Disconnect electrical power when making any
internal adjustments or repairs. Installation
and servicing should be performed by qualified Simplex Representatives.
When removing power from this system.
disconnect batteries FIRST and AC power last.
When connecting power lo this system. connect
AC power FIRST and batteries last.
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance
with the instructions manual, may cause interference to
radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant
to Subpart J of Part 15 of FCC Rules, which
provide reasonable protection against such interference
when operated in a commercial environment. Operation of this
equipment in a residential ares is likely to cause interference in
which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.
ELECTRICAL HAZARD
CAUTION
POWERING REQUIREMENT
WARNING
are
designed to
Page 5
INTRODUCTION
The 2120 Multiplex System consists of equipment that is designed to provide fire alarm, security, and energy
management functions. As such, you must make sure that the system is installed in strict compliance with
.I national, state, and local codes.
The 2120 can be configured in many different ways, depending on customer requirements. Since the system is
so versatile, installations will vary significantly from site to site. The purpose of this publication is to provide
general installation considerations and instructions for the major components of the system. Specific installation
drawings are provided with each system.
Receiving/Inspecting Equipment
When the equipment cartons are received, examine each for signs of damage that may have occurred during
shipping.
If you detect damage, you must immediately place a claim with the carrier. If you know the extent of the damage,
inform the carrier.
If possible, leave the equipment in the original containers until installation time.
Basic System Components
Although a 2120 system may include other equipment, the basic system components are shown below.
The Basic Multiplex, or BMUX
FIGURE 1
One or more Transponders
FIGURE 2A
3
Page 6
One or more Expanded Transponders
FIGURE 28
One or more Status Command Centers (SCCs)
FIGURE 3
Each equipment carton will be marked to identify its contents. Transponder equipment cartons will be marked with
the transponder number (or numbers) to identify the unit’s relative location in the system. The specific location
of each piece of equipment is identified in the documentation supplied with the system.
Removing Equipment from Cartons
When you remove the equipment from the cartons, choose tools that will open the cartons with a minimal amount
of jarring. Be careful not to extend the tool into the container far enough to damage the equipment. As you remove
the equipment, inspect it for signs of damage (dents, bent corners, etc.).
When possible, leave all documents with the associated equipment. Otherwise, be sure to mark both the
documents and the inside of the equipment so that they can be reunited later.
4
Page 7
EQUIPMENT DOCUMENTATION
Since each installation is unique, specific documentation is provided with every system. This documentation
describes the equipment used in your system, and provides wiring and interconnection information. The
documents usually supplied with each system are listed in Table A.
IMPORTANT!: Do not discard documents after the installation is complete. They are required for testing,
inspection, and maintenance.
In addition to system-supplied documents, each installation will have specific site drawings. Site drawings show the
location of all 2120 equipment required for an installation, as well as the amount and type of wire required. These
site drawings may include either architectural drawings, riser diagrams, or both.
The site drawings and system-supplied documents provide sufficient information to completely install a 2120
system. We will discuss the system-supplied documents one-at-a-time.
Each specification sheet is divided into different areas. Some of the information on these sheets affects the way in
which the system is installed; other information is used during inspection, maintenance, and repair of existing
systems. For the purpose of this manual, the numbered areas on each sheet indicate information that affects
system installation.
In addition to the numbered areas, the letters A, B, or C are written in the area adjacent to specific system features.
These letters indicate the following:
A - This feature always affects external wiring. Refer to system wiring and interconnection drawings for
details.
B - This feature may affect external wiring. Refer to system wiring and interconnection drawings for details.
C - This feature affects unit backbox installation. See the section of this manual dealing with backboxes for
details.
5
Page 8
TABLE A
2120 SYSTEM DOCUMENTATION
DOC. #
M-l 204
M-1326
M-l 203
M-l 202
M-l 325
M-1320
M-l 293
M-l 294
M-l 205-l
I
a. Basic Multiplex Order and Specification Sheet
I
b. 2120 CPU Equipment Order Form (replaces “a” above)
I
2120 Pre-Configured CPU, CPUSCC Multiplex Equipment Order Sheet (if applicable)
I
CPUSCC Specification Sheet (with “b” above or OV-004 only)
I
2120 General System Features (with “b” above or OV-004 only)
I
2120 Console Order and Specification Sheet (with console-mounted version only)
I
2120 Transponder Equipment Order and Specification Sheet
2120 Status Command Center Equipment Order Sheet (SCC-equipped systems only)
I
2120 Status Command Centercontinuation Specification Sheet (accompanies M-l 293)
I
2120 Control By Event Specification Sheet (control-by-event software only)
I
DOCUMENT NAME
7
M-l 274
M-21 20
M-2120-ET
(See Note Below)
*Document number will be supplied in the next revision of this manual.
Note: Drawing numbers will vary from site-to-site.
210012120 Multiplex Life Alarm System-Call Report Form
I
2120 Initiating Wiring Diagrams
2120 ET Initiating Wiring Diagram (only for systems equipped with expanded transponders)
Various system interconnection wiring diagrams
Page 9
Basic Multiplex Equipment Order and Specification Sheet M-l 204 (Figure 4)
The BMUX equipment order and specification sheet identifies BMUX components and defines overall system limits.
Examine the numbered areas on this sheet. Each area contains information that relates to system installation. For
example, Area 1 tells you how many communications channels are present in the system. Area 1 also tells you if
the channels use a single pair of wires (“STANDARD DC”) or two pairs of wires (“MCCULLOCH LOOP DC”).
The “A” in the quantity column means that these options always affect external wiring.
Look at Area 2 on the specification sheet. Notice that the “33 AH (PAIR)” battery standby option has the letter “C”
in the quantity column. Therefore, this feature affects the BMUX’s backbox installation.
Simplex
2120 BASIC MULTIPLEX EQUIPMENT ORDER AND SPECIFICATION SHEET
ORDERENTRY
2120 Basic Multiplex Equipment Order
and Specification Sheet
FIGURE 4
7
:OPY. PINK. SALESPERSON/BRANCH COPY. GOLDEN ROD
Page 10
2120 CPU Equipment Order Form M-1204 (Figure 5)
The 2120 CPU equipment order form is currently replacing the BMUX equipment order and specification sheet.
The information supplied in both forms is the same; however, an additional form is supplied with the CPU form. This
may either be:
l
The CPUSCC Specification Sheet OV-003, Figure 6
or
l
The 2120 General System Features form, Figure 7.
These forms provide general information about various 2120 system features. Attach the appropriate form to the
CPU order form.
2120 6101
nm- 3101 I*ip.
sm.3.d DC
COMMVNICATIONS CHANNELS
RETAINER COLOR
ix.
2120 CPU Equipment Order Form
FIGURE 5
8
Page 11
CUSTOMER
CONTRACTOR
~ El%sSO*i
UOST . ..A
W#T” “O,LCT
Simplex
a
X = INCLUDED FEATURE
CPWSCC Spoclflcallon Shoot
(For “I. with pncontlgund
and nowstock modelr)
.
I
0
LIST PERIPHERIAL DEVICES (PRINTERS, CRTS. KEYBOARDS TAPE DUMP.
REMOTE PORT BAUD RATES
PORT 4
SW POS SW POS
1 ADDRESS I ADDRESS
1 1/21416[161321 64 I
1 1/214I6[161321 64 I
IllI I I IllI I I 1 I
1 CONTROLLER #l
CONTROLLER #l
1
1
I 11214161161321 64 I
Ill11 I I I
j CONTROLLER n2
j CONTROLLER n2
l
I
6
6
I
SW POS SWPOS
6
STA
RATESELECTION -----
------------------CONTROLLERI / 29
/ /j u( iW
%l,d.d W.,l for “.adq”.n.n US. Only
ETC) BY PRODUCT ID NUMBER CONNECTED TO EACH PORT
BAUD BAUD
,I 11411
21 113
4600 BAUD
4600 BAUD I
*Not r.qolr.d
vd21m-8211
.x.821? ordan
I
IFX
Ex
I
IEX
I
IFX
I I
IEX
lW 1EX
Insert Module ldentificallon numbers
CBE _ _ _ - - - - - (CBE)
PORT 2-7 _ _ _ - - - -(PORT 2)
PORT 3- _ _ - - - - -(PORT 3
PORT4 _ _ _ _ _ _ -
FRONT
PANEL-
IEX
1U: /EX /EX (EX
REMOTE ACKNOWLEDGE MESSAGES
(CUSTOM OR STANDARD MESSAGE)
_ _
I I
IEX IEX IEX
_ - - - -<‘-,.--I
I
I I
IEX
/EX
above
ENOINEERINQ COPY 1
CPU/SCC Specification Sheet
FIGURE 6
9
Page 12
~simPlex 2120 GENERAL SYSTEM FEATURES
/ - .YOW MANY CHANNELS ARE USED I I or21 A
2 - TRANSPONDERS ON CHANNEL I (O-63 J A
3 - TRANSPONDERS ON CHANNEL 2 (O-63) m&m.
4 - IS THERE A LOCAL KEYBOARD IV/NJ
5 - IS THERE A LO,CAL PRINTER
6 - EXPANDED FONT FOR PRIORITY I ALARMS I Y/N) -
7 - MPANOEO FONT FOR PRICRITY 2 ALARMS (Y/N I -
8 - EXPANDED FJNT FOR SYSTEM TROUBLE MESSAGES (Y/NJ __
9 - EXPANOED FONT FOR POINT TROUBLE MESSAGES
I 0- EXPANDED FONT FOR PRIORITY 3 ALARMS (Y/NJ -
I i - EXPANDED FONT FOR CONTROL POINT MESSAGES f Y/NJ -
I 2- EXPANDED FONT FOR PSEUDO POINT MESSAGES (Y/NJ -
I3 -- CUSTOM LABELS (Y/N) I4 - USER PROGRAMMABLE CONTROL BY EVENT (0, I, or 2 J I = 512 2 = 1024 ___
HOW MUCH TIME CONTROL DO YOU HAVE I 0, I, II, IIIJ __
15I6 - WHAT IS THE SIGNAL SILENCE DELAY IO, /5,30,or 60 SECONDS J -
I7- WHAT IS THE LOCAL COMMANO CENTER PRIORITY (O-7) __
I 8- WHAT IS WE REMOTE COMMAND CENTER PRIORITY (0 - 71 __
WHAT IS PRIORITY I MESSAGE (STANDARD IS FIRE) I8 CHAR MAXI L 1 t I t t I 1 I
1920- WHAT IS PRIORITY 2 MESSAGE fSTANtJARCl IS SECURITY) fB CHAR MAX) I ! I ! I 1 I 2
2 I - WHAT /S PRIORITY 3
22- IS THERE LOCAL PRINTER POWER FAIL ONLY OPTION I Y/NJ 23 - IS THERE REMOTE ACKNOWLEDGE ON RS232 PORT 2 (Y/N J -
2d- IS THERE REMOTE ACKNOWLEDGE ON RS232 PORT 3 (Y/N ) -
25 - IS THERE REMOTE ACKNOWLEDGE ON RS232 ?ORT 4 (Y/N ) __
26- WHICH PORT HAS TAPE CASSETTE PROGRAM LOAOER (0,2,4J
27- ENERGY MANAGEMENT (Y/NJ ___
28- FIRE AL.aRM (Y/NJ __
WHAT IS PORT 3 REMOTE COMMAND CENTER PRIORITY (0 -7) -
2930- WilLIT IS PORT 4 REMOTE COMMAND CENTER PRIORITY (O-7 1 ___
3 I - WHAT IS THE MONITOR POINT
32- WHAT IS THE CONTROL POINT TsQGlJELE MESSAGES (8 CHAR MAX) I I I L I I
WHAT IS THE REMOTE ACKNOWLEDGE CBE HESSAGE (8 CHAR MAXI: : 1
3334- REMOTE ACKNOWLEDGE PORT 2 YESSAGE f8 CHAR MAXJ I : 1 1 ’ 1 ! i
35- REMOTE ACKNOWLEDGE PORT 3 MESSAGE (8 CHAR MAXI L I ’ ’ ’ ’ I
3 6- REMOTE ACKNOWLEDGE PORT 4 MESSAGE ( 8 CHAR MAXI I 1 t I c c I I I
37 - REMOTE ACKNOWLEDGE FRONT PnNEL MESSAGE (8 CHAR MAXI I I : I I I 1 1
38- e-.uux aox s/zf (4 or 6 J C
In certain systems, form M-1204 will not be supplied with the system documentation. Instead, the 2120 pre-
configured CPU, CPUSCC multiplex equipment order sheet will be supplied. Notice that the information supplied
in the OV-004 form is very similar to that supplied in the M-1204 form. The difference is that the pre-configured
multiplex order sheet refers only to “standard,” predefined 2120 multiplex systems.
Another form is supplied with the pre-configured multiplex order sheet. This may either be:
l
The CPUSCC Specification Sheet OV-003, Figure 6
or
l
The 2120 General System Features form, Figure 7
Attach the appropriate form to the pre-configured multiplex order sheet.
2120 Pre -Configured CPU, CPU / SCC Multiplex Equipment Order
5
D’
I
II
5
I ID
ID
I
,NCL INCL INU
INU
Am
WJAKIE~USEC
f
HE
5
II
ID
II
ID
3
m
lNCL
Y
INU
,NCL
/
m
--l-- e
5
:
5
II
5
5
s
2120 Pre-Configured CPU, CPU/SCC Multiplex Equipment Order
FIGURE 8
11
I
II
5
5
5
5
5
$
5
5
5
5
$
5
Page 14
2120 Console Order and Specification Sheet M-l 326 (Figure 9)
The 2120 console order and specification sheet is supplied with all console-mounted 2120 systems. The
information supplied on this sheet is almost the same as that supplied on form M-l 204. However, the console order
and specification sheet also defines the size of the console or rack ordered, as well as any console options that may
have been specified.
hpkX 2120 CONSOLE ORDER AND SPECIFICATION SHEET
LlWE No
2120 Console Order and Specification Sheet
FIGURE 9
12
Page 15
2120 Transponder Equipment Order and Specification Sheet M-1203 (Figure 10)
The transponder equipment order and specification sheet defines the transponder equipment associated with a
specific transponder cabinet. One sheet will be supplied for each group of transponders in a cabinet. Older versions
of the specification sheet have a transponder specification worksheet at the bottom of the form. This worksheet
defines the parameters of the first transponder in a cabinet; any other transponders are described in form M-1202
(the transponder continuation specification sheet).
New versions of the transponder equipment order and specification sheet do not include the transponder
specification sheet. Therefore, all transponders will be described in form M-l 202.
HWTSUSE
iSimplex
2120 TRANSPONDER EQUIPMENT ORDER AND SPECIFICATION SHEET
, 1 C”STOMEFvCONTR*CTOR
wm 1
aK* c.*c tiam
ONL”
BT WI8 MONlTOR 4 CONTROL ‘/I “NIT SURFACE
2120-9332
2120-9100
2120.9101 2 CONTROL: POWER SUI
2120-7001 ST 8 MONITOR ONLY la I I
2120.7003 1 IDPDT) I2O”AC A
YOICE COMM FAST WE ZONES; 3 VOICE CIRCUITS;
SMOKE RESET. % “NIT SURFACE
ST W,S MON,TOR .4 CONTROL; POWER SUPPLY;
CHARGER; 33 AH BAIT. 2 “NIT SURFACE
The transponder continuation specification sheet is made up of three transponder specification worksheets. Each
of these worksheets defines the parameters of a single transponder; a set of these worksheets comes with each
group of transponders located in the same cabinet.
For easy reference, tape each worksheet next to its associated transponder in the transponder cabinet.
Note:
Each transponder specification worksheet describes a specific transponder. Look at the numbered areas on each
worksheet: these areas contain information that affects the transponder’s external wiring. For example, Area 1 on
each sheet lists the custom labels for each transponder Monitor Point. These custom labels identify the circuit that
is to be monitored. Therefore, when you are making connections to a transponder’s Monitor Points, you should refer
to that transponder’s worksheet to determine where each monitored circuit is connected.
Look at Area 2 on each worksheet. This area lists the custom labels for each transponder Control Point. The custom
labels identify the circuit that is to be controlled. Refer to the specific transponder worksheet to determine where
each controlled circuit is connected.
Area 5 on each worksheet described special notes or instructions relating to a specific transponder. Make sure you
check Area 5 on each worksheet to determine if special wiring is required for each transponder.
B Simplex
TRANSPONDER SPECIFICATION WORKSHEET
1 CHANNEL NO (1 217 TRANSPONDER NO 1,.63,-
TRANSPONDER TYPE ,PROD IDI 5 LOCAL MODE [CONTROL PTS, 0
TRANSPONDER SPECIFICATION WORKSHEET
CHANNEL NO II 21TRANSPONDER NO ,I 631-
TRANSPONDER TYPE ,PROD IDI 5 LOCAL MODE ,CONTROL PTS / 0
212070-m OR2120-9---
MON,lOR Pi PRI SENSE
lDENllFICATION 0 31 F , A , 5 , H PNRq “IN
^ - _I
TRANSPONDER SPECIFICATION WORKSHEET
CBE
/I
2120 TRANSPONDER CONTINUATIC
TRANSIENT
TRANSIENT SUPPRESSOR 0
SUPPRESSOR
CUSTOM LABELS
0 0 2
a 7
CY E FIRE ALARM DIGiTAL CONTftOt
cl 7 FIRE ALARM DIGITAL
Cl 2 MGITAL CONTROL
0 8 FIRE ALAAM DIBITAL CONTROL
IN SPECIFICATION SHEET
CARD’
fw ALARM DIGITAL
DIGITAL CONTROL
MONITOR
2120 Transponder Continuation Specification Sheet
FIGURE 11
14
Page 17
2120 Expanded Transponder Order and Specification Sheet M-l 325 (Figure 12)
The expanded transponder order and specification sheet is supplied with each expanded transponder (ET) in a
2120 system. The specification sheet described the equipment associated with the ET. ET Monitor and Control
Points are described in the expanded transponder functions sheet.
BSimplex
0:
LINE
NC.
6ERbAL NC.
2120 EXPANDED TRANSPONDER ORDER AND ~PECIPICAT~~N SHEET
TWFAE 0
TWVE
OVANTITY: I
FAPND- i C”S.TCMERICONTRACTCR
FAPNO-
0
MARK FOR: LOCATKJN
R- OATi
START n*TE
scEuu.w
YIPDAlZ
2120-6101 FOUR “NIT
2120-0614
2120-0615 12” 2 AMP PWR OUTPUT OPTION
21204616
PWNT
PACKAGE SIZE
24Y 10 AMP SIGNAL PWR OPTICN
DETECTOR RESET RELAY
.hx
-
LSTINOS REOUIREC (4
UL-CSFM-FM-CSA-ULC-NONENFPA 72 STANDARD Ii4
A_B_C_D-1076SEC-N0~~~
M 1321
I
I I I
TOTAL EQUIPMENT(S)
APPLICATION SOFTWARE COPIES. WHITE AND YELLOW. SALESPERSONIERANCli COPY PINK.
2120 Expanded Transponder Order and Specification Sheet
The expanded transponder functions sheet is divided into three sections. Each section describes an ET card,
providing information on ET Monitor and Control Points. A set of these function sheets is provided with each ET.
PROJECT:
CONTRACTOR
CABINET:
MONITOR
-1 RELAY. i ‘N’o
I
MONITOR
TYPE
6 I
IF VOLTAGE MONITOR IS
USED FILL IN THIS SECTION
NO VOLTAGE
PRT VOLTAGE (Y’N)
RELAY q YES
FUNCTIONS SHEET
EXT
VOLTAGE
1 EXT
atw?nt
n NO
2120 EXPANDED
TRANSPONDER
,
I
I
‘Insert “T” for telephone
REMARKS.
TYPE
ORDER #
DATE.
REF. PAGE
CONTROL
OF-------
NO SUPV. OR *
PRT NON-SUPV. AUX.
0 SUPV
q non-sup”
0 SUPV
q “on-sup”
0 SUPV
q non-sup”
0 SUPV
q “on-sup”
I
IF VOLTAGE MCWIITCR IS
MONITOR
TYPE I ~I%TIVOLTAGE I $iAGE
5
7
PPLICATION SOFTWARE COPIES WHITE AND YELLOW SALESPERSO
USED FILL IN THIS SECTICN
RELAY g YES
I
0 NO
2120 Expanded Transponder Functions Sheet
FIGURE 13
TYPE
a
BRANCH COPY PINK
16
CONTROL
NO SUPV. OR *
PRT NON-SllPV AUX.
Page 19
2120 Status Command Center Equipment Order Sheet M-l 293 (Figure 14)
The Status Command Center equipment order sheet describes the overall Status Command Center (SCC)
parameters. The SCC continuation specification sheet provides the details for each SCC point.
SHADEDARE&
Fimplex
2120 STATUS COMMAND CENTER EQUIPMENT ORDER SHEET
UNIT
TOTAL
HOOTS “SE
ONLY
“NIT
TOTAL
29 28 27 26 25 24 23 22 21 m-
M.1293 PO
Insert Module Identification numbers above.
2120 Status Command Center Equipment Order Sheet
----------------
FIGURE 14
17
Page 20
2120 Status Command Center Continuation Specification Sheet M-1294 (Figure 15)
The SCC continuation specification sheets describe the modules equipped with each SCC. The information on
these sheets is not needed for installation, but will be required for system checkout. Therefore, do not discard these
sheets.
2120 STATUS COMMAND CENTER CONTINUATION SPECIFICATION SHEET
Channel NO (1.2) ___
Transponder No (l-63)
I
Mod NO. (129)
Channel NO. (1.2) ___
Transponder NO. (1.63)
Transponder No. (l-63)- 6 = Monitor Bypass P = Pseudo on
SCC Card POSI,IO” IlOB)-
Required for SW only
Transponder No. (163)SCC Card Positron (1.8:
I I I I I
T = R = =
I I I I I I I I
A = Monitor Alnl
6 = Momfor Bypass P = Pseudo on
T =
c = Control on x = TranSpOnder
R = Switch POS. 6 = System Trouble
R H
I I I
2120 Status Command Center Continuation Specification Sheet
FIGURE 15
I I I I I I
Ref. Equip. Order
Price Page
- of -
18
Page 21
.
,
2120 Control By Event Specification Sheet M-l 205-l (Figure 16)
The control-by-event specification sheets are supplied with all 2120 systems that l!se control-by-event software.
These sheets describe BMUX reactions to specific system events. As such, they are not required during installation;
however, the sheets are needed for system checkout. Therefore, do not discard these sheets.
2120 CONTROL BY EVENT
SPECIFICATION SHEET
(SYSTEM RESET) 00162
DETECTOR RESET 0 SIGNAL SILENCE 00161
MONITOR POINT 0 CENTER
‘SECURITY BYPASS
(USE MONITOR PT. 1-8) 0
A SEPARATE S
(FOR REFERENCE ONLY)
IDENTIFICATION
THIS SHEET USED TO IDENTIFY CONTROL BY EVENT
33FICATION SHEET IS REQUIRED FOR EACH CATEGORY SELECTED.
,SEl.ECT ONE 0)
STATUS COMMAND
0
0
2120 Control By Event Specification Sheet
FIGURE 16
19
Page 22
2100/2120 Multiplex Life Alarm System
-Call Report Form M-1274 (Figure 17)
Each system is shipped with several copies of the call report form. While these report forms are not needed during
installation, they will be used for system checkout and all subsequent service calls. Therefore, do not discard these
sheets.
Simplex
2100 I2120 MULTIPLEX LIFE ALARM SYSTEM
CALL REPORT
Branch
TR Manager
Customer name
Date placed in service
Type of System
Type 01 Call
Check which of the followlng caused the malfunction:
C.P.U./BMUX ;’ Pllnter C Remote Printer 0 Remote C.R.T.
BTIFABTITPR Serial Number(s)
Peripheral Dewces :: w,r,ng
Explain what caused the malfunction. Be specific and use part numbers
2100
lnstallatlon C Inspection and Test 0 Program Change
7 2120
0 Other, Explain
Date 01 last report
Date
TR signatue
current status
Specify
0 CRT
0 Malfunction
Travel time Labor-
Description
PT NO
--~~
city.
2100/2120 Multiplex Life Alarm System Call Report Form
PARTS REPLACED
PrlCe
Total
FIGURE 17
20
Total tome -
Description
PT. NO.
----
__---
----
TOP COPY: TO SERVICE SUPPORT
2ND COPY: REGIONAL SPECIALIST
3RD COPY: BRANCH COPY
4TH COPY: TO REMAIN WITH EQUIPMENT
The 2120 initiating wiring diagrams provide details on how to connect external devices to 2120 transponders.
Information on fire alarm, security, and control peripherals is included. Specific diagrams illustrate how these
peripherals are interconnected, and how they should be terminated at a specific transponder.
The 2120 initiating wiring diagrams are referred to by figure letter in the system interconnection drawings.
CONTRACTOR
TERMINAL
LAYOUT
TEII
SIGN AL
-1
“RzculT
n
C
FABT
NOTES:
SIGNAL
1 ALL WIRING MlHlMUM 14 AWC OR TO
LOCAL CODES.
2.
RATED
20 -28
c I RCUIT
28VDC
VDC, STR TYPE
3?8-030
E.O.L.R.
IOK l/2W
-J
2901- 9320
2901-9321 SELLS
2901- 9322
2.902-9203 CH,MES
2902 - 9204
3. MAXIMUM Of 2
4.
SIGNALING CIRCUITS
BOAR0 ZONES 6, 7 8 8
5. REFER 70
SPECIPICATIONS.
Fig. @ From M-21 20 Initiating Wiring Diagrams
FIGURE 18
21
AMPS PER ANY ONE SIGNAL.
ARE
900-036 2120
MONnOR RV FABT
FIELD WIRING
Page 24
2120 ET Initiating Wiring Diagrams M-2120~ET (Example, Figure 19)
The 2120 ET initiating wiring diagrams are very similar to the standard 2120 initiating wiring diagrams. However,
the M-2120-ET drawings are provided only with 2120 systems equipped with ETs and only provide information
regarding external device connections to an ET.
The 2120 ET initiating wiring diagrams are referred to by figure letter in the system interconnection drawings.
Note: System interconnection and wiring diagrams are discussed in the SYSTEM WIRING section of this manual.
SIGNAL
CIRCUIT
4
2120
ST0
ASSY. 562-447
W.O. SOi-572
e-r
RELAY 80
Y/O IV
c I8
WC 17
N/O I6
C
N/C I4
I
N/O 13
c I2
IS
pa. __ .--- -.-.._.
SIGNIL
CIRCUIT
2
t
J
SIGNAL
CIl?CUIT
I
“”
NOTES:
-.-_.
1. ALL WIRING MINIMUM I4AWG
LOCAL CODES
Z.RAlfiO ZO-28VOC
29Ol- 9320
2901-9321
2901-9322
2902- 9203
2902- 9204
4.FIEFER TO 2120 PlELO WIRING SPECS. 900-036.
ET SIGNAL CIRCUIT
Fig. @ From M-2120-ET Initiating Wiring Diagrams
FIGURE 19
\
J
OR TO
STR fYP6
BELLS
22
Page 25
BACKBOXES
Backboxes and cabinets (without their doors) are usually delivered prior to other system components. Make sure
that the backboxes are installed in the proper location by referring to the building’s architectural drawings. Some
boxes will have to be modified in accordance with instructions in this section. (See Figure 20 for backbox sizes.)
Backboxes whose mounting positions are not obvious contain a label indicating their mounting position. When one
of these labels is in the box, mount the box with the word “TOP” in the uppermost position.
Some backboxes will be installed side by side. Make sure you allow at least 2 inches between the backboxes to
leave enough room for the doors to swing open.
Note: Instructions for mounting doors onto backboxes are provided with the door’s mounting hardware.
-r
20.75”
52.71 cm
L
El
38.25”
92.08
48.26cm ’
i-UNIT
CABINET
I I
8.9 cm
6.44”
6.34 cm
r-
L 25.75” -+/
I
65.41 cm
I
2-UNIT
CABINET
’ 20.57cm ’
t
cm
4-UNIT
CABINET
Backboxes
FIGURE 20
23
B-UNIT
CABINET
Page 26
Limitations Imposed By 33AH Batteries
Note: This information is applicable to those installations not using the battery shelf described under “Conduit
Entry in Transponder Cabinets with Power Supplies.”
A set of 33AH batteries will not fit in the backboxes when the lower-left mounting screw is in place. Therefore,
when 33AH batteries are to be installed in a box (see Area 2 on form M-1204; Area 1 on form M-l 305; Area 3
on form M-1326; Area 5 on form M-1203; Area 3 on form M-1325; or Area 3 on form M-1293) drill another l/4”
mounting hole in the lower-left corner centered 7-Y=? above the original hole. See Figure 21 for location details.
NEW
MOUNTING
/Y %iETER
f
7.5”
ORIGINAL
MOUNTING
(DO NOT USE WHEN
33AH BAlTERlES
c
1.626”
A--
ARE ORDERED)
CABINET
KNOCKOUT
i/
CONTRACTOR-CUT HOLE
New Mounting Hole for 33AH Batteries
FIGURE 21
CABINET
KNOCKOUT
Note: Battery shelf height is 2 inches.
(CONDUIT NUT MUST CLEAR A MARK
THE BOX AS SHOWN)
FROM THE BOTTOM OF
INCHES
Conduit Location for Transponder Cabinet
Containing a Power Supply
FIGURE 22
Install backbox using a X” hex-head screw with a 1” flat washer in each corner. Mounting fasteners protrude %”
from the back of each backbox, so install a pad (l-7116” square x l/8” thick with a 5116” hole in the center) over
each mounting hole when the backbox is to be installed on a flat surface.
Conduit Entry in Transponder Cabinets with Power Supplies
When a power supply is located in a transponder’s backbox (see Area 2 of Form M-1203, Figure 10) or in an
SCC’s backbox (see Area 1 of Form M-l 293, Figure 14), use Figure 22 to determine appropriate conduit entrance.
A battery shelf is shipped with each transponder cabinet that will contain a power supply: use the shelf by placing
it in the bottom left side of the cabinet. The shelf allows conduit entry on the bottom left-hand side of the cabinet
only.
24
Page 27
.
SYSTEM WIRING
This section provides a description of all system wiring diagrams provided with your 2120 system. These drawings
include:
l
System interconnection drawings for the communications channels, any audio/phone lines, and all powering.
o Equipment cabinet drawings showing component locations and external (contractor) connections.
l
M-21 20 and M-2120-ET (if applicable) initiating wiring diagrams.
We will discuss each of these drawings separately.
Note: The drawings discussed in this section are samples only. Each individual 2120 system has its own set of
drawings similar to the ones shown in this manual.
System Interconnection Drawings
Each 2120 system is provided with a set of specific system interconnection drawings. These drawings include:
l
Communications channel, or data line, interconnections.
0 Power line interconnections.
l
Audio line interconnections (if applicable).
l
Telephone line interconnections (if applicable).
o A cabinet interconnection and drawing list.
The cabinet interconnection and drawing list (see sample, Figure 24) should be the first drawing you check. This
drawing tells you:
l
Which cabinets are interconnected on Channel 1 for the power line and audio sub-riser (if required).
l
Which cabinets are interconnected on Channel 2 for the power line and audio sub-riser (if required).
l
What specific cabinet wiring diagrams should be included for your system.
You should verify that all wiring diagrams listed on the cabinet interconnection and drawing list are included in your
system. Each equipment cabinet should have its own wiring diagram.
Note: If your system does NOT have all the wiring diagrams specified in the cabinet interconnection and drawing
list, notify your Simplex representative or Simplex Technical Support immediately.
Take a look at the sample in Figure 23. This table is labeled “CHANNEL 1.” Notice that all equipment on Channel
1 is listed by cabinet number. For example, the first cabinet number is called “B-MUX.” Therefore, the BMUX is the
first equipment cabinet on Channel 1. The BMUX in this case contains a local BT; therefore, transponder number
1 is located in the BMUX equipment cabinet. The associated wiring diagram number for the BMUX cabinet is 3981-
743.
CHANNEL
I
Cabinet Interconnection and Drawing List Close-Up
FIGURE 23
25
Page 28
The second cabinet on Channel 1 contains the SCC. The SCC’s transponder number is 6. Its associated wiring
diagram number is 3981;743.
Now . . .
look at the third entry in the table. The cabinet number is specified as “1. ” That means that this cabinet
contains transponders. Under the “TRANSPONDER NUMBER(S)” column, we see that transponder numbers 2,
3, and 4 are included in cabinet number 1. The wiring diagram number for this cabinet is 3981-745. Notice also that
the “POWER LINE INTERCONNECTION” column indicates that the line from cabinet number 1 is used to
provide power for the equipment in cabinet number 2.
The fourth entry in the first table refers to cabinet number 2. You can see that transponder number 5 is included
in this cabinet. The wiring diagram number for cabinet number 2 is 3981-746. Also, we know that the transponder
located in cabinet number 2 is powered by equipment located in cabinet number 1 (see table entry for cabinet
number 1).
The table for Channel 2 is interpreted in the same way. The information provided on this drawing for your system,
will be quite similar.
Data and Power Line Interconnections
Data and power line interconnections are illustrated on the same system interconnection drawing (see sample,
Figure 25). This system interconnection drawing also includes:
l
Local BT Monitor and Control Point wiring (if the BMUX is equipped with a local BT).
l
RS232C port numbers and remote device connections.
l
Celestra clock connections (if the BMUX is equipped with a Celestra interface board).
On this system interconnection drawing, all contractor wiring is denoted by dashed lines. The connections
illustrated are “typical” . . .
meaning that you must determine the way in which your system is configured for each
data and power line interconnection.
The circled portion of Figure 25 is shown enlarged in Figure 26. Here, the BMUX local BT and AC I/O board
connections are shown. In the case of local BT connections (TB2 and TB3 in Figure 26), a reference is made to
“FIG. Kl .” This refers to Figure Kl on the M-21 20 initiating wiring diagram. Refer to this diagram to determine how
to connect the external device(s) required to the local BT I/O board.
Audio and Telephone Line Interconnections
Audio and telephone line interconnections (if applicable to your system) are listed on the same system
interconnection drawing (see sample, Figure 27). This system interconnect drawing also shows how the audio
Control Points can be wired (the audio sub-riser configuration). However, specific audio Control Point wiring is
shown in the system’s individual cabinet drawings.
On this system interconnection drawing, all contractor wiring is denoted by dashed lines. The connections
illustrated are “typical” . . . meaning that you must determine the way in which your system is configured for each
audio and telephone line interconnection.
26
Page 29
2120
B-MUX
OPTIONAL FEATURE ;
DUAL REMOTE RS232-C )
PORT OUTPUT
-!
.- ------- 0” ,,,mo
-------
-- --
4293
REMOTE
STATION
FIG. @
REFER 70 900-036 FOR
2120
FIELD WIRJNG SPEClFlCATlONS
r
I
I
1
I
L-
Page 30
SCL NOTE 4 i
r-
?
-__ --------_-_------------~___
--- -_-- ----- ------------------.I
6
c ~:-----~---~-~-~-----: II - - -1
TYPICAL DATA LIfsE INTERCONNECTION
---------------_---- ____-------
-.
----------
-----
r
~yni. -- - --f
UT-
‘I ’
I ’
I ’
‘1 .I
a
--- ‘J
’
: ; ’
J I
SLL NOTL 3.II
L-“------J
CONNECTION FOR WLTIPLE
TRANSPOHOER CAEINET
I
’ I
I
0fTlOtdA~ DATA LINE INTERCONNECTION
WHEN NOT USING MCCULOH LOa”
NOTL: YAXIYUY WTAhCE MOT TO EXCEL0 10.000 FEET
TOTAL OISP+ICE ‘WE SUM OF ALL SERIES IWO/OR
PARALLLL RlnS
TYPICAL POWER LINE INTERCONNECTION
r-- -- --)A’ ;
- -a--; J L _ _ _ -~--- 10 Aoo1r~0YIL
; r--
COWECTION FOR WCLE
’ I
I I
’ I
’ I
1 I
TRANSPONDER CNIINET
ORDER No. 205 I85
FILE NO. H93t002A
I I
L _ _ _ _ - - -I--- ?n~‘poNDLIS
L NOTL 3.1’
1
>
‘1) Iwu1nco 1
NOTES:
I. OISNCO LINES INOICATI CONTlACTO” WlllYE
2. “,.LLl CONTACTS RITCO t UPS ZUYDC
3, POWL” LINES I6 A16 “.I. e.eLlc6.l.mcl
4. OAT. LINES e‘LW* 676.0 0” LG”,“.
- C*CLL*m, e.eLICx, s. WILL0
_----
AL POM ER LINE INTERCOtiNECTlON
---
I
“.PRENTISS
) S’T-3El.I INTERCONNFCTION
:. I ,,
02-28-83 2120
:.I, .<. 2
-8201
I
Data and Power Line lnterconnectic
FIGURE 25
Page 31
AUDIO POWER WE-AMP W/O BACK UP
<
I--IT--
g--y! J
c---,
0--,
$ ,
TYPICAL AUDlQ LINE INTERC(
FIRST
~--me------ ____
OPTIONAL AUDIO
--e-J
------CL
.- - -_
r.-e++i--
v-f-
r-C-At-t---‘-
L-;.s
‘I
‘I
1,
I I
‘I
1 I
It
II
II
CL-----
L-----
LINE INTER
1 I
’ I
I I
I!
r----c
I ;
I ’
I 1
r--0
r--C-:‘+-
I r-
I ’
’ I
1 I
’ I
’ I
I I
I I
0 -Aq- -
‘5.
; I-------- ----_ -- -
L - __ _ _ ___ _ _ _ _ _
T’fPICAL TELEPHONE LINE IhlTERCONNECTi3N
_JJ
-I
L-----------A- - ---
Page 32
--------J
GJNECTI~N
SECOND
--------II
-------A
AUDIO SUB-RISER
CONFIGURATION
.-LO
s. NOLtN
0~~~~‘205185
H93 1002A
F,LE l
oz.&%]
-. _.-
398 I-744
tin3 -3
Audio and Telephone Line
Interconnection Drawing
FIGURE 27
Page 33
1
I
I
ONrRlCrOR CONNECTION
EFER TO NOTE , F,C,
-
ST&TVS COMMAND CENTER
ASSEMBLY 616-623
CONTA CTOR C0NNEC110NS
REFER TO NOTE ,FIG __
a
A
.Th LIKE
FIG
@
FIG
0
-0YI
-+v I
4
ROW 3
Page 34
ORDERff 128507
F,LE bE92237lA
SCC Cabinet Drawing
FIGURE 29
Page 35
.
BMUX Cabinet Drawing (Figure 28)
The BMUX cabinet drawing shows the position of each piece of equipment located in the BMUX cabinet. As you
can see in Figure 28, this particular BMUX cabinet contains:
l
One 2120 BMUX.
l
One 2001 audio panel containing an oscillator control switch module, a pre-amp monitor module, and a
microphone enclosure (ROW 4).
l
One 2001 audio panel containing an oscillator control board and an audio pre-amplifier (ROW 5).
l
One 2001 audio panel containing a tape player (ROW 6).
The following is written directly beneath ROW 6:
6 UNIT
CABINET 1 OF2
B-MUX
This indicates that the cabinet is a 6-unit cabinet, and that it is the first of two cabinets that will be installed side
by side. If you look at the drawing number (3981-743), you can see that there are two sheets to this drawing. The
second sheet of this drawing is the second cabinet. . .
in this case, the SCC cabinet, which we will discuss shortly.
Therefore, you know that the BMUX and SCC cabinets are to be installed side-by-side.
Now. . . the circled information to the right of ROW 6 in Figure 28 is enlarged below:
733-l 81
360-018
7 M CONN.
0
Pl
1 (C)
P2
l(S)
P3
1 (B)
P4
) TO SCC
733-226
360-018
8 M CONN.
0
Pl
+VB
P2 ov
ATBL
P3
P4 PTBL
Two male connectors are described, both of which will mate with a corresponding female connector at the SCC
cabinet. The male connectors are labeled 7M and 8M, respectively; once the BMUX and SCC cabinets are
installed, you should locate these M connectors. There will be associated female connectors in the SCC cabinet
labeled 7F and 8F, respectively. You should connect the connectors labeled 7M and 7F together; you should
connect the connectors labeled 8M and 8F together.
39
Page 36
A similar interpretation is given for the circled information to the left of the BMUX in Figure 28:
733-l 38
360-063
@M CONN
-1
-2
-3
-4
-5
-6
-7
-8
-9
- 10
-)- 11
_c 12
+ 13
- 14
- 15
- 16
This male connector is labeled 9M, and mates with a corresponding female connector in the SCC cabinet.
In general, the same nomencalture applies to any connectors which must be connected by the contractor. You will
see such connector references only in the case of two (or more) interconnected cabinets.
SCC Cabinet Drawing (Figure 29)
The SCC cabinet drawing shows the position of each piece of equipment located in the SCC cabinet. As you can
see in Figure 29, this particular SCC cabinet contains:
l
One 2120 Status Command Center (SCC).
l
One lamp driver board and one switch I/O board (ROW 2).
l
One relay driver board (ROW 3).
l
One 2001 telephone enclosure (ROW 4).
l
One audio amplifier (ROW 5).
“CABINET 2 OF 2” is written beneath the cabinet drawing. This indicates that the SCC cabinet is the second of
the two cabinets that are to be installed side by side (the first cabinet was the BMUX cabinet).
Notice that the left- and right-hand sides of the SCC cabinet drawing are labeled “CONTRACTOR
CONNECTIONS.” Any connections to be made by the contractor are indicated in these columns. Let’s look at
ROWS 1 and 2 and examine the indicated contractor connections.
The terminal block (TBl) directly to the right of ROW 1 is shown enlarged in Figure 30. The data line connections
(shown by dashed lines) are to be made by the contractor. If you look at the SCC assembly to the left, you will see
that the location of TBl on the SCC is shown. Therefore, at TBl of the SCC, you will connect the “INCOMING
DATA LINE” and outgoing data line (“CONTINUE DATA LINE”), if required, at the terminals shown.
40
Page 37
Now look at the contractor connections to the right of ROW 2, shown enlarged in Figure 31. The first terminal
block (the shorter one) has two designations. A “@” is written on the terminal block itself, and “FIG. Bl” appears
directly to the right of this terminal block. The “0 ” is a reference letter; if you look at the lamp driver
2, you will see a corresponding terminal block designated “0 .” So. . the terminal block labeled ” C ” to the right
oard in ROW
6
of ROW 2 is located on the lamp driver board. The “FIG. Bl ” designation refers to Figure Bl in the M-21 20 initiating
wirfng diagrams.
The terminal blocks designated I’@” and ‘@” are interpreted in the same way. These terminal blocks are
located on the switch I/O board, and you make connections to these terminal blocks as shown in Figure Cl in the
M-21 20 initiating wiring diagrams.
All the remaining contractor connections on the left- and right-hand sides of the SCC cabinet drawing are
interpreted in the same way as the examples presented here. This includes any power line wiring (if required) and
audio/telephone wiring (if required).
Transponder Cabinet Drawings - Sample 1
‘\
Each 2120 transponder cabinet is supplied with its own cabinet drawing. This drawing shows the position of each
piece of equipment located in the transponder cabinet, as well as all contractor connections for each transponder
in the cabinet. We are going to examine two such cabinet drawings.
Take a look at Figure 32. This transponder cabinet drawing shows four basic transponders (BTs), each of which
uses a standard relay board for Monitor and Control Point wiring. The cabinet is also equipped with a “BT/FABT
PWR BD” (ROW 6). Notice that the left-hand side of this transponder cabinet drawing is labeled “CONTRACTOR
CONNECTIONS.” The illustrations in this column show the data line connections for the units in this cabinet. Let’s
take a closer look at the connections shown.
The terminal block to the left of ROW 2 (TBl) is shown enlarged in Figure 33. Notice that the reference letter “@”
appears directly above this terminal block. If you lo k at the BT controller board shown in ROW 2 (Figure 32), you
can see a corresponding terminal block labeled “
2 is located on the BT controller board.
A .” So the terminal block labeled “@” to the left of ROW
6
You should make the “INCOMING DATA LINE” connections to this terminal block as shown.
Now. :
. the terminal block labeled “ @
” to the left of ROW 5 is shown enlarged in Figure 34. This terminal block
is located on the BT controller board in ROW 5. You should make the connections for the outgoing data line
(“CONTINUE DATA LINE”) as shown.
Note: The incoming and outgoing data line connections are made at the first and last transponders in the cabinet,
respectively. The data lines between the four transponders are factory-connected.
Looking at Figure 32 again, you can see that the right-hand side of this cabinet drawing is broken up into two
columns. The first column illustrates the contractor connections for the Monitor Points on each transponder. The
second column illustrates the contractor connections for the Control Points on each transponder. Let’s look at the
Monitor and Control Point connections shown for the transponder in ROW 2.
The contractor connections to the right of ROW 2 are enlarge
Points are made at terminal block TB2. The reference letter “
top of the standard relay board shown in ROW 2 of Figure 32. The bottom two terminals can be connected as shown
in Figure 35. Connections for the first four Monitor
B ” tells you that this terminal block is located at the
8
in the sample to the right of TB2. Notice that each sample has a reference figure number beside it. These
referenced figures are located in the 2120 initiating wiring diagrams . . refer to the reference
the proper way to connect the monitored devices to the Monitor Point. As indicated by the ” Y ” designation, the
three remaining Monitor Points on this terminal block are connected just like the sample shown for the first Monitor
figure to determine
8
Point.
41
Page 38
Beneath TB2 in Figure 35 is the terminal block for the last four Monitor Points (TB3), designated by a “@.” The
“ C ” tells you that this terminal
0
Figure 32. As indicated by the ”
shown for TB2.
Connections for the BT’s Control Points are made at terminal block TBl, as shown in Figure 35. The reference letter
”
D ” tells you that TBl is located on the right-hand side of the standard relay board shown in ROW 2 of Figure
0
32. Notice that this terminal block has “FIG E” written beside it. “FIG E” refers to Figure E in the M-2120 initiating
wiring diagrams. See the referenced figure to determine the proper way to connect external devices to the Control
Points.
We have only described contractor connections for the first transponder in this particular cabinet. However, all
contractor connections are interpreted in the same way. For each transponder, be sure to:
l
Check both sides of the drawing for contractor connections.
l
Use the designated reference letter to physically locate the terminal block.
l
Refer to the data and power line system interconnection drawing to determine the possible source and
destination of data and power lines.
l
Refer to referenced figures in the M-21 20 initiating wiring diagrams to see how you connect external devices
to a transponder’s Monitor and Control Points.
Transponder Cabinet Drawings-Sample 2
We have discussed one sample of a 2120 transponder cabinet drawing. All such drawings are interpreted in much
the same way. However, there are two other aspects of 2120 systems that need some discussion: the audio sub-
riser configuration, and the telephone line interconnection.
lock is located at the bottom of the standard relay board shown in ROW 2 of
Y ” designation, the Monitor Points on TB3 are connected just like the sample
6
Take a look at Figure 36. The transponder cabinet shown is quite similar to the one in Figure 32; the only difference
involves the audio and telephone line connections shown. Let’s focus on the contractor connections shown in the
second column to the right of ROW 1 (“CONTRACTOR CONNECTIONS/RELAY BOARD CONTROL
POINTS”). These connections are enlarged in Figure 37.
The terminal blocks shown in Figure 37 (TBl through TB3) are located on the audio relay board in ROW 1, as
indicated by the reference letter ”
audio system. Notice that the incoming audio line (“AUDIO SUB-RISER IN”) is also connected to terminals on
TBl. Therefore, the speaker circuits connected to TBl are fed by the 2120 audio sub-riser. Refer to the audio and
telephone line system interconnection drawing to determine the possible source of the incoming audio line.
Moving on to TB2, you can see that connections to this terminal block are made according to “FIG K” in the M-2120
initiating wiring diagrams.
Finally, look at TB3. Connections for the incoming telephone line are made at this terminal block, along with the
associated telephone circuit. The telephone circuit itself is connected according to “FIG M” in the M-2120 initiating
wiring diagrams. Refer to the audio and telephone line system interconnection drawing to determine the source of
the incoming telephone line.
In Figure 36, the telephone line continues from the last transponder at the cabinet; the audio line ends at the last
transponder in the cabinet (ROW 3). If there had been other audio speaker circuits in the system, the outgoing audio
line would have been connected to appropriate terminals on TBl in ROW 3.
D .” The Control Points on TBI are connected to speaker circuits for the 2120
0
42
Page 39
CONTRACTOR U
CONTROLLER
HEFtA TO NOTC
ECTIONS
ID
.-
MODULE LAYOUT AND FACTORY INTERCONNECT IOk
r
-
-
r
7
F
:
J
r
1
Page 40
J
L
L
i-
.Pg.C,
S NOLIN
-A-: 13981-747
I w I
Transponder Cabinet Drawing
Sample 1
FIGURE 32
Page 41
Page 42
4 UNIT
FACTOR” wIRI*G IS lNOlClTE0 a” SOllO
LlNES ALL FACTOR” ,NTERCONNECTlkO
WIRES ARE NO 18 AWG UNLESS OTtlERWISE SPEClFlEO
,w,S,ED PAIR
STR NO. S63-10s a=aLAcK R=RED
FOR WIRES NUMBERED
HO. 14 liwo FOR WIRES NUMBERED ‘Y-2120) .=I@.-
HARNESSED SEPARATELY
CoNTRdCTOe WlRlNO IS SrlOWN Ik 0AS”E0 LIMES
I REFER TO SlSTEY ,NTERCONNECTlON DlAORlY
FOR DATA LIr4E, &“DIO LINE AND TELEPHONE
LlHE TERMlNATlON 8. .9LAClc C=CLE*R S=WIELD
z REFER TO SISTEM ,NTERCONNECTlON DII\ORAM
FOR POWER LINE TERMINATION. B= BLACK
R . RED
SYSTEM POWER REQIIIREMENTS
CABINET8 1
Page 43
LONTRACTOR CONNECTIONS
I-
I-“NTAOLLEA BO&AO
. .
MODULE LAYOUT AND FACTORY INTERSON N t-CT I ON
CONTf?AC/CiR CONNtL’ lUlV.,
RELAY
BDA”0
MONITOR
POINTS
LU,,I,~,l,L.,~L,~, LLSI (_I ” -
RELAY BOAR0 CONTROL POINTS
REFER TO NOTE S FIO -
I
I
1
Page 44
lder Monitor
Dint Connections
l d Telephone)
JRE 37
AU010 SUB-RISa
I” I SEE NOTE I )
INCOMINQ TELEPHONE
LINE (IF REOUIR~D)
Stt NOTE I
i I
i
FIGURE 37
Page 45
Expanded Transponder Cabinet Drawings (Figure 38)
The expanded transponder (ET) cabinet drawings are similar to the “standard” transponder cabinet drawings we
have already discussed. The left- and right-hand sides of the ET drawings are devoted to contractor connections.
The terminal blocks illustrated have reference letters so that you can easily locate each terminal block on the ET
itself. Similarly, figure references to M-2120-ET initiating wiring diagrams are made at each Monitor and Control
Point terminal block for appropriate contractor connections.
Note: The M-2120-ET initiating wiring diagrams are not the same as the M-21 20 initiating wiring diagrams. DO
NOT CONFUSE THE TWO.
The ET cabinet drawing also uses numerical references enclosed in squares (e.g.,
boards located in an ET, and these boards are numbered for easy reference. Therefore, when you see a numeric
reference next to a terminal block in the contractor connections column, look for the corresponding number on the
cabinet layout. In this way you can easily relate each set of contractor connections to the associated ET circuit
board.
q
). There are many circuit
55
Page 46
INSTALLATION GUIDE
So far in this publication, we have discussed the various documents that are supplied with every new 2120 system.
After studying the examples provided, you should be able to accurately interpret the documents supplied with your
system. Remember: even though there may be many documents provided, they are all interpreted in the same
way as the examples in this publication.
Now that you know how to interpret system documentation, we need to spend some time discussing the installation
itself. Therefore, this segment of the manual is devoted to a general guide for all 2120 installations.
Installation Precautions
Before you install any part of a new 2120 system, there are precautions you need to know and apply to your
particular installation. These precautions are listed below; if you adhere to the rules they provide, your installation
should proceed smoothly and safely.
A. Used twisted, shielded pair for the following:
l
Data lines.
l
Audio and telephone lines.
. RS232C ports.
Note: Monitor Point wiring may or may not require twisted, shielded pair. Refer to the 2120 Field Wiring
Specifications (900-036) for specific recommendations.
B. Each equipment cabinet should be connected to building ground via a single, unbroken conductor (12AWG
wire, typical).
C. DO NOT MAKE ANY CONNECTIONS TO BASIC TRANSPONDERS (BTs), FIRE ALARM BASIC
TRANSPONDERS (FABTs), OR EXPANDED TRANSPONDERS (ETs) WITH POWER APPLIED. This
includes all Monitor and Control Point wiring.
D. Before applying power to new equipment:
l
Verify that power connections have been terminated at the proper terminals.
l
Verify that equipment with a mixture of high and low voltages has all connections properly terminated (for
example, transponders containing low-voltage Monitor Point wiring and high-voltage Control Point
wiring).
l
Verify that all wiring is free of grounds.
E. Apply power to equipment ONLY in the presence of a qualified Simplex Technical Representative and in the
following sequence:
1. Apply AC power first.
2. Apply battery power last.
Reverse this sequence when you power down equipment.
F. NEVER APPLY OR DISCONNECT EQUIPMENT POWER BY USING AN INTERCONNECT PLUG.
G. Do not remove the end-of-line (EOL) resistors on transponder Monitor Points until you are ready to install the
Monitor Point wiring.
56
Page 47
Installation Guide
The following is a set of recommended procedures to following during installation. Before you begin wiring the
system:
l
Ensure that all system interconnection and wiring diagrams required for your system are provided.
l
All backboxes (cabinets) and the associated equipment should be properly installed AND grounded via a
single, unbroken conductor (12AWG, typical). Conduit ground is NOT sufficient.
1. Connect the data line between all equipment first. To do so, you must:
l
Refer to the 2120 General System Features form to see whether each data line equipped is single line
(one pair of wires, with shield, option number 6201) or McCulloh loop (two pairs of wires, with shields,
option number 6202).
l
Refer to the appropriate system interconnection diagram to see how cabinet-to-cabinet connections are
made.
l
Refer to the individual equipment cabinet drawings to determine how the data line is terminated at each
equipment cabinet.
2. Next, connect the audio lines (if audio is equipped) between all equipment associated with the audio system. To
do so, you must:
l
Refer to the cabinet interconnection and drawing list (part of the system interconnection drawings) to see
which equipment cabinets are interconnected for the audio sub-riser configuration.
l
Refer to the appropriate system interconnection diagram to see how cabinet-to-cabinet audio connections
are made.
l
Refer to the cabinet drawings specified in the cabinet interconnection and drawing list to determine how
the audio sub-riser is connected to audio Control Points at each equipment cabinet.
3. Connect the telephone lines (if telephone is equipped) between all equipment associated with the telephone
system. To do so, you must:
l
Refer to the appropriate system interconnection diagram to see how cabinet-to-cabinet telephone line
connections are made.
l
Refer to the appropriate cabinet drawings to determine how the telephone line is terminated at each
equipment cabinet. The specification sheet (or transponder specification worksheet, for transponders) for
each piece of equipment will tell you if the telephone line is associated with that piece of equipment.
4. Connect the power lines between all equipment cabinets as required. To do so, you must:
l
Refer to the cabinet interconnection and drawing list to see which equipment cabinets are interconnected
for the power line configuration.
l
Refer to the appropriate system interconnection diagram to see how cabinet-to-cabinet power
connections are made.
l
Refer to the cabinet drawings specified in the cabinet interconnection and drawing list to determine how
the power line is connected at each equipment cabinet, if such a connection is required.
57
Page 48
5. At this point, enough connections have been made for a Simplex Technical Representative (TR) to check out
the basic operation of your 2120 system. It is recommended that you contact your local TR and have him verify
that all data, audio/telephone, and power line connections have been properly made. Then the TR will have you
apply power to the system so that he can verify the operation of the system’s basic components. When the TR
has completed his preliminary checkout, power-down all equipment.
6. Wire all external devices for the Monitor and Control Point circuitry. To do so, you must:
l
Refer to each equipment cabinet drawing to determine where each transponder’s Monitor and Control
Point circuit is terminated.
l
Refer to the M-21 20 or M-2120-ET initiating wiring diagrams, as appropriate, to determine how peripheral
devices are connected to a transponder’s Monitor and Control Points.
As you finish wiring a group of external devices, verify that your wiring is free from grounds before terminating
each circuit to its associated Monitor or Control Point.
Note: Monitor Point wiring includes an EOL resistor at the end of each circuit (with the exception of McCulloh loop
Monitor Point circuitry). Therefore, as you connect each Monitor Point to its associated circuit, remove the
EOL resistor connected at the Monitor Point terminal (this EOL resistor was installed by the factory).
8. Now that the system is completely installed, you should again contact your local TR. The TR will completely
check out your system. Once he has completed his checkout he will either notify you of any wiring problems he
encountered, or will let you know that the system is operating properly.
9. Correct any wiring defects the TR found. If no defects were found, then the installation phase of your job is
complete. If there were wiring defects, contact the TR after you have corrected the problem and have him verify
that your system is now operating properly.
58
Page 49
I
i
i
Page 50
-- t
,Simplex
s3
Simplex Time Recorder Co., l Simplex Plaza l Gardner, Massachusetts 01441 U.S.A.
MUX2-21-003
(575-557)
1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.