV-SM800BT-E

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

 

 

 

 

 

 

 

(A)

10

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

Current

8

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

RAV-SM560BT-E

 

 

 

 

 

RAV-SM560BT-E

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Indoor : DB27 C/WB19 C

 

 

 

 

 

Indoor : DB20 C

 

 

 

 

 

Outdoor : DB35 C

 

 

2

 

 

Outdoor : DB7 C/WB6 C

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

Pipe length : 7.5m

 

 

 

00

 

 

230V

 

 

 

 

00

 

 

230V

 

 

 

 

15 20

40

60

70

80

100

 

1520

40

60

80

90

100

Compressor speed (rps)

Compressor speed (rps)

• Capacity variation ratio according to temperature

<Cooling>

<Heating>

 

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(%)

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

Indoor : DB27 C/WB19 C

 

 

 

 

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

33

34

35

36

37

38

39

40

41

42

43

Outsoor temp. ( C)

Capacity ratio (%)

120

 

 

 

110

 

 

 

100

 

 

 

90

 

 

 

80

 

 

 

70

 

 

 

60

 

 

 

50

 

 

 

40

 

 

 

30

 

 

 

20

 

 

 

 

• Conditions

 

 

 

 

10

 

Indoor : DB20 C

 

 

Indoor air flow : High

 

 

 

Pipe length : 7.5m

 

0

 

 

 

-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10

 

 

Outsoor temp. ( C)

– 6 –

1-1-3. High-Wall Type

Model name

 

 

 

 

RAV-SM560KRT-E

 

RAV-SM800KRT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

Heating

Average

 

Cooling

Heating

Average

Standard capacity (Note 1)

 

(kW)

 

 

 

 

 

 

 

 

 

5.1

 

5.6

 

 

6.7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1.5 – 5.6)

 

(1.5 – 6.3)

 

 

(2.2 – 8.0)

(2.2–9.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating low temp. capacity (Note 1) (kW)

 

 

4.9

 

 

 

5.8

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy consumption effect ratio (Cooling)

 

2.93 [D]

 

3.29 [C]

3.11

 

2.46 [E]

3.00 [D]

3.24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

1 phase 230V (220 – 240V) 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

(A)

8.33–7.63

 

8.138–7.46

 

 

13.15–12.05

12.91–11.84

 

Electrical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

1.74

 

1.7

 

 

2.72

2.67

 

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Low temp.)

 

(kW)

1.95

 

 

2.21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

 

(%)

95

 

95

 

 

94

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

 

Pure white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

 

Ceiling Panel

 

Model

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Sold separately)

 

Panel color

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

 

 

 

298

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

Width

(mm)

 

 

 

998

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

 

Depth

(mm)

 

 

 

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dimension

 

 

 

Height

(mm)

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

(mm)

 

 

 

——

 

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

 

Main unit

 

(kg)

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

Finned tubu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Soundproof/Heat-insulating material

 

 

Inflammable polyethylene foam

 

Foamed polyethylen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Turbo fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

 

Standard air flow High (Mid./Low)

(m³/h)

 

840

 

 

 

1110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

(W)

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

Attached main unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller (Sold separately)

 

 

 

 

Wired remote controller RBC-AMT21E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

 

(mm)

 

Ø12.7 (1/2”)

 

 

Ø15.9 (5/8”)

 

Connecting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

 

(mm)

 

Ø6.4 (1/4”)

 

 

Ø9.5 (3/8”)

 

pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain port

(Nominal dia.)

 

 

25 (Polyvinyl chloride tube)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound level

High (Mid./Low) (Note 2)

(dB•A)

45

 

41

36

 

45

41

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.

Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

– 7 –

• Operation characteristic curve

 

 

 

 

 

 

 

 

 

 

 

<Cooling>

 

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

RAV-SM800KRT-E

 

 

 

 

 

 

RAV-SM800KRT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

 

 

 

 

 

 

 

(A)

10

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

4

 

 

RAV-SM560KRT-E

 

 

 

 

RAV-SM560KRT-E

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Indoor : DB27 C/WB19 C

 

 

 

 

 

Indoor : DB20 C

 

 

 

 

 

Outdoor : DB35 C

 

 

2

 

 

Outdoor : DB7 C/WB6 C

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

Pipe length : 7.5m

 

 

 

00

 

 

230V

 

 

 

 

00

 

 

230V

 

 

 

 

15 20

40

60

70

80

100

 

1520

40

60

80

90

100

Compressor speed (rps)

Compressor speed (rps)

• Capacity variation ratio according to temperature

<Cooling>

<Heating>

 

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(%)

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

Indoor : DB27 C/WB19 C

 

 

 

 

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

33

34

35

36

37

38

39

40

41

42

43

Outsoor temp. ( C)

Capacity ratio (%)

120

 

 

 

110

 

 

 

100

 

 

 

90

 

 

 

80

 

 

 

70

 

 

 

60

 

 

 

50

 

 

 

40

 

 

 

30

 

 

 

20

 

 

 

 

• Conditions

 

 

 

 

10

 

Indoor : DB20 C

 

 

Indoor air flow : High

 

 

 

Pipe length : 7.5m

 

0

 

 

 

-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10

 

 

Outsoor temp. ( C)

– 8 –

1-1-4. Flexible Type

Model name

 

 

 

 

 

RAV-SM560XT-E

 

RAV-SM800XT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

Heating

Average

 

Cooling

Heating

Average

Standard capacity (Note 1)

 

(kW)

 

 

 

 

 

 

 

 

 

5.1

 

5.6

 

 

6.7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1.5 – 5.6)

 

(1.5 – 6.3)

 

 

(2.2 – 8.0)

(2.2–9.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating low temp. capacity (Note 1) (kW)

 

 

4.9

 

 

 

5.8

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy consumption effect ratio (Cooling)

 

2.93 [D]

 

3.29 [C]

3.11

 

2.46 [E]

3.00 [D]

3.24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

1 phase 230V (220 – 240V) 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

(A)

8.33–7.63

 

8.138–7.46

 

 

13.15–12.05

12.91–11.84

 

Electrical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

1.74

 

1.7

 

 

2.72

2.67

 

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Low temp.)

 

(kW)

1.95

 

 

2.21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

 

(%)

95

 

95

 

 

94

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

 

Pure white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

 

Ceiling Panel

 

Model

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Sold separately)

 

Panel color

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

 

 

 

298

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

Width

(mm)

 

 

 

998

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

 

Depth

(mm)

 

 

 

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dimension

 

 

 

Height

(mm)

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

(mm)

 

 

 

——

 

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

 

Main unit

 

(kg)

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

 

 

 

 

 

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

Finned tubu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Soundproof/Heat-insulating material

 

 

Inflammable polyethylene foam

 

Foamed polyethylen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Cross flow fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

 

Standard air flow High (Mid./Low)

(m³/h)

 

840

 

 

 

1110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

(W)

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

Attached main unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller (Sold separately)

 

 

 

 

Wired remote controller RBC-AMT21E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

 

(mm)

 

Ø12.7 (1/2”)

 

 

Ø15.9 (5/8”)

 

Connecting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

 

(mm)

 

Ø6.4 (1/4”)

 

 

Ø9.5 (3/8”)

 

pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain port

(Nominal dia.)

 

 

25 (Polyvinyl chloride tube)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound level

High (Mid./Low) (Note 2)

(dB•A)

39

 

36

36

 

45

41

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.

Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

– 9 –

• Operation characteristic curve

<Cooling>

 

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

RAV-SM800XT-E

 

 

 

 

 

 

RAV-SM800XT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

 

 

 

 

 

 

 

(A)

10

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

Current

8

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

RAV-SM560XT-E

 

 

 

 

 

RAV-SM560XT-E

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Indoor : DB27 C/WB19 C

 

 

 

 

 

Indoor : DB20 C

 

 

 

 

 

Outdoor : DB35 C

 

 

2

 

 

Outdoor : DB7 C/WB6 C

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

Pipe length : 7.5m

 

 

 

00

 

 

230V

 

 

 

 

00

 

 

230V

 

 

 

 

15 20

40

60

70

80

100

 

1520

40

60

80

90

100

Compressor speed (rps)

Compressor speed (rps)

• Capacity variation ratio according to temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Cooling>

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

 

 

 

 

 

105

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

110

 

 

 

 

 

 

 

 

 

 

 

 

 

95

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

 

 

 

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(%)

85

 

 

 

 

 

 

(%)

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio

80

 

 

 

 

 

 

ratio

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

• Conditions

 

 

 

20

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

 

 

 

Indoor : DB27 C/WB19 C

 

 

10

 

 

 

 

 

 

Indoor : DB20 C

 

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

50

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

32

33

34 35

36

37 38 39 40 41

42

43

 

-14

-12

-10

-8

-6

-4

-2

0

2

4

6

8

10

Outsoor temp. ( C)

Outsoor temp. ( C)

– 10 –

1-2. Outdoor Unit

Model name

 

 

 

RAV-SM560AT-E

 

 

RAV-SM800AT-E

 

 

 

 

 

 

 

 

Appearance

 

 

 

Silky shade (Muncel 1Y8.5/0.5)

 

 

 

 

 

 

 

 

Power supply

 

 

 

1 phase 230V (220 – 240V) 50Hz

 

 

 

(Power exclusive to outdoor is required.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

Hermetic compressor

 

 

 

 

 

 

 

 

 

Compressor

 

Motor

(kW)

1.1

 

1.6

 

 

 

 

 

 

 

 

 

 

 

Pole

 

 

4 poles

 

 

 

 

 

 

 

 

Refrigerant charged

(kg)

R410A 0.9

 

 

R410A 1.5

 

 

 

 

 

 

 

Refrigerant control

 

Pulse motor valve

 

 

 

 

 

 

 

 

 

 

Standard length

 

20 (without additional charge)

 

 

 

 

 

 

 

 

 

 

 

Max. total length

(m)

30

 

50

 

 

 

 

 

 

 

 

 

Pipe

 

Over 20m

 

Add 20g/m (Max. 200g)

 

 

Add 40g/m (Max. 1200g)

 

 

 

 

 

 

 

 

 

 

 

Height difference

Outdoor lower

(m)

 

30

 

 

 

 

 

 

 

 

 

 

Outdoor higher

(m)

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

595

 

795

Outer

 

 

 

 

 

 

 

 

 

Width

(mm)

780

 

780

dimension

 

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

270

 

270

 

 

 

 

 

 

 

 

 

Total weight

 

 

(kg)

35

 

55

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

Fan unit

 

Standard air flow High

(m³/h)

2400

 

3400

 

 

 

 

 

 

 

 

 

 

 

Motor

(W)

43

 

63

 

 

 

 

 

 

 

 

 

Connecting

 

Gas side

(mm)

Ø12.7 (1/2”)

 

 

Ø15.9 (5/8”)

 

 

 

 

 

 

 

 

pipe

 

Liquid side

(mm)

Ø6.4 (1/4”)

 

 

Ø9.5 (3/8”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge temp. sensor

Protection device

 

Over-current sensor

 

 

 

 

 

Compressor thermo.

 

 

 

 

 

 

 

 

 

Sound level

 

High (Mid./Low)

(dB•A)

46/48

 

45/50

(Note 2)

 

(Cooling/Heating)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping. The reference piping consists of 3 m piping connected with 0 meter height.

Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

– 11 –

Toshiba RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM800BT-E, RAV-SM560BT-E User Manual

2. AIR DUCTING WORK

2-1. Static Pressure Characteristics of Each Model

Fig. 1 RAV-SM560BT-E

External static pressure (mmAq)

External static pressure (mmAq)

12

11

10

9

8

7

6

5

4

3

2

1

0

500

12

11

10

9

8

7

6

5

4

3

2

1

0700

70% (570m³/h) Standard air volume : 840m³/h

110% (925m³/h)

Extra High tap

High tap

Middleoletaptap

Low tap

570 600

700

800

900

925

1000

 

Air volume (m³/hr.)

 

 

 

Fig. 2 RAV-SM800BT-E

70% (800m³/h) Standard air volume : 1140m³/h

110% (1255m³/h)

Extra High tap

 

High tap

Middleoletaptap

Low tap

800

900

1000

1100

1200

1255

1300

 

 

Air volume (m³/hr.)

 

 

 

– 12 –

3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)

3-1. Indoor Unit

4-Way Air Discharge Cassette Type

RAV-SM560UT-E/RAV-SM800UT-E

200

 

860 to 910 Recommended external size

 

 

 

Check port (450)

200

 

Check port

 

 

 

( 450)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

Cable draw-in port

 

30

 

 

 

 

 

 

 

 

 

173

113

 

 

 

105

 

 

Refrigerant pipe

 

 

 

 

connecting port A

 

270

 

 

 

Refrigerant pipe

 

 

 

 

70

250

 

 

 

connecting port B

 

 

 

 

 

130

 

 

 

950 Panel external dimension

 

 

 

 

 

790 Hanging bolt pitch

 

 

 

 

 

346.5

Surface

 

 

Electric

 

 

 

 

parts box

 

 

under ceiling

 

 

 

 

 

dimensionexternal

80

240

105

415.0

 

150

 

 

 

840 Unit

 

 

105

 

 

105

 

 

 

Ø162

254.5

840 Hanging bolt

480

227

 

A

B

120

 

 

SM560

Ø6.4

Ø12.7

97

SM800

Ø9.5

Ø15.9

Surface under ceiling

860 to 910 Recommended external size

 

 

 

 

 

Standing

 

 

850 or less

Surface

 

Standing

under ceiling

640 or less

 

 

130

210 360

 

Surface

 

 

 

under ceiling

 

Indoor unit

Drain up standing size

 

 

 

Hanging bolt M10 or W3/8

Procured locally

 

 

 

 

256

 

 

 

 

 

 

 

88

 

381.6

 

Panelexternal dimension

 

 

 

Knockout

Hangingbolt pitch

 

227

 

for

 

 

humidifier

480

 

Ceiling

 

723

950

 

 

 

 

 

 

 

panel

 

 

 

 

 

 

 

 

 

 

 

 

(Sold

35

 

 

 

 

separately)

 

 

 

 

120

97

Surface

 

 

 

 

under ceiling

 

 

 

 

 

 

 

 

 

 

 

35

 

 

 

57

 

64

 

 

 

5

 

 

 

 

 

 

.

 

 

 

 

 

57

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Z view

 

188

 

 

 

 

Surface under ceiling

– 13 –

Concealed Duct Type

RAV-SM560BT-E

2-Ø200

750

± 7.5 Hanging bolt pitch

 

170

700

Dimension of main unit

 

Discharge port flange

 

 

 

 

 

 

 

 

20

 

 

120

 

 

 

 

 

4-M10

 

 

 

Drain up kit

Hanging bolt

280

252

70

(Sold separately)

(Procured locally)

 

 

 

 

150

 

 

 

to457637

160~640

 

 

60

 

 

 

 

For hanging bolt M10

 

 

80

 

 

 

 

 

(4-12 x 25 long hole)

 

 

 

 

5

 

 

 

 

 

730

 

 

 

 

780 Ceiling opening size

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

800 Dimension of main unit

 

 

 

 

 

 

 

 

 

 

 

 

Drain pipe connecting port

 

25

 

 

 

 

 

 

 

 

565 Hanging bolt pitch

210

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at drain up kit side

 

 

720

 

 

 

 

(For polyvinyl chloride pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Inner dia. 32, Nominal dia. 25))

 

 

240

 

 

 

314.5

 

 

 

 

 

 

 

 

 

 

 

 

211

 

 

 

 

 

509

Refrigerant pipe

 

 

630

 

Ø125 knockout hole (Only rear side)

connecting port

 

 

 

 

(For air suction)

(Gas side Ø12.7)

 

45

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130

80

 

6-Ø4 tapping screw lower hole Ø160

 

25

 

35

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

305

90 120

 

 

 

100

170

210

320

 

 

 

 

 

 

 

70

 

Refrigerant pipe

 

80

 

 

 

 

 

30

connecting port

 

170

 

 

 

 

 

 

(Liquid side Ø6.4)

 

 

 

 

Suction port canvas

 

 

 

335

 

 

 

Drain pipe connecting port

Panel

 

 

 

 

at main unit side

 

to

 

Suction panel

(For polyvinyl chloride pipe

155

 

 

(Inner dia. 32, Nominal dia. 25))

450

 

 

 

 

 

 

 

 

 

 

 

 

2-Ø26 power supply remote

470 Ceiling opening size

 

 

 

 

 

 

 

 

 

 

controller cord draw-out port

 

 

 

 

 

 

Check port A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Plane view of main unit

450

 

 

 

 

 

NOTE 1 :

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

For maintenance of the equipment, be sure to install

 

 

 

 

(Pipe side)

 

 

 

 

 

 

 

 

a check port A at the position as shown below.

 

 

 

 

 

 

 

 

NOTE 2 :

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using the drain up kit sold separately, drain-up by 300 (mm)

 

 

 

 

 

 

 

from drain pipe draw-out port of the main unit is necessary.

 

 

 

 

 

 

 

The drain-up over 300mm or more is impossible.

 

 

Discharge side

 

 

– 14 –

RAV-SM800BT-E

 

 

 

 

 

2-Ø200

1050 ± 7.5 Hanging bolt pitch

 

 

 

1000 Dimension of main unit

 

170

 

Discharge port flange

 

 

 

 

 

 

 

4-M10

 

 

20

120

Drain up kit

Hanging bolt

 

 

 

 

(Sold separately)

(Procured locally)

290

290

252

 

70

 

 

150

 

 

 

 

457to 637

460~640

 

 

 

 

 

 

 

 

 

60

For hanging bolt M10

 

 

 

 

80

 

 

 

 

 

(4-12 x 25 long hole)

 

 

 

 

 

5

 

 

 

 

 

 

 

1030

 

 

 

 

1050 Ceiling opening size

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

800 Dimension of main unit

 

 

 

 

 

 

 

 

 

 

 

 

Drain pipe connecting port

 

25

 

 

 

 

 

 

 

 

565 Hanging bolt pitch

210

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at drain up kit side

 

 

720

 

 

 

(For polyvinyl chloride pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Inner dia. 32, Nominal dia. 25))

 

 

 

240

 

 

314.5

 

 

 

 

 

 

 

 

211

 

 

509

 

 

 

 

Refrigerant pipe

 

 

 

630

 

Ø125 knockout hole (Only rear side)

connecting port

 

 

 

 

 

(For air suction)

(Gas side Ø12.7)

 

 

45

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130

80

 

6-Ø4 tapping screw lower hole Ø160

 

25

 

 

35

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

305

90 120

 

 

 

 

100

170

210

320

 

 

 

 

 

 

 

 

70

 

Refrigerant pipe

80

 

 

 

 

 

 

30

connecting port

170

 

 

 

 

 

 

 

(Liquid side Ø6.4)

 

 

 

 

 

Suction port canvas

 

 

 

 

 

 

 

 

Drain pipe connecting port

335

 

Panel

 

 

 

 

at main unit side

 

to

 

 

Suction panel

(For polyvinyl chloride pipe

 

 

 

155

 

 

 

(Inner dia. 32, Nominal dia. 25))

 

450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-Ø26 power supply remote

470 Ceiling opening size

 

 

 

 

 

 

 

 

 

 

 

controller cord draw-out port

 

 

 

 

 

Check port A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Plane view of main unit

450

 

 

 

 

 

 

NOTE 1 :

150

 

 

 

 

 

 

For maintenance of the equipment, be sure to install

 

 

 

(Pipe side)

 

 

 

 

 

a check port A at the position as shown below.

 

 

 

 

 

 

NOTE 2 :

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using the drain up kit sold separately, drain-up by 300 (mm)

 

 

 

 

 

 

from drain pipe draw-out port of the main unit is necessary.

 

 

 

 

 

 

The drain-up over 300mm or more is impossible.

 

Discharge side

– 15 –

High-Wall Type

RAV-SM560KRT-E/RAV-SM800KRT-E

7 75

 

298

 

51

Pipe port from left

Discharge port

 

 

 

(Knockout hole)

 

Z views

998

Suction port

Pipe port from lower side 75 56 (Knockout hole)

50

Pipe port from right (Knockout hole)

50

Z

8 75

110

390

Drain hose

Refrigerant pipe connecting port B

 

490

 

540

 

 

 

Refrigerant pipe connecting port A

 

 

 

998

 

 

 

 

 

 

 

763.5

 

 

 

 

 

20

48

450

20

29 48

 

 

 

10

41

 

 

 

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

 

55 55

298

40

 

 

 

 

40

 

 

115

100

 

 

100

115

 

 

Position of installation plate

 

A

B

 

more

 

Liquid Side

Gas Side

 

55 or

SM560

Ø6.4

Ø12.7

 

 

 

 

 

 

53 or more

53 or more

SM800

Ø9.5

Ø15.9

Space required for service

– 16 –

Under Ceiling/Console Type

RAV-SM560XT-E/RAV-SM800XT-E

Front panel

1093

208

 

 

 

633

Knock out system

Grille air inlet

Back body

For stud bolt

200 Min

1093

(Ø8 – Ø10)

 

1015

For stud bolt (Ø6)

 

742

 

450

 

 

 

20

20

330

 

165

74

Ø

 

UNDER CEILING & CONSOLE INSTALLATION

Installation plate

Mount plate

M10 Suspention bolt

633

 

 

460

 

 

 

 

160

Min

57

18

70

Wireless remote control

 

Knock out system

– 17 –

3-2. Outdoor Unit

RAV-SM560AT-E

Drain hole (Ø25)

Drain hole (2-Ø20 x 88 long hole)

 

 

83

600

97

 

 

 

 

 

A legs

 

115.3

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

 

 

 

308

pitchhole(Long bolt)anchorFor

302

pitchholeØ6

153

150

11

 

76

 

 

30

 

330

 

 

30

 

 

 

 

270

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B legs

21

780

 

 

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49.5

147

 

 

 

 

(49.3)

 

 

115.3

 

Discharge guide mounting hole

 

216

21

 

 

 

 

 

Discharge guard

 

 

(4-Ø4 embossing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

Valve cover

 

 

 

 

 

 

center dividing)

 

 

 

 

 

 

 

 

 

521

 

 

 

593 598

 

 

 

 

 

31

 

 

 

 

 

 

 

 

 

 

(Fan

 

 

 

 

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth

 

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

terminal

 

 

 

 

 

 

 

 

 

 

 

 

132

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90.6

 

 

 

25

220

 

 

 

 

 

 

500 (Fan center dividing)

Charge port

31

134

Protective net mounting hole (2-Ø4 embossing)

43

707

Protective net mounting hole

 

(4-Ø4 embossing)

 

30

60

475

Refrigerant pipe connecting port

(Ø12.7 flare at gas side) Refrigerant pipe connecting port (Ø6.4 flare at liquid side)

Space required for service

 

 

600

 

 

52

 

 

36

11

R15

2-Ø6 hole

308

302

Product

external line

 

 

 

Ø11 x 14 U-shape hole

Details of A legs

 

Ø11 x 14 U-

 

2-Ø11 x 14 U-shape holes

 

 

shape holes 2-Ø6 hole

 

 

(For Ø8–Ø10 anchor bolt)

more

308 302

Product

 

 

external

 

 

150 or

 

 

line

 

 

 

11

 

R15

365

150

 

36

or more

 

 

 

 

 

 

 

 

 

52

 

 

 

 

 

 

600

 

 

 

Details of B legs

 

 

500

 

 

 

or more

600

Suction port

 

 

300

 

or more

Discharge

(Minimum

port

distance up to wall)

Discharge

2-Ø11 x 14 long hole

port

(For Ø8–Ø10 anchor bolt)

 

– 18 –

RAV-SM800AT-E

Knockout

(For draining) Drain hole (Ø20 x 88 burring hole)

17.5

 

 

21

 

 

 

 

 

 

 

pitch bolt) 70

365

(Long hole for anchor 40

29

90

191

20 Drain hole (Ø25 burring hole)

 

 

Suction

Part B

 

 

port

 

 

 

43

40

Suction

Knockout

port

(For draining)

 

17.5

Installation bolt hole (Ø12 x 17 U-shape holes)

40

Details of B part

Details of A part

17.5

21

26

60

Discharge

 

 

port

Part A

 

 

150

300

95

 

 

 

 

900

 

 

 

 

 

 

314

 

 

 

101

 

 

 

 

 

 

565

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

Discharge guide

 

 

 

 

 

 

 

Z

 

 

 

300

 

 

 

 

 

 

 

96

 

mounting hole

 

 

307

 

(4-Ø4 embossing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43

39 47

 

40

 

17.5

 

 

 

Installation bolt hole

 

 

 

 

 

 

(Ø12 x 17 U-shape holes)

Handles (Both sides)

Refrigerant pipe connecting port (Ø9.5 flare at liquid side)

Refrigerant pipe connecting port (Ø15.9 flare at gas side)

2

60 67

 

 

154

 

264

 

 

 

 

 

 

 

 

 

 

 

 

27

 

 

1

 

 

Knockout for lower piping

28 320

Z views

86

7

 

7

 

58

 

 

 

 

 

 

 

Space required for service

 

 

 

795

 

 

 

2-Ø12 x 17 U-shape holes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(For Ø8–Ø10 anchor bolt)

 

 

 

 

 

2

46

 

more

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

150 or

9060

 

25

85

165

8060

 

365

150

 

 

 

 

 

 

 

 

or more

27

58

2

 

 

1 30

 

45

500

 

161

 

 

 

 

 

 

 

400

 

 

 

 

 

or more

600

Suction port

 

 

150

 

or more

Discharge

(Minimum

port

distance up to wall)

Discharge

2-Ø12 x 17 long hole

port

(For Ø8–Ø10 anchor bolt)

 

– 19 –

4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM

Indoor Unit/Outdoor Unit

RAV-SM560UT-E, RAV-SM560BT-E, RAV-SM560KRT-E/RAV-SM560AT-E

Indoor unit

TCJ sensor

Air heat exchanger

TC sensor

Outer diameter of refrigerant pipe

Gas side ØA Liquid side ØB

12.7mm 6.4mm

TS sensor

TD sensor

4-way valve (VT7101D)

Muffler

Ø19 × L160

Rotary compressor (DA130A1F-23F)

Refrigerant pipe

Refrigerant pipe

at liquid side

at gas side

Outer dia. ØB

Outer dia. ØA

Max 30m

Packed valve

 

Packed valve

Outer dia. ØB

Outdoor unit

Outer dia. ØA

 

 

 

 

PMV

 

 

(SKV-18D26)

TO sensor

 

 

 

 

Strainer

 

TE

 

 

sensor

 

Heat exchanger Ø8 multiple thread

ripple 1 row 22 stages FP1.3 flat fin

Distributor

R410A 0.9 kg

Cooling

Heating

 

 

 

Pressure

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor heat

Outdoor heat

Indoor

temp. conditions

 

 

(MPa)

(kg/cm²G)

 

 

revolutions per

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

 

 

 

 

 

 

exchanger

exchanger

second (rps)

fan

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

Standard

3.1

0.9

31.9

8.9

85

15

10

50

74

HIGH

27/19

35/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.6

1.0

37.1

10.4

93

20

15

57

72

HIGH

32/24

43/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

0.9

0.7

9.1

7.1

20

7

3

5

28

LOW

18/15.5

–5/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.3

0.6

23.6

6.2

71

1

39

3

84

HIGH

20/–

7/6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.3

1.2

33.2

11.8

78

20

54

19

47

LOW

30.–

24/18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.7

0.2

16.4

1.8

110

–20

26

–22

110

HIGH

15/–

–20/(70%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

20 –

Indoor Unit/Outdoor Unit

RAV-SM800UT-E, RAV-SM800BT-E, RAV-SM800KRT-E/RAV-SM800AT-E

Indoor unit

TCJ sensor

Air heat exchanger

TC sensor

Outer diameter of refrigerant pipe

Gas side ØA Liquid side ØB

15.9mm 9.5mm

 

Refrigerant pipe

 

Refrigerant pipe

 

 

at liquid side

 

at gas side

 

 

Outer dia. ØB

 

Outer dia. ØA

 

 

 

 

 

Max

 

 

 

 

50m

Pd

Packed valve

 

Packed valve

Ps

 

Outer dia. ØB

Outdoor unit

Outer dia. ØA

 

 

 

 

 

TS sensor

Strainer

 

Modulating (PMV)

 

 

(SKV-18D26)

 

 

 

 

 

 

TO sensor

 

 

 

TD sensor

Strainer

4-way valve

Accumulator

Muffler (STF-0213Z)

(1500cc)

Ø25 × L210

 

 

Ø25 × L160

 

Rotary compressor

 

(DA220A2F-20L)

TE sensor

Heat exchangerØ8 1 row 30 stages FP1.3 flat fin

Capillary Ø3×Ø2× L530

R410A 1.5 kg

Cooling

Heating

 

 

 

Pressure

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor heat Outdoor heat

Indoor

temp. conditions

 

 

(MPa)

(kg/cm²G)

 

 

revolutions per

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

 

 

 

 

 

 

exchanger

exchanger

second (rps)

fan

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

Standard

3.3

0.9

33.4

8.8

86

11

9

44

64

HIGH

27/19

35/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.7

1.1

37.8

11.4

90

21

18

54

52

HIGH

32/24

43/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.0

0.8

10.0

7.9

19

4

4

8

27

LOW

18/15.5

–5/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.5

0.6

25.8

6.3

67

6

42

2

65

HIGH

20/–

7/6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.4

1.1

34.7

11.5

85

23

55

16

31

LOW

30.–

24/18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

2.0

0.2

20.3

2.3

89

–16

34

–18

90

HIGH

15/–

–20/(70%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

21 –

5. WIRING DIAGRAM

5-1. Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-Way Air Discharge Cassette Type

 

 

 

 

 

 

 

 

 

 

 

 

RAV-SM560UT-E/RAV-SM800UT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TA

TCJ

 

TC

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2

1 2

1

2

 

 

 

 

(EXCT)

 

 

 

 

 

 

 

CN34

1 2

1 2

1

2

 

1 2 3

1 2

12

 

 

 

 

 

FS

CN104

CN102

 

CN101

 

CN80

CN73

CN70

 

 

 

 

 

(RED)

 

 

 

 

 

 

 

 

3 3

(YEL)

(RED)

 

(BLK)

 

(GRN)

(RED)

(WHI)

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 2

 

 

 

 

 

 

 

 

 

 

4

CN620

 

 

 

1 1

 

MCC-1402

 

 

 

 

3

 

 

5 5

 

 

 

 

 

 

2

(BLU)

 

LM1

4 4

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

3 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 2

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

1 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN33

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

Control P.C. Board for

 

 

CN60

 

 

 

 

 

4

 

 

 

(WHI)

 

 

 

 

5 5

5 5

 

 

3

(WHI)

 

 

 

Indoor Unit

 

 

 

2

 

 

 

 

4 4

4 4

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

3 3

3 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 2

2 2

 

 

 

 

 

 

 

 

 

 

2

CN32

 

 

1 1

1 1

 

 

 

 

 

 

DC20V

 

 

 

 

 

 

 

 

 

 

 

 

 

DC15V

 

 

 

1

(WHI)

 

 

 

 

 

 

 

 

 

 

DC12V

 

 

 

(FAN DRIVE)

 

 

 

 

 

 

 

 

 

 

DC7V

 

 

 

6

 

 

 

 

5 5

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

LM2

4 4

 

 

 

 

 

supply

 

 

 

 

4

CN61

 

3 3

 

 

 

 

 

circuit

 

 

 

 

3

(YEL)

 

 

2 2

 

 

 

 

Fuse

 

 

 

 

 

 

2

 

 

 

 

1 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F302

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T3.15A

 

 

 

 

 

 

 

 

 

 

 

CN333

 

 

 

250V~

 

 

 

 

 

 

5

 

 

 

 

 

(WHI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

5 5

 

 

 

 

 

 

 

 

 

 

CN50

 

 

 

4 4

 

Motor

 

 

 

 

 

 

 

 

3

(WHI)

 

 

 

3 3

 

drive

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

2 2

 

circuit

 

 

 

 

 

 

 

 

 

 

 

FM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

CN334

 

 

 

 

drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

circuit

 

 

 

 

3

 

 

 

 

 

(WHI)

 

 

 

 

 

 

 

 

CN309(YEL)

 

 

 

1 1

 

 

 

 

 

 

 

 

 

 

2

 

 

 

2 2

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

3 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 4

 

 

 

 

 

 

 

 

 

 

 

3 BLK

B

 

 

5 5

 

 

 

Fuse

 

 

 

 

 

 

3

 

 

 

RY

RY

 

 

 

 

 

 

 

2

2

BLK

 

 

 

 

302

303

 

F301

 

 

 

 

 

 

1

1

A

 

 

 

 

250V~

 

 

P301

 

 

 

 

 

 

 

 

 

T6.3A

 

 

 

 

 

CN41

 

 

 

CN68

1 2 3

1 2 3

 

CN67

1 2 3 4 5

BLK

1 2

 

(BLU)

 

 

 

 

 

 

 

 

 

 

 

(BLU)

1 2 3

CN304

 

(BLK)

1 2 3 4 5

 

CN66

 

 

 

 

 

 

 

 

 

(GRY)

 

 

 

 

 

 

(WHI)

 

 

 

 

 

 

 

 

 

 

 

RED WHI BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

Closed-end

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DP

 

 

 

 

 

 

 

connector

 

 

 

 

 

 

 

 

 

 

 

 

WHI

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

NOTE

 

 

 

earth screw

 

 

 

 

 

FM

: Fan motor

1

2

3

 

TA

: Indoor temp. sensor

 

 

 

 

Outdoor unit

TC

: Temp. sensor

 

 

 

L

N

signalSerial

earth screw

TCJ

: Temp. sensor

 

Single phase

 

LM1,LM2

: Louver motor

 

220 to 240V

 

DP : Drain pump motor

50Hz

 

 

 

 

 

 

 

FS : Float switch

 

 

 

 

RY302 : Drain control relay

 

 

 

 

BLK

2 2 CN001

1 1 (WHI)

WHI

Adapter for Wireless Remote Controller

BLK

 

2 2

CN1

1 1 (WHI)

WHI

 

Wired Renote

Controller

Color

Identification

BLK : BLACK BLU : BLUE RED : RED GRY : GRAY PNK : PINK GRN : GREEN WHI : WHITE BRW : BROWN ORN : ORANGE YEL : YELLOW

– 22 –

Concealed Duct Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAV-SM560BT-E/RAV-SM800BT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TA

TCJ

TC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2

1 2

 

1 2

PNL

EXCT

1 2

 

 

 

 

 

 

 

 

 

 

 

1 2

1 2

 

1 2

1 2 3

1 2

1 2

 

 

 

 

 

 

 

 

 

FS

CN104 CN102 CN101

CN080

CN073 CN070

 

6

 

 

 

 

 

 

 

CN030

(YEL) (RED)

(BLK)

(GRN)

(RED)

(WHI)

 

5

 

 

 

 

 

 

 

(RED)

 

 

 

 

 

 

CN060

4

OPTION

 

 

 

 

 

 

3 3

 

 

 

 

 

 

(WHI)

3

 

 

 

 

 

 

 

 

2 2

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

1 1

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

LM

 

 

 

 

 

 

CN032

2

FAN

 

 

 

 

 

 

 

 

 

 

 

(WHI)

1

DRIVE

 

 

 

 

 

CN033

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(GRN)

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

CN061

4

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

(YEL)

3

 

 

 

 

 

 

 

CN068

 

RY001

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

(BLU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DP

 

 

3 3

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

2 2

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

1 1

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

RY002

 

 

 

 

 

 

CN074

 

 

 

1 1

1 1

YEL 1 1

UL

 

 

 

 

 

 

 

(WHI)

TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

6

 

 

 

RED

2 2

2 2

BLU

2 2

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

5

5

 

 

 

3 3

3 3

3 3

 

 

 

RY005

 

 

 

 

FM

YEL

4 4

4 4

 

4 4

M

 

 

 

 

supply

 

4

4

 

 

BLU

5 5

5 5

 

5 5

 

 

RY006

 

 

circuit

 

3

3

 

 

 

OPN

 

 

 

 

 

 

 

 

 

2

2

 

 

 

BLK

6 6

6 6

ORN

6 6

H

 

 

 

 

 

 

 

1

1

 

 

 

 

7 7

7 7

BLK

7 7

 

 

 

 

 

 

 

 

CN075

 

 

RC

BRW

8 8

 

 

8 8

 

 

 

 

 

 

 

 

(WHI)

 

 

 

9 9

 

RED 9 9

RY007

 

 

 

 

 

 

6

 

 

 

 

 

 

 

CN083

 

 

 

 

 

 

 

 

 

 

 

 

 

(WHI)

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

1 1

1 1

 

1

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

2 2

2 2

 

2

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

CN050

 

 

3 3

3 3

 

3

 

 

 

 

 

 

 

 

 

FM

YEL

4 4

4 4

 

4

 

RY

 

 

 

Fuse

 

 

(WHI)

 

 

BLU

 

 

 

 

 

 

 

 

 

 

OPN

5 5

5 5

 

5

 

004

 

 

 

F001

 

 

3

3

B

2 2

 

6 6

6 6

 

6

 

 

 

 

 

T5A

 

 

 

BLK

7 7

7 7

 

7

 

 

 

 

 

250V~

 

 

2

2

A

1 1 CN1

 

BRW

8 8

 

 

8

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

CN041

 

 

9 9

 

 

9

 

 

 

 

 

 

 

 

Remote

 

 

 

 

 

 

 

1 2 3

 

1 2 3

 

1 2 3 4 5

1 2

(BLU)

 

 

 

 

 

 

 

 

 

Controller

 

(When selecting

 

 

 

 

CN304

 

CN309

1 2 3 4 5 CN067 CN066

 

 

 

 

 

 

 

 

(GRY)

 

(YEL)

 

 

(BLK)

(WHI)

 

 

 

 

high-static pressure)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED WHI BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

Closed-end

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

earth screw

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FM : Fan motor

 

1

2

3

 

 

 

Color

 

 

 

 

 

 

 

RC : Runing capacitor

 

 

 

Identification

 

 

 

 

 

TR : Transformer

 

 

 

 

 

 

 

 

BLK

: BLACK

LM : Louver motor

 

L

N

 

 

 

BLU

: BLUE

TA : Indoor temp. sensor

 

 

 

 

 

 

 

 

RED : RED

Outdoor unit

 

 

 

 

 

GRY : GRAY

TC, TCJ : Indoor heat exchanger sensor

earth screw

 

 

 

 

 

PNK

: PINK

RY001 : Louver control relay

 

 

 

 

 

 

 

 

GRN : GREEN

 

 

 

 

 

 

 

 

WHI : WHITE

RY002 : Drain control relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRW : BROWN

RY005~007 : Air volume control relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORN : ORANGE

DP : Drain pump motor

 

 

 

 

 

 

 

 

YEL

: YELLOW

– 23 –

High-Wall Type

RAV-SM560KRT-E/RAV-SM800KRT-E

 

 

 

 

 

SUB-CONTROL P.C. BOARD

 

CN12

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

2 1

 

TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2 CN63 6

5

4

3

2

1 CN62

CN16 1

2

3

 

 

 

 

 

 

 

 

 

 

CN

1 2

WHI 6 5 4 3 2 1

WHI

BLU

1 2 3

GRN&YEL

 

 

 

 

 

 

 

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Controller

 

BLK

1 2

CN64 6 5 4 3 2 1 CN61

 

 

 

 

 

RED

1

 

P03

P02

 

 

 

F201

CN230

 

 

 

 

 

(Option)

 

 

 

 

 

1 2

 

6 5 4 3 2 1

WHI

 

 

 

T3,15A

 

WHI

2

 

 

ORG

 

 

 

 

 

 

 

 

A

A

 

1 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250V~

CN231

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

B

YEL

 

2 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

3

C

C

BLU

 

3 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN223

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN11

 

 

 

 

 

 

WHI

 

1 1

1 1

 

 

 

MCC-1370A

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

 

Central Centroller

 

 

 

2

2

2

2

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

3 3

3 3

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection (Option)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

1 1

 

 

 

4

4

4

4

 

 

 

 

 

 

 

 

 

 

 

CN207

 

 

 

 

 

 

5

5

5

5

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

2 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

 

 

 

 

 

 

6

6

6

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN01

 

AI-NET

 

 

 

 

 

 

 

 

 

 

 

 

6

6

BLU

 

 

 

 

 

 

7 7

7 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

PNK

 

 

 

 

 

P.C. BOARD

8

8

8

8

 

 

 

 

 

 

 

 

 

 

 

5

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

4

YEL

 

 

 

 

 

9

9

9

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCC-1337

 

 

 

 

 

 

 

 

 

 

 

3

3

OPG

 

 

 

 

 

10 10

10 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 11

11 11

 

 

 

 

 

 

 

 

 

 

 

2

2

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

BRN

 

 

 

 

 

 

 

 

12 12

12 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13 13

13 13

 

 

 

 

 

 

 

 

 

 

 

6

6

BLU

 

 

 

 

 

 

 

 

14 14

14 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

5

YEL

 

 

 

 

 

 

 

 

15 15

15 15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

4

WHI

 

 

 

 

 

 

 

 

16 16

16 16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

BLK

 

 

 

 

 

 

 

 

CN02

CN31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

WHI

WHI

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

BLU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

1 1

1 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN210

 

 

 

Receiver

2 2

BLU

2 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

 

 

 

3 3

BLU

3 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

5 5

BLU

5 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 4

BLU

4 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Infra-Red

6 6

BLU

6 6

 

Control P.C. Board for

2

CN14

 

 

 

8 8

BLU

8 8

 

4

 

 

 

 

7 7

BLU

7 7

 

3

 

 

 

 

 

 

9 9

BLU

9 9

 

 

 

 

 

Indoor Unit

 

 

 

5

WHI

 

 

 

 

10 10

WHI

10 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

CN25

 

CN213

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

WHI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

Outdoor unit

(1 Phase model)

Earth

Screw

1 F2 L Power Supply

2N 220/240 50Hz

3Serial Signal

LM

FM

2 1

 

 

2 1

 

 

2 1

6 5 4 3 2 1

2

1 CN04

2

1 CN05

2

1 CN20

CN13

BLK BLK

WHI

BLK BLK

WHI

BLK BLK

YEL

WHI

 

 

 

 

2

1

4

3

2

1

2

1 CN50

CN06

 

GRY PNK

WHI

WHI

 

 

 

 

 

2 1

CN21 WHI

TA

NOTE

F : Fuse (PCB) FM : Fan motor LM : Louver motor

TA : Temperature sensor TC : Temperature sensor TCJ : Temperature sensor TR : Transformer

O/D : Outdoor

R/C : Remote Contoller

TC TCJ

 

 

LED Detall

D05

Orange

O/D Serial Signal Input

D02

Green

O/D Serial Signal Output

D13

Orange

R/C Serial Signal Input

D11

Green

R/C Serial Signal Output

Chack Code

Diagnosis

04

Serial Signal Error

08

4-Way Valve Error

09

I/D Heart Exchange Error

0C

TA Sensor Error

0d

TC Sensor Error

0F

TCJ Sensor Error

11

Indoor Fan Error

12

Indoor unit Error

97

LAN Comms Circuit Error

98

LAN Adress Setting

99

R/C Mis-Wiring

– 24 –

RAV-SM560XT-E/RAV-SM800XT-E

 

HEAT

 

SWITCH PCB

EXCHANGER

 

MCC-1428B

SENSOR

 

(TCJ)

 

 

 

CN101 1 2 3

FOR FLOAT SWITCH

1 2

 

WHI GRY GRY

(OPTION)

When you use float

1 2

 

switch you should cut J401

 

 

 

 

 

 

 

1 2 3

CN402

 

 

 

 

 

 

 

 

 

 

 

RECEIVERAYSINFRARED PARTSINDICATIONAND

 

 

 

 

CN100 1 2 3

1 2

 

CN05

1 2

CN03

BLK

 

THERMO

 

 

WHI

 

 

 

 

 

 

 

 

 

J401

 

 

2

2

 

SENSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 10

10 10

 

 

 

 

 

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

(TA)

 

 

9 9

BLU

9

9

4

 

 

POWER

 

 

DC12V

 

 

1

1

BLK

 

 

 

 

8 8

BLU

8

8

 

 

SUPPLY

 

 

DC5V

IC03

 

2 2

 

HEAT

 

 

7 7

BLU

7

7

 

 

 

CIRCUIT

 

 

 

 

 

 

1

1

BLK

 

EXCHANGER

 

2

6 6

BLU

6

6

 

 

C02

 

 

 

 

 

 

 

CN01

 

 

SENSOR

 

5 5

BLU

5

5

 

 

 

 

 

 

 

 

R506

 

 

 

 

(TC)

 

 

4 4

BLU

4

4

 

 

DB01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 3

BLU

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 2

BLU

2

2

 

 

 

 

 

 

 

CR502

 

 

1 1

 

 

 

 

 

1 1

BLU

1

1

 

 

R01

 

 

 

 

 

 

CR501

WHI 1 1 WHI

 

 

CN25

 

CN13

 

 

 

C01

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

 

2 2

 

 

 

 

BRW

1

1

5

 

 

 

 

 

 

RY501

 

 

4

4

RED

3 3

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

5

5

 

4 4

 

 

 

 

RED

2

2

 

 

 

 

 

 

 

 

 

C501

CN10

BLK

5 5

BLK

 

 

 

ORN

3

3

 

 

 

 

 

 

 

MCC-1428A

 

 

 

 

 

6 6

 

 

 

 

YEL

4

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNK

5

5

 

 

 

 

 

 

 

 

 

 

 

3

3

BRW

3 3

BLU

 

 

 

BLU

6

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN07

IC04

 

C15

 

 

 

 

R405

CR401

2

2

GRY

2 2

PUR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1

YEL

1 1

GRY

FAN-MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN11

 

 

 

LOUVER

 

 

 

 

 

 

 

 

 

 

 

RY401

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100”C

 

MOTOR

 

 

 

 

R507

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R09

 

 

R21

 

 

 

 

 

 

 

23

FOR DRAIN PUMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

(OPTION)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R22

 

FUSE

 

 

 

 

 

 

 

 

CN401

 

 

 

 

 

 

 

 

250VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SG01

 

F01

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T6.3A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

P04

 

CN30

 

 

CN31

CN23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

WHI

RED

INDOOR

 

GRN&YEL

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

 

 

 

 

 

 

1 2 3

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOCK

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS

Check items

Diagnosis result

 

 

 

1

OPERATION

Check to see if OPERATION indicator goes on and off when the main switch

indicator

or breaker is turned on.

 

 

 

 

 

 

 

2

Terminal

Check the power supply voltage between

1

- 2 (Refer to the name plate.)

block

Chack the fluctuate voltage between 2 -

3

(DC15 to 60V)

 

 

 

3

Fuse

Check to see if the fuse blows out. (Check the varistor. : R22, R21)

6.3A

 

 

 

 

 

 

4

DC 5V

Check the voltage at the No.8 pin on CN13 connector of the infrared receiver.

(Check the transformer and the power supply circuit of the rated voltage.)

 

 

 

5

DC 12V

Check the voltage at the brown lead of the louver motor.

(Check the transformer and the power supply circuit of the rated voltage.)

 

 

 

 

 

Color

Identification

BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE

GRN&YEL : GREEN& YELLOW

GRN : GREEN

PUR : PURPLE

– 25 –

5-2. Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAV-SM560AT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q200

 

 

 

 

 

 

 

 

DB01

 

 

 

REACTOR

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONVERTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGBT MODULE

 

 

 

 

 

 

 

 

 

FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

BZ BY BX EW BW EV BV EU BU

BRW

 

 

 

 

ORN

2

1

2

1 CN500

 

 

 

 

 

 

 

 

+ ~

 

 

 

 

 

2

1

 

 

 

 

 

 

 

 

~ A E G

P10

P09

2

1

 

 

TE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P17 P18

 

 

 

 

 

 

 

P20

P19

 

 

 

 

P08

P07

CN600

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

TD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRONIC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CT

 

 

 

CN601 2

2

 

 

 

P23

P22

P21

 

 

 

 

 

 

 

 

STARTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

WHI

RED

 

 

 

 

 

 

 

 

 

 

 

RELAY

 

 

 

 

 

1

1

TO

 

 

P.C. BOARD

 

 

 

 

 

 

 

 

 

 

 

CN602

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

4

3

2

1

 

(MCC-813)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS

3

2

1

 

 

 

 

 

 

 

 

 

+

C12

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

CN603 2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

C13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

CM

 

 

 

 

 

 

 

 

 

+

C14

 

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

Q300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN701 2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COIL FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P06

 

BLK

4-WAY VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F04

 

 

 

 

 

 

SURGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

2

 

 

 

 

ABSORBER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T3. 15A

 

 

 

 

 

 

1

1

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250V~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VARISTOR

 

2

2

YEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

4

ORN PMV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

 

 

2

 

5

5

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T25A

F01

 

6

6

GRY

PULSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250V~

 

 

 

 

CN703

MODULATING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P14

P13

 

 

P02

P03 P01

 

 

 

 

 

 

 

 

 

 

 

CN301 5

4

3

2

1

3

2

1

CN300

P12

P11

WHI

ORN BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

5

4

3

2

1

3

2

1

 

 

2

1

 

 

 

 

 

TERMINAL OF COMPRESSOR

 

 

 

 

 

 

PUR

 

 

 

 

 

 

 

 

 

 

 

 

GRY PNK

 

YEL

BLK WHI RED

 

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE (S)

 

BLACK (C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FM

 

 

 

 

 

1

2 3 L N

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REACTOR

 

 

 

 

 

 

 

 

 

 

 

RED (R)

FAN MOTOR

TO

POWER

The sign in ( ) is displayed

 

INDOOR

SUPPLY

 

in the terminalcover

 

UNIT

220 to 240

 

 

 

 

50Hz

 

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS

Check

Diagnosis result

items

 

 

 

1

TERMINAL BLOCK

 

 

There is no supply voltage

 

Power supply and connecting

(AC220 to 240V) between L - N , 1 - 2

 

cable check

 

There is no voltage (DC15 to 25V) 2 - 3

 

 

 

 

 

 

 

FUSE

 

 

2

T25A 250V to fuse (F01) blown

 

Converter module (DB01) and

 

 

electrolytic capacitor (C12 to C14) check

T3.15A 250V to fuse (F04) blown

 

IGBT module (Q200) check

 

 

 

Fan motor check

 

 

 

3

ELECTROLYTIC CAPACITOR VOLTAGE (C12, C13, C14)

DC320V not available between

 

T25A fuse (F01) check

+ – terminal of electrolytic capacitor

 

P.C. board and converter

 

 

 

 

module (DB01) check

 

 

 

 

INVERTER OUTPUT (Inverter and compressor connector out of position)

4

(Please confirm within six minutes after instructing in the drive.)

Voltage between each line of inverter side

 

IGBT module and

 

conector pins are not equal.

 

P.C. board check

 

 

 

 

Color Identification

BLK : BLACK

WHI : WHITE

BLU : BLUE

BRW : BROWN

RED : RED

ORN : ORANGE

GRY : GRAY

YEL : YELLOW

PNK : PINK

PUR : PURPLE

GRN : GREEN

 

 

 

NOTE

 

 

 

 

CM

: Compressor

PMV

: Pulse modulating valve

FM

: Fan motor

TE

: Heat exchanger Temp. Sensor

TD

: Discharge Temp. Sensor

TO

: Outdoor Temp. Sensor

TS

: Suction Temp. Sensor

IGBT

: Insulated Gate Bipolar Transistor

DB01

: Converter module

CT

: Curreut Transformer

Q300

: Fan motor driver module

 

 

 

 

– 26 –

RAV-SM800AT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T03

+

 

 

 

 

 

 

 

 

 

RED

 

CN09

 

BU

 

 

 

 

 

 

 

 

 

 

 

CT

 

 

 

 

 

 

 

 

 

 

 

EU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CM

WHI

 

CN10

 

 

BV

 

 

 

 

 

 

 

Compressor

 

 

T04

EV

 

IGBT

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

CN11

 

CT

BW

 

module

FOR

 

 

 

 

 

 

 

 

 

 

 

 

EW

 

COMPRESSOR

 

CN604 2 2

 

TE

 

 

 

 

 

4

BX

 

 

ORN

2 2

CN500

 

1 1

 

 

POWER SUPPLY CIRCUIT

BY

 

 

 

 

 

 

 

 

 

BZ

 

 

ORN

1 1

 

CN605 2 2

 

 

 

(FOR P.C. BOARD)

 

 

 

 

 

 

 

GRN

TS

 

 

 

 

 

 

 

 

Q200

 

 

 

 

 

 

 

 

 

 

 

4-WAY VALVE COIL

 

 

1 1

 

 

F04

2

 

 

 

 

 

 

 

 

 

 

 

FUSE

 

 

 

 

 

3 3

3

 

 

3 3

 

 

 

 

3.15A

 

 

 

 

 

 

 

 

 

TD

 

 

 

 

 

 

 

 

 

 

 

CN700

CN600 2

 

 

 

 

 

 

 

P20

 

 

1 1

1

 

 

1 1

 

 

 

 

 

C13

3

 

P19

 

YEL

FAN MOTOR

 

 

CN601 2 2

 

TO

 

 

 

C12

 

P18

 

BLU

5 5

 

 

1 1

 

 

 

 

C11

 

 

P17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FM

4 4

 

Fan

 

 

 

 

 

 

C10

2

F02

 

 

 

3 3 CN300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

G

 

 

 

2 2

 

circuit

 

BLU

 

 

 

 

 

 

15A

 

 

 

1 1

 

 

3 3

 

3 3

 

 

 

 

 

E

 

 

 

 

2

CN302

 

 

CN04

 

 

 

 

A

Converter

 

3 3

 

YEL

 

 

 

 

 

 

 

 

 

1 1

 

1 1

 

 

 

 

 

~

 

module

 

2 2 CN301

F300

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

 

 

1 1

 

FUSE

5 5

BLK

 

5 5

 

 

RELAY

 

 

 

 

 

 

 

T5A

WHI

 

 

 

 

 

 

+

 

DB01

 

6 6

 

CN800

4 4

BLU

 

4 4

CN06

 

RY01

 

P10

 

 

 

 

 

3 3

 

3 3

 

 

 

 

 

 

5 5

 

RED

 

 

 

 

 

 

 

ORN

 

 

 

2 2

 

2 2

P.C. BOARD

R05

 

 

 

 

PMV

4 4

 

 

1 1

PNK

 

1 1

 

P11

REACTOR

3 3 CN702

 

 

 

 

 

 

 

 

 

 

 

(MCC-1359)

R06

 

P13

2 2

 

 

 

2 2

 

 

2 2

 

 

2 2

 

 

 

 

 

 

CN04

 

 

 

 

 

 

1 1

 

 

 

1 1

 

ORN

 

CN05

 

 

 

P12

 

 

 

 

1 1

 

1 1

 

T02

 

REACTOR

 

 

 

 

 

BLK

 

 

 

 

CT

 

P09

2 2

 

 

 

 

 

 

5 5

 

5 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1

 

 

 

 

PHOTO COUPLER

 

 

 

 

 

 

P08

 

 

 

 

4 4

WHI

 

4 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P15

 

 

 

 

 

 

 

3 3

 

3 3

 

 

 

 

 

 

BRN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN01 2 2

RED

 

2 2

 

 

 

 

P14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1

 

1 1

CN13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUB

 

2

F01

 

 

 

 

 

 

 

 

 

 

 

 

P.C. BOARD

 

FUSE

 

 

 

 

 

F01

VARISTOR

SURGE

 

 

 

(MCC-1398)

 

T3.15A

 

 

 

 

2

25AFUSE

 

 

 

 

 

 

 

 

 

ABSORBER

 

 

 

 

 

CN02

1 2 3

 

 

REACTOR

 

CN01

CN02

 

CN03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

WHI

 

BLK

 

 

 

 

 

 

1 2 3 GRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

1

 

 

2

3

 

 

L

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL OF COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO

POWER

WHITE(S)

 

BLACK(C)

The sign in ( )

 

 

 

 

 

 

 

 

 

INDOOR SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

220-240V

 

 

 

 

 

 

 

is displayed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~50Hz

 

 

 

 

 

 

 

in the terminal

 

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS

 

 

 

 

 

RED(R)

cover

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check

 

 

 

 

Diagnosis result

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

items

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

TERMINAL BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

There is no supply voltage

Connecting cable check

 

 

 

 

 

 

 

 

 

(AC220 to 240V) between L - N , 1 - 2

 

 

 

 

 

 

 

 

 

 

 

 

There is no voltage (DC15 to 25V) 2 - 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

25A fuse (F01) blown, 15A fuse (F02) blown

Converter module (DB01) and electrolytic

 

 

 

 

 

 

 

 

 

3.15A fuse (F04) blown,

capacitor (C10 to C13) check IGBT

 

 

 

 

 

 

 

 

 

T5A fuse (F300) blown (SUB P.C. board)

 

 

module (Q200) check, Fan motor check

 

 

 

 

 

 

 

 

 

 

T3.15A fuse (F01) blown (SUB P.C. board)

SUB P.C. board check

 

 

 

Color Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTROLYTIC CAPACITOR VOLTAGE (C10, C11, C12, C13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

: BLACK

WHI

: WHITE

DC320V not available between

25A fuse (F01) check

 

 

+ terminal of electrolytic capacitor

 

 

P.C. board and coverter

 

 

BLU

: BLUE

BRN : BROWN

 

 

 

 

 

 

 

 

 

 

 

module (DB01) check

 

 

RED : RED

ORN : ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVERTER OUTPUT (CN09, CN10, CN11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRY

: GRAY

YEL

: YELLOW

4

(Please confirm within six minutes after instructing in the drive.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNK

: PINK

PUR : PURPLE

Voltage between each line of inverterside

IGBT module and

 

 

 

conector pins are not equal.

 

 

P.C. board check

 

 

GRN : GREEN

 

 

 

 

– 27 –

6. SPECIFICATIONS OF ELECTRICAL PARTS

6-1. Indoor Unit

4-Way Air Discharge Cassette Type

RAV-SM560UT-E/RAV-SM800UT-E

No.

Parts name

Type

 

Specifications

 

 

 

 

1

Fan motor (for indoor)

SWF-230-60-1

Output (Rated) 60 W, 220–240 V

 

 

 

 

 

2

Thermo. sensor (TA-sensor)

155 mm

10 kΩ

at 25°C

 

 

 

 

 

3

Heat exchanger sensor (TCJ-sensor)

Ø6 mm, 1200 mm

10 kΩ

at 25°C

 

 

 

 

 

4

Heat exchanger sensor (TC-sensor)

Ø6 mm, 1200 mm

10 kΩ

at 25°C

 

 

 

 

 

5

Float switch

FS-0218-106

 

 

 

 

 

 

 

6

Drain pump motor

ADP-1406

 

 

 

 

 

 

 

Concealed Duct Type

RAV-SM560BT-E/RAV-SM800BT-E

No.

Parts name

Type

 

Specifications

 

 

 

 

1

Fan motor (RAV-SM800BT-E)

STF-230-80-4C

Output (Rated) 80 W, 220–240 V, 4P

 

 

 

 

2

Fan motor (RAV-SM560BT-E)

STF-220-80-4C

Output (Rated) 80 W, 220–240 V, 4P

 

 

 

 

3

Capacitor (RAV-SM800BT-E)

EAG40M805UF1

400WV, 5µF

 

 

 

 

4

Capacitor (RAV-SM560BT-E)

CMPS400-4.0

400WV, 4.0µF

 

 

 

 

 

5

Thermo. sensor (TA-sensor)

818 mm

10 kΩ

at 25°C

 

 

 

 

 

6

Heat exchanger sensor (TC-sensor)

Ø6 mm, 1200 mm

10 kΩ

at 25°C

 

 

 

 

 

7

Heat exchanger sensor (TCJ-sensor)

Ø6 mm, 1200 mm

10 kΩ

at 25°C

 

 

 

 

 

High-Wall Type

RAV-SM560KRT-E/RAV-SM800KRT-E

No.

Parts name

Type

 

Specifications

 

 

 

 

1

Fan motor (for indoor)

ICF340-30-1

Output (Rated) 30 W, 220–240 V

 

 

 

 

 

2

Grille motor

MP35EA12

 

 

 

 

 

 

 

3

Thermo. sensor (TA-sensor)

268 mm

10 kΩ

at 25°C

 

 

 

 

 

4

Heat exchanger sensor (TC-sensor)

Ø6 mm, 400 mm

10 kΩ

at 25°C

 

 

 

 

 

5

Heat exchanger sensor (TCJ-sensor)

Ø6 mm, 400 mm

 

 

 

 

 

 

 

RAV-SM560XT-E/RAV-SM800XT-E

No.

Parts name

Type

 

 

Specifications

 

 

 

 

1

Fan motor (for indoor)

AFP-220-50-4A

Output (Rated) 50 W, 220–240 V

 

 

 

 

2

Grille motor

MP35EA

DC 12 V

 

 

 

 

 

 

3

Thermo. sensor (TA-sensor)

mm

 

10 kΩ

at 25°C

 

 

 

 

 

 

4

Heat exchanger sensor (TC-sensor)

Ø6 mm,

mm

10 kΩ

at 25°C

 

 

 

 

 

 

5

Heat exchanger sensor (TCJ-sensor)

Ø6 mm,

mm

 

 

 

 

 

 

 

 

– 28 –

6-2. Outdoor Unit

RAV-SM560AT-E

No.

Parts name

Type

 

Specifications

 

 

 

 

1

Fan motor

ICF-140-43-1

Output (Rated) 40 W

 

 

 

 

2

Compressor

DA130A1F-23F

3 phase, 4P, 1100 W

 

 

 

 

3

Reactor

CH-57

1=10 mH, 16A

 

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

10 kΩ

at 25°C

 

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

10 kΩ

at 25°C

 

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

10 kΩ

at 25°C

 

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

50 kΩ

at 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

 

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect)

 

25 A, AC 250 V

 

 

 

 

 

10

4-way valve solenoid coil

STF-0108G

 

 

 

 

 

 

11

Compressor thermo. (Protection)

US-622

ON : 90 ± 5°C, OFF : 125 ± 4°C

 

 

 

 

 

RAV-SM800AT-E

No.

Parts name

Type

 

 

Specifications

 

 

 

 

1

Fan motor

ICF-140-63-1

Output (Rated) 63 W, 220–240 V

 

 

 

 

2

Compressor

DA220A2F-20L

3 phase, 4P, 1600 W

 

 

 

 

 

3

Reactor

CH-47

mH,

A

 

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

10 kΩ

at 25°C

 

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

10 kΩ

at 25°C

 

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

10 kΩ

at 25°C

 

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

50 kΩ

at 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

 

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect))

 

25 A, AC 250 V

 

 

 

 

 

 

10

4-way valve solenoid coil

DKV-M0ZS743B0

 

 

 

 

 

 

 

11

Compressor thermo. (Protection)

 

ON : 90 ± 5°C, OFF : 125 ± 4°C

 

 

 

 

 

 

6-3. Accessory Separate Sold Parts

RBC-U21PG (W) E (Ceiling panel)

No.

Parts name

Type

Specifications

 

 

 

 

1

Motor-louver

MP24GA

DC 12 V

 

 

 

 

2

 

 

 

 

 

 

 

TCB-DP11E (Drain up pump)

No.

Parts name

Type

Specifications

 

 

 

 

1

Pump-drain

PJD-05230TF-1

AC 220–240 V

 

 

 

 

2

 

 

 

 

 

 

 

– 29 –

7. REFRIGERANT R410A

This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.

The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.

The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.

7-1. Safety During Installation/Servicing

As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.

(1)Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.

If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.

(2)Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.

The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.

(3)If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.

If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

(4)When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.

(5)After completion of installation work, check to make sure that there is no refrigeration gas leakage.

If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

(6)When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.

If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.

(7)Be sure to carry out installation or removal according to the installation manual.

Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.

(8)Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.

Improper repair’s may result in water leakage, electric shock and fire, etc.

7-2. Refrigerant Piping Installation

7-2-1. Piping Materials and Joints Used

For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.

(1)Copper Pipes

It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.

As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown in Table 7-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.

– 30 –