Siemens PC 677B User Manual

0 (0)

SIMATIC

Industrial PC

SIMATIC Panel PC 677B

Operating Instructions (Compact)

06/2008

A5E02217246-01

Safety

1

 

 

Delivery

2

 

 

Installation / panel-mounting

3

 

 

Connecting

4

 

 

Commissioning

5

 

 

Service and support

6

 

 

Siemens PC 677B User Manual

Safety Guidelines

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.

DANGER

indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING

indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION

with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

CAUTION

without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

NOTICE

indicates that an unintended result or situation can occur if the corresponding information is not taken into account.

If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified Personnel

The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards.

Prescribed Usage

Note the following:

WARNING

This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance.

Trademarks

All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

Disclaimer of Liability

We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

(A )

.

Siemens AG

A5E02217246-01

Copyright © Siemens AG 2008.

Industry Sector

06/2008

Technical data subject to change

Postfach 48 48 90327 NÜRNBERG GERMANY

Table of contents

1

Safety........................................................................................................................................................

 

5

2

Delivery......................................................................................................................................................

 

7

 

2.1

Unpacking and checking the delivery............................................................................................

7

 

2.2

Device identification data...............................................................................................................

8

 

2.3

Product Documentation .................................................................................................................

8

3

Installation / panel-mounting......................................................................................................................

9

 

3.1

Mounting depth of the device.........................................................................................................

9

 

3.2

Permitted mounting positions.......................................................................................................

10

 

3.3

Preparing the mounting cut-out....................................................................................................

11

 

3.4

Securing the device with clamps..................................................................................................

13

 

3.5

Securing with screws...................................................................................................................

14

4

Connecting ..............................................................................................................................................

17

 

4.1

Connection elements and operator controls................................................................................

18

 

4.2

Connecting the 120 V / 240 V AC power supply..........................................................................

20

 

4.3

Connecting the (24 V) DC power supply .....................................................................................

22

 

4.4

Connecting the Equipotential Bonding Circuit .............................................................................

23

5

Commissioning........................................................................................................................................

25

 

5.1

Initial Startup................................................................................................................................

25

 

5.2

Setting up the language selection................................................................................................

26

 

5.3

Setting the panel type..................................................................................................................

27

 

5.4

KeyTools (for key panel devices).................................................................................................

28

 

5.5

On-screen keyboard (for touch panel device)..............................................................................

29

6

Service and support.................................................................................................................................

31

SIMATIC Panel PC 677B

3

Operating Instructions (Compact), 06/2008, A5E02217246-01

Safety

1

CAUTION

In order to avoid substantial damage and for your own safety, note the safety instructions in this documentation and in the operating instructions.

WARNING

Function test while installing the device in machines or execute systems

Following the results of a risk analysis, additional protection equipment on the machine or the system is necessary to avoid endangering persons. With this, especially the programming, configuration and wiring of the inserted I/O modules have to be executed, in accordance with the safety performance (SIL, PL or Cat.) identified by the necessary risk analysis. The intended use of the device has to be ensured.

The proper use of the device has to be verified with a function test on the system. This test can detect programming, configuration and wiring errors. The test results have to be documented and, if necessary, entered into the relevant documents that verify safety.

SIMATIC Panel PC 677B

5

Operating Instructions (Compact), 06/2008, A5E02217246-01

Safety

6

SIMATIC Panel PC 677B

Operating Instructions (Compact), 06/2008, A5E02217246-01

Delivery

2

2.1Unpacking and checking the delivery

1.Please check the packaging material for transport damage upon delivery.

2.If any transport damage is present at the time of delivery, lodge a complaint at the shipping company in charge. Have the shipper confirm the transport damage immediately.

3.Unpack the device.

CAUTION

Do not lie the device on its back. This will avoid any damage to an optical drive which may be present. Lie the front side on a soft surface to avoid damaging the front panel USB port.

4. Keep the packaging material in case you have to transport the unit again.

NOTICE

The packaging protects the device during transport and storage. Therefore, never dispose of the original packaging material!

5.Please keep the enclosed documentation in a safe place. You will need the documentation when you start up the device for the first time.

6.Check the contents of the package for completeness and transportation damage. Check for completeness using the enclosed scope of delivery list.

7.Should the contents of the package be incomplete or damaged, please inform the responsible supply service immediately and fax us the enclosed form "SIMATIC IPC/PG quality control report".

WARNING

Make sure that a damaged device is not installed nor put into operation.

8. Note the identification information (see chapter "Identification data of the device").

SIMATIC Panel PC 677B

7

Operating Instructions (Compact), 06/2008, A5E02217246-01

Delivery

2.2 Device identification data

2.2Device identification data

Enter the identification data of the device into the table.

SVP number (on the type plate)

Order No.

Package with Windows 2000 / XP Professional:

"Microsoft Windows Product Key" from "Certificate of Authenticity" (COA)

The label is attached to the device.

Ethernet address:

BIOS Setup (F2 key) under

"Main > Hardware Options > Ethernet Address"

2.3Product Documentation

The detailed operating instructions for Panel PC 677B can be downloaded as a PDF file on the Internet under the following address:

http://www.siemens.com/automation/service&support, article ID 25737077

8

SIMATIC Panel PC 677B

Operating Instructions (Compact), 06/2008, A5E02217246-01

Installation / panel-mounting

3

3.1Mounting depth of the device

7

Panel PC with operator control units

Depth D

Key panel with 12" TFT

105 mm

Key panel with 15" TFT

124 mm

Touch panel with 12" TFT

123 mm

Touch panel with 15" TFT

121 mm

Touch panel with 17" TFT

130 mm

Touch panel with 19" TFT

130 mm

Note

Additional mounting depth with optical drive

The installation depth increases by 21 mm when an optical drive is installed in the device.

SIMATIC Panel PC 677B

9

Operating Instructions (Compact), 06/2008, A5E02217246-01

Installation /panel-mounting 3.2 Permitted mounting positions

3.2Permitted mounting positions

Approval

Only certain mounting positions are approved for the device.

$ %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3-1

Mounting position

 

 

 

 

 

Table 3-1

Permissible deviations from the vertical mounting position

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

 

 

Angle A

 

 

 

 

Angle B

to 45°C

 

 

20°

 

 

 

 

20°

Note

When mounting the device at an angle, note the following.

Do not subject the device to mechanical stress.

Operation of a DVD drive is not permitted.

10

SIMATIC Panel PC 677B

Operating Instructions (Compact), 06/2008, A5E02217246-01

Loading...
+ 22 hidden pages