Toshiba RAV-SP1104AT8Z-TR, RAV-SP1104AT8-TR, RAV-SP1404AT8-E, RAV-SP1404AT8-TR, RAV-SP1104AT8ZG-TR User Manual

...
0 (0)

FILE NO. A10-002

SERVICE MANUAL

SPLIT TYPE

OUTDOOR UNIT

<SUPER DIGITAL INVERTER>

RAV-SP1104AT8-E

RAV-SP1104AT8Z-E

RAV-SP1104AT8ZG-E

RAV-SP1404AT8-E

RAV-SP1404AT8Z-E

RAV-SP1404AT8ZG-E

RAV-SP1604AT8-E

RAV-SP1604AT8Z-E

RAV-SP1604AT8ZG-E

RAV-SP1104AT8-TR RAV-SP1104AT8Z-TR RAV-SP1104AT8ZG-TR

RAV-SP1404AT8-TR RAV-SP1404AT8Z-TR RAV-SP1404AT8ZG-TR

RAV-SP1604AT8-TR RAV-SP1604AT8Z-TR RAV-SP1604AT8ZG-TR

RAV-SP1104AT7 RAV-SP1404AT7 RAV-SP1604AT7 RAV-SP1104AT7Z RAV-SP1404AT7Z RAV-SP1604AT7Z RAV-SP1104AT7ZG RAV-SP1404AT7ZG RAV-SP1604AT7ZG

R410A

PRINTED IN JAPAN, Apr., 2010 ToMo

CONTENTS

ORIGINAL INSTRUCTION .....................................................................................................

3

WARNING INDICATIONS ON THE AIR CONDITIONER UNIT ..............................................

5

PRECAUTION FOR SAFETY .................................................................................................

6

NEW REFRIGERANT (R410A) ............................................................................................

11

1.

SPECIFICATIONS ........................................................................................................

13

 

1-1.

Indoor Unit ..................................................................................................................................

13

 

1-2.

Outdoor Unit ...............................................................................................................................

29

 

1-3.

Operation Characteristic Curve ...............................................................................................

30

2.

CONSTRUCTION VIEWS (EXTERNAL VIEWS) ..........................................................

32

 

2-1.

Outdoor Unit ...............................................................................................................................

32

3.

OUTDOOR UNIT REFRIGERATING CYCLE DIAGRAM .............................................

35

4.

WIRING DIAGRAM ......................................................................................................

36

 

4-1.

Outdoor Unit ...............................................................................................................................

36

5.

SPECIFICATIONS OF ELECTRICAL PARTS ..............................................................

37

 

5-1.

Outdoor Unit ...............................................................................................................................

37

6.

REFRIGERANT R410A ................................................................................................

38

 

6-1.

Safety During Installation/Servicing ........................................................................................

38

 

6-2.

Refrigerant Piping Installation ...............................................................................................

38

 

6-3.

Tools ............................................................................................................................................

42

 

6-4.

Recharging of Refrigerant ........................................................................................................

42

 

6-5.

Brazing of Pipes .........................................................................................................................

43

 

6-6.

Instructions for Re-use Piping of R22 or R407C ....................................................................

45

7.

CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS ..............................

48

 

7-1.

Outdoor Unit Control .................................................................................................................

48

 

7-2.

Outline of Main Controls ...........................................................................................................

52

8.

TROUBLESHOOTING..................................................................................................

57

 

8-1.

Summary of Troubleshooting ...................................................................................................

57

 

8-2.

Troubleshooting .........................................................................................................................

59

9.

SETUP AT LOCAL SITE AND OTHERS ......................................................................

82

 

9-1.

Calling of Error History .............................................................................................................

82

 

9-2.

Group Control Operation ..........................................................................................................

82

 

9-3.

Outdoor Unit ...............................................................................................................................

84

10.

ADDRESS SETUP .......................................................................................................

91

 

10-1.

Address Setup Procedure .........................................................................................................

91

 

10-2.

Address Setup & Group Control ..............................................................................................

92

 

10-3.

Remote Controller Wiring ..........................................................................................................

95

 

10-4.

Address Setup (Manual setting from remote controller) .......................................................

96

 

10-5.

Confirmation of Indoor Unit No. Position ................................................................................

97

11.

REPLACEMENT OF THE SERVICE P.C. BOARD (4316V392) MCC-1599 .................

99

12.

HOW TO EXCHANGE COMPRESSOR ......................................................................

100

 

12-1.

Exchanging Procedure of Compressor (Outline) .................................................................

100

 

12-2.

Exchange of Compressor .......................................................................................................

100

13.

INSTALLATION MANUAL ..........................................................................................

101

14.

DETACHMENTS .........................................................................................................

118

 

14-1.

Outdoor Unit .............................................................................................................................

118

15.

EXPLODED VIEWS AND PARTS LIST ......................................................................

130

 

15-1.

Outdoor Unit .............................................................................................................................

130

– 2 –

Original instruction

Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them.

Some of the details provided in these instructions differ from the service manual, and the instructions provided here take precedence.

Generic Denomination: Air Conditioner

Definition of Qualified Installer or Qualified Service Person

The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person.

When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.

A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.

Agent

 

Qualifications and knowledge which the agent must have

 

 

 

Qualified

The qualified installer is a person who installs, maintains, relocates and removes the air

installer ( 1)

 

conditioners made by Toshiba Carrier Corporation.

 

 

He or she has been trained to install, maintain, relocate and remove the air conditioners made by

 

 

Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by

 

 

an individual or individuals who have been trained and is thus thoroughly acquainted with the

 

 

knowledge related to these operations.

 

The qualified installer who is allowed to do the electrical work involved in installation, relocation

 

 

and removal has the qualifications pertaining to this electrical work as stipulated by the local laws

 

 

and regulations, and he or she is a person who has been trained in matters relating to electrical

 

 

work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has

 

 

been instructed in such matters by an individual or individuals who have been trained and is thus

 

 

thoroughly acquainted with the knowledge related to this work.

 

The qualified installer who is allowed to do the refrigerant handling and piping work involved in

 

 

installation, relocation and removal has the qualifications pertaining to this refrigerant handling

 

 

and piping work as stipulated by the local laws and regulations, and he or she is a person who

 

 

has been trained in matters relating to refrigerant handling and piping work on the air conditioners

 

 

made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such

 

 

matters by an individual or individuals who have been trained and is thus thoroughly acquainted

 

 

with the knowledge related to this work.

 

The qualified installer who is allowed to work at heights has been trained in matters relating to

 

 

working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively,

 

 

he or she has been instructed in such matters by an individual or individuals who have been

 

 

trained and is thus thoroughly acquainted with the knowledge related to this work.

 

 

 

Qualified service

The qualified service person is a person who installs, repairs, maintains, relocates and removes

person ( 1)

 

the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install,

 

 

repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or,

 

 

alternatively, he or she has been instructed in such operations by an individual or individuals who

 

 

have been trained and is thus thoroughly acquainted with the knowledge related to these operations.

 

The qualified service person who is allowed to do the electrical work involved in installation,

 

 

repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated

 

 

by the local laws and regulations, and he or she is a person who has been trained in matters

 

 

relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or,

 

 

alternatively, he or she has been instructed in such matters by an individual or individuals who

 

 

have been trained and is thus thoroughly acquainted with the knowledge related to this work.

 

The qualified service person who is allowed to do the refrigerant handling and piping work

 

 

involved in installation, repair, relocation and removal has the qualifications pertaining to this

 

 

refrigerant handling and piping work as stipulated by the local laws and regulations, and he or

 

 

she is a person who has been trained in matters relating to refrigerant handling and piping

 

 

work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she

 

 

has been instructed in such matters by an individual or individuals who have been trained

 

 

and is thus thoroughly acquainted with the knowledge related to this work.

 

The qualified service person who is allowed to work at heights has been trained in matters

 

 

relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or,

 

 

alternatively, he or she has been instructed in such matters by an individual or individuals who

 

 

have been trained and is thus thoroughly acquainted with the knowledge related to this work.

 

 

 

– 3 –

Definition of Protective Gear

When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing.

In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.

Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.

Work undertaken

Protective gear worn

 

 

All types of work

Protective gloves

“Safety” working clothing

 

 

 

 

Gloves to provide protection for electricians and from heat

Electrical-related work

Insulating shoes

 

Clothing to provide protection from electric shock

 

 

Work done at heights (50 cm or more)

Helmets for use in industry

 

 

Transportation of heavy objects

Shoes with additional protective toe cap

 

 

Repair of outdoor unit

Gloves to provide protection for electricians and from heat

 

 

The important contents concerned to the safety are described on the product itself and on this Service Manual.

Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them.

[Explanation of indications]

Indication

Explanation

 

 

DANGER

Indicates contents assumed that an imminent danger causing a death or serious injury of

the repair engineers and the third parties when an incorrect work has been executed.

Indicates possibilities assumed that a danger causing a death or serious injury of the WARNING repair engineers, the third parties, and the users due to troubles of the product after work

when an incorrect work has been executed.

Indicates contents assumed that an injury or property damage ( ) may be caused on the CAUTION repair engineers, the third parties, and the users due to troubles of the product after work

when an incorrect work has been executed.

Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet

[Explanation of illustrated marks]

Mark

Explanation

Indicates prohibited items (Forbidden items to do)

The sentences near an illustrated mark describe the concrete prohibited contents.

Indicates mandatory items (Compulsory items to do)

The sentences near an illustrated mark describe the concrete mandatory contents.

Indicates cautions (Including danger/warning)

The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.

– 4 –

Warning Indications on the Air Conditioner Unit

[Confirmation of warning label on the main unit]

Confirm that labels are indicated on the specified positions

If removing the label during parts replace, stick it as the original.

Warning indication

Description

WARNING

WARNING

 

ELECTRICAL SHOCK HAZARD

ELECTRICAL SHOCK HAZARD

Disconnect all remote electric power supplies

Disconnect all remote electric

before servicing.

power supplies before servicing.

 

 

 

WARNING

WARNING

 

Moving parts.

Moving parts.

Do not operate unit with grille removed.

Do not operate unit with grille removed.

Stop the unit before the servicing.

Stop the unit before the servicing.

 

 

 

CAUTION

CAUTION

 

 

High temperature parts.

High temperature parts.

You might get burned when removing

You might get burned when removing this panel.

this panel.

 

 

 

CAUTION

CAUTION

 

Do not touch the aluminum fins of the unit.

Do not touch the aluminum fins of the unit.

Doing so may result in injury.

Doing so may result in injury.

 

 

 

CAUTION

CAUTION

 

BURST HAZARD

BURST HAZARD

Open the service valves before the

Open the service valves before the operation,

otherwise there might be the burst.

operation, otherwise there might be the

 

burst.

 

 

 

– 5 –

Precaution for Safety

WARNING

Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions.

Only qualified service person ( 1) is allowed to repair the air conditioner.

Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks and/or other problems.

Only a qualified installer ( 1) or qualified service person ( 1) is allowed to carry out the electrical work of the air conditioner.

Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.

Wear protective gloves and safety work clothing during installation, servicing and removal.

When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.

Failure to wear this protective gear may result in electric shocks.

Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws.

Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.

Only a qualified installer ( 1) or qualified service person ( 1) is allowed to undertake work at General heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to

undertake work.

When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions.

Also wear a helmet for use in industry as protective gear to undertake the work.

When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work.

Parts and other objects may fall from above, possibly injuring a person below.

Do not touch the aluminum fin of the outdoor unit.

You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.

Do not climb onto or place objects on top of the outdoor unit.

You may fall or the objects may fall off of the outdoor unit and result in injury.

When transporting the air conditioner, wear shoes with additional protective toe caps.

When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.

This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.

DENGER

Turn off breaker.

Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF position. Otherwise, electric shocks may result.

Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position.

Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts.

Only a qualified installer ( 1) or qualified service person ( 1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.

Before starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.

When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.

– 6 –

 

Even if the circuit breaker has been set to the OFF position before the service panel is removed

 

and the electrical parts are repaired, you will still risk receiving an electric shock.

 

For this reason, short-circuit the high-voltage capacitor terminals to discharge the voltage before

Execute

proceeding with the repair work.

discharge

For details on the short-circuiting procedure, refer to the Service Manual.

between

You may receive an electric shock if the voltage stored in the capacitors has not been sufficiently

terminals.

discharged.

 

 

 

Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair

 

or removal work is being carried out.

Prohibition

There is a danger of electric shocks if the circuit breaker is set to ON by mistake.

 

 

 

 

If, in the course of carrying out repairs, it becomes absolutely necessary to check out the

 

electrical parts with the electrical parts box cover of one or more of the indoor units and the

 

service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear

 

insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to

Stay on

avoid touching any live parts.

protection

You may receive an electric shock if you fail to heed this warning. Only qualified service person

 

( 1) is allowed to do this kind of work.

 

 

WARNING

 

Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of

 

the main unit, otherwise an electric shock is caused when a leak occurs.If the earth wire is not

 

correctly connected, contact an electric engineer for rework.

 

 

 

After completing the repair or relocation work, check that the ground wires are connected properly.

Check earth

 

Be sure to connect earth wire. (Grounding work) Incomplete grounding causes an electric shock.

wires.

Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for

 

 

telephone wires.

 

 

 

Do not modify the products.Do not also disassemble or modify the parts.

 

It may cause a fire, electric shock or injury.

Prohibition of

 

modification.

 

 

 

 

When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the

 

specifications given in the Service Manual (or use the parts contained on the parts list in the

 

Service Manual).

Use specified

Use of any parts which do not satisfy the required specifications may give rise to electric shocks,

parts.

smoking and/or a fire.

 

 

 

If, in the course of carrying out repairs, it becomes absolutely necessary to check out the

 

electrical parts with the electrical parts box cover of one or more of the indoor units and the

 

service panel of the outdoor unit removed in order to find out exactly where the trouble lies, place

Do not bring

"Keep out" signs around the work site before proceeding.

a child close to

Third-party individuals may enter the work site and receive electric shocks if this warning is not

the equipment.

heeded.

 

 

 

Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then

 

apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.

Insulating

 

measures

 

 

 

 

When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because

 

the oil that coats the pipes may otherwise burn.

 

When repairing the refrigerating cycle, take the following measures.

 

1) Be attentive to fire around the cycle.

 

When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with

No fire

refrigerant gas may catch fire.

2) Do not use a welder in the closed room.

 

 

When using it without ventilation, carbon monoxide poisoning may be caused.

 

3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch

 

the inflammables.

 

 

– 7 –

 

The refrigerant used by this air conditioner is the R410A.

 

Check the used refrigerant name and use tools and materials of the parts which match with it.

 

For the products which use R410A refrigerant, the refrigerant name is indicated at a position on

 

the outdoor unit where is easy to see.

 

To prevent miss-charging, the route of the service port is changed from one of the former R22.

 

For an air conditioner which uses R410A, never use other refrigerant than R410A.

 

For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.

 

If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating

 

cycle and an injury due to breakage may be caused.

 

Do not charge refrigerant additionally.

 

If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the

 

refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over

 

the specified standard amount is charged and an abnormal high pressure is applied to the inside

 

of the refrigerating cycle resulted in cause of breakage or injury.

Refrigerant

Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute

 

vacuuming, and then newly recharge the specified amount of liquid refrigerant.

 

In this time, never charge the refrigerant over the specified amount.

 

When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other

 

than R410A into the specified refrigerant.

 

If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating

 

cycle resulted in cause of injury due to breakage.

 

After installation work, check the refrigerant gas does not leak.

 

If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such

 

as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.

 

Never recover the refrigerant into the outdoor unit.

 

When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device.

 

The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as

 

breakage or injury is caused.

 

 

 

After repair work, surely assemble the disassembled parts, and connect and lead the removed

 

wires as before.

 

Perform the work so that the cabinet or panel does not catch the inner wires.

Assembly/

If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is

Cabling

caused at user’s side.

 

 

 

After the work has finished, be sure to use an insulation tester set (500V Megger) to check the

 

resistance is 2MΩ or more between the charge section and the non-charge metal section

 

(Earth position).

Insulator

If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.

check

 

 

 

 

When the refrigerant gas leaks during work, execute ventilation.

 

If the refrigerant gas touches to a fire, poisonous gas generates.

 

A case of leakage of the refrigerant and the closed room full with gas is dangerous because a

Ventilation

shortage of oxygen occurs. Be sure to execute ventilation.

 

 

 

When the refrigerant gas leaks, find up the leaked position and repair it surely.

 

If the leaked position cannot be found up and the repair work is interrupted, pump-down and

 

tighten the service valve, otherwise the refrigerant gas may leak into the room.

 

The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove

 

though the refrigerant gas itself is innocuous.

 

When installing equipment which includes a large amount of charged refrigerant such as a multi

 

air conditioner in a sub-room, it is necessary that the density does not the limit even if the

 

refrigerant leaks.

 

If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.

 

 

 

Tighten the flare nut with a torque wrench in the specified manner.

Compulsion

Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may

result in refrigerant leakage.

 

 

 

 

Nitrogen gas must be used for the airtight test.

 

 

 

The charge hose must be connected in such a way that it is not slack.

 

 

 

For the installation/moving/reinstallation work, follow to the Installation Manual.

 

If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or

 

fire is caused.

 

 

– 8 –

 

Once the repair work has been completed, check for refrigerant leaks, and check the insulation

 

resistance and water drainage.

 

Then perform a trial run to check that the air conditioner is running properly.

 

 

 

After repair work has finished, check there is no trouble. If check is not executed, a fire, electric

Check after

shock or injury may be caused. For a check, turn off the power breaker.

 

After repair work (installation of front panel and cabinet) has finished, execute a test run to check

repair

there is no generation of smoke or abnormal sound.

 

 

If check is not executed, a fire or an electric shock is caused. Before test run, install the front

 

panel and cabinet.

Check the following matters before a test run after repairing piping.

Connect the pipes surely and there is no leak of refrigerant.

The valve is opened.

Do not

Running the compressor under condition that the valve closes causes an abnormal high

operate the

pressure resulted in damage of the parts of the compressor and etc. and moreover if there is

unit with the

leak of refrigerant at connecting section of pipes, the air is suctioned and causes further

valve closed.

abnormal high pressure resulted in burst or injury.

 

Only a qualified installer ( 1) or qualified service person ( 1) is allowed to relocate the air

conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual

since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.

Check the following items after reinstallation.

1)The earth wire is correctly connected.

2)The power cord is not caught in the product.

3) There is no inclination or unsteadiness and the installation is stable.

Check after If check is not executed, a fire, an electric shock or an injury is caused.

reinstallation

When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.

Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.

When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.

If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.

When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor, Cooling check inverter or the areas around these parts to be repaired immediately after the air conditioner has

been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.

If you fail to heed this warning, you will run the risk of burning yourself because the fan motor, reactor, inverter heat sink and other parts will be very hot to the touch.

In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.

Only a qualified installer ( 1) or qualified service person ( 1) is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.

Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.

Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas.

If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.

Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure Installation themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit

while the air conditioner is running.

Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.

Install the circuit breaker where it can be easily accessed by the qualified service person ( 1).

Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.

– 9 –

Explanations given to user

If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done.

Do not set the circuit breaker to the ON position until the repairs are completed.

Relocation

Only a qualified installer ( 1) or qualified service person ( 1) is allowed to relocate the air conditioner.

It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.

When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.

( 1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”

Declaration of Conformity

Manufacturer:

Toshiba Carrier Corporation

 

336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN

Authorized

Nick Ball

Representative/TCF holder:

Toshiba EMEA Engineering Director

 

Toshiba Carrier UK Ltd.

 

Porsham Close, Belliver Industrial Estate,

 

PLYMOUTH, Devon, PL6 7DB.

 

United Kingdom

Hereby declares that the machinery described below:

Generic Denomination:

Air Conditioner

Model/type:

RAV-SP1104AT8-E

 

RAV-SP1104AT8Z-E

 

RAV-SP1104AT8ZG-E

 

RAV-SP1104AT8-TR

 

RAV-SP1104AT8Z-TR

 

RAV-SP1104AT8ZG-TR

RAV-SP1404AT8-E RAV-SP1404AT8Z-E RAV-SP1404AT8ZG-E RAV-SP1404AT8-TR RAV-SP1404AT8Z-TR RAV-SP1404AT8ZG-TR

Commercial name:

Super Digital Inverter Series Air Conditioner

RAV-SP1604AT8-E RAV-SP1604AT8Z-E RAV-SP1604AT8ZG-E RAV-SP1604AT8-TR RAV-SP1604AT8Z-TR RAV-SP1604AT8ZG-TR

Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing into national law.

Complies with the provisions of the following harmonized standard: EN 378-2: 2008

Note: This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer’s consent.

Disposal

How to dispose of air conditioners with a rating of 12 kW and below in accordance with the 2002/96/EC Directive WEEE (Waste Electrical and Electronic Equipment) is provided in the Installation Manual supplied with your product. For disposal of the product above 12 kW in rating you should use a registered company in accordance with any national or EU legislation.

<Model names with a rating of 12 kW and below (outdoor units)>

DI series

RAV-SM563AT-E

SDI series

RAV-SP404AT-E RAV-SP454AT-E RAV-SP564AT-E RAV-SP804AT-E RAV-SP1104AT-E RAV-SP1104AT8-E RAV-SP1104AT8-TR

RAV-SM803AT-E

RAV-SP404ATZ-E RAV-SP454ATZ-E RAV-SP564ATZ-E RAV-SP804ATZ-E RAV-SP1104ATZ-E RAV-SP1104AT8Z-E RAV-SP1104AT8Z-TR

RAV-SM1103AT-E

RAV-SP404ATZG-E RAV-SP454ATZG-E RAV-SP564ATZG-E RAV-SP804ATZG-E RAV-SP1104ATZG-E RAV-SP1104AT8ZG-E RAV-SP1104AT8ZG-TR

– 10 –

New Refrigerant (R410A)

This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.

1. Safety Caution Concerned to New Refrigerant

The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed.

Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work.

If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.

2.Cautions on Installation/Service

1)Do not mix the other refrigerant or refrigerating oil.

For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them.

2)As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.

3)In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.

Use the clean pipes.

Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)

4)For the earth protection, use a vacuum pump for air purge.

5)R410A refrigerant is azeotropic mixture type refrigerant.

Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)

3.Pipe Materials

For the refrigerant pipes, copper pipe and joints are mainly used.

It is necessary to select the most appropriate pipes to conform to the standard.

Use clean material in which impurities adhere inside of pipe or joint to a minimum.

1) Copper pipe

<Piping>

The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.

When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without seam” and one with bonded oil amount 40mg/10m or less.

Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)

<Flare nut>

Use the flare nuts which are attached to the air conditioner unit.

2)Joint

The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installation of the air conditioner. However clear impurities when using them.

– 11 –

4.Tools

1.Required Tools for R410A

Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.

1)Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

2)Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

3)Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

 

 

 

 

R410A

Conventional air

 

 

 

air conditioner installation

conditioner installation

No.

Used tool

Usage

 

 

 

Existence of

Whether conventional

Whether

 

 

 

 

 

 

new equipment

conventional equipment

 

 

 

equipment can be used

 

 

 

for R410A

can be used

 

 

 

 

 

 

 

 

 

 

Q

Flare tool

Pipe flaring

Yes

(Note)

Yes

 

 

 

 

 

 

 

Copper pipe gauge

Flaring by

 

 

 

R

for adjusting

Yes

(Note)

(Note)

conventional flare tool

 

projection margin

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

Torque wrench

Tightening of flare nut

Yes

No

No

 

 

 

 

 

 

T

Gauge manifold

Evacuating, refrigerant

 

 

 

 

 

Yes

No

No

U

Charge hose

charge, run check, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

V

Vacuum pump adapter

Vacuum evacuating

Yes

No

Yes

 

 

 

 

 

 

W

Electronic balance for

Refrigerant charge

Yes

Yes

Yes

 

refrigerant charging

 

 

 

 

 

 

 

 

 

 

X

Refrigerant cylinder

Refrigerant charge

Yes

No

No

 

 

 

 

 

 

Y

Leakage detector

Gas leakage check

Yes

No

Yes

 

 

 

 

 

 

(Note) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.

1)Vacuum pump. Use vacuum pump by attaching vacuum pump adapter.

2)Torque wrench

3)Pipe cutter

4)Reamer

5)Pipe bender

6)Level vial

7)Screwdriver (+, –)

8)Spanner or Monkey wrench

9)Hole core drill

10)Hexagon wrench (Opposite side 4mm)

11)Tape measure

12)Metal saw

Also prepare the following equipments for other installation method and run check.

1)

Clamp meter

3)

Insulation resistance tester (Megger)

2)

Thermometer

4)

Electroscope

– 12 –

1. SPECIFICATIONS

1-1. Indoor Unit

1-1-1. 4-Way Air Discharge Cassette Type

<Single type>

 

 

Indoor unit

RAV-SM

1104UT-E

1404UT-E

1604UT-E

1104UT-E

1404UT-E

1604UT-E

Model

Outdoor unit

RAV-SP

1104AT8-E

1404AT8-E

1604AT8-E

1104AT7

1404AT7

1604AT7

 

 

 

 

 

 

1104AT8-TR

1404AT8-TR

1604AT8-TR

 

 

 

Cooling capacity

 

(kW)

10.0

12.5

14.0

10.0

12.5

14.0

 

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

 

 

 

 

Heating capacity

 

(kW)

11.2

14.0

16.0

11.2

14.0

16.0

 

(2.4-15.6)

(2.4-18.0)

(2.4-19.0)

(2.4-15.6)

(2.4-18.0)

(2.4-19.0)

 

 

 

 

Power supply

 

 

3 phase 4wired (3N-4pole)

3 phase 4wired (3N-4pole)

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

Running current

(A)

4.45 - 4.07

6.03 - 5.52

7.55 - 6.91

4.45

6.03

7.55

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

2.37

3.46

4.49

2.37

3.46

4.49

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

4.22

3.61

3.12

4.22

3.61

3.12

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

A

A

B

 

 

 

 

 

 

 

 

 

 

Running current

(A)

4.52 - 4.14

5.97 - 5.47

7.26 - 6.65

4.52

5.97

7.26

characteristics

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

2.42

3.42

4.30

2.42

3.42

4.30

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

4.63

4.09

3.72

4.63

4.09

3.72

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

A

A

A

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

(A)

14.7

14.7

14.7

14.7

14.7

14.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Ceiling panel

Model

 

 

 

RBC-U31PG(W,WS)-E , RBC-U31PGS(W,WS)-E

 

 

 

 

 

W:Moon-white(2.5GY 9.0/0.5),

 

 

(Sold separately)

Panel color

 

 

 

 

 

 

 

 

WS:Stripe-white(2.5GY 9.0/0.5,(Gray:8B 3/0.3))

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

319

319

 

319

319

 

319

319

 

Main unit

Width

 

(mm)

840

840

 

840

840

 

840

840

Outer dimension

 

Depth

 

(mm)

840

840

 

840

840

 

840

840

Ceiling panel

Height

 

(mm)

30

30

 

30

30

 

30

30

 

 

 

 

 

Width

 

(mm)

950

950

 

950

950

 

950

950

 

(Sold separately)

 

 

 

 

Depth

 

(mm)

950

950

 

950

950

 

950

950

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

24

24

 

24

24

 

24

24

Ceiling panel (Sold separately)

 

(kg)

4.2

4.2

 

4.2

4.2

 

4.2

4.2

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

Finned tube

 

 

 

Fan

 

 

 

 

 

 

Turbo fan

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

33.5/24.0/19.5

35.0/24.0/20.5

35.5/25.0/21.0

33.5/24.0/19.5

35.0/24.0/20.5

35.5/25.0/21.0

 

Motor

 

 

(W)

68

72

 

72

68

 

72

72

Sound pressure level

 

H/M/L

(dB•A)

43/38/33

44/38/34

 

45/40/36

43/38/33

 

44/38/34

45/40/36

Sound power level

 

H/M/L

(dB•A)

58/53/48

59/53/49

 

60/55/51

58/53/48

 

59/53/49

60/55/51

Connecting pipe

Drain port

 

 

 

 

 

 

VP25

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

7.5

7.5

 

7.5

7.5

 

7.5

7.5

 

Min. length

 

 

(m)

3

3

 

3

3

 

3

3

Outer dimension

Max. total length

 

 

(m)

75

75

 

75

75

 

75

75

Over 30m

 

 

 

 

 

 

40g/m (31m to 75m)

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

30

30

 

30

30

 

30

30

 

Outdoor high

(m)

30

30

 

30

30

 

30

30

 

 

 

 

Connecting pipe

Gas side

 

 

(mm)

15.9

15.9

 

15.9

15.9

 

15.9

15.9

Liquid side

 

 

(mm)

9.5

9.5

 

9.5

9.5

 

9.5

9.5

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Propeller fan

 

 

Fan unit

Standard air flow high

(m³/min)

101

103

 

103

101

 

103

103

 

Motor

 

 

(W)

100 + 100

100 + 100

 

100 + 100

100 + 100

 

100 + 100

100 + 100

Sound pressure level

Cooling/Heating

 

(dB•A)

49/50

51/52

 

51/53

49/50

 

51/52

51/53

Sound power level

Cooling/Heating

 

(dB•A)

66/67

68/69

 

68/70

66/67

 

68/69

68/70

 

 

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 13 –

<Twin type>

 

 

Indoor unit 1

RAV-SM

564UT-E

804UT-E

804UT-E

564UT-E

804UT-E

804UT-E

Model

Indoor unit 2

RAV-SM

564UT-E

804UT-E

804UT-E

564UT-E

804UT-E

804UT-E

 

 

 

 

 

 

 

 

Outdoor unit

RAV-SP

1104AT8-E

1404AT8-E

1604AT8-E

1104AT7

1404AT7

1604AT7

 

 

 

 

 

 

1104AT8-TR

1404AT8-TR

1604AT8-TR

 

 

 

Cooling capacity

 

(kW)

10.0

12.5

14.0

10.0

12.5

14.0

 

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

 

 

 

 

Heating capacity

 

(kW)

11.2

14.0

16.0

11.2

14.0

16.0

 

(2.4-15.6)

(2.4-18.0)

(2.4-19.0)

(2.4-15.6)

(2.4-18.0)

(2.4-19.0)

 

 

 

 

Power supply

 

 

3 phase 4wired (3N-4pole)

3 phase 4wired (3N-4pole)

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

Running current

(A)

4.45 - 4.07

6.03 - 5.52

7.55 - 6.91

4.45

6.03

7.55

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

2.37

3.46

4.49

2.37

3.46

4.49

 

Cooling

Power factor

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

4.22

3.61

3.12

4.22

3.61

3.12

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

A

A

B

 

 

 

 

 

 

 

 

 

 

Running current

(A)

4.52 - 4.14

5.97 - 5.47

7.26 - 6.65

4.52

5.97

7.26

characteristics

 

 

 

 

 

 

 

 

 

 

 

Power consumption

(kW)

2.42

3.42

4.30

2.42

3.42

4.30

 

 

 

Heating

Power factor

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

4.63

4.09

3.72

4.63

4.09

3.72

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

A

A

A

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

(A)

14.5

14.5

14.5

14.5

14.5

14.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Ceiling panel

Model

 

 

RBC-U31PG(W,WS)-E , RBC-U31PGS(W,WS)-E

 

 

 

 

 

W:Moon-white(2.5GY 9.0/0.5),

 

 

(Sold separately)

Panel color

 

 

 

 

 

 

WS:Stripe-white(2.5GY 9.0/0.5,(Gray:8B 3/0.3))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

256

256

 

256

256

 

256

256

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

Width

(mm)

840

840

 

840

840

 

840

840

Outer dimension

 

Depth

(mm)

840

840

 

840

840

 

840

840

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel

Height

(mm)

30

30

 

30

30

 

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

(mm)

950

950

 

950

950

 

950

950

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

950

950

 

950

950

 

950

950

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

(kg)

20

20

 

20

20

 

20

20

Ceiling panel (Sold separately)

(kg)

4.2

4.2

 

4.2

4.2

 

4.2

4.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Turbo fan

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

17.5/14.5/13.0

20.5/16.0/13.5

20.5/16.0/13.5

17.5/14.5/13.0

20.5/16.0/13.5

20.5/16.0/13.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

(W)

14

20

 

20

14

 

20

20

Sound pressure level

 

H/M/L

(dB•A)

32/29/28

35/31/28

 

35/31/28

32/29/28

 

35/31/28

35/31/28

 

 

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

47/44/43

50/46/43

 

50/46/43

47/44/43

 

50/46/43

50/46/43

Connecting pipe

Drain port

 

 

 

 

 

VP25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

Standard length

 

 

(m)

7.5

7.5

7.5

7.5

7.5

7.5

 

Min. length

 

 

(m)

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

50

50

50

50

50

50

 

 

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

30

30

30

30

30

30

 

 

 

Gas side

Main

 

(mm)

15.9

15.9

15.9

15.9

15.9

15.9

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

12.7

15.9

15.9

12.7

15.9

15.9

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

9.5

9.5

9.5

9.5

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

6.4

9.5

9.5

6.4

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

 

 

Fan unit

Standard air flow high

(m³/min)

101

103

103

101

103

103

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

49/50

51/52

51/53

49/50

51/52

51/53

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

66/67

68/69

68/70

66/67

68/69

68/70

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 14 –

<Triple type>

 

 

Indoor unit 1

 

RAV-SM

 

564UT-E

 

564UT-E

 

 

Indoor unit 2

 

RAV-SM

 

564UT-E

 

564UT-E

Model

 

 

 

 

 

 

 

 

 

Indoor unit 3

 

RAV-SM

 

564UT-E

 

564UT-E

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1604AT8-E

 

1604AT7

 

 

 

 

1604AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

14.0 (2.6-16.0)

 

14.0 (2.6-16.0)

 

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

16.0 (2.4-19.0)

 

16.0 (2.4-19.0)

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

 

380V – 415V, 50Hz

 

380V, 60Hz

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

7.55 - 6.91

 

7.55

 

 

Power consumption

 

(kW)

 

4.49

 

4.49

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

 

3.12

 

3.12

 

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

7.26 - 6.65

 

7.26

characteristics

 

 

 

 

 

 

Power consumption

 

(kW)

 

4.30

 

4.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

 

3.72

 

3.72

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

14.8

 

14.8

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

Appearance

Ceiling panel

Model

 

 

 

 

RBC-U31PG(W,WS)-E , RBC-U31PGS(W,WS)-E

 

 

 

 

 

 

 

 

 

 

 

 

 

W:Moon-white(2.5GY 9.0/0.5),

 

 

(Sold separately)

Panel color

 

 

 

 

 

 

 

 

 

 

WS:Stripe-white(2.5GY 9.0/0.5,(Gray:8B 3/0.3))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

256

 

256

 

 

Main unit

Width

 

(mm)

 

840

 

840

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

 

Depth

 

(mm)

 

840

 

840

 

 

 

 

 

 

 

 

 

Ceiling panel

Height

 

(mm)

 

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

 

(mm)

 

 

950

 

950

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

 

950

 

950

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

 

20

 

20

 

 

 

 

 

 

 

 

 

Ceiling panel (Sold separately)

 

(kg)

 

 

4.2

 

4.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Turbo fan

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

 

17.5/14.5/13.0

 

17.5/14.5/13.0

 

 

Motor

 

 

(W)

 

14

 

14

 

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

(dB•A)

 

32/29/28

 

32/29/28

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

 

47/44/43

 

47/44/43

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

 

VP25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

50

 

50

 

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

30

 

 

Outdoor high

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

15.9

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

 

12.7

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

6.4

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

 

103

 

103

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

100 + 100

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

51/53

 

51/53

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

 

68/70

 

68/70

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 15 –

1-1-2. Concealed Duct Type

<Single type>

 

 

Indoor unit

 

RAV-SM

1102BT-E

1402BT-E

 

1102BT-E

1402BT-E

Model

 

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

1104AT8-E

1404AT8-E

 

1104AT7

1404AT7

 

 

 

 

 

 

 

1104AT8-TR

1404AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

10.0

12.5

 

10.0

12.5

 

 

 

(2.6-12.0)

(2.6-14.0)

 

(2.6-12.0)

(2.6-14.0)

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

11.2

14.0

 

11.2

14.0

 

 

 

(2.4-14.0)

(2.4-18.0)

 

(2.4-14.0)

(2.4-18.0)

 

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

5.51 - 5.05

6.73 - 6.16

 

5.51

6.73

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.94

3.86

 

2.94

3.86

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

81

87

 

81

87

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

3.40

3.24

 

3.40

3.24

 

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

A

A

 

 

Running current

 

 

(A)

5.18 - 4.74

6.20 - 5.68

 

5.18

6.20

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.77

3.55

 

2.77

3.55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

81

87

 

81

87

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

4.04

3.94

 

4.04

3.94

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

A

A

 

 

 

Maximum current

 

 

(A)

15.6

16.0

 

15.6

16.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

Appearance

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

320

320

 

320

320

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

1350

1350

 

1350

1350

 

 

 

Depth

 

(mm)

800

800

 

800

800

 

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

54

54

 

54

54

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard air flow

H/M/L

(m³/min)

27.0/23.0/18.9

33.0/28.0/23.1

 

27.0/23.0/18.9

33.0/28.0/23.1

 

 

Motor

 

 

(W)

120

120

 

120

120

 

 

 

 

 

 

 

 

 

 

 

Fan unit

 

Standard

 

(Pa)

 

 

40

 

 

 

External static

(at shipment)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

Set up

 

 

 

 

 

 

 

 

 

 

for tap exchange (Pa)

20/40/70/100

20/40/65/90

 

20/40/70/100

20/40/65/90

Sound pressure level

 

H/M/L

 

(dB•A)

42 / 39 / 36

44 / 41 / 38

 

42 / 39 / 36

44 / 41 / 38

 

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

 

(dB•A)

57 / 54 / 51

59 / 56 / 53

 

57 / 54 / 51

59 / 56 / 53

Connecting pipe

Drain port

 

 

 

 

VP25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

7.5

7.5

 

7.5

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

3

3

 

3

3

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

75

75

 

75

75

Over 30m

 

 

 

 

40g/m (31m to 75m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

30

30

 

30

30

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

 

(m)

30

30

 

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Gas side

 

 

(mm)

15.9

15.9

 

15.9

15.9

 

 

 

 

 

 

 

 

 

Liquid side

 

 

(mm)

9.5

9.5

 

9.5

9.5

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

101

103

 

101

103

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

100 + 100

100 + 100

 

100 + 100

100 + 100

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

 

(dB•A)

49/50

51/52

 

49/50

51/52

 

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

 

(dB•A)

66/67

68/69

 

66/67

68/69

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 16 –

<Twin type>

 

 

Indoor unit 1

 

RAV-SM

562BT-E

802BT-E

802BT-E

562BT-E

802BT-E

802BT-E

Model

Indoor unit 2

 

RAV-SM

562BT-E

802BT-E

802BT-E

562BT-E

802BT-E

802BT-E

Outdoor unit

 

RAV-SP

1104AT8-E

1404AT8-E

1604AT8-E

1104AT7

1404AT7

1604AT7

 

 

 

 

 

 

 

 

 

1104AT8-TR

1404AT8-TR

1604AT8-TR

 

 

 

Cooling capacity

 

 

 

(kW)

10.0

12.5

14.0

10.0

12.5

14.0

 

 

 

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

11.2

14.0

16.0

11.2

14.0

16.0

 

 

 

(2.4-14.0)

(2.4-18.0)

(2.4-19.0)

(2.4-14.0)

(2.4-18.0)

(2.4-19.0)

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

3 phase 4wired (3N-4pole)

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

5.51 - 5.05

6.73 - 6.16

8.61 - 7.88

5.51

6.73

8.61

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.94

3.86

5.12

2.94

3.86

5.12

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

3.40

3.24

2.73

3.40

3.24

2.73

 

 

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

A

A

D

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

5.18 - 4.74

6.20 - 5.68

7.77 - 7.11

5.18

6.20

7.77

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.77

3.55

4.60

2.77

3.55

4.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

4.04

3.94

3.48

4.04

3.94

3.48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

A

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

16.4

16.4

16.4

16.4

16.4

16.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

Appearance

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

320

320

320

320

320

320

 

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

700

1000

1000

700

1000

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

800

800

800

800

800

800

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

30

39

39

30

39

39

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard air flow

H/M/L

(m³/min)

13.0/11.9/9.8

19.0/16.2/13.3

19.0/16.2/13.3

13.0/11.9/9.8

19.0/16.2/13.3

19.0/16.2/13.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

120

120

120

120

120

120

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

 

Standard

 

(Pa)

 

 

40

 

 

 

 

External static

(at shipment)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

Set up for

 

(Pa)

 

 

20/40/70/100

 

 

 

 

 

tap exchange

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

(dB•A)

40/37/33

40/37/34

40/37/34

40/37/33

40/37/34

40/37/34

 

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

55/52/48

55/52/49

55/52/49

55/52/48

55/52/49

55/52/49

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

VP25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

Standard length

 

 

(m)

7.5

7.5

7.5

7.5

7.5

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

50

50

50

50

50

50

 

 

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

15.9

15.9

15.9

15.9

15.9

15.9

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

12.7

15.9

15.9

12.7

15.9

15.9

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

9.5

9.5

9.5

9.5

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

6.4

9.5

9.5

6.4

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

101

103

103

101

103

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

49/50

51/52

51/53

49/50

51/52

51/53

 

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

66/67

68/69

68/70

66/67

68/69

68/70

 

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 17 –

<Triple type>

 

 

Indoor unit 1

 

RAV-SM

 

562BT-E

 

562BT-E

 

 

Indoor unit 2

 

RAV-SM

 

562BT-E

 

562BT-E

Model

 

 

 

 

 

 

 

 

Indoor unit 3

 

RAV-SM

 

562BT-E

 

562BT-E

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1604AT8-E

 

1604AT7

 

 

 

 

1604AT8-TR

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

14.0 (2.6-16.0)

 

14.0 (2.6-16.0)

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

16.0 (2.4-19.0)

 

16.0 (2.4-19.0)

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

8.61 - 7.88

 

8.61

 

 

Power consumption

 

(kW)

 

5.12

 

5.12

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

2.73

 

2.73

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

7.77 – 7.11

 

7.77

characteristics

 

 

 

 

 

 

Power consumption

 

(kW)

 

4.60

 

4.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

3.48

 

3.48

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

16.4

 

16.4

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

320

 

320

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

 

700

 

700

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

800

 

800

Total weight

Main unit

 

 

(kg)

 

30

 

30

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

 

 

Standard air flow

H/M/L

(m³/min)

 

13.0 / 11.9 / 9.8

 

13.0 / 11.9 / 9.8

 

 

 

 

 

 

 

 

 

 

Fan unit

Motor

 

 

(W)

 

120

 

120

 

 

 

Standard

 

(Pa)

 

 

40

 

 

External static

(at shipment)

 

 

 

 

 

 

 

 

 

 

 

pressure

Set up for

 

(Pa)

 

20/40/70/100

 

 

 

tap exchange

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

(dB•A)

 

40 / 37 / 33

 

40 / 37 / 33

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

 

55 / 52 / 48

 

55 / 52 / 48

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

VP25

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

7.5

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

50

 

50

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

15.9

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

 

12.7

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

9.5

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

 

103

 

103

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

100 + 100

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

51/53

 

51/53

Sound power level

Cooling/Heating

 

(dB•A)

 

68/70

 

68/70

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 18 –

1-1-3. Under Ceiling Type

<Single type>

 

 

Indoor unit

 

RAV-SM

1102CT-E

1402CT-E

1102CT-E

1402CT-E

Model

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

1104AT8-E

1404AT8-E

1104AT7

1404AT7

 

 

 

 

 

 

1104AT8-TR

1404AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

10.0

12.5

10.0

12.5

 

 

 

(2.6-12.0)

(2.6-14.0)

(2.6-12.0)

(2.6-14.0)

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

11.2

14.0

11.2

14.0

 

 

 

(2.4-14.0)

(2.4-18.0)

(2.4-14.0)

(2.4-18.0)

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

3 phase 4wired (3N-4pole)

 

 

 

 

380V - 415V 50Hz

380V 60Hz

 

 

 

 

 

 

 

 

Running current

 

 

(A)

5.23 - 4.79

6.67 - 6.11

5.23

6.67

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.79

3.83

2.79

3.83

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

81

87

81

87

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

(W/W)

3.58

3.26

3.58

3.26

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

A

A

 

Running current

 

 

(A)

4.99 - 4.57

6.46 - 5.92

4.99

6.46

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.67

3.70

2.67

3.70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

81

87

81

87

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

(W/W)

4.19

3.78

4.19

3.78

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

A

A

 

 

Maximum current

 

 

(A)

15.2

15.2

15.2

15.2

 

 

 

 

 

Indoor unit

 

 

 

Appearance

Main unit

 

 

 

 

Shine white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

210

210

210

210

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

1595

1595

1595

1595

 

 

 

Depth

 

(mm)

680

680

680

680

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

33

33

33

33

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

27.5/24.0/21.2

30.0/26.0/23.1

27.5/24.0/21.2

30.0/26.0/23.1

 

 

Motor

 

 

(W)

120

120

120

120

 

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

 

(dB•A)

41 / 38 / 35

43 / 40 / 37

41 / 38 / 35

43 / 40 / 37

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

 

(dB•A)

56 / 53 / 50

58 / 55 / 52

56 / 53 / 50

58 / 55 / 52

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

VP20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

Standard length

 

 

(m)

7.5

7.5

7.5

7.5

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

3

3

3

3

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

75

75

75

75

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

40g/m (31m to 75m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

30

30

30

30

 

 

Outdoor high

 

(m)

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Gas side

 

 

(mm)

15.9

15.9

15.9

15.9

 

 

 

 

 

 

 

 

Liquid side

 

 

(mm)

9.5

9.5

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

101

103

101

103

 

 

Motor

 

 

(W)

100 + 100

100 + 100

100 + 100

100 + 100

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

 

(dB•A)

49/50

51/52

49/50

51/52

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

 

(dB•A)

66/67

68/69

66/67

68/69

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 19 –

<Twin type>

 

 

Indoor unit 1

 

RAV-SM

562CT-E

802CT-E

802CT-E

562CT-E

802CT-E

802CT-E

Model

Indoor unit 2

 

RAV-SM

562CT-E

802CT-E

802CT-E

562CT-E

802CT-E

802CT-E

 

 

Outdoor unit

 

RAV-SP

1104AT8-E

1404AT8-E

1604AT8-E

1104AT7

1404AT7

1604AT7

 

 

 

 

 

 

1104AT8-TR

1404AT8-TR

1604AT8-TR

 

 

 

Cooling capacity

 

 

 

(kW)

10.0

12.5

14.0

10.0

12.5

14.0

 

 

 

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

(2.6-12.0)

(2.6-14.0)

(2.6-16.0)

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

11.2

14.0

16.0

11.2

14.0

16.0

 

 

 

(2.4-14.0)

(2.4-18.0)

(2.4-19.0)

(2.4-14.0)

(2.4-18.0)

(2.4-19.0)

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

3 phase 4wired (3N-4pole)

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

5.23 - 4.79

6.67 - 6.11

8.39 - 7.68

5.23

6.67

8.39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.79

3.83

4.99

2.79

3.83

4.99

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

3.58

3.26

2.81

3.58

3.26

2.81

 

 

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

A

A

C

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

4.99 - 4.57

6.46 - 5.92

7.77 -7.11

4.99

6.46

7.77

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.67

3.70

4.60

2.67

3.70

4.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

4.19

3.78

3.48

4.19

3.78

3.48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

A

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

14.8

15.6

15.6

14.8

15.6

15.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

Appearance

Main unit

 

 

 

 

 

Shine white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

210

210

210

210

210

210

 

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

910

1180

1180

910

1180

1180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

680

680

680

680

680

680

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

21

25

25

21

25

25

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

13.0/11.2/10.0

18.5/16.7/14.6

18.5/16.7/14.6

13.0/11.2/10.0

18.5/16.7/14.6

18.5/16.7/14.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

60

60

60

60

60

60

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

(dB•A)

36/33/30

38/36/33

38/36/33

36/33/30

38/36/33

38/36/33

 

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

51/48/45

53/51/48

53/51/48

51/48/45

53/51/48

53/51/48

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

VP20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

Standard length

 

 

(m)

7.5

7.5

7.5

7.5

7.5

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

50

50

50

50

50

50

 

 

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

15.9

15.9

15.9

15.9

15.9

15.9

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

12.7

15.9

15.9

12.7

15.9

15.9

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

9.5

9.5

9.5

9.5

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

6.4

9.5

9.5

6.4

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

101

103

103

101

103

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

49/50

51/52

51/53

49/50

51/52

51/53

 

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

66/67

68/69

68/70

66/67

68/69

68/70

 

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 20 –

<Triple type>

 

 

Indoor unit 1

 

RAV-SM

 

562CT-E

 

 

 

562CT-E

 

 

Indoor unit 2

 

RAV-SM

 

562CT-E

 

 

 

562CT-E

Model

 

 

 

 

 

 

 

 

 

 

Indoor unit 3

 

RAV-SM

 

562CT-E

 

 

 

562CT-E

 

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1604AT8-E

 

 

 

1604AT7

 

 

 

 

1604AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

14.0 (2.6-16.0)

 

 

14.0 (2.6-16.0)

 

 

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

16.0 (2.4-19.0)

 

 

16.0 (2.4-19.0)

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

380V - 415V 50Hz

 

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

8.39 - 7.68

 

 

8.39

 

 

Power consumption

 

(kW)

 

4.99

 

 

4.99

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

90

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

2.81

 

 

2.81

 

 

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

7.77 -7.11

 

 

7.77

characteristics

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

4.60

 

 

4.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

90

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

3.48

 

 

3.48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

15.3

 

 

15.3

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Main unit

 

 

 

 

 

Shine white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

210

 

 

210

 

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

 

910

 

 

910

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

680

 

 

680

Total weight

Main unit

 

 

(kg)

 

21

 

 

21

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

 

13.0 / 11.2 / 10.0

 

 

13.0 / 11.2 / 10.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

60

 

 

60

Sound pressure level

 

H/M/L

(dB•A)

 

36 / 33 / 30

 

 

36 / 33 / 30

 

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

 

51 / 48 / 45

 

 

51 / 48 / 45

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

 

VP20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

 

7.5

 

 

Min. length

 

 

(m)

 

3

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

50

 

 

50

 

 

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

 

30

 

 

 

30

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

 

15.9

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

 

12.7

 

 

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

 

 

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

 

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

Fan unit

Standard air flow high

(m³/min)

 

103

 

 

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

 

100 + 100

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

51/53

 

 

51/53

 

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

 

68/70

 

 

68/70

 

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 21 –

1-1-4. High Wall Type

<Twin type>

 

 

Indoor unit 1

 

RAV-SM

562KRT-E

802KRT-E

802KRT-E

562KRT-E

802KRT-E

802KRT-E

 

 

 

 

 

 

 

 

 

 

 

Model

Indoor unit 2

 

RAV-SM

562KRT-E

802KRT-E

802KRT-E

562KRT-E

802KRT-E

802KRT-E

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

1104AT8-E

1404AT8-E

1604AT8-E

1104AT7

1404AT7

1604AT7

 

 

 

 

 

 

1104AT8-TR

1404AT8-TR

1604AT8-TR

 

 

 

Cooling capacity

 

 

 

(kW)

10.0

12.3

14.0

10.0

12.3

14.0

 

 

 

(2.6-12.0)

(2.6-13.5)

(2.6-16.0)

(2.6-12.0)

(2.6-13.5)

(2.6-16.0)

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

11.2

14.0

16.0

11.2

14.0

16.0

 

 

 

(2.4-14.0)

(2.4-18.0)

(2.4-19.0)

(2.4-14.0)

(2.4-18.0)

(2.4-19.0)

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

3 phase 4wired (3N-4pole)

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

5.48 - 5.02

6.97 - 6.38

8.57 - 7.85

5.48

6.97

8.57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.92

4.00

5.10

2.92

4.00

5.10

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

3.42

3.08

2.75

3.42

3.08

2.75

Electrical

 

Energy efficiency class

 

 

A

B

D

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

5.33 - 4.88

6.78 - 6.20

8.24 - 7.54

5.33

6.78

8.24

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

2.85

3.88

4.88

2.85

3.88

4.88

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

81

87

90

81

87

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

3.93

3.61

3.28

3.93

3.61

3.28

 

 

Energy efficiency class

 

 

A

A

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

14.5

14.8

14.8

14.5

14.8

14.8

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Main unit

 

 

 

 

 

Pure white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

298

298

298

298

298

298

Outer dimension

Main unit

Width

 

(mm)

998

998

998

998

998

998

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

221

221

221

221

221

221

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

12

12

12

12

12

12

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Cross flow fan

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

14.0/12.5/10.7

18.5/14.6/12.2

18.5/14.6/12.2

14.0/12.5/10.7

18.5/14.6/12.2

18.5/14.6/12.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

(dB•A)

39/36/33

45/41/36

45/41/36

39/36/33

45/41/36

45/41/36

 

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

54/51/48

60/56/51

60/56/51

54/51/48

60/56/51

60/56/51

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

VP16

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

7.5

7.5

7.5

7.5

7.5

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

50

50

50

50

50

50

Over 30m

 

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

15.9

15.9

15.9

15.9

15.9

15.9

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

12.7

15.9

15.9

12.7

15.9

15.9

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

9.5

9.5

9.5

9.5

9.5

9.5

 

 

 

 

 

Sub

 

(mm)

6.4

9.5

9.5

6.4

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

101

103

103

101

103

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

49/50

51/52

51/53

49/50

51/52

51/53

Sound power level

Cooling/Heating

 

(dB•A)

66/67

68/69

68/70

66/67

68/69

68/70

 

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 22 –

<Triple type>

 

 

Indoor unit 1

 

RAV-SM

 

562KRT-E

 

 

562KRT-E

 

 

Indoor unit 2

 

RAV-SM

 

562KRT-E

 

 

562KRT-E

Model

 

 

 

 

 

 

 

 

 

Indoor unit 3

 

RAV-SM

 

562KRT-E

 

 

562KRT-E

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1604AT8-E

 

 

1604AT7

 

 

 

 

1604AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

14.0 (2.6-16.0)

 

 

14.0 (2.6-16.0)

 

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

16.0 (2.4-19.0)

 

 

16.0 (2.4-19.0)

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

8.57 - 7.85

 

 

8.57

 

 

Power consumption

 

(kW)

 

5.10

 

 

5.10

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

90

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

2.75

 

 

2.75

 

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

8.24 - 7.54

 

 

8.24

characteristics

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

4.88

 

 

4.88

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

90

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

3.28

 

 

3.28

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

14.9

 

 

14.9

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Main unit

 

 

 

 

 

 

Pure white

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

298

 

 

298

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

 

998

 

 

998

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

221

 

 

221

Total weight

Main unit

 

 

(kg)

 

12

 

 

12

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Cross flow fan

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

 

14.0 / 12.5 / 10.7

 

 

14.0 / 12.5 / 10.7

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

30

 

 

30

Sound pressure level

 

H/M/L

(dB•A)

 

39 / 36 / 33

 

 

39 / 36 / 33

 

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

 

54 / 51 / 48

 

 

54 / 51 / 48

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

 

VP16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

 

7.5

 

 

Min. length

 

 

(m)

 

3

 

 

3

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

50

 

 

50

 

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

 

30

 

 

30

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

 

15.9

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

 

12.7

 

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

 

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

Fan unit

Standard air flow high

(m³/min)

 

103

 

 

103

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

 

100 + 100

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

51/53

 

 

51/53

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

 

68/70

 

 

68/70

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 23 –

1-1-5. Compact 4-Way Cassette (600 × 600) Type

<Twin type>

 

 

 

Indoor unit 1

 

RAV-SM

 

562MUT-E

 

562MUT-E

 

 

 

 

 

 

 

 

 

 

Model

Indoor unit 2

 

RAV-SM

 

562MUT-E

 

562MUT-E

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1104AT8-E

 

1104AT7

 

 

 

 

 

1104AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

10.0 (2.6-12.0)

 

10.0 (2.6-12.0)

 

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

11.2 (2.4-14.0)

 

11.2 (2.4-14.0)

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

5.23 - 4.79

 

5.23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

2.79

 

2.79

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

81

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

3.58

 

3.58

Electrical

 

Energy efficiency class

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

4.99 - 4.57

 

4.99

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

2.67

 

2.67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

81

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

4.19

 

4.19

 

 

 

Energy efficiency class

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

14.9

 

14.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

Appearance

Ceiling panel

Model

 

 

 

RBC-UM11PG(W)-E

 

 

 

(Sold separately)

Panel color

 

 

 

Moon-white ( Muncel 2.5GY 9.0/0.5 )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

268

 

268

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

Width

 

(mm)

 

575

 

575

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

 

Depth

 

(mm)

 

575

 

575

 

 

 

 

 

 

 

 

Ceiling panel

Height

 

(mm)

 

27

 

27

 

 

 

 

 

 

 

 

 

Width

 

(mm)

 

700

 

700

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

700

 

700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

 

16

 

16

 

 

 

 

 

 

 

 

Ceiling panel (Sold separately)

 

(kg)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

Fan

 

 

 

 

 

Turbo fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

 

13.3 / 11.2 / 9.1

 

13.3 / 11.2 / 9.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

60

 

60

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

(dB•A)

 

43 / 39 / 34

 

43 / 39 / 34

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

 

58 / 54 / 49

 

58 / 54 / 49

Connecting pipe

Drain port

 

 

 

 

 

VP16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

50

 

50

Over 30m

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

15.9

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

 

12.7

 

12.7

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

 

101

 

101

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

100 + 100

Sound pressure level

Cooling/Heating

 

(dB•A)

 

49/50

 

49/50

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

 

66/67

 

66/67

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 24 –

<Triple type>

 

 

Indoor unit 1

 

RAV-SM

 

562MUT-E

 

562MUT-E

 

 

Indoor unit 2

 

RAV-SM

 

562MUT-E

 

562MUT-E

Model

 

 

 

 

 

 

 

 

Indoor unit 3

 

RAV-SM

 

562MUT-E

 

562MUT-E

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1604AT8-E

 

1604AT7

 

 

 

 

1604AT8-TR

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

14.0 (2.6-16.0)

 

14.0 (2.6-16.0)

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

16.0 (2.4-19.0)

 

16.0 (2.4-19.0)

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

8.39 - 7.68

 

8.39

 

 

Power consumption

 

(kW)

 

4.99

 

4.99

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

2.81

 

2.81

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

7.77 - 7.11

 

7.77

characteristics

 

 

 

 

 

 

Power consumption

 

(kW)

 

4.60

 

4.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

3.48

 

3.48

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

15.4

 

15.4

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

Appearance

Ceiling panel

Model

 

 

 

RBC-UM11PG(W)-E

 

 

(Sold separately)

Panel color

 

 

 

Moon-white ( Muncel 2.5GY 9.0/0.5 )

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

268

 

268

 

 

Main unit

Width

 

(mm)

 

575

 

575

 

 

 

 

 

 

 

 

 

 

Outer dimension

 

Depth

 

(mm)

 

575

 

575

 

 

 

 

 

 

 

 

Ceiling panel

Height

 

(mm)

 

27

 

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

 

(mm)

 

700

 

700

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

700

 

700

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

 

16

 

16

 

 

 

 

 

 

 

 

Ceiling panel (Sold separately)

 

(kg)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Turbo fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

 

13.3 / 11.2 / 9.1

 

13.3 / 11.2 / 9.1

 

 

Motor

 

 

(W)

 

60

 

60

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H/M/L

(dB•A)

 

43 / 39 / 34

 

43 / 39 / 34

 

 

 

 

 

 

 

 

 

Sound power level

 

H/M/L

(dB•A)

 

58 / 54 / 49

 

58 / 54 / 49

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

VP25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

7.5

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

50

 

50

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

30

 

 

Outdoor high

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

15.9

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

 

12.7

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

6.4

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

 

103

 

103

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

100 + 100

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

51/53

 

51/53

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

 

68/70

 

68/70

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 25 –

1-1-6. Slim Duct Type

<Twin type>

 

 

 

Indoor unit 1

 

RAV-SM

 

564SDT-E

 

564SDT-E

 

 

 

 

 

 

 

 

 

 

Model

Indoor unit 2

 

RAV-SM

 

564SDT-E

 

564SDT-E

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1104AT8-E

 

1104AT7

 

 

 

 

 

1104AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

10.0 (2.6-12.0)

 

10.0 (2.6-12.0)

 

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

11.2 (2.4-14.0)

 

11.2 (2.4-14.0)

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

5.23 - 4.79

 

5.23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

2.79

 

2.79

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

81

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

3.58

 

3.58

Electrical

 

Energy efficiency class

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

4.99 - 4.57

 

4.99

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

2.67

 

2.67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

81

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

4.19

 

4.19

 

 

 

Energy efficiency class

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

15.1

 

15.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

210

 

210

Outer dimension

Main unit

Width

 

(mm)

 

845

 

845

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

645

 

645

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

 

22

 

22

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Centrifugal fan

Fan unit

Standard air flow

H/M/L

(m³/min)

 

13.0 / 11.3 / 9.7

 

13.0 / 11.3 / 9.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

60

 

60

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Under air inlet

H/M/L

(dB•A)

 

45 / 40 / 36

 

45 / 40 / 36

 

 

 

 

 

 

 

 

Back air inlet

H/M/L

(dB•A)

 

33 / 31 / 28

 

33 / 31 / 28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound power level

Under air inlet

H/M/L

(dB•A)

 

60 / 55 / 51

 

60 / 55 / 51

Back air inlet

H/M/L

(dB•A)

 

48 / 46 / 43

 

48 / 46 / 43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

VP25

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

 

3

 

3

Outer dimension

Max. total length

 

 

(m)

 

50

 

50

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

15.9

Connecting pipe

Sub

 

(mm)

 

12.7

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

 

101

 

101

 

 

 

Motor

 

 

(W)

 

100 + 100

 

100 + 100

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

49/50

 

49/50

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

 

66/67

 

66/67

 

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 26 –

<Triple type>

 

 

Indoor unit 1

 

RAV-SM

 

564SDT-E

 

564SDT-E

 

 

Indoor unit 2

 

RAV-SM

 

564SDT-E

 

564SDT-E

Model

 

 

 

 

 

 

 

 

Indoor unit 3

 

RAV-SM

 

564SDT-E

 

564SDT-E

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1604AT8-E

 

1604AT7

 

 

 

 

1604AT8-TR

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

14.0 (2.6-16.0)

 

14.0 (2.6-16.0)

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

16.0 (2.4-19.0)

 

16.0 (2.4-19.0)

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

3 phase 4wired (3N-4pole)

 

3 phase 4wired (3N-4pole)

 

 

 

 

 

380V - 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

8.39 - 7.68

 

8.39

 

 

Power consumption

 

(kW)

 

4.99

 

4.99

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

2.81

 

2.81

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

Running current

 

 

(A)

 

7.77 - 7.11

 

7.77

characteristics

 

 

 

 

 

 

Power consumption

 

(kW)

 

4.60

 

4.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

90

 

90

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

3.48

 

3.48

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum current

 

 

(A)

 

15.8

 

15.8

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

210

 

210

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

 

845

 

845

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

 

645

 

645

Total weight

Main unit

 

 

(kg)

 

22

 

22

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

H/M/L

(m³/min)

 

13.0 / 11.3 / 9.7

 

13.0 / 11.3 / 9.7

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

60

 

60

Sound pressure level

Under air inlet

H/M/L

(dB•A)

 

45 / 40 / 36

 

45 / 40 / 36

 

 

 

 

 

 

 

 

Back air inlet

H/M/L

(dB•A)

 

33 / 31 / 28

 

33 / 31 / 28

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound power level

Under air inlet

H/M/L

(dB•A)

 

60 / 55 / 51

 

60 / 55 / 51

 

 

 

 

 

 

 

 

Back air inlet

H/M/L

(dB•A)

 

48 / 46 / 43

 

48 / 46 / 43

 

 

 

 

Connecting pipe

Drain port

 

 

 

 

 

VP25

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

7.5

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

50

 

50

 

 

 

 

 

 

 

 

Over 30m

 

 

 

 

40g/m (31m to 50m)

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas side

Main

 

(mm)

 

15.9

 

15.9

 

 

 

 

 

 

 

 

 

Connecting pipe

Sub

 

(mm)

 

12.7

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

Liquid side

Main

 

(mm)

 

9.5

 

9.5

 

 

 

 

 

 

 

Sub

 

(mm)

 

6.4

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

 

103

 

103

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

100 + 100

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

51/53

 

51/53

Sound power level

Cooling/Heating

 

(dB•A)

 

68/70

 

68/70

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 27 –

1-1-7. High Static Duct Type

<Single type>

Model

Indoor unit

 

RAV-SM

 

1403DT-A

 

1603DT-A

 

 

 

 

 

 

 

 

Outdoor unit

 

RAV-SP

 

1404AT8-E

 

1604AT8-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

(kW)

 

13.0 (3.3-14.1)

 

14.3 (3.3-16.0)

 

 

 

 

 

 

 

 

 

 

Heating capacity

 

 

 

(kW)

 

14.0 (4.2-18.0)

 

16.0 (4.2-19.0)

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

 

3 phase 4wired (3N-4pole) 415V 50Hz

 

 

Running current

 

 

(A)

 

6.89

 

7.71

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

4.32

 

5.01

 

 

 

 

 

 

 

 

 

 

 

Cooling

Power factor

 

 

(%)

 

87

 

90

 

 

 

 

 

 

 

 

 

 

 

 

EER

 

 

 

 

3.01

 

2.85

 

 

 

 

 

 

 

 

 

 

Electrical

 

Energy efficiency class

 

 

 

( B )

 

( C )

 

Running current

 

 

(A)

 

5.48

 

6.85

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

 

(kW)

 

3.43

 

4.43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Power factor

 

 

(%)

 

87

 

90

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

 

 

 

4.08

 

3.61

 

 

 

 

 

 

 

 

 

 

 

 

Energy efficiency class

 

 

 

( A )

 

( A )

 

 

Maximum current

 

 

(A)

 

16.3

 

16.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

Appearance

Main unit

 

 

 

 

Zinc hot dipping steel plate

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

 

 

380

 

 

 

 

 

 

 

 

 

 

Outer dimension

Main unit

Width

 

(mm)

 

 

1050

 

 

 

Depth

 

(mm)

 

 

600

 

 

 

 

 

 

 

 

 

 

Total weight

Main unit

 

 

(kg)

 

 

57

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Centrifugal fan

 

 

 

 

 

 

 

 

 

 

Standard air flow

at 100pa/HH tap

 

55.0

 

58.0

 

 

 

(m³/min)

 

 

 

 

 

 

 

 

 

 

Fan unit

Motor

 

 

(W)

 

 

600

 

 

 

 

 

 

 

 

 

 

 

Standard

 

(Pa)

 

 

100

 

 

External static

(at HH tap)

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

Range

 

(Pa)

 

 

50 – 250

 

 

 

at HH tap

 

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

 

H

(dB•A)

 

49

 

50

 

 

 

 

 

 

 

 

 

Sound power level

 

H

(dB•A)

 

64

 

65

Connecting pipe

Drain port

 

 

 

 

 

VP25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

 

(m)

 

7.5

 

7.5

 

 

 

 

 

 

 

 

 

 

 

 

Min. length

 

 

(m)

 

3

 

3

 

 

 

 

 

 

 

 

 

 

Outer dimension

Max. total length

 

 

(m)

 

75

 

75

Over 30m

 

 

 

 

 

40g/m (31m to 75m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hight difference

Outdoor lower

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

Outdoor high

(m)

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Gas side

 

 

(mm)

 

15.9

 

15.9

 

 

 

 

 

 

 

 

Liquid side

 

 

(mm)

 

9.5

 

9.5

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow high

(m³/min)

 

103

 

103

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

 

100 + 100

 

100 + 100

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

 

(dB•A)

 

51/52

 

51/53

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

 

(dB•A)

 

68/69

 

68/70

 

 

 

 

 

 

 

 

 

 

: IEC standard

– 28 –

1-2. Outdoor Unit

Model

Outdoor unit

RAV-SP

1104AT8-E

1404AT8-E

1604AT8-E

1104AT7

1404AT7

1604AT7

RAV-SP

1104AT8-TR

1404AT8-TR

1604AT8-TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 phase 4wired (3N-4pole)

3 phase 4wired (3N-4pole)

Power supply

 

 

 

 

380V – 415V 50Hz

 

380V 60Hz

 

 

 

 

 

 

(Power exclusive to outdoor required.)

(Power exclusive to outdoor required.)

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

 

 

Hermetic compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

Motor

 

 

(kW)

3.75

3.75

3.75

3.75

3.75

3.75

 

 

 

 

 

 

 

 

 

 

 

 

Pole

 

 

 

4

4

4

4

4

4

 

 

 

 

 

 

 

 

 

 

 

Refirigerant charged

 

 

(kg)

3.1

3.1

3.1

3.1

3.1

3.1

 

 

 

 

 

 

 

 

 

 

 

Refirigerant control

 

 

 

 

 

Pulse motor valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard length

 

(m)

7.5

7.5

7.5

7.5

7.5

7.5

 

 

 

 

 

 

 

 

 

 

 

 

Minmum length

 

(m)

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

Max. total length

 

(m)

75

75

75

75

75

75

Pipe

 

 

 

 

 

 

 

 

 

 

Additional refrigerant chrge

 

 

 

40g/m (31m to 75m)

 

 

 

 

 

 

 

 

 

under long piping connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

Outdoor lower

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

difference

Outdoor higher

(m)

30

30

30

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

 

(mm)

1340

1340

1340

1340

1340

1340

Outer

 

 

 

 

 

 

 

 

 

 

Width

 

 

(mm)

900

900

900

900

900

900

dimension

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

 

(mm)

320

320

320

320

320

320

 

 

 

 

 

 

 

 

 

 

 

Appearance

 

 

 

 

 

Silky shade (Muncel 1Y8.5-0.5)

 

 

 

 

 

 

 

 

 

 

 

 

Total weight

 

 

 

(kg)

95

95

95

95

95

95

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting pipe

Gas side

 

(mm)

15.9

15.9

15.9

15.9

15.9

15.9

 

 

 

 

 

 

 

 

 

Liquid side

 

(mm)

9.5

9.5

9.5

9.5

9.5

9.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

(m³/min)

101

103

103

101

103

103

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

(W)

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

100 + 100

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

49/50

51/52

51/53

49/50

51/52

51/53

 

(dB•A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

66/67

68/69

68/70

66/67

68/69

68/70

 

(dB•A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside air temperature, cooling

 

(°C)

 

 

46 to –15°C

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside air temperature, Heating

 

(°C)

 

 

15 to –20°C

 

 

 

 

 

 

 

 

 

 

 

 

 

– 29 –

Toshiba RAV-SP1104AT8Z-TR, RAV-SP1104AT8-TR, RAV-SP1404AT8-E, RAV-SP1404AT8-TR, RAV-SP1104AT8ZG-TR User Manual

1-3. Operation Characteristic Curve

• Operation characteristic curve, 50Hz <Super Digital Inverter>

RAV-SP1104AT8 (Z) (ZG)-E, -TR

RAV-SP1404AT8 (Z) (ZG)-E, -TR

RAV-SP1604AT8 (Z) (ZG)-E, -TR

<Cooling>

 

 

 

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

SP160

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

(A)

6

 

 

 

 

 

 

 

 

(A)

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP140

 

8

 

 

 

 

 

 

 

 

 

 

Current

5

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

SP110

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

• Conditions

 

 

 

 

2

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

Indoor : DB27˚C/WB19˚C

 

 

 

 

 

 

Indoor : DB20˚C

 

 

 

 

 

 

 

Outdoor : DB35˚C

 

 

 

2

 

 

 

 

Outdoor : DB7˚C/WB6˚C

 

1

 

 

 

Air flow : High

 

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

1

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

 

400V, 50Hz (3 phase)

 

 

 

 

 

 

400V, 50Hz (3 phase)

 

0

10

20

30

40

50

60

70

80

 

0

10

20

30

40

50

60

70

80

90

100 110

 

0

 

0

Compressor speed (rps)

Compressor speed (rps)

• Operation characteristic curve, 60Hz <Super Digital Inverter>

RAV-SP1104AT7 (Z) (ZG)

RAV-SP1404AT7 (Z) (ZG)

RAV-SP1604AT7 (Z) (ZG)

<Cooling>

 

 

 

 

 

 

 

 

<Heating>

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

(A)

6

 

 

 

 

 

 

 

 

(A)

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

Current

5

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

SP110

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

2

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

Indoor : DB27˚C/WB19˚C

 

 

 

 

 

 

 

Indoor : DB20˚C

 

 

 

 

 

 

Outdoor : DB35˚C

 

 

 

2

 

 

 

 

 

Outdoor : DB7˚C/WB6˚C

 

1

 

 

 

Air flow : High

 

 

 

 

 

 

 

 

Air flow : High

 

 

 

 

 

 

Pipe length : 7.5m

 

 

 

1

 

 

 

 

 

Pipe length : 7.5m

 

 

 

 

 

 

380V, 60Hz (3 phase)

 

 

 

 

 

 

 

380V, 60Hz (3 phase)

 

0

10

20

30

40

50

60

70

80

 

0

10

20

30

40

50

60

70

80

90

100 110

 

0

 

0

Compressor speed (rps)

Compressor speed (rps)

– 30 –

Loading...
+ 113 hidden pages