Simplex 4100ES Installation instructions and Operator's manual

Page 1
Fire Control Panels
UL, ULC, CSFM Listed; 4100-3106 IDNet Expansion Module with FM Approved* QuickConnect/QuickConnect2 Sensor Compatibility
Features
IDNet expansion module for 4100ES fire alarm control panels:
Provides 250 IDNet device point control including
both QuickConnect and QuickConnect2 sensors
Extends the 4100ES QuickConnect and
Requires a single block (4” x 5”) module location Also compatible with 4100U systems
Intended for upgrade of Simplex® 4010 fire alarm control panels:
Allows for system expansion beyond 250 addressable
points, up to the 2500 point capacity of the 4100ES control panel
Systems can retain the installed QuickConnect and/or
QuickConnect2 sensors
Additional IDNet SLC (Signaling Line Circuit)
channels are available from 4100ES standard or expansion IDNet modules
UL Listed to Standard 864
Description
4010 System Upgrade. The Simplex model 4010 fire
alarm control panel provides for up to 250 addressable points using IDNet communications. One of the 4010 unique devices is the QuickConnect sensor.
QuickConnect sensors provide TrueAlarm analog sensing in a feature optimized package, primarily suited to smaller systems. The original QuickConnect sensor has been replaced with the QuickConnect2 sensor.
When a facility expands beyond the capacity of the 4010 control panel, the preferred upgrade is the 4100ES fire alarm control panel. Standard 4100ES IDNet signaling line circuits (SLCs) are not compatible with QuickConnect sensors. However, with the 4100-3106, all of the 4100ES compatible IDNet devices and the QuickConnect and QuickConnect2 sensors can be connected to the same fire alarm control panel.
Expanded Sensitivity Range. Additionally, the 4100ES with the 4100-3106 module can provide a full range of sensitivity for the QuickConnect sensors with seven levels of adjustment from 0.2% to 3.7%. Standard sensitivities are
1.5%, 2.0%, 2.5%, and 3.7%. Sensitivities of 0.2%, 0.5%, and 1% are for special applications in clean areas. (For detailed application information including sensitivity selection, refer to Installation Instructions 574-709.)
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. This product was not approved by MEA (NYC) as of document revision date. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
To additional IDNet
devices, up to 250 total
Original Facility
Requirements
QuickConnect2
TrueAlarm sensor
Supervised IAM
ALARMFIRE
PULL DOWN
Addressable station
QuickConnect
TrueAlarm sensor
Original 250 point
4010 Fire Alarm
Control Panel
New 2500 point 4100ES
Fire Alarm Control Panel
4100-3106 IDNet module
with QuickConnect
Sensor Support
Modular TrueAlarm
sensor with base
Modular TrueAlarm sensor
with IDNet isolator base
TM
4009 IDNet NAC EXTENDER
4009 IDNet NAC
Extender
5
1
6
2
SIMPLEX TI ME RECO RDER CO.
7
3
4090-9002 RELAY IAM INSTAL. INSTR. 574-184 DATE CODE:
8
4
1
Monitor ZAMs
and Relay IAMs
Facility Expansion
Requirements
To additional IDNet
devices, up to 250
total per IDNet SLC
CAUTION
DISCONNECT
POWER BEFORE SERVICING
IDNet SLC channel for standard devices
4010 System Expansion using a 4100-3106 IDNet Module
4100-3106 Specifications
Capacity 250 points
Standby Current
Alarm Current
Operating Temperature Range
Humidity Range
Mounting
Installation Instructions 574-800
with 250 devices 275 mA
without devices 75 mA
per device 0.8 mA
with 250 devices 265 mA
without devices 115 mA
per device 1 mA
32 F to 120 F (0 C to 49 C)
Up to 93% RH, non-condensing @ 90° F (32° C)
Single 4100ES block; 4” x 5” (102 mm x 127 mm)
S4100-0039-4 2/2014
Page 2
Addressable Device Control Reference
Overview. The 4100ES provides standard addressable
device communications for IDNet compatible devices and accepts optional modules for communications with MAPNET II compatible devices. Using a two-wire communications circuit, individual devices such as manual fire alarm stations, TrueAlarm sensors, conventional IDC zones, and sprinkler waterflow switches can be interfaced to the addressable controller to communicate their identity and status.
Addressability allows the location and condition of the connected device to be displayed on the operator interface LCD and on remote system annunciators. Additionally, control circuits (fans, dampers, etc.) may be individually controlled by using a relay IAM (individual addressable module).
Addressable Operation. Each addressable device on the communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuit for Class B (Style 4) operation. The device LED blinks to indicate receipt of a communications poll and is steady on to indicate an alarm (or trouble) condition.
IDNet Channel Capacity. The CPU bay system power supply (SPS) provides an IDNet signaling line circuit (SLC) that supports up to 250 addressable monitor and control points intermixed on the same pair of wires. Additional IDNet circuit modules are available for 64, 127, or 250 addressable devices.
Wiring Requirements for IDNet Communications.
Refer to the specifications chart below. Distances are for shielded or unshielded wire. Shielded wire may provide protection from unexpected sources of interference.
Wiring Specifications
Size 18 AWG minimum (0.82 mm2 )
Type
Farthest Distance from Control Panel to Device
Total Wire Length Allowed With “T” Taps for Class B Wiring
* Some applications may require shielded wiring. Review system
with your local Simplex product supplier.
Preferred Shielded twisted pair (STP)
Acceptable* Unshielded twisted pair (UTP)
Up to 2500 feet (762 m)
Up to 10,000 ft (3 km).
Additional Simplex Product Reference
Product Data Sheet Reference
QuickConnect2 Sensors S4098-0034
Standard TrueAlarm Sensors S4098-0019
Basic 4100ES Fire Alarm Control Panels
Basic 4100ES Fire Alarm Control Panels with EPS/EPS+ for IDNAC Addressable Notification
S4100-0031
S4100-0100
Expansion Bay Module Loading Reference
Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2
Block A
Block B
Size Definitions: Block = 4” W x 5” H card area
Slot = 2” W x 8” H motherboard with daughter card
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.