Siemens SED2 VFD User Manual

0 (0)

SED2 VFD Electronic Bypass Options

Operating Instructions

Item Number 125-3208, Rev. FA

SED2 VFD Electronic

Bypass Option

Operating Instructions

NOTICE

The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document.

All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license.

WARNING

The Siemens Building Technologies SED2 Variable Frequency Drives are shipped without EMC line filters. (The EMC filter is most commonly used in Europe.) Where local codes or customer/installation requirements dictate, separately orderable Class A line filters are available. More stringent Class B line filters are also available for most models. Installation of these filters satisfies the requirements for the EU's EMC directive.

SERVICE STATEMENT

Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. All Siemens Building Technologies, Inc. branch offices and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system performance.

For further information, contact your nearest Siemens Building Technologies, Inc. representative.

CREDITS

Product or company names mentioned herein may be the trademarks of their respective owners.

Copyright © 2007 by Siemens Building Technologies, Inc.

TO THE READER

Your feedback is important to us. If you have comments about this manual, please submit them to SBT_technical.editor@siemens.com

Country of Origin: US

Table of Contents

Table of Contents

 

How to Use this Manual................................................................................................

1

Manual Organization..................................................................................................

1

Manual Notations.......................................................................................................

1

Where To Send Comments .......................................................................................

2

Reference Documents ...............................................................................................

2

Safety Instructions........................................................................................................

3

Electronic Bypass Option Overview ...........................................................................

4

General Description ...................................................................................................

4

Controller Board.........................................................................................................

5

Contactors..................................................................................................................

6

Keypad Functions ......................................................................................................

6

Installation Instructions ...............................................................................................

9

Environmental Conditions..........................................................................................

9

Mechanical Installation ..............................................................................................

9

Inspection ................................................................................................................

9

Dimensions and Weights ........................................................................................

9

Mounting..................................................................................................................

10

Electrical Installation ..................................................................................................

12

Startup Procedures.......................................................................................................

19

Safety Precautions.....................................................................................................

19

Installation Inspection ................................................................................................

19

Power-On...................................................................................................................

19

Quick Commissioning ................................................................................................

21

Additional Parameter Settings ...................................................................................

31

Flying Start ..............................................................................................................

31

Automatic Restart....................................................................................................

33

Vdc Controller..........................................................................................................

36

Pulse Frequency .....................................................................................................

37

Motor Data Identification .........................................................................................

38

Reset to Factory Defaults........................................................................................

40

Required SED2 Parameter Settings ............................................................................

41

Siemens Building Technologies, Inc.

i

SED2 VFD Electronic Bypass Option Operating Instructions

Application Feature Setup ...........................................................................................

42

Overview ....................................................................................................................

42

Auto Bypass without Interlock....................................................................................

42

Description ..............................................................................................................

42

Settings ...................................................................................................................

43

Example SED2 Settings..........................................................................................

43

Interlock .....................................................................................................................

44

Description ..............................................................................................................

44

Settings ...................................................................................................................

44

Wiring Example for Interlock ...................................................................................

46

Essential Services......................................................................................................

46

Description ..............................................................................................................

46

Settings ...................................................................................................................

47

Wiring Example for Essential Services ...................................................................

47

Interlock and Auto Bypass on VFD Fault...................................................................

48

Description ..............................................................................................................

48

Settings ...................................................................................................................

48

Wiring Example for Interlock and Auto Bypass on VFD Fault ................................

48

Technical Specifications ..............................................................................................

49

Troubleshooting............................................................................................................

51

Power-on Initialization Failure (Unit Fault Condition) ...............................................

51

Override Jumper ........................................................................................................

52

Fuses .........................................................................................................................

52

ii

Siemens Building Technologies, Inc.

How to Use this Manual

How to Use this Manual

Manual Organization

This manual contains the following sections:

How to Use this Manual, describes the organization of this manual and the symbols used throughout this manual.

Safety Instructions, provides general guidelines for your safety and to prevent equipment damage.

Electronic Bypass Option Overview, describes the Electronic Bypass Option Controller board, inputs, outputs, contactors, and keypad.

Installation Instructions, provides mounting information and details on electrical connections.

Startup Procedures, provides step-by-step procedures to start up the Electronic Bypass Option.

Required SED2 Parameter Settings, lists SED2 parameter settings necessary for operation of the Electronic Bypass Option.

Application Feature Setup, describes application features and provides the necessary parameter settings.

Technical Specifications, lists Electronic Bypass Option and SED2 VFD specifications.

Troubleshooting, provides guidelines for troubleshooting the Electronic Bypass Option.

Manual Notations

Notation

Symbol

Meaning

 

 

 

WARNING:

 

Indicates that personal injury/loss of life may occur if you do

 

 

not perform a procedure as specified.

 

 

 

CAUTION:

 

Indicates that equipment damage, or loss of data may occur if

 

 

you do not perform a procedure as specified.

 

 

 

NOTES:

(no symbol)

Provides other important information or helpful hints.

 

 

 

Siemens Building Technologies, Inc.

1

SED2 VFD Electronic Bypass Option Operating Instructions

Where To Send Comments

Your feedback is important to us. If you have comments about this manual, please submit them to technical.editor@sbt.siemens.com.

Reference Documents

The following SED2 documentation is available from your local Siemens Building Technologies, Inc. representative:

SED2 VFD Startup Operation, and Maintenance Manual (125-3201), provides operating instructions and procedures for the SED2.

SED2 VFD Parameter Reference Guide (125-3214), provides descriptions of SED2 parameters.

SED2 VFD Submittal Sheet (154-042), provides a synopsis of the SED2 product line, accessories, and technical data.

SED2 VFD Electronic Bypass Options Submittal Sheet (154-051), provides a comprehensive overview of the SED2 Electronic Bypass option.

2

Siemens Building Technologies, Inc.

Safety Instructions

Safety Instructions

The following guidelines are provided for your safety, to prevent damage, and to extend the service life of the SED2 product and any connected equipment. Read this information carefully. Specific Warnings, Cautions, and Notes are provided in the relevant sections of this manual.

WARNING:

The SED2 uses hazardous voltages and controls potentially dangerous rotating mechanical parts. Non-compliance with warnings or failure to follow the instructions contained in this manual can result in loss of life, severe personal injury, or serious damage to property/equipment.

Only authorized personnel should work on this equipment, and only after becoming familiar with all local regulations and ordinances; safety notices; and installation, operation, and maintenance procedures in this manual. Successful and safe operation of this equipment depends upon its proper handling, installation, operation, and maintenance.

Before carrying out any installation and commissioning procedures, you must read all safety instructions and warnings, including all warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and ensure missing or damaged labels are replaced.

Observe the regulations of Safety Code VBG 4.0 (in particular, “Permissible Deviations when Working with Live Parts”) whenever measuring or testing is performed on live equipment. Also, use suitable electronic tools.

Only use this equipment for the purpose specified by the manufacturer. Unauthorized modifications and the use of spare parts and accessories that are not sold or recommended by the manufacturer of the equipment can cause fires, electric shocks, and injuries.

Prevent the general public from accessing or approaching this equipment.

NOTE: Keep these Operating Instructions near the equipment and available to all users.

Siemens Building Technologies, Inc.

3

SED2 VFD Electronic Bypass Option Operating Instructions

Electronic Bypass Option Overview

General Description

During normal operation in a typical application, the input and output contactors close and the SED2 operates the motor (Figure 1). The bypass contactor provides the ability to operate the motor on utility power and eliminate the SED2 from the motor control circuit. The SED2 Electronic Bypass Option also allows you to select features that enhance the control of the contactors and the outputs that report operation.

The SED2 Electronic Bypass (E-Bypass) Option consists of a SED2 VFD, and a bypass enclosure with electronic controls (Figure 2). The electronic controls include:

Controller board

Keypad

Step-down power transformer

Contactors:

Bypass

Output

Input (optional)

Overload (current) relay

Reactor (optional)

Disconnect switch (or optional circuit breaker)

BYPASS OVERLOAD

CONTACTOR RELAY

VFD0093R1

 

 

 

 

 

 

VFD

 

 

 

 

 

 

MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

CONTACTOR

CONTACTOR

 

 

INPUT

 

OUTPUT

Figure 1. Functional Block Diagram of

Typical Electronic Bypass Option.

CONTROLLER

SED2 VFD

BOARD

KEYPAD (DOOR MOUNTED)

 

 

INPUT

 

 

CONTACTOR

 

STEP-DOWN

 

 

POWER

REACTOR

 

TRANSFORMER

 

(OPTIONAL)

 

 

 

OUTPUT

 

 

CONTACTOR

 

 

BYPASS

 

 

CONTACTOR

 

 

 

DISCONNECT

 

 

SWITCH

VFD0094R1

 

(OR OPTIONAL

OVERLOAD

CIRCUIT BREAKER

 

 

SHOWN)

 

(CURRENT)

 

 

 

RELAY

 

• Fuses (optional)

Figure 2. Typical SED2 E-Bypass Components.

Cable harnesses

4

Siemens Building Technologies, Inc.

Electronic Bypass Option Overview

Controller Board

The Controller board is the foundation of the SED2 Electronic Bypass Option. It controls communications to and from the SED2, keypad, isolated digital inputs, relay/digital outputs, and contactors (Figure 3).

VFD0095R1

SED2 INTERFACE

Supports two SED2 non-isolated, digital relay outputs and three SED2 digital inputs. The maximum current draw for a relay output is 2 mA and

the voltage between the digital output source and return lines is 24V. The Controller board provides unregulated, non-isolated 24V to power the SED2 digital inputs.

BASIC SANITY TEST INDICATOR

Provides indication of initialization and normal operation.

KEYPAD INTERFACE

Supports inputs and outputs from the Electronic Bypass Option keypad. The keypad provides user interface indicators and push buttons.

FACTORY USE ONLY

Connector J8 is for factory use only.

DIGITAL INPUTS

Supports six isolated digital inputs for customer use. The inputs require a contact closure capable of providing a low impedance path at currents less than 20 mA.

DIGITAL RELAY OUTPUTS

Supports six digital relay outputs for customer use. Each relay has a maximum rating of 2A at 120 Vac.

OVERRIDE JUMPER

DIP SWITCHES

The Controller board DIP switches enable/disable the Electronic Bypass Option features.

J4

CONTROLLER

BOARD

 

 

 

 

J3

MCU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J8

 

 

 

 

 

 

ON

 

 

OFF

 

 

SW1

 

 

J2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J1

TRANSFORMER

F1

J6

J7

J5

CONTACTOR POWER

CONTROLS

ON

 

 

 

 

 

 

 

 

5

 

5

OPTIONS 3 4

 

 

3 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

2

 

ON

 

 

 

 

 

 

 

1

1

 

 

 

 

 

OFF

Not used, factory test selector switch #2; leave this switch OFF.

Not used, factory test selector switch #1; leave this switch OFF.

Interlock selector switch; requires SED2 programming.

Automatic Bypass selector switch; requires SED2 programming.

Essential Services selector switch.

SW1

When the switch is ON the option is enabled; when the switch is OFF the option is disabled.

Figure 3. Controller Board Inputs and Outputs.

Siemens Building Technologies, Inc.

5

SED2 VFD Electronic Bypass Option Operating Instructions

Contactors

The Controller board provides two or three relay contact circuits controlled by the Electronic Bypass Option: bypass, input, and output contactors. Each circuit includes a NO relay. Controller board connector J7 enables circuit connections. The relay circuits route power to the SED2 and the motor via the contactors. Controlling the contactors through the relay circuits is the main function of the Controller board.

Bypass Contactor – The bypass relay on the Controller board controls the bypass contactor. The output and bypass relays are interconnected to 120 Vac Hot. This enables a safety circuit that prevents the bypass and output contactors from simultaneously being energized.

Output Contactor – The output relay on the Controller board controls the output contactor.

Input Contactor – The input relay on the Controller board controls the optional input contactor.

Keypad Functions

VFD0096R1

 

 

 

Bypass

 

VFD

 

 

Bypass

 

Input

 

Hand

 

Input

Input

 

Hand

 

Contactor

 

Start

 

On/Off

Contactor

 

Start

 

Bypass

 

 

 

Bypass

 

 

Contactor

 

 

 

Contactor

 

 

VFD

 

 

 

 

VFD

 

 

Enable

Overload

Remote

 

Enable

Overload

Remote

Start

 

Start

 

Relay

 

 

Relay

 

 

 

 

 

 

Output

 

 

 

 

Output

 

 

 

Contactor

 

 

 

 

Contactor

 

 

 

Motor

 

 

 

 

Motor

 

 

STOP

AutoBypassEnabled

 

VFDFault

 

STOP

AutoBypassEnabled

 

VFDFault

 

 

 

 

 

RESET

 

SafetyFault

 

RESET

 

SafetyFault

 

 

VFD0097R1

 

 

 

EssentialServices

 

OverloadFault

 

EssentialServices

 

OverloadFault

 

 

 

 

 

 

 

 

 

 

 

 

 

Enable

Commanded Proofed

 

 

Enable

Commanded Proofed

INTERLOCKSTARTLOGIC

 

 

 

INTERLOCKSTARTLOGIC

 

 

2-CONTACTOR KEYPAD 3-CONTACTOR KEYPAD

Figure 4. E-Bypass Keypad Indicators and Pushbuttons.

The keypad provides user interface indicators and pushbuttons. The following table describes specific pushbutton and indicator functions:

6

Siemens Building Technologies, Inc.

Electronic Bypass Option Overview

Pushbutton/Indicator

 

 

VFD0098R1

Input

 

 

On/Off

 

 

 

 

 

VFD0099R1

Enable

 

 

 

 

 

VFD0100R1

Hand

 

 

Start

 

 

 

 

 

VFD0101R1

Remote

 

 

Start

 

 

 

 

 

VFD0102R1

STOP

 

 

RESET

 

 

 

 

 

 

VFDFault

 

VFD0103R1

SafetyFault

 

OverloadFault

 

 

 

 

 

VFDFault

 

VFD0104R1

SafetyFault

 

OverloadFault

 

 

 

 

 

VFDFault

 

VFD0105R1

SafetyFault

 

OverloadFault

 

 

VFD0106R1

AutoBypassEnabled

 

EssentialServices

 

 

AutoBypassEnabled

VFD0107R1

EssentialServices

 

Description

The Input On/Off pushbutton is supplied with the optional drive input contactor. In VFD mode, this switch does nothing. In bypass mode, this switch closes/opens the input contactor, switching the SED2 power on/off.

Enables SED2 operation by closing the input and output contactors.

Manually enables bypass mode operation by ensuring that the output contactor is open and then closing the bypass contactor.

Activates the bypass mode and operates the bypass contactor according to the status of the Remote Start input on the Controller board.

Opens the output and bypass contactors, disconnecting the motor.

When a VFD Fault is indicated, the VFD Fault indicator lights and the VFD Fault Relay output on the Controller Board is triggered.

The Safety Fault indicator lights when either of the Remote Safety inputs on the Controller board opens. The motor is prohibited from operating in either the VFD or bypass modes while either of these contacts is open.

EXCEPTION: Essential Services ignores a Safety Fault.

NOTE: If not using the Remote Safety feature, hard wire the two Remote Safety inputs.

If the Electronic Bypass Option current overload relay trips, the Overload Fault indicator lights and the motor will not run in bypass mode.

When the Auto Bypass DIP switch is enabled, the Auto Bypass Enabled indicator is on steady. Bypass operation is automatically initiated by the SED2.

When Auto Bypass is active, the Auto Bypass Enabled indicator flashes.

When the Essential Services DIP switch is enabled, the Essential Services indicator is on steady.

When the Essential Services input is open, normal operation is indicated as the output contactor remains closed to keep the motor running and the Essential Services indicator is on steady.

When the Essential Services input is closed, the bypass contactor closes and the Essential Services indicator flashes.

Nothing can interrupt the Essential Services mode except for the Essential Services input opening.

Siemens Building Technologies, Inc.

7

SED2 VFD Electronic Bypass Option Operating Instructions

VFD0108R1

Pushbutton/Indicator

Description

When the Interlock DIP switch is enabled, the Interlock Start Logic Enable indicator is on steady. Any call to start the motor in either VFD or bypass modes will not start the motor; instead it will close the Programmable Output relay on the Controller board.

The Programmable Output can be used to actuate another device. When

INTERLOCKSTARTLOGIC Enable Commanded Proofed this occurs, the Interlock Start Logic Commanded indicator also lights, and the Interlock Start Logic Proofed indicator flashes.

A contact closure from this other device is wired to the Interlock Start on the Controller board which then starts the motor and turns the Interlock Start Logic Proofed indicator on steady. This feature is also called damper end switch relay logic.

8

Siemens Building Technologies, Inc.

Installation Instructions

Installation Instructions

Environmental Conditions

Install the Electronic Bypass Option in a heated, indoor controlled environment that is free of moisture and conductive contaminants such as condensation and dust. The air entering the unit for ventilation/cooling must be clean and free from corrosive gases.

The ambient temperature must be between 14°F and 104°F (-10°C to 40°C) and the relative humidity must be 0% to 95% noncondensing. Do not mount unit in direct sunlight.

Mechanical Installation

Inspection

1.As you unpack the Electronic Bypass Option, check for shipping damage. In the event of damage, contact the transport company.

2.Locate the Electronic Bypass Option nameplate and confirm that the unit is configured to the installation requirements.

3.Verify the delivery is complete. If not, contact the supplier.

Dimensions and Weights

Figure 5 shows overall and mounting dimensions for the Electronic Bypass Option. Figures 6 through 8 show conduit locations.

Approximate weights are as follows.

 

 

 

 

 

 

 

Bypass

Weight lb (kg)

 

Frame Size

 

 

 

 

A

45

(20)

 

B

55

(25)

 

C

75

(34)

 

D

150 (68)

 

E

180 (82)

 

F

470

(213)

NOTE: Exact weight will be affected by actual horsepower/voltage and selected power options.

Siemens Building Technologies, Inc.

9

SED2 VFD Electronic Bypass Option Operating Instructions

Mounting

1.To ensure safe installation, verify that the surface of the mounting location is level.

2.Mount the Electronic Bypass Option vertically with the SED2 operator panel, Electronic Bypass Option keypad, and disconnect accessible.

= Protective Shield

 

 

Depth

 

 

With

 

 

Handle

Depth

 

9.6 (24)

 

 

With

13.2

1.5

Handle

9.6 (24)

(34)

(3.8)

34

 

48

 

(122)

(86)

 

 

 

 

 

10.5 TYP

 

 

(27)

 

12.4

1.5

 

(31)

(3.8)

Frame Size

A and B

 

 

 

 

 

 

 

Depth

 

 

 

 

 

 

 

With

11.5

 

 

 

 

 

 

Handle

 

1

10.4 (26)

(29)

 

(2.5)

2

 

 

 

 

 

 

 

 

 

(5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

53.5

 

(136)

 

11 TYP

 

(28)

10.6

2

(27)

(5)

Frame

 

Size C

 

20.82.9

(53)(7.4) 4

(10)

 

11.5 TYP

 

(29)

19.9

3.4

(51)

(8.6)

Frame

 

Size D

 

Depth

20.8

 

2.9

 

With

 

 

Handle

 

(53)

 

(7.4) 3

12.2 (31)

 

 

 

 

 

 

 

 

(7.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58.5

 

 

(149)

 

 

 

10 TYP

 

 

(25)

 

19.9

5.5

VFD0127R2

(51)

(14)

Frame Size E

 

 

45.5

 

 

Depth

 

 

 

 

 

 

17.4

 

(116)

 

 

 

 

 

(44)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57.5

(146)

Frame Size F

NOTE: It is recommended to leave 6 inches (15 cm) around the top and sides of the unit.

Figure 5. E-Bypass Dimensions in Inches (Centimeters).

10

Siemens Building Technologies, Inc.

Siemens SED2 VFD User Manual

Installation Instructions

VFD0201R1

1/2 (1.3) AND 3/4 (1.9) CONDUIT KNOCKOUTS

3/4 (1.9) AND 1 (2.5) CONDUIT KNOCKOUTS

6

(15.2)

3-5/8

(9.2)

2-1/8

(5.3)

9-1/2

(24.1)

Figure 6. Frame Sizes A through C Conduit Locations. Viewed from Bottom; Dimensions in Inches (Centimeters).

1/2 (1.3) AND 3/4 (1.9) CONDUIT KNOCKOUTS

1-1/4 (3.2) AND 1-1/2 (3.8) CONDUIT KNOCKOUTS (3)

 

8

 

 

(20.3)

 

 

4

 

 

(10.2)

 

 

2-3/4

 

VFD0202R1

(6.9)

 

8-1/2

(40.7)

 

(21.7)

16

 

 

Figure 7. Frame Sizes D and E Conduit Locations. Viewed from Bottom;

Dimensions in Inches (Centimeters).

VFD0203R1

 

 

 

 

20-3/8

 

 

 

15-3/8

(51.7)

 

 

13-5/8

(39.1)

 

 

11-7/8

(34.6)

 

 

7-3/8

(30.1)

 

 

 

(18.7)

 

 

 

 

4-1/4

(10.8)

3/4 (1.9) AND 1 (2.5) CONDUIT KNOCKOUTS (3)

3 (7.6) CONDUIT KNOCKOUTS (2)

Figure 8. Frame Size F Conduit Locations. Viewed from Top; Dimensions in Inches (Centimeters).

Siemens Building Technologies, Inc.

11

SED2 VFD Electronic Bypass Option Operating Instructions

Electrical Installation

See Figure 9 for all Electronic Bypass Option wiring.

1.Route shielded twisted pair (recommended wire type) cable, 24 gauge minimum control wiring in conduit through knockout and into housing (Figures 10 through 12). Connect control wiring per job-specific drawings.

NOTES:

Terminate shield at control device.

Control wiring is 12 to 26 AWG and tightening torque is 5 lb-in.

2.If applicable, route communications wiring (P1) in conduit through knockout and into housing (Figures 10 through 12). Continue to route communications wiring to SED2 and terminate per SED2 VFD Startup, Operation, and Maintenance Manual (125-3201).

3.Route motor wiring in conduit through knockout and into housing (Figures 10 through 12). Connect motor wiring to motor overload and ground lug. See Tables 1 through 4 for wire sizes and tightening torques.

4.Route input power wiring in conduit through knockout and into housing (Figures 10 through 12). Connect input power wiring to disconnect switch and ground lug or to circuit breaker and ground lug. See Tables 1 through 4 for wire sizes and tightening torques.