3.1 Mounting the 4007ES panels..............................................................................................................................................................................6
3.2 Trim Kit.................................................................................................................................................................................................................. 7
4NAC power supply.........................................................................................................................................................11
4.1 NAC power supply specifications.....................................................................................................................................................................12
4.3.3Class A wiring....................................................................................................................................................................................................................... 14
4.3.4Class B wiring....................................................................................................................................................................................................................... 15
5IDNAC power supply.....................................................................................................................................................17
5.1 Power supply specifications............................................................................................................................................................................. 18
5.5 IDNAC Class B wiring tables............................................................................................................................................................................. 20
5.6 IDNAC Class B wiring......................................................................................................................................................................................... 21
5.7 Compatible devices and appliances................................................................................................................................................................ 22
5.9.1SLC channel trouble LED codes...................................................................................................................................................................................... 27
5.9.2System trouble LED codes................................................................................................................................................................................................28
64007ES power supplies.................................................................................................................................................29
6.1 Power supplies specifications.......................................................................................................................................................................... 29
6.4 Device addressing, Class A and Class B.......................................................................................................................................................... 30
6.6 Class A Wiring..................................................................................................................................................................................................... 32
6.7 Class B Wiring..................................................................................................................................................................................................... 32
6.8 Auxiliary power selection.................................................................................................................................................................................. 33
7Optional modules and cards....................................................................................................................................... 37
7.1 Example of combinations................................................................................................................................................................................. 38
8Appendix A ULC programming requirements........................................................................................................... 39
8.1 Common earth fault ground and common trouble indicator......................................................................................................................39
CONTENTS
Page 4
This page is intentionally blank
Page 5
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
1 Cautions, Warnings, and Regulatory Information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the
contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized
Simplex product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
EYE SAFETY HAZARD Under certain fiber optic application conditions, the optical output of this device may exceed eye safety limits. Do
not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
SULFURIC ACID WARNING Battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can destroy
fabric. Replace any leaking or damaged battery while wearing appropriate protective gear. If you come in contact with sulfuric acid,
immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
FCC RULES AND REGULATIONS – PART 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with
NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations,
or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper
system operation verified.
Page 3579-1102 Rev H
Page 6
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
2 Overview
The 4007ES fire alarm control panel provides audible and visible indication of alarms, troubles, and supervisory conditions. The 4007ES panels
supports addressable notification and initiating devices and the 4007ES Hybrid panels supports non-addressable notification devices and addressable
initiating devices*. The panel can be configured by using a panel programmer.
*From this point on, the 4007ES and the 4007ES hybrid is referred to as 4007ES, unless stated otherwise.
4007ES operator instructions are described in the 4007ES Operator’s Manual 579-1165.
4007ES programming instructions are described in the 4007ES Programmer’s manual 579-1167.
2.1 4007ES product list
Table 1: Product list
Part numberBase panels
4007-91014007ES Hybrid, red
4007-92014007ES, red
4007-91024007ES Hybrid, platinum
4007-92024007ES, platinum
Table 2: Product List and manual
Part numberOptional modules: field installedManual
4007-9801Zone/Relay Module579-1103
4007-980225V Regulator Module579-812
4007-9803IDNet+ Loop Expansion Module579-1106
4007-9804Dual Class A Module579-1029
4007-9805LED Module579-1105
4007-9806DACT Module579-954
4007-9807City Circuit with Disconnect Module579-955
4007-9808City Circuit without Disconnect Module579-955
4007-9809Relay Module579-955
4007-98104120 NIC579-956
4007-9812Dual RS-232 Module579-910
4007-9813Wired Media Card579-956
4007-9814Fiber-Optic Media Card579-956
4190-6106TrueInsight Remote Service Gateway and Programming579-953
Page 4579-1102 Rev H
Page 7
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
2.2 Glossary
Table 3: Glossary
TermDefinition
AuxAbbreviation for Auxiliary; typically used to describe Auxiliary Power.
EOL
FACPFire Alarm Control Panel.
Hybrid
IDCInitiating Device Circuit.
IDNetAddressable SLC for up to 250 addressable devices.
IDNet+IDNet which is electrically isolated from internal panel electronics.
IDNACIndividual Device Notification Appliance Circuit (Addressable).
NACNotification Appliance Circuit, formerly called signal circuit.
NICNetwork Interface Card for the 4120 network.
Regulated 24 DC
RS-232 module
RUI
Simple NAC
SLCSignaling Line Circuit
SmartSync
User interface The user interface is a 4.3 in. (109mm) diagonal color LCD with a built-in resistive touch panel and 12 indicating LEDs. The color LCD
provides system status and access to perform system functions and to change the system configuration.
Figure 1: 4007ES panel inside view on page 5 shows an inside view of the 4007ES panel with the optional LED module (4007-9805) installed.
End-of-Line, typically in reference to and end-of-line resistor or EOL
resistor.
In this document, “Hybrid” the 4007ES Hybrid models that provide both
addressable and conventional initiation with conventional non addressable Notification Appliance Circuits.
Notification appliance operation that meets the minimum listing
requirements; inrush currents typically require power supply and NAC rating.
The Dual RS-232 interface module provides a serial communication
interface to an AC or DC printer, a PC Annunciator, or a third party computer.
Remote Unit Interface; SLC for communications with remote
annunciators.
A Reverse Polarity Supervised Notification Appliance Circuit that is
capable of on steady or coded operation. Sync or SmartSync operation is not supported.
A reverse polarity monitored NAC capable of synchronizing and
controlling both horns and strobes on the same circuit using a proprietary signaling protocol. Used as the
protocol for TrueAlert Non-Addressable Devices.
Fig 1: 4007ES panel inside view
Page 5579-1102 Rev H
Page 8
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
3 Installation
Introduction
This chapter describes how to install the 4007ES panel. It can be semi-flush or surface mount.
3.1 Mounting the 4007ES panels
• Due to the danger of metal fragments falling into electronics when drilling the holes for the conduits, remove the electronics in the system:
- To remove the electronics, unscrew the ten screws. Remove the power supply and store it in a safe, clean, and dry location until the panel
installation is completed, see Figure 2: Screws location on page 6.
- If installing a 4007ES hybrid panel, also remove the Zone/Relay card (three screws).
• Use a suitable punch where a conduit entrance is required. The knockouts are not provided. Locate and create on-site as required during installation.
Fig 2: Screws location
• For surface or semi-flush mounting to a wooden wall structure, the panel must be attached with four 1 1/2 in. (38 mm) long lag bolts and four 1/2 in.
(13 mm) diameter washers, supplied by others.
• For surface mounting, secure the box to the wall using the tear-drop mounting holes on the back surface. For semi-flush mounting, secure the box
along the sides to the wall studs. Note that the front surface of the back box must protrude at least 1-1/2 in. (38mm) from the wall surface for semiflush installation. A trim kit is supplied for semi-flush mounting, see the Trim kit application on page 7 section for more information.
• To install the panel, see Figure 3: Back Box Installation dimensions and Semi-Flush Mounting (Right) on page 7 for the dimensions and use the
holes in the back box to secure it to the wall.
Page 6579-1102 Rev H
Page 9
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 3: Back Box Installation dimensions and Semi-Flush
Mounting (Right)
3.2 Trim Kit
3.2.1 Trim kit application
Trim kits are used to cosmetically cover wall openings when boxes are mounted semi-flush into the wall. The kit includes:
• Two top trim bands (shorter).
• Two side trim bands (longer).
• Four corner pieces.
Fig 4: Semi-flush trim kit
After mounting the box semi-flush to the wall, attach the trim per the following procedure:
1. The strips need to be cut before being attached. Carefully cut them to length using a hacksaw or sharp utility knife. Cut the strips approximately
1in. (25 mm) shorter than the box dimension. The box is 20-7/8 in. (530 mm) wide and 20-3/16 in. (512 mm) high.
2. Attach the strips one at the time. Peel off the adhesive tape release and center the strip on the box placing the edge of the strip against the box
surface, then press solidly to assure adhesion.
3. Each corner piece overlaps the trim strip slightly less than 3/4 in. (19 mm). Align the corner pieces tight to the box corner and attach with a drywall
or similar screw, suitable for the wall material. The screws are not supplied.
Fig 5: Applying the trim
Page 7579-1102 Rev H
Page 10
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
3.3 Wiring
Wiring guidelines
Follow these guidelines when connecting power-limited (PL) systems. For more information about these guidelines, contact your authorized Simplex
product supplier.
• Non-power limited (NPL) field wiring (AC power, batteries, City connection, DACT) must be installed and routed in the shaded areas shown in Figure 6:
Field wiring guidelines (NAC power supply shown as reference) on page 8
• You must maintain a minimum of 0.25 in. (6.35 mm) space between NPL and PL field wiring.
• The AC harness is pre-wired and tied to back of the box.
Fig 6: Field wiring guidelines (NAC power supply shown as reference)
• The conductors must test free of all grounds.
• A system ground must be provided for earth detection and lightning protection devices. This connection must comply with approved earth detection
per NFPA780.
• Splicing is permitted. All spliced connections must either be soldered (resin-core solder), crimped in metal sleeves, or encapsulated with an epoxy
resin. When soldering or crimped metal sleeves are used, the junction must be insulated with a high-grade electrical tape that is as sound as the
original insulating jacket. Shield continuity must be maintained throughout.
• Excess slack should be kept to a minimum inside the back box enclosure. The wiring should be neatly dressed and bundled together using wire ties.
• All wiring must use copper conductors only, unless noted otherwise.
• For IDNet, shielded wire is not recommended. If shielded wires are present, cut and tape off the shield at each end in the panel to prevent it coming
into contact with other components. The metallic continuity of the shield must be maintained and insulated throughout the entire length of the
cable.
• If shielded wire is used, the metallic continuity of the shield must be maintained throughout the entire cable length, and the entire length of the cable
must have a resistance greater than 1 megohm to earth ground. Underground wiring must be free of all water.
Page 8579-1102 Rev H
Page 11
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 7: EOL relay diagram
• In areas of high lightning activity, or in areas that have large power surges, use the 2081- 9027 or the 2081-9044 Transient Suppressor on monitor
points.
• Wires must not be run through elevator shafts.
• Only system wiring can be run together in the same conduit. When powering remote units using relay contacts, power for these circuits must be
provided by a PL power supply listed for fire-protective signaling use. An end-of-line (EOL) relay must be used to supervise the auxiliary power circuit.
• Connect the output of the EOL relay to cause a trouble. Wire in series with the EOL resistor on an available initiating device circuit (IDC) or individual
addressable module (IAM).
3.3.1 Safety ground/ ferrite bead
Correct operation and protection against transient energy in accordance with UL 864 and ULC-S527 require the connection of safety ground wire to
cabinet chassis. Connect the safety ground before wiring any other circuits to the panel. Ferrite beads must be attached to the incoming AC power line
as shown in Figure 8: Safety ground and ferrite bead on page 9. Wrap the line leg twice through a ferrite bead, and the neutral leg of the power
line twice through the other ferrite bead.
Fig 8: Safety ground and
ferrite bead
NOTE: The ferrite bead should be installed as close as possible to where power enters the panel.
3.3.2 AC supply wiring
Adhere to the following guidelines when wiring AC Power. See Safety ground/ ferrite bead on page 9 for information about attaching the ferrite
bead to the AC power wires.
• The AC power must be wired from a dedicated circuit breaker or fuse, rated no more than 20 A, in accordance with NFPA-72, NEC, and local codes.
• Before handling the AC feed, verify that it is not live using a voltmeter. Make sure the circuit is de-energized and tagged to prevent injury.
• The AC supply wiring must be 14 AWG minimum to 12 AWG maximum.
• Connect a 12 AWG copper ground wire from safety ground in the electrical distribution panel to the panel safety ground stud.
• Input voltage:
- 120 VAC, 50/60 Hz.
- 240 VAC, 50/60 Hz.
No configuration settings required to select.
Page 9579-1102 Rev H
Page 12
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
3.3.3 Battery guidelines
A fused harness is required to connect the backup batteries. Use harness 734-304 for a NAC power supply, and harness 734-303 for an IDNAC power
supply. The harness is shipped with the panel. The mating spade lug on the battery should be 0.250 in. X 0.032 in. (6.35 mm X 0.81 mm). If another size
is needed, you need to replace the battery terminal connectors on the supplied battery harness.
• The 4007ES battery charger supports up to 33 Ah batteries (maximum) within UL864 and ULCS527 guidelines.
- 18 Ah batteries can fit inside the box.
- 25 Ah and 33 Ah batteries use 2081-9282(red 25 Ah or 33 Ah) or 4009-9801 (beige 25 Ah).
• To minimize the power losses due to wiring from the external battery box to the 4007ES, use at least a 12 AWG wire. Mount the battery box within 20
feet (609.6 cm) of the panel in accordance with the mounting instruction label in the box. All interconnecting wiring must be enclosed in conduit.
• Seismic battery brackets can be used internally in the 4007ES box (the 2081-9401: 12.7 Ah bracket, and the 2081-9402: 18 Ah bracket). For more
information on how to install the seismic brackets, see the Battery Bracket installation instructions (579-944).
3.4 Power
Final installation To finalize the installation:
1. Reinstall the power supply and the electronics.
2. To install the batteries:
a. Place the first battery on the left side of the panel to avoid interference with the DACT, if installed.
NOTE: The battery terminals should face the front of the box.
b. Insert the second battery and make sure it is snugly positioned beside the first battery.
c. Wire the batteries in series such that you have 24 V. Use the white wire provided to bridge the batteries together, see Figure 9: Power supply on
page 10.
IMPORTANT: Verify all field wiring before applying any power to the panel.
Power up the system:
1. Connect the negative lead to the battery.
2. Apply AC.
3. Connect the positive to the battery.
Fig 9: Power supply
Page 10579-1102 Rev H
Page 13
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4 NAC power supply
A conventional reverse polarity NAC power supply is used in a 4007ES hybrid panel. It provides 6A and can support the following:
• Non-addressable notification devices.
• Addressable initiating devices.
See Figure 10: NAC power supply on page 11 and Table on page 11 for the main components of the NAC power supply.
Fig 10: NAC power supply
Table 4: Main components information
P1RUI Class A/B jumpersP2IDNet Class A/B jumper
TB4Battery connectionTB2NAC 1 and NAC 2
P10AC Power ConnectionTB3NAC 3 and NAC 4
J5 and J15Zone / RelayJ7IDNet Loop B
J16CPU ConnectionJ8IDNet Loop C
J17Option ConnectionP4NAC Power Supply Card On-line
P11City/Relay ConnectionP6Battery Depleted Jumper
P81-2 (default) / IDNet card on line
TB1
IDNet Loop 1, Aux Power, RUI
Connection
P9
25V Regulator Jumpers 1-2, 3-4
default. Power is fed to the zone/ relay card. No jumpers.
Using 4007-9802, 25V Regulator Module.
Page 11579-1102 Rev H
Page 14
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.1 NAC power supply specifications
The NAC power supply can supply 6 A of 24 V power in addition to the base draw of the CPU/ Power Supply cards. The current draw taken from
optional cards, IDNet Devices, Aux Power, and NACs must be subtracted from 6 A.
IMPORTANT: See the 4007-9801 8-Point Zone/Relay Card Installation Instructions 579-1103, to determine the draw of the pre-installed Zone/Relay
card.
Table 5: 4007ES hybrid system current draw
Maximum AC input
Standby conditions
No alarms (NACs normal). No IDNet devices connected.145 mA
Add to above for each additional IDNet device in standby.0.8 mA
Total current for fully loaded IDNet channel in standby.345 mA
Alarm conditions
4 NACs ON: TBL Relay Activated: IDNet LED On. No IDNet devices connected.190 mA
Add to above for each IDNet device in alarm.1 mA
Add to above for each IDNet LED On (20 maximum IDNet devices LEDs On).2 mA
Total current for fully loaded IDNet channel in alarm.480 mA
2 A at 120 VAC, 50/60Hz
1 A at 240 VAC, 50/60Hz
Current
(battery standby 24 V)
Current
(battery alarm 24 V)
4.2 NAC section overview
The NAC power supply allows connection to up to four Class A NAC circuits. Notification appliances within the 4007ES system are synchronized
including any attached 4009 series NAC extenders. Do not mix Wheelock and Simplex branded devices in the same system, they will not be
synchronized. The following TrueAlert non-addressable appliances are Special Application compatible with the NAC power supply:
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.3 Specifications
Table 6: Specifications
Maximum appliances70 per circuit.*
* Each 49CMT series appliance counts as 5 regular appliances for the maximum 70 appliances that can be supported per NAC. As the earth fault
sensitivity with thirteen MT appliances drops from 10 K to 9.6K ohms, no more than thirteen 49CMT series appliances may be placed on one circuit.
Electrical specifications:
Voltage24 VDC nominal.
Alarm currentThe maximum alarm current is 3 A per circuit.
Supervisory currentRefer to Table on page 13.
Special application appliances (TrueAlert Non-
Addressable)
NOTE:
When NACs are used for Regulated 24DC appliances, maximum current per NAC is reduced to 2 A and total power supply notification current rating
is reduced to 3 A. Current used by modules powered from the 4007ES power supply must be deducted from the total current.
4.3.1 Wiring parameters
The NAC power supply is supervised and power-limited. See Table on page 13 for the NACs’ supported EOL resistors and the related supervisory
current, and see Table on page 13 for the wiring parameters.
NOTE: If a shielded wire is used, cut it and tape it at both ends.
Table 7: Wiring parameters
Maximum wiring distance
Maximum cable load10,000 ft (3,048 m) per channel
Maximum wire length from panel to any device4,000 ft (762 m)
Maintain the correct polarity on terminal connections. Do not loop wires under terminals.
Table 8: Supported EOLR and supervisory current
6 A total.
EOLRCurrent
3.9 k5.7 mA
4.7 k4.8 mA
5.1 k4.4 mA
5.6 k4.0 mA
10 k2.2 mA
15 k1.4 mA
Page 13579-1102 Rev H
Page 16
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.3.2 Wiring distances
Table on page 14 lists the maximum distances from the NAC terminal block to the last appliance in a Class A configuration, depending on wire
gauge and current. Use Table on page 14 to calculate the wire distances for your application if you are using Class A wiring. Table on page 14
gives the values for a Class B configuration.
Table 9: Class A wiring distances
Alarm current
0.25 A420 ft (128 m)667 ft (203 m)1,063 ft (324 m)1,691 ft (515 m)6 Ohms
0.50 A210 ft (64 m)334 ft (102 m)532 ft (162 m)845 ft (258 m)3 Ohms
0.75 A140 ft (43 m)222 ft (68 m)354 ft (108 m)564 ft (172 m)2 Ohms
1.00 A105 ft (32m)167 ft (51 m)266 ft (81 m)423 ft (129 m)1.5 Ohms
1.25 A84 ft (26 m)133 ft (41 m)213 ft (65 m)338 ft (103 m)1.2 Ohms
1.50 A70 ft (21 m)111 ft (34 m)177 ft (54 m)282 ft (86 m)1 Ohm
1.75 A60 ft (18 m)95 ft (29 m)152 ft (46 m)242 ft (74 m)0.86 Ohm
2.00 A53 ft (16 m)83 ft (25 m)133 ft (41 m)211 ft (64 m)0.75 Ohm
2.25 A47 ft (14 m)74 ft (23 m)118 ft (36 m)188 ft (57 m)0.67 Ohm
2.50 A42 ft (13 m)67 ft (20 m)106 ft (32 m)169 ft (51 m)0.60 Ohm
2.75 A38 ft (12 m)61 ft (19 m)97 ft (30 m)154 ft (47 m)0.55 Ohm
3.00 A35 ft (11 m)56 ft (17 m)89 ft (27 m)141 ft (43 m)0.50 Ohm
Table 10: Class B wiring distances
Alarm current
0.25 A840 ft (256 m)1,335 ft (407 m)2,126 ft (648 m)3,382 ft (1,031 m)12 Ohms
0.50 A420 ft (128 m)667 ft (203 m)1,063 ft (324 m)1,691 ft (515 m)6 Ohms
0.75 A280 ft (85 m)445 ft (136 m)709 ft (216 m)1,127 ft (344 m)4 Ohms
1.00 A210 ft (64 m)334 ft (102 m)532 ft (162 m)845 ft (258 m)3 Ohms
1.25 A168 ft (51 m)267 ft (81 m)425 ft (130 m)676 ft (206 m)2.4 Ohms
1.50 A140 ft (43 m)222 ft (68 m)354 ft (108 m)564 ft (172 m)2 Ohms
1.75 A120 ft (37 m)191 ft (58 m)304 ft (93 m)483 ft (147 m)1.71 Ohms
2.00 A105 ft (32 m)167 ft (51 m)266 ft (81 m)423 ft (129 m)1.5 Ohms
2.25 A93 ft (28 m)148 ft (45 m)236 ft (72 m)376 ft (115 m)1.33 Ohms
2.50 A84 ft (26 m)133 ft (41 m)213 ft (65 m)338 ft (103 m)1.2 Ohms
2.75 A76 ft (23 m)121 ft (37 m)193 ft (59 m)307 ft (94 m)1.09 Ohms
3.00 A70 ft (21 m)111 ft (34 m)177 ft (54 m)282 ft (86 m)1 Ohm
Max distance w/ 18
AWG(0.8231 mm2)
Max distance w/ 18
AWG(0.8231 mm2)
Max distance w/ 16
AWG(1.309 mm2)
Max distance w/ 16
AWG(1.309 mm2)
Max distance w/ 14
AWG(2.081 mm2 )
Max distance w/ 14
AWG(2.081 mm2)
Max distance w/ 12
AWG(3.309 mm2)
Max distance w/ 12
AWG(3.309 mm2)
DC resistance
DC resistance
NOTE:
• Max distance = distance from the power supply to last appliance.
• This table is calculated at 49°C (120°F). If you are installing in locations that could be exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output voltage.
• If circuit integrity wire is used instead of housing cable in a fire rated enclosure, reduce the wiring distances by 38 ft (12 m) for every 10 ft (3 m) of
potential exposure.
4.3.3 Class A wiring
NOTE: The Class A wiring style is set up in the ES Panel Programmer. See the 4007ES Programmer’s Manual (579-1167), for more information.
To connect the power supply to reverse-polarity, non-addressable notification appliances using Class A wiring, complete the following steps:
1. Route wire from the B+ and B- outputs of the power supply to the appropriate inputs on a peripheral notification appliance. Use NAC1, NAC2,
NAC3, or Figure 12: Class A NAC wiring on page 15.
2. Route the wire from the first appliance to the next. Repeat this for each appliance.
Page 14579-1102 Rev H
Page 17
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 12: Class A NAC wiring
3. Route the wire from the last appliance to the A+ and A- inputs on the same NAC circuit of the power supply.
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the 10 KOhms, 1/2 W, brown/black/orange resistor (378-030) on each unused circuit. No external end-of-line resistor is needed for circuits in
use.
4.3.4 Class B wiring
NOTE: The Class B wiring style is set up in the ES Panel Programmer. See the 4007ES Programmer’s Manual (579-1167), for more information.
To connect the power supply to appliances using Class B wiring, complete the following steps:
1. Route the wire from the B+, B- outputs on TB2 and TB3 of the power supply to the appropriate inputs on a peripheral notification appliance. Use
NAC1, NAC2, NAC3, or NAC4.
Fig 13: Class B NAC wiring
2. Route the wire from the first appliance to the next. T-tapping is not permitted. Repeat this for each appliance.
3. Route the wire from the last appliance to the EOLR harness (10KOhms, 1/2 W: P/N 733- 894).
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the factory installed EOL resistor (10 KOhms*, 1/2 W; brown/black/orange) on each unused circuit. The circuit must connect B+ to B-
terminals.
6. Document the EOL value in the panel for each circuit.
*If using a 4007ES hybrid panel, keep the original value and set the ES Panel Programmer accordingly.
Page 15579-1102 Rev H
Page 18
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
4.4 Troubleshooting
Figure 14: LEDs on the 4007ES hybrid power supply on page 16 and Table on page 16 show the LED definition for the NAC power.
Fig 14: LEDs on the 4007ES hybrid power supply
Table 11: LEDs on the 4007ES hybrid power supply
LED10ACGreen. Off on AC failure.
LED2RUI TroubleYellow. On for Class A RUI trouble.
LED6RUI OCYellow. Indicates a short (overcurrent).
LED3CommYellow. Indicates that the communication between the NAC power supply and the CPU is lost.
LED 4Gen PowerSteady On, yellow. Indicates AC power loss, earth fault, overcurrent and battery trouble.
LED5, 7, 8,
and 9
LED1Aux/SNACSteady On, yellow. Use to signal overcurrent, short, and open circuit.
NAC 1, 2, 3,
4
Steady On, yellow. Used to signal overcurrent, short, and open circuit.
Page 16579-1102 Rev H
Page 19
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5 IDNAC power supply
An IDNAC power supply is used in the 4007ES panel, the non-hybrid panel. It provides 4 A and can support the following:
• Addressable notification devices.
• Addressable initiating devices.
See Figure 15: IDNAC power supply on page 17 and Table on page 17 for the main components of the IDNAC power supply.
Fig 15: IDNAC power supply
Table 12: Main components information
P1RUI Class A/B jumpersP2IDNet Class A/B jumper
TB4Battery connectionTB2IDNAC
P10AC Power ConnectionTB3Aux Relay 1 and 2
J15
J7Zone/RelayJ11IDNet Loop 3
J16CPU ConnectionP5Battery Depleted Jumper
J17Option ConnectionP81-2 (default) / IDNet card on line
P11City Circuit Connection
TB1IDNet Loop 1, Aux Power, RUI Connection
Page 17579-1102 Rev H
DCAI
Zone/Relay Connection
J10IDNet Loop 2
25V Regulator Jumpers 1-2, 3-4
P9
default. Power is fed to the zone/relay card. No jumpers.
Using 4007-9802, 25V Regulator Module
Page 20
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
+ -
IDNAC
+ -
5.1 Power supply specifications
The IDNAC Power Supply can supply 4A of 24V power in addition to the base draw of the CPU/power supply cards. The current draw taken from
optional cards, IDNet Devices, Aux Power, and NACs must be subtracted from 4A.
Table 13: 4007ES system current draw
Maximum AC input
2 A at 120 VAC, 50/60 Hz
1 A at 240 VAC, 50/60 Hz
Standby conditions (see Note 1)Current (see Note 1) (Battery Standby 24 V)
No alarms (NACs normal). No IDNet devices connected180 mA
Add to above for each additional IDNet or IDNAC device in standby0.8 mA
Total current for fully loaded IDNet or IDNAC channel in standby431 mA
Alarm conditions (see Note 1)Current (see Note 1) (Battery Alarm 24 V)
IDNAC ON: No IDNet LED On. No IDNet devices connected185 mA
Add to above for each IDNet device in alarm (see note 2)1 mA
Add to above for each IDNet LED On (20 maximum IDNet devices LEDs On)2 mA
Total current for fully loaded IDNet channel in alarm (20 LEDs On) (see note 2)475 mA
NOTE:
1. Add an additional 9 mA per active auxiliary relay (Alarm or Standby).
2. The IDNAC Alarm current depends on the IDNAC device used. See the relevant device manual for more information on currents.
5.2 IDNAC section overview
The IDNAC power supply has a single SLC for connecting addressable IDNAC devices. The power supply is compatible with TrueAlertES and TrueAlert
Addressable product lines, both multi and fixed candela. The IDNAC output is Class B only. Class A operation requires use of the optional module
4007-9804, IDNAC dual Class A isolator.
The output is duplicated on the terminal block to facilitate T-tapping on the circuit at the panel. EOL resistors are not required.
All wiring is supervised and power-limited.
Fig 16: IDNAC terminal
Page 18579-1102 Rev H
Page 21
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.3 Specifications
Table 14: IDNAC specifications
• Up to 12 4905-9929 remote TrueAlert Addressable Isolators per IDNAC Circuit.
Supports
Electrical specifications:
Channel voltage29.5 VDC nominal.
Circuit requirementsThe maximum alarm current is 3 A per circuits.
Isolator
Isolator (DCAI)
• Up to 30 devices connected directly to any isolator terminal pair*.
• Up to six isolators between any appliance and the IDNAC SLC terminals. All wiring is 20 AWG to 12 AWG. *For
more information on the isolator, refer to the 4905 Isolator+ Installation Instructions, 574-769.
To wire an IDNAC as a Class A circuit, the DCAI modules (4007-9804) is required (2 Class A circuits with fault
isolation). For more information about Dual Class A isolators and on how to calculate Class B wiring with
isolation, see the DCAI Installation Instructions (579-1029).
5.4 Wiring parameters
Table on page 19 identifies the wiring parameters for the IDNAC.
Table 15: IDNAC Wiring parameters
IDNAC wiring limits
Channel loading
Max. wiring distance
Max. cable load10,000 ft (3,048m) per channel.
Max. wire length from panel to any
device
NOTE: If a shielded wire is used, cut it and tape it. The required wiring is unshielded twisted pair (UTP). This wiring must have a capacitive
rating of less than 60pF/ft and a minimum of 3 twists (turns) per foot.
127 devices (IDNAC devices or other compatible devices). See
Compatible devices and appliances on page 22 for more information.
4,000ft (762m).
Page 19579-1102 Rev H
Page 22
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Wiring Limit Based on Alarm Current
Alarm
Current
Line
Distance to the Last Appliance
(Ohms)
DevicesImpedance
20
AWG
18
Distance to the Last Appliance
AWG
16
AWG
14
AWG
12
AWG
20
AWG
18 16
AWG AWG
14
AWG
12
AWG
0.050
4000 ft 4000 ft 4000 ft 4000 ft 4000 ft14.5411252 ft 2038 ft 3241 ft 4000 ft 4000 ft
0.1002644 ft
4000 ft 4000 ft 4000 ft 4000 ft12.9651142 ft 1815 ft 2887 ft 4000 ft 4000 ft
0.1501763 ft
2802 ft 4000 ft 4000 ft 4000 ft11.38101003 ft 1595 ft 2536 ft 4000 ft 4000 ft
0.2001322 ft
2102 ft 3342 4000 ft 4000 ft10.1415893 ft 1420 ft 2258 ft 3590 ft 4000 ft
0.2501058 ft 1681 ft 2674 ft
4000 ft 4000 ft9.1220804 ft 1278 ft 2033 ft 3231ft 4000 ft
0.300881 ft2228 ft 1401 ft
3542 ft 4000 ft8.2825730 ft 1160 ft 1845 ft 2934 ft 4000 ft
0.350755 ft 1201 ft 1910 ft
3036 ft 4000 ft7.5830668 ft 1061 ft 1688 ft 2683 ft 4000 ft
0.400661 ft 1051 ft 1671 ft
2657 ft6.974000 ft35614 ft977 ft1553 ft 2469 ft 3928 ft
0.450588 ft934 ft 1485 ft 2362 ft 37566.4540568 ft904 ft1437 ft 2285 ft 3634 ft
0.500529 ft1337 ft 841 ft2125 ft 33806.0045528 ft840 ft 1336 ft3378 ft2124 ft
0.750353 ft891 ft 560 ft1417 ft5.6050 2254 ft493 ft784 ft1247 ft 1982 ft 3152 ft
1.000264 ft 420 ft 668 ft 1063 ft5.2455 1690 ft462 ft734 ft1168 ft 1856 ft 2952 ft
1.250212 ft 336 ft 535 ft 850 ft4.9260 1352 ft434 ft690 ft1097 ft 1744 ft 2774 ft
1.500176 ft446 ft 280 ft708 ft4.7563 1127 ft419 ft665 ft1058 ft 1682 ft 2675 ft
1.750151 ft382 ft 240 ft607 ft4.6465 966 ft409 ft650 ft 1034 ft 1643 ft 2613 ft
2.000132 ft334 ft 210 ft531 ft 845 ft4.3870386 ft614 ft 976 ft 1552 ft 2468 ft
2.250118 ft 187 ft 297 ft 472 ft4.15
75 751 ft366 ft581 ft 924 ft 1469 ft 2337 ft
2.500106 ft168 ft 267 ft 425 ft3.9480 676 ft347 ft551 ft 877 ft 1394 ft 2217 ft
2.75096 ft 153 ft 243 ft 386 ft3.7485 615 ft330 ft524 ft833 ft 1325 ft 2107 ft
3.00088 ft 140 ft 223 ft 354 ft3.5690 563 ft314 ft499 ft794 ft 1262 ft
2006 ft
3.4095
Wiring distance must not exceed 4000 ft
299 ft476 ft757 ft 1203 ft 1913 ft
3.24100286 ft454 ft723 ft 1149 ft 1827 ft
3.10105273 ft435 ft691 ft
Ohms per 1000 ft
1099 ft
Gage
1748 ft
2.97
Ohms/1000 ft
110262 ft416 ft662 ft 1052 ft 1673 ft
2.85
20 AWG11.347
115251 ft399 ft634 ft 1009 ft 1604 ft
7.13718 AWG
2.73120241 ft383 ft609 ft968 ft1539 ft
16 AWG4.488
2.58127228 ft362 ft576 ft915 ft 1456 ft
14 AWG
2.8230
Wiring distance must not exceed 4000 ft
12 AWG
1.7750
Wiring Limit Based on Communication
5.5 IDNAC Class B wiring tables
Use the following tables to calculate the wiring distance to farthest appliance. The maximum wiring distance is the shorter of the distance limits as
calculated by alarm current voltage drop or by reaching the communications distance limit.
Fig 17: Class B wiring tables
NOTE: Although the required wiring for IDNAC circuits is twisted pair (controlled impedance) wiring, some applications will wish to take
advantage of existing wiring that is not twisted pair. This is only allowed if both conductors of the IDNAC circuit reside in the same metal conduit,
and only under certain conditions. Check with your local sales office before using wiring that is not twisted pair.
Page 20579-1102 Rev H
Page 23
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.6 IDNAC Class B wiring
To connect the power supply to appliances using Class B wiring:
1. Route the wire from the + and the - outputs on the IDNAC terminal block (TB2) to the appropriate inputs on a peripheral notification appliance.
2. Route the wire from the first appliance to the next. T- tapping is permitted. Repeat this for each appliance.
3. Repeat steps 1 and 2 for each IDNAC output you want to use.
Fig 18: Class B wiring
NOTE:
1. Notification appliances are rated using an individual nameplate label. Maintain the correct polarity on terminal connections.
2. Each IDNAC + and - terminal is rated for 2 identical wires. This allows up to 4 Class B T-TAP circuits directly from each IDNAC terminal block, see
IDNAC Class B wiring on page 21.
Page 21579-1102 Rev H
Page 24
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.7 Compatible devices and appliances
The devices and appliances listed in Table on page 22 are compatible with the IDNAC power supply. Notification devices are synchronized within the
4007ES system, including any attached 4009 series NAC extenders.
Table 16: Compatible devices and appliances
Addressable device descriptionModel numbers
4009 IDNAC Repeater
Dual Class A Isolator (DCAI)4007-9804
TrueAlert Addressable Isolator+ module4905-9929
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.8 Auxiliary relays section overview
Table 18: Electrical specifications for Auxiliary relays
Electrical specifications:
Relay circuit rated to switch:2 A at 30 VAC or 30 VDC, resistive load.
Contacts:
Table 19: Power specifications for auxiliary relays
Power
When power through auxiliary contacts is provided by the power supply, the wiring is power-limited.
When power through auxiliary contacts is not provided by the power supply, use in-line fuse holder 208-165 with 208-183, 1A fuse with attached cap
(supplied separately). If the power source is not power-limited to the requirements of UL864, wiring is to be segregated to the non-power-limited
spaces of the cabinet.
Note:
The Aux relay terminals on the IDNAC power supply are controlled by two on-board
programmable relays. The relay circuits are not supervised.
Relay contacts are Form C dry contacts. Transorbs provide suppression to earth. Do not switch voltages
greater than rating, or damage may result.
Fig 19: Aux relay terminals
Page 25579-1102 Rev H
Page 28
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.9 Troubleshooting
The code produced by the illuminated yellow indicator LEDs corresponds to a trouble that is either occurring on the system, or on the SLC channels.
See Table on page 26 for the 4007ES LED definitions, and see Figure 21: SLC channel trouble LED codes on page 27 for the 4007ES LEDs and
their codes.
IDNAC channel troubles are indicated by yellow LEDs labeled IDNAC TBL and letters A to D. When the IDNAC TBL LED illuminates, the IDNAC channel
is experiencing a trouble. Refer to Figure 22: System trouble LED codes on page 28 or the trouble codes for LEDs A to D. The LED SCROLL
pushbutton can be used to scroll through multiple trouble indicators.
Table 20: 4007ES indicator LEDs
Signal various trouble conditions on the 4007ES and its SLC. Refer to Figure 21: SLC channel
LED: A, B, C, D
IDNAC TBL
LED COMM LossIndicates that the communication between the IDNAC power supply and the CPU is lost.
Scroll Push Button (SW1)Used to scroll through multiple troubles, since only one trouble can be displayed at a time.
trouble LED codes on page 27 and
Figure 22: System trouble LED codes on page 28 for troubles details.
When On steady, refer to Figure 21: SLC channel trouble LED codes on page 27 for
detailed troubles indicated by LEDs A-D.
Fig 20: LEDs on the 4007ES power supply
Page 26579-1102 Rev H
Page 29
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5.9.1 SLC channel trouble LED codes
SLC channel troubles are indicated by LEDs A to D, as well as IDNAC. See Figure 21: SLC channel trouble LED codes on page 27 for the description
of the LEDs.
Fig 21: SLC channel trouble LED codes
Page 27579-1102 Rev H
Page 30
5.9.2 System trouble LED codes
System troubles are indicated by LEDs A to D.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Fig 22: System trouble LED codes
Page 28579-1102 Rev H
Page 31
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6 4007ES power supplies
This chapter describes the common sections of both the 4007ES Hybrid NAC power supply and the 4007ES IDNAC power supply.
6.1 Power supplies specifications
Table 21: Operating conditions
Operating conditions:
Operating temperature range32 °F - 120 °F (0 °C - 49 °C).
Operating humidity rangeUp to 93% relative humidity at 90 °F (32 °C), non-condensing.
6.2 Wiring guidelines
Class A: Using Class A wiring allows devices to communicate with the FACP even in the event of a single open circuit somewhere on the loop. Class A
wiring requires that two wires are routed from the power supply to each device, and then back to the power supply.
Class B: T-tapping is permitted on Class B wiring. Class B wiring therefore requires less cable distance per installation than Class A.
Auxiliary power only: Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit. In order to connect a circuit
using PL wiring, the devices being powered must all be addressable, or a UL Listed EOL relay must be used to supervise the circuit.
Page 29579-1102 Rev H
Page 32
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.3 IDNet Section overview
The power supply provides an isolated IDNet channel. This section is compatible with IDNet communicating initiating devices and enables the system
CPU to communicate with up to 250 peripheral devices, such as smoke detectors and pull stations.
Fig 23: IDNET on the power
Specifications
Table 22: IDNet specifications
Up to 250 addressable IDNet devices and up to 43 coded piezo sounders may be coded by the IDNet
Supports:
Electrical specifications:
Channel voltage
to remote devices
Earth detection threshold:10k ohms minimum from either positive or negative terminals.
Circuit requirements:
LEDS:
For detailed information on LEDs troubleshooting, refer to Figure 21: SLC channel trouble LED codes on page 27Figure 22: System trouble LED
codes on page 28 in the Troubleshooting section.
channel. Base panel supports 100 points, with 75 additional points per additional IDNet+ Loop Expansion
Module (refer to manual 579-1106).
30 VDC (normal); 35 VDC Alarm.
Data rate is 3333 bps.
Output circuits are supervised and power-limited.
Refer to Table on page 12 for the IDNet current on a NAC power supply. Refer to Table on page 18
for the IDNet current on a IDNAC power supply.
supply
6.4 Device addressing, Class A and Class B
The IDNet section can be wired as a Class A circuit or a Class B circuit.
Class A wiring: Class A wiring provides an alternate communication path that maintains communication to all devices when a single open circuit fault
occurs. Class A wiring requires two wires to be routed from the IDNet Primary Terminals (B+, B-) to each device, and then back to the IDNet Secondary
Terminals (A+, A-). Wiring is in/out, and T-tapping is not permitted.
Class B wiring: T-tapping is permitted on Class B wiring. IDNet wiring is inherently supervised due to individual device level communications. EOL
resistors are not required.
• If there are no remote isolators or isolator bases on the loops, device addressing can be assigned without concern for sequence.
• If there are remote isolators or isolator bases on the loops, the required addressing approach is to start from the B side and assign each
successive isolator a higher address than the isolator it precedes.
• For Class B wiring only, the A output and B output on a loop are connected in parallel using a jumper.
Page 30579-1102 Rev H
Page 33
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.5 Wiring parameters
Table on page 31 identifies the IDNet wiring parameters that you must consider when installing this card. For additional wiring information, see
Simplex Addressable Fire Alarm Panels Field Wiring Specifications (900-408).
• The maximum wiring distance is the maximum distance from both the IDNet control terminals (primary and return) to the farthest device on the
circuit. See Figure 24: Maximum wiring distance on page 31.
• The maximum wiring distance is determined by either reaching the maximum resistance, the maximum capacitance, or the stated maximum
distance, whichever occurs first.
• The total circuit cable load (amount of cable used) must not exceed 12,500ft (3,8km).
• Twisted wiring is recommended for improved noise immunity.
50 ohms maximum35 ohms maximum
4000 ft (1219 m)2500 ft (762 m)
The sum of line-to-line capacitance, plus the capacitance of either line-toshield (if shield is present) = 0.6 µF
Fig 24: Maximum wiring distance
Table 24: IDNet wiring considerations
External wiring must be shielded (for lightning suppression) and 2081-9044 Overvoltage Protectors must be
installed at building exit and entrance locations.
IDNet wiring considerations using
2081-9044 Overvoltage Protectors
(2081-9044 is UL listed to Standard
1459, Standard for Telephone
Equipment)
Page 31579-1102 Rev H
For more information, refer to the Model 2081-9044 Overvoltage Protector Installation Instructions
(S4906-0016).
Capacitance; each protector adds 0.006 µF across the connected line.
Resistance; each protector adds 3 ohms per line of series resistance; both IDNet wires are protected; 6 ohms
per protector will be added to the total loop resistance.
The maximum distance of a single protected wiring run is 3270 ft (1 km).
See the 2081-9044 Overvoltage Protector Installation Instructions (574-832), for additional information.
Page 34
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.6 Class A Wiring
To wire an IDNet section as a Class A circuit:
1. Make sure the jumpers on P2 are set to positions 3-5 and 4-6.
2. Route the wiring from the IDNet circuit primary terminals (B+, B-) on TB1 of the IDNet to the corresponding inputs on the first device.
3. Route the wiring from the first device to the next as in/out. See Figure 25: IDNet Class A wiring on page 32. Repeat this for each device.
4. Route the wiring from the last device to the terminals A+, A- to the panel, maintaining polarity.
5. Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield at each end in the panel to prevent it from coming into
contact with other components. The metallic continuity of the shield must be maintained and insulated throughout the entire length of the cable.
Fig 25: IDNet Class A wiring
6.7 Class B Wiring
When wiring the circuit as Class B, both the B+, B- and A+, A- terminals are available for parallel connections. Within the IDNet circuitry, A+ is connected
to B+, and A- is connected to B- so circuits can stem from either one. Additionally, two wires can be connected to each screw terminal.
To wire an IDNet as a Class B circuit, complete the following steps:
1. Set the jumpers on P2 to positions 1-3 and 2-4.
2. Route the wiring from the IDNet circuit primary terminals (B+, B-) to the corresponding inputs on the first device. It is possible to add up to 4
circuits on the terminal block when using Class B wiring. See Figure 26: IDNet Class B wiring on page 32 for the diagram.
3. Route the wiring from the first device to the next as in/out, see Figure 26: IDNet Class B wiring on page 32. Repeat this for each device.
4. Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield at each end (in the panel and at the last device in each
run) in the panel to prevent it coming into contact with other components. The metallic continuity of the shield must be maintained and insulated
throughout the entire length of the cable.
Fig 26: IDNet Class B wiring
Page 32579-1102 Rev H
Page 35
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.8 Auxiliary power selection
AUX PWR/SNAC overview
The AUX PWR/SNAC terminal block is located on the top left corner of the power supply. Using the ES Panel Programmer, this point can be configured
as either a 24V Auxiliary (AUX) power or as a simple reverse polarity Notification Appliance Circuit (NAC). This circuit does not support TrueAlert
addressable devices nor non-addressable SmartSync appliances.
The AUX PWR/SNAC is rated 2 A maximum. The current used is deducted from the total available power supply current.
Fig 27: AUX/SNAC
terminal
Output rating:29.5 V maximum
Current Rating:2 A, maximum.
Earth Detection
Threshold
Wiring Gauge:
Wiring Notes:
1. All wiring from the AUX/SNAC is power limited.
2. The conductors must test free of all grounds and stray voltages before connection to appliances and panel.
3. Terminate Class B NACs, as shown, using a 733- 894 EOL. For Canadian applications, mount end-of-line resistor to a Simplex-US Model 431537
EOL plate in accordance with ULC-S527.
4. If the wiring is routed outside the building, use of a listed secondary protector is required. Use Simplex2081-9028 (rated 5 A) or 2081-9044 (rated
0.2 A). A protector must be installed at each building exit or entrance. Each 2081-9028 adds 0.2 ohms wiring resistance. 2081-9044 adds 6 ohms
wiring resistance, and greatly reduces the wiring distance.
10K ohms minimum from either positive
or negative terminals.
18 AWG (min.)
to 12 AWG (max.).
2.0077 ft123 ft195 ft310 ft493 ft1.75
Note: This chart indicates the maximum distance for 1/4 -2A loads. The wiring distance is from the panel terminals to the last appliance. Use of a
2081-9044 protector reduces wiring distance.
Output of AUX or NAC is 24 V nominal. The minimum voltage is 19.5 at minimum battery; the maximum is 29.5 V. Aux Loads include the compatible
4007ES annunciators series, 4090 series of IDNet ZAMs and IAMs, and any listed device operating within the output limits of the AUX. Calculate the
wiring loss for the actual devices used. Compatible appliances include 4904 series of free-run strobes, 4901 series non-SmartSync horns, 4098 series
TrueAlarm Sounder Base and 4009 NAC extenders, used in reverse-polarity activation mode.
The 4007ES RUI channel supports the following devices:
• 4100-7401, 7402 Graphic Modules.
• 4602-6001, 7001, 7101, 9150 RCU/SCU Modules.
Wire from the power supply's RUI channel on terminal block TB1 to each RUI device. The wiring can be Class A or Class B.
Fig 29: Location of the RUI terminal
block
Table 27: RUI specifications
Supports:Up to 10 RUI devices.
Electrical specifications:
Channel voltage29.5 V nominal.
Earth detection threshold10K ohms minimum from either positive or negative terminals.
The maximum allowed line-to-line capacitance (“+” to “-” terminals) is 0.58uF. For
Capacitance
Wiring
Maximum wiring distance:
(18 AWG, 16 AWG, 14 AWG, 12 AWG)
Maximum T- tapping length10,000 feet (3,048 m).
Notes:
Maintain the correct polarity on terminal connections. Do not loop wires under terminals. If Class A is not used, configure jumpers P1 accordingly.
Shielded wire is not required. Twisted wire is recommended for improved noise immunity.
Figure 30: RUI wiring to the host panel on page 35 depicts Class A and Class B wiring.
Page 34579-1102 Rev H
applications with shielded wire, be sure that the total capacitance from line-toline plus the shield to either line is not more than 0.58uF.
2,500 feet (762 m) to device from PSU card.
Page 37
Fig 30: RUI wiring to the host panel
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Page 35579-1102 Rev H
Page 38
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
6.10Troubleshooting
The code produced by the illuminated indicator LEDs corresponds to a trouble occurring on the system. See Table on page 36 for the IDNet LED
definitions, and see Table on page 36 for the 4007ES trouble messages.
Table 28: LEDs on the 4007ES power supplies
Comm trouble
IDNet trouble
Earth fault+Illuminates to indicate a positive earth fault.
Earth fault -Illuminates to indicate a negative earth fault.
IDNet LEDs: A, B, and C
Table 29: 4007ES system trouble messages
Normally off. Turns on steady if the IDNet is
not communicating with the FACP CPU.
Normally off. Illuminates to indicate a problem
with the IDNet channel:
• Channel failure.
• Line short.
• Class A failure or an open line.
Steady ON: Indicates an open or short
condition on indicated loop.
Fig 31: LEDs on the 4007ES power supplies
MessageDefinition
AC FailAC power is not present or is too low for proper system operation.
Low BatteryThe battery voltage is below the 22.8 V nominal level by 10% or more.
Depleted/Missing BatteryThe battery is either below 19.4 V or completely undetected.
Card OvercurrentThe module is drawing more current than it should. Check for faults on the circuit.
The battery charger is either defective or being heavily loaded by batteries. Read charger current at front panel,
if charger current is approximately 1.4 A, batteries are likely loading the charger. Remove battery connection and
Charger trouble
Extra Device
Earth Fault Search
Positive EarthAppears when a positive earth fault is detected.
Negative EarthAppears when a negative earth fault is detected.
Short Circuit
Channel Fail
measure the output. If the output is 27.6 (or close, temperature dependent), there is a possibility of depleted
batteries or a bad set of batteries. Allow batteries to charge or replace them if they do not take a charge.
If the current is ~1.4 A with batteries and charger voltage below 20 V, remove the batteries and recheck the charger
voltage. If the voltage is around ~27.3 V, then the batteries are heavily depleted.
Appears if one or more extra devices (i.e., devices that have not been configured for the IDNAC or IDNet channel) are
on the system. Only one message appears, regardless of the number of extra devices found.
Comes up during the Earth Fault Search diagnostic function. Once the search is initiated, the front panel display
indicates how far along the search process has progressed (10%, 25%…75%), and then shows the results of the
search. The result either identifies the offending circuit or indicates that the earth fault could not be found. During
the search of circuits (IDNet, NAC, IDNAC, and aux power), system alarm and trouble processing is suspended.
Appears when a short is detected on the IDNAC/NAC channel. This status clears automatically when the short circuit
is removed.
Appears when each device on the IDNet channel has been configured, and when none of the devices are
communicating on the channel. This message does not appear if there are no configured devices on the IDNAC
channel.
Page 36579-1102 Rev H
Page 39
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
7 Optional modules and cards
The 4007ES can be ordered with a variety of optional cards and modules, depending on the system requirements.
8 Point Zone/ Relay Card
The 8-point Zone/relay Card (4007-9801) mounts in the 4007ES panel. Up to four cards can be added. Each card monitors up to eight Class B or four
Class A zones, or eight relay contacts. For more information about the 8-point zone/relay card, see the 4007-9801 8-Point Zone/Relay Card installationinstructions (579-1103).
25V Regulator Module
The 25V Regulator Module (4007-9802) regulates the panel power supply output received from the NAC power supply (4007ES) or the IDNAC power
supply (4007ES hybrid) to a 25VDC level. The 25VDC regulated output is isolated from the panel and complies with power-limited requirements. For
more information about the 25V regulator module, see the 25 V Regulator Module installation instructions (579-812).
IDNet+ Loop Expansion Card
The IDNet+ loop expansion card (4007-9803) mounts directly on the IDNAC/NAC power supply. Up to two cards can be added. Each card adds a single
Class A/Class B IDNet+ loop and increases the device capacity by 75 points. For more information about the IDNet+ loop expansion card, see the
4007-9803 IDNet+ Loop Expansion Card installation instructions (579-1106).
LED module
The operator uses the LED module (4007-9805) to view the simultaneous signaling of alarm and trouble conditions on up to 24 zones. All the LEDs
have configurable colors, red or yellow, except the LEDs in the last column, which are configurable as red or green.
For more information about the LED module, see the 4007-9805 LED Module installation instructions (579-1105).
The SDACT card
The SDACT card (4007-9806) can be mounted in the 4007ES panel. It is used to notify a central station when an event occurs, to report changes to a
specific point, and to connect a transmitter to a central station. For more information, see the 4010 ES and 4007ES Serial Digital Alarm CommunicationsTransmitters installation instructions (579-954).
City Circuit
The city circuit card with disconnect switches (4007-8907), and without disconnect switches (4007-9808), are used to annunciate alarms and other
urgent indications to remote facilities. Each city circuit module has two configurable circuits (alarm, trouble, or supervisory reporting) and supports
Reverse Polarity and Local Energy Master Box Applications. Only one city card can be installed on a system. It is not available when an alarm relay is
used.
For more information about city circuits cards, see the City and Relay Cards installation instructions (579-955).
Alarm Relay Card
The Alarm relay card (4007-9809) is used to provide common unsupervised control functions or indications for devices. Each relay module has three
circuits (alarm, trouble, and supervisory signals). It is not available when a city circuit card is used. For more information about alarm relay card, see the
City and Relay Cards installation instructions (579-955).
TrueInsight Service Gateway
The remote service gateway (4190-6104) sends data to a remote service monitoring facility to detail troubles in the panel. When the data reaches the
monitoring facility, a qualified technician is notified by e-mail, and can then begin the diagnostic process remotely. For more information about the
remote service gateway, see the TrueInsight Remote Service gateway installation instructions (579-953).
Dual Class A Isolator
The Dual Class A Isolator (DCAI) (4007-9804) card converts the Class B output of the IDNAC SLC into two isolated Class A outputs. For more
information about the DCAI, see the 4100- 6103, 4007-9804 DCAI Cards installation instructions (579-1029).
NIC
The panel connects to a 4120 network using a NIC slave card. This enables communication between each panel by fiber, modem, or twisted shielded
pair wire in a Style 4 or Style 7 wiring configuration.
Two types of cards can be used with the NIC:
• The Fiber-Optic Media card can be used for noisy electrical environments, or for connecting externally to other buildings.
• The Wired Media Card is used for all other applications.
The 4007ES NIC is part of the 4007-9810 kit which also includes the mounting bracket used to mount the card inside the 4007ES panel. See the
4010ES and 4007ES Network Interface and Media Cards Installation Instructions (579-956) for more information about installing the NIC.
Dual RS-232 Module
The Dual RS-232 interface module provides a serial communication interface to an AC or DC printer, a PC Annunciator, or a third party computer.
Power to both ports can be either isolated or non-isolated. The isolated power is intended for AC printers or PC Annunciators. Ground faults can result
if isolated power is not used for AC devices and third party computers. DC printers use the non-isolated power.
The 4007-9812 Dual RS-232 Interface Module is pre-installed on a bracket and it must be mounted in the top left corner (Block E) of the 4007ES box.
To complete the module installation, complete the following steps:
NOTE: The Dual RS-232 Interface Module cannot be installed if a module such as a 25 V Regulator, DCAI or a Zone Relay Card is already
mounted in Block E inside the panel.
1. Connect one end of the provided harness (734-308) to connector P7 on the back of the RS-232 card.
Page 37579-1102 Rev H
Page 40
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
2. Use the provided hardware to secure the RS-232 bracket to the 4007ES box.
3. Connect the free end of harness 734-308 to connector J17 (Zone/Relay) on the IDNAC PSU.
See the Dual RS-232 Interface Module installation instructions (579-910) for more information about installing the module.
7.1 Example of combinations
Figure 32: Example 1 on page 38 , Figure 33: Example 2 on page 38, and Figure 34: Example 3 on page 38 are examples of some of the
combinations that can be made in a 4007ES using the available optional cards and modules.
Fig 32: Example 1
Fig 33: Example 2
Fig 34: Example 3
Page 38579-1102 Rev H
Page 41
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
8 Appendix A ULC programming requirements
8.1 Common earth fault ground and common trouble indicator
This application monitors a system pseudo that counts the number of ground faults or troubles that occur on the system. Each time this counter
increments, such as when a ground fault or trouble occurs, a yellow LED on the operator interface panel illuminates.
Step 1. Add a Custom Control equation to monitor all ground faults:
1. Click the Custom Control tab.
2. Add a new equation.
3. Paste the following equation:
[INPUTS]
STATUS ON
A112 | ANALOG | COUNTER | GROUND TROUBLE COUNTER
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY |
[END OUTPUTS]
NOTE: P535 is shown as an example; use any digital point.
Step 2. Open Color User Interface Card Properties Dialog
1. Click the Hardware tab and expand the Unit 0, Box 1, Bay 1 icons to display the Color User Interface Card. Click the + signs to the left of the
Unit 0, Box 1, and Bay 1 icons to expand them.
Fig 35: Selecting the Color User Interface
Card
2. Right-click the Color User Interface card icon and select Properties.
3. Click the Point Editing tab, see Figure 36: The Display tab:Display Checkboxes on page 39.
Fig 36: The Display tab:Display Checkboxes
Step 3. Program the LED
1. Select one of the multicolor LEDs (3-2-1, 3-2-2, or 3-2-3) to program.
2. Click the Point Type drop down list and select LEDYELLOW.
3. Click the Mode drop down list and select ON.
4. Enter P535, or your chosen digital point number from the equation, in the Reference Address field to program the LED for ground faults.
OR
5. Enter A2 (no spaces) in the Reference Address field to program the LED to illuminate whenever a general system trouble is present.