Siemens FC700A User Manual

0 (0)

FC700A

Fire detection system

Planning

Fire & Security Products

Siemens Building Technologies

Liefermöglichkeiten und technische Änderungen vorbehalten.

Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité.

© 2004 Copyright by

Siemens Building Technologies AG

Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder außerhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist.

We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.

Nous nous réservons tous les droits sur ce document, ainsi que sur l'objet y figurant. La partie recevant ce document reconnaît ces droits et elle s'engage à ne pas le rendre accessible à des tiers, même partiellement, sans notre autorisation écrite préalable et à ne pas l'employer à des fins autres que celles pour lesquelles il lui a été remis.

1

About this document ..............................................................................

6

2

Safety regulations...................................................................................

8

2.1

Signal words and symbols ........................................................................

8

2.1.1

Signal words and their meaning................................................................

8

2.1.2

Symbols and their meaning ......................................................................

8

2.1.3

Classification and meaning of additional symbols ....................................

9

2.2

Safety-relevant working instructions .........................................................

9

3

Main features.........................................................................................

11

4

Technical data FC700A.........................................................................

12

5

Logical and physical structure............................................................

13

6

Bus systems..........................................................................................

14

6.1

Bus overview...........................................................................................

15

6.2

Modifying the impedance of the various C-Bus cables...........................

15

6.2.1

Diagram...................................................................................................

16

7

C-Bus stations.......................................................................................

17

7.1

Station .....................................................................................................

17

7.2

Types of stations.....................................................................................

17

7.3

Hardware.................................................................................................

17

7.4

Visualizer for Windows remote operation software (not available yet) ...

18

7.5

Logical AREAS........................................................................................

19

8

Limitations of C-Bus participants .......................................................

20

8.1

Main CPU limits.......................................................................................

20

8.1.1

Maximum number of devices ..................................................................

20

8.1.2

Limits in the logical structure...................................................................

20

8.1.3

Maximum number of criteria in zones control 4 and 6............................

20

8.1.4

Maximum number of ZONE time channel...............................................

20

8.1.5

Maximum number of I-Bus-modules.......................................................

21

8.1.6

Limits of 5V supply..................................................................................

21

8.2

Control terminal limits (FC/FT)................................................................

21

8.2.1

Limitation of visible texts on a FC700A...................................................

21

8.2.2

Limitation of visible texts on a FT700A ...................................................

21

8.3

Gateway limits (FG) ................................................................................

22

9

Specify hardware required...................................................................

23

10

Control unit FC700A .............................................................................

24

10.1

Configuration...........................................................................................

24

10.2

Block diagram .........................................................................................

25

10.3

Modules...................................................................................................

25

11

Auxiliary power supply.........................................................................

26

11.1

Configuration...........................................................................................

26

11.2

Block diagram .........................................................................................

26

11.3

Modules...................................................................................................

26

12

Control terminal B3Q700 (FC/FT) ........................................................

27

12.1

Features ..................................................................................................

27

12.2

Options....................................................................................................

27

12.2.1

Plexiglas door to B3Q700 (FC/FT)..........................................................

27

12.2.2

Place of the E3I020 RS232 module (FT)................................................

28

12.2.3

Place of the E3I040 LON interface (FT) .................................................

28

 

 

3

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

12.3

Installation possibilities (FT)....................................................................

29

12.4

Block diagram .........................................................................................

29

12.5

Connection lines between control unit and external operating units ......

30

12.6

Power supply (24V).................................................................................

30

12.7

Modules...................................................................................................

31

13

Range of cabinets H23 / H26 / H28 ......................................................

32

13.1

Recessed mounting H23G230 and H28G200 ........................................

33

13.2

Modules...................................................................................................

33

14

19” accessories.....................................................................................

34

14.1

Modules...................................................................................................

34

15

Line modules .........................................................................................

35

15.1

Overview .................................................................................................

35

15.2

Modules...................................................................................................

35

15.3

Detection line "addressable" SynoLOOP................................................

36

15.4

Detection line "collective" SynoLINE600/-Ex ..........................................

37

16

Connection factors, line resistances and capacitances ...................

38

16.1

Terminology and abbreviations...............................................................

38

16.2

Collective detection line ..........................................................................

38

16.3

Addressable detection line......................................................................

38

16.4

Line resistance and capacitance.............................................................

39

17

Control modules....................................................................................

40

17.1

Application of control modules ................................................................

40

17.1.1

Overview of the available modules with control outputs .........................

40

17.2

Means of linking ......................................................................................

40

17.3

Control outputs station type FC700A ......................................................

41

17.4

Control outputs remote station type FT700A ..........................................

41

17.5

Modules...................................................................................................

41

17.6

CPU-overlapping controls .......................................................................

42

17.7

Mimic Display panel outputs ...................................................................

43

17.8

Modules...................................................................................................

43

17.9

Relay outputs ..........................................................................................

44

17.10

Modules...................................................................................................

44

18

LON-Bus devices ..................................................................................

45

18.1

Features ..................................................................................................

45

18.2

LON-Bus as stub line ..............................................................................

45

18.3

LON-Bus as free topology.......................................................................

46

18.4

LON/Mimic Display p.c.b K3I050 ............................................................

46

18.5

LON I/O card K3I110...............................................................................

46

18.6

Indicator devices B3Q580 and B3Q590/595...........................................

47

18.7

Modules...................................................................................................

47

19

Gateway..................................................................................................

48

19.1

Main features ..........................................................................................

48

19.2

Application...............................................................................................

48

19.3

Modules...................................................................................................

49

20

Remote transmission............................................................................

50

21

Printer interface.....................................................................................

51

4

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

21.1

Features ..................................................................................................

51

21.2

Application variant FT .............................................................................

51

21.3

Application variant FC.............................................................................

51

21.4

Modules...................................................................................................

51

22

Power supply.........................................................................................

52

22.1

Concept...................................................................................................

52

22.2

Special functions.....................................................................................

52

22.3

Application...............................................................................................

52

22.4

Power supply for the control unit.............................................................

52

22.5

Auxiliary power supply ............................................................................

52

22.6

Modules...................................................................................................

53

22.7

Operation with power supply from control unit........................................

53

22.8

Power supply for remote transmission equipment and accessories.......

53

23

Emergency power supply ....................................................................

54

23.1

Specifying battery capacity .....................................................................

54

23.1.1

Battery rated capacity .............................................................................

54

23.1.2

Ageing of battery.....................................................................................

54

23.1.3

Calculation ..............................................................................................

54

23.2

Capacity values for standard configurations...........................................

54

23.3

Quiescent current table...........................................................................

55

24

Alarm concept .......................................................................................

56

24.1

Cerberus Alarm Concept (CAC) .............................................................

56

24.2

Principle of the Cerberus alarm concept.................................................

56

24.3

Determine the alarm organization...........................................................

57

24.4

Organization of system operation ...........................................................

57

25

Commissioning .....................................................................................

58

26

Parameterization, Flash programming ...............................................

59

26.1

Functions.................................................................................................

59

26.2

Modules...................................................................................................

59

27

FC700A modules in alphabetical order ..............................................

60

28

Spare parts ............................................................................................

62

29

Configuration sheets ............................................................................

63

29.1

List of configuration sheets .....................................................................

63

30

Control unit FC700A .............................................................................

64

31

Auxiliary power supply.........................................................................

65

32

Control terminal FT700A ......................................................................

66

33

Display & operating terminals .............................................................

67

34

Externally placed modules...................................................................

68

 

5

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

About this document

1

About this document

 

 

 

 

 

 

 

 

 

 

 

Purpose

 

 

 

 

 

This document describes the project planning of the hardware modules of the con-

 

 

 

trol unit FC700A. The consistent adherence to these instructions is a prerequisite

 

 

 

for a safe application.

 

 

 

 

 

Scope

 

 

 

 

 

This document contains information of all FC700A components, including part

 

 

 

numbers for ordering.

 

 

 

 

 

Target group

 

 

 

 

 

This product documentation and the work instructions are aimed at the following

 

 

 

persons, who have a particular function and have the corresponding training and

 

 

 

qualification.

 

 

 

 

 

 

 

 

Group of persons

Activity

 

Qualification

 

Project Manager

The project manager is responsible for the local

He has had the technical training appropriate to

 

 

 

project management. He co-ordinates the sched-

his function and the size of a project or the prod-

 

 

 

ules of all groups of people working on a project

uct line used in the project and has attended the

 

 

 

as well as resources. He also continuously ob-

training courses for project managers at the sup-

 

 

 

tains the technical information required for project

plier’s works.

 

 

 

realization.

 

 

 

 

 

Reference documents

 

 

 

 

 

Information in

Document

 

 

 

 

007831

Hardware description

 

 

 

007827

Installation housing H26... /H28...

 

 

 

007832

Visualizer Customizing / End user (not yet available)

 

 

 

007835

Operating instructions

 

 

 

007828

Installation / Hardware Commissioning

 

 

 

007833

Maintenance instructions

 

 

 

007894

Templates for inscription stripes

 

 

 

007895

Operating platform for Tools

 

Work and operational safety

Before personnel begin work on the system they must have read and understood the related operating instructions, in particular chapter 2 ”Safety regulations”.

Disregard of the safety regulations

Before they are delivered, products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warnings of danger contained in the documentation. This applies in particular to:

Personal injuries or damage caused by improper use and incorrect use;

Personal injuries or damage caused by disregarding safety instructions in the documentation or on the product;

Personal injuries or damage caused by poor maintenance or a lack of maintenance.

6

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

 

 

About this document

Conventions

 

 

(...)

 

Additional information

..)

 

Notes

’’......’’ / ’.....’

 

Definitions of designations

->

 

Details see page ...., chapter or document .....

 

 

Configuration sheets to fill out

Document identification

 

Place

 

Signification

Title page

 

System names

 

 

Product type

 

 

Document purpose

Last page

bottom left

The document number consists of: Language, number, index

 

 

Version date

 

bottom right

Manual

 

 

Register

Modification index

Version

Date

Brief description

007836_a_en_--

03. 2004

First edition

 

7

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Safety regulations

2 Safety regulations

This chapter describes the danger levels and the relevant safety regulations applicable for the use of our products. Please read the work instructions as well as the chapter ”About this document” thoroughly before beginning any work.

2.1Signal words and symbols

2.1.1Signal words and their meaning

The danger level that is, the severity and probability of danger are indicated by the signal words listed below. Non-observance may lead to the consequences indicated:

DANGER

Imminent danger!

May cause serious bodily injury or danger to life!

WARNING

Dangerous situation!

May cause serious bodily injury or danger to life!

CAUTION

Possibly dangerous situation!

May cause light injuries!

NOTE

Possibly harmful situation!

May cause damage to the product or to objects in the immediate vicinity of the product!

2.1.2Symbols and their meaning

The symbols listed below indicate the nature and origin of the danger.

Signal word

General danger

 

 

 

 

Signal word

Electrical voltage

 

 

Example for a danger warning

DANGER

Disconnect the module from power supply.

External voltage

 

 

 

8

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Safety regulations

2.1.3Classification and meaning of additional symbols

Tips and information

Refers to extremely important or critical decisions to be taken into account before continuing the work.

2.2Safety-relevant working instructions

Country-specific standards

The products are developed and produced in compliance with the relevant international and European safety standards. Should additional country-specific, local safety standards or regulations concerning project planning, assembly, installation, operation and disposal of the product apply in the place of operation, then these standards or regulations must also be taken into account in addition to the safety regulations mentioned in the product documentation.

Electrical installations

DANGER

Any work on electrical installations may only be carried out by qualified electri-

Work on electrical

cians or instructed persons working under the guidance and supervision of a

installations

qualified electrician, in accordance with the electro technical regulations.

Control units must be disconnected from the power supply during commissioning or maintenance work.

Terminals with an external voltage supply must be provided with a sign ”DANGER - External voltage”.

Mains leads to the control unit must be installed separately and provided with a clearly marked fuse.

Earthing must be carried out in compliance with local safety regulations. When work is carried out in explosion-hazardous areas, the appropriate safety precautions must be taken.

Assembly, installation, commissioning and inspection work

If any tools or accessories such as ladders are required, safe and suitable devices must be used.

Prevention of spurious tripping of the remote transmission must be assured. Always inform the fire brigade before testing the remote transmission.

The activation of fire control installations for test purposes must not cause damage to the system or parts thereof.

Fire control installations must only be activated after the test has been completed and the system has been handed over to the customer.

Third party systems or devices must only be activated in the presence of the responsible person.

When work on management stations and system terminals are performed, the safety regulations of the connected sub-systems must be observed. This especially applies when switching-off system components.

In the case of extinguishing systems, always use the ”General installation instructions” as a guideline. This guideline is available on request.

 

9

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Safety regulations

Testing the product operability

Evacuate and cordon off extinguishing sector.

Inform people about the possibility of occurring fog and noise.

Inform people before testing of alarm devices; take the possibility of panic reactions into account.

Inform the alarm and fault receiving stations connected to the system before running the tests.

Modifications to the system design and the product

Modifications to a system or to individual products may cause faults or malfunctioning. Please request written approval from us, and the relevant authorities concerning intended system modifications and system extensions.

Modules and spare parts

Locally procured modules and spare parts must comply with the technical specifications laid down by the manufacturer. This compliance is always ensured for original spare parts supplied by us.

Only use fuses with the specific fuse characteristics.

Wrong battery types and improper battery exchange may introduce the danger of explosion. Only use the specified battery type or an equivalent battery type recommended by the manufacturer.

Batteries require environmentally safe disposal. They must be handed in at the local collecting points.

Please take into account that the extinguishing agent cylinders are pressurized and must be exchanged in compliance with the local safety regulations.

10

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Main features

3 Main features

Fire detection system for modular configuration

Up to 1000 detectors per FC700A possible

For the processing of addressable and conventional detectors

Logical and physical structure totally separated

Control console as main CPU

Interfaces for VdS peripheral equipment, printer, host systems

Different types of input and output modules

Special Mimic Display terminal activating module

Multidetector logic

Up to 16 free selectable type of stations per C-Bus

Comfortable operation with soft keys and large LC display

Up to 64 independent logical AREAS (Organization levels)

Single-AREA or multi-AREA operation

Event memory with sub-menu / search functions

Integrated real time clock with auxiliary battery

Automatic summer/winter time switchover

Integrated emergency operation function

Flexible detector parameters setting via maintenance PC

Connectible detector systems

 

Stations

 

Synova™ 300/600, Special detectors

 

 

 

 

 

 

 

 

Control terminal / Main-CPU ‘FC700A’

Control terminal ‘FT700A’

 

 

 

 

 

B3Q700

B3Q700

SynoLOOP

 

 

 

 

 

 

 

 

 

 

 

CPU

 

 

 

 

 

 

WINDOWS based

FG700A

SynoLINE300

 

 

 

 

Configuration software

 

 

 

 

 

 

 

 

 

DO1101A-Ex

EEx ib

IIC T4

Gateway

ype

S

PTB Nr.

T

 

 

EN

 

 

s®

 

M

 

 

E

 

 

 

ru I

 

 

 

 

be S

 

 

 

 

 

r

 

 

 

 

 

e

 

 

 

 

 

C

 

 

 

 

 

SynoLINE600 / SynoLINE600-Ex

 

 

 

 

 

 

 

 

SWE700A

 

Special detectors

 

 

 

 

 

 

 

11

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Technical data FC700A

4

Technical data FC700A

 

 

 

 

 

Operating voltage

 

115 / 230VAC

±15%

50... 60Hz

Power consumption

 

40... 220VA (per converter B2F020)

 

Battery operation in the event of mains failure

 

 

 

 

 

-

Standard operating period

 

12...24h

 

 

 

-

Optional

 

Up to 72h (see chapter 23)

 

 

Environmental conditions

 

 

 

 

 

 

Temperature during

operation

0°C... +40°C

 

 

 

 

 

Storage

-20°C... +60°C

 

 

 

Humidity

 

Max. 95%, no condensation

 

 

 

 

 

Complies with class 3K5 according to IEC 721–3–3

IP protection category (EN 60529 / IEC 529)

 

 

 

 

 

 

-

Control unit

 

IP50

 

 

 

 

-

Remote control terminal

 

IP52

H26G220 cabinet

 

 

 

 

 

IP40

H28G200 cabinet

 

 

Dimensions

 

 

 

 

 

 

-

Control unit cabinet

 

W =

520mm,

H = 602mm,

D = 100mm / 155mm

-

Separate control terminal

in cabinet H26G220

W =

366mm,

H = 219mm,

D = 76mm

 

 

H28G200

W = 520mm,

H = 300mm,

D = 70mm

Colors

 

 

 

 

 

 

-

Control unit cabinet

 

RAL 7035 light grey

 

 

- Operating unit front terminal B3Q700

 

Dark grey like Pantone 431C, Pantone 429C grey

-

Control terminal cabinet

H26G220

Pantone 421 grey

 

 

 

 

 

H28G200

RAL 7035 light grey

 

 

 

 

H28T110/120

1E110 dark grey

 

 

 

12

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Siemens FC700A User Manual

Logical and physical structure

5 Logical and physical structure

 

In the FC700A fire detection system, the logical structure is completely separated

 

from the physical structure. This enables the greatest possible flexibility. Display

 

and control terminal are based on the geographical and organizational aspects and

 

are independent of the actual hardware installation of the detector network.

 

 

Geographical features (-> building structure)

 

 

 

2nd floor

 

1st floor

 

1st floor

Room 101

 

 

Room 102

 

 

 

 

 

ground floor

Room 103

 

 

Room 104

 

 

 

 

 

 

Room 104 (Zone)

 

Main building (Area)

1st floor (Section)

 

 

Logical structure

The logical structure is a configuration of the geographical features of a system. It can be modified easily to the building structure, room utilization etc.

Within the same control unit the logical structure is independent of the wiring of the detector network.

Linking

The lowest levels of both structures are linked to each other. It is determined which physical devices (e.g. detectors) are in which logical or geographical location.

logical structure

Area

 

 

 

Main

 

 

 

 

 

 

 

building

 

 

 

Section

 

Ground

 

1st

 

2nd

 

 

 

floor

 

floor

 

floor

 

Zone

Ware

Reception

Room

Room

Room

Canteen

EDP

 

house

 

102

103

104

room

Element

Linking

Level 2

Level 1

 

 

Device

 

SynoLOOP

Level 2

Line 2

Line 3

Line 1

 

 

Line 4

 

 

Level 1

 

Line modules E3M111

 

 

Function unit

 

I-Bus

Physical structure

C-Bus

Control unit ‘FC’

The physical structure is a configuration of the

hardware. It results from the hardware instal-

Control terminal ‘FT’

Station

lation. The number of used levels is depend-

 

ing on the type of hardware.

physical structure

 

13

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Bus systems

6 Bus systems

In the FC700A fire detection system there are 5 communication levels:

I-Bus

Internal data bus between individual modules in the control unit (line modules, control modules etc.)

C-Bus

Local data bus between control unit(s), control terminal(s) and Gateway(s)

SynoLOOP and SynoLINE600

Local detector bus; connects the detectors to the control unit

LON-Bus

Local data bus for floor repeater panels, mimic display converter and LON I/O card

Data Bus

Local data bus for parallel indicator panel, synoptic panel or relay

Control terminal

FT700A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gateway

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FG700A

 

 

 

 

 

 

 

E3I040

 

 

 

 

 

 

 

 

 

 

 

 

Building

 

 

 

 

 

 

 

 

LON-Bus

 

 

 

 

 

 

 

 

 

I-Bus

 

 

 

 

 

 

 

 

 

 

 

 

 

RS232

 

 

 

 

 

 

 

 

 

E3H020

 

 

management

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Databus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ISO1745 Protocol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C-Bus

 

 

 

I-Bus

Control unit FC700A

 

 

CPU

Line modules

 

B3Q700

 

 

 

E3M111

E3M080

E3I040

 

 

LON-Bus

 

 

B3Q580/

 

 

B3Q590/

 

 

B3Q595

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K3I110

In-/Outputs

 

 

 

 

 

 

 

SynoLOOP

 

SynoLINE600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K3I050

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Databus

B3R051 or

K3R072/

K3G060

14

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

 

 

 

 

 

 

 

Bus systems

6.1

Bus overview

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

C-Bus

I-Bus

SynoLOOP

SynoLINE600

LON-Bus

Data Bus

Field of applica-

 

 

 

 

Local data bus

Local data bus

tion

 

 

 

For addressable

For collective

parallel ind.

 

Local system bus

Inside control unit

for floor indicator

 

 

detectors

detectors

panel, synoptic

 

 

 

 

panels

 

 

 

 

 

 

panel or relay

 

 

 

 

 

 

 

Speed of trans-

57kBaud

1000kBaud

2 messages/sec

(Direct current

78kBaud

SPI-Bus 2KHz

mission

 

signal)

 

 

 

 

 

 

Length of line

Max. 1000m

Max. 3m (only

 

Max.

Max. 500m as

 

 

 

Max. 150Ω/300nF

free topology

Max. 1000m

 

 

150/250Ω/4µF

 

 

(G51 0,8: 1400m)

inside cabinet)

See chapter 16

Max. 1000m as

 

 

See chapter 16

 

 

 

 

 

 

stub line

 

 

 

 

 

 

 

 

Number of users

… 16

… 16

… 128

1 address

… 32

… 24

connected or

(Max. 25 detec-

LON-Bus de-

C-Bus devices

I-Bus modules

D-Bus devices

Max. 8 addresses

addresses

 

tors)

vices

 

 

 

 

 

Number of wires

2

26

2

2

2

6

 

 

(+3 wires for emer-

 

 

(+3 wires supply)

 

 

gency operation)

 

 

 

 

 

 

 

 

 

 

 

Type of cable

Twisted 1)

Flat cable

Twisted

Twisted

Twisted

Twisted

 

 

(Un-twisted per-

(Un-twisted

 

 

 

 

missible)

permissible)

 

 

Loop line

 

 

 

T-branch

 

 

 

 

(See chapter 18)

 

 

 

 

 

 

 

Short-circuit proof

Yes

 

Yes

 

 

 

 

 

Each user con-

Each user con-

No

No

Yes

 

 

nected with line

nected with line

 

 

 

 

 

 

 

 

separator

 

separator

 

 

 

Network structure

Master/master

Master/slave

Master/slave

Master/slave

Master/slave

Master/slave

Scanning

 

Event-controlled,

Cyclic,

Cyclic

 

Event-controlled,

 

 

 

- typ. all 64s

presence moni-

Cyclic

 

 

presence monitoring

Event controlled

- Interrupt on

toring

- typ. all 250ms

 

 

 

 

 

 

 

alarm

 

(All 60s)

 

Principle

 

Serial Bus

 

Sensor/actor-Bus

Conventional

Network

 

 

 

C-Bus

- Cerberus proto-

 

 

 

- Echelon Chip

Serial bus

 

 

- Cerberus protocol

col 'K31'

- Current gain

 

 

- Cerberus protocol

(LON protocol)

- Cerberus proto-

 

 

- Collision detection

- Serial 8bit

principle

 

 

- Manchester coding

- SPI/Motorola

- Start-up: daisy-

- Voltage levels

- Cerberus

col

 

 

 

 

chain

 

specific telegram

 

 

 

 

 

 

 

 

1Calibrated according to cable impedance: 50Ω (MICC) / 110Ω (G51, ø 0.8mm, not shielded)

6.2Modifying the impedance of the various C-Bus cables

C-Bus standard cables have a characteristic impedance of 110Ω. The driver and end-of-line resistors are soldered to solder lugs and can be adapted accordingly with other characteristic impedances (see diagram chapter 6.2.1).

1. Explanation

A cable must be terminated with resistors. The resistance value must correspond to the impedance of the cable. Each C-Bus user has four end-of-line resistors (Ri). In addition two driver resistors (Rd) are integrated on the p.c.b. In order that the resistors can be exchanged easily they are all soldered to solder lugs.

C-Bus p.c.b.

Ri

Rd

B3Q700

R31 ... R34

R49, R50

E3H020

R173, R174, R177, R178

R180, R183

The driver resistors specify the current on the C-Bus. In order that the signal on the

C-Bus always has the same amplitude (1.35Vpp), the following correlation is valid:

Rd = Ri x 3,65 (45Ω < Ri < 200Ω)

 

15

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Bus systems

6.2.1Diagram

Ri [Ohm]

200

 

 

 

 

 

190

 

 

 

 

 

180

 

 

 

 

 

170

 

 

 

 

 

160

 

 

 

 

 

150

 

 

 

 

 

140

 

 

 

 

 

130

 

 

 

 

 

120

 

 

 

 

 

110

 

 

 

 

Standard

100

 

 

 

 

 

 

 

 

 

90

 

 

 

 

 

80

 

 

 

 

Lifeline

70

 

 

 

 

 

 

 

 

 

60

 

 

 

 

Radox

50

 

 

 

 

 

 

 

 

MICC

40

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

20

 

 

 

 

 

10

 

 

 

 

 

0 0

20

40

60

80

100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 620 640 660 680 700 720 740

Rd [Ohm]

2.Procedure

Request characteristic impedance of the cable from manufacturer (45Ω ... 200Ω) Select the value of the Ri the same as the value of the cable characteristic im-

pedance and insert the four end-of-line resistors on the p.c.b. Insert two driver resistors Rd = Ri x 3.65 on the p.c.b. Each C-Bus user must be adapted

If only the inductance and the capacitance are known for a cable, the impedance can be calculated with the aid of the following formula:

Zc =

Lc

 

Cc

 

 

 

Zc:

Cable impedance [Ω]

Lc:

Cable inductance [µH]

Cc:

Cable capacitance [µF]

3. Mixing of different types of cable

In a C-Bus loop (or stub line) only one type of cable may be used. 4. Operation as a stub line

If the C-Bus is operated as a stub line, two end-of-line resistors (values as for Ri) must be inserted externally at both ends of the line (default 110Ω). In the choice of other cables the above rules apply (the Ri are in this case the external end-of-line resistors).

For further information, see document 007831

16

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

C-Bus stations

7 C-Bus stations

The C-Bus network contains max. 16 stations (user connected)

Within the limits stated below (FC, FT, FG) are any stations in any arrangement possible

Max. 64 AREAS

 

 

Building mangement system

 

 

ISO1745 Protocol

Control terminal

FT700A

FG700A

Gateway

 

 

(max.15)

(max.15)

 

 

 

 

C-Bus Network

 

- max. 16 Stations

 

- 3 different types of stations

 

- loop line max. 1400m with G51 ø 0.8mm

 

 

 

C-Bus

 

Control terminal

I-Bus

 

 

 

 

 

Main-CPU

Line

Control

 

modules

modules

 

 

 

FC700A

 

 

 

(max.16)

 

Detector

 

 

 

 

7.1Station

Function unit within C-Bus network

Several stations are be located in geographically dispersed cabinets

7.2Types of stations

Differentiated by function and represented by a certain module

Certain modules can be used for different types of stations

Types of stations available:

FC700A

Combination of main CPU and operating unit

FT700A

Control terminal

FG700A

Gateway (e.g. conversion of C-Bus Protocol -> ISO1745)

7.3Hardware

Type of station

Module

Function

Function

Function

’Main CPU’

’Operation’

’Gateway’

 

 

FC700A

B3Q700

 

 

FT700A

B3Q700

 

 

FG700A

E3H020

 

 

 

17

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

C-Bus stations

7.4Visualizer for Windows remote operation software (not available yet)

Operating platform requirements in detail see document 007895

For details see document ……. (not available yet)

 

 

 

max. length of line

 

 

 

 

dependent on

 

FC/FT

E3I020

Modem

type of modem

 

Dedicated line

Modem

 

 

 

 

 

 

 

 

temporary public

 

 

E3I020

Tel.

telephone line

Tel.

 

Modem

 

Modem

 

 

 

 

E3I020

(RS232)

....15m

 

 

 

 

 

 

 

Standard PC with keyboard, software

 

 

’Visualizer for Windows’,

 

C-BUS

 

 

 

 

FC/FT

 

 

 

 

 

B3D021

 

 

 

 

 

 

temporary public

 

 

E3I020

Tel.

telephone line

Tel.

 

 

 

Modem

 

Modem

 

 

e.g. Service Notebook, software

 

 

 

’Visualizer for Windows’,

 

 

 

SWE700A for Windows

 

Visualizer

Remote Operation

(temporary)

18

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

C-Bus stations

7.5Logical AREAS

FC

FC

FC

FC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

2

3

 

4

5

 

6

7

8

..

..

..

..

61

62

63

64

AREA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AREA

FC

FC

All AREAS control terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FG

 

 

 

 

 

 

 

 

 

 

FG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Within one main CPU (FC) max. 4 AREAS can be configured

CPUs cannot link up with AREAS of other CPUs

CPU overlapping controls are possible

Control terminals (FT) can be freely allocated to AREAS as required

Visibilities on gateways (FG) shall be set per station only, not per AREA!

 

19

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Limitations of C-Bus participants

8 Limitations of C-Bus participants

This chapter describes the quantitative limits of the FC700A station.

The selection of the station type depends on the requirements. The following variants are available:

 

 

Flash ROM

SRAM

 

 

Station type

Modules

(2x1024Kx8Bit)

EPROM set

RAM set

Soldered

 

 

'Program file'

 

 

 

 

 

 

 

FC700A

B3Q700

CIY00760

4x512Kx8Bit

FT700A

B3Q700

CTY00760

4x512Kx8Bit

 

 

 

 

CKQ007.60

2 x Z3S070

FG700A

E3H020

(2x512Kx8Bit)

(2x512Kx8Bit)

 

 

 

 

(Assembly ex works)

 

 

 

 

 

8.1Main CPU limits

8.1.1Maximum number of devices

1000 devices (with AMPK=1) per FC700A.

8.1.2Limits in the logical structure

The limits in the logical structure are given by the node-type, by the highest possible CSX number and the maximum amount of display-digits. These limits are given by the system and are independent of the memory capacity.

Table 'Limits of the logical structure'

Maximum rating

Maximum rating

Maximum rating

Maximum rating

AREAS per STATION

SECTIONS per AREA

ZONES per SECTION

ELEMENTS per ZONE

... 4

…255

…255

…99

 

 

 

International 5: …255

8.1.3Maximum number of criteria in zones control 4 and 6

The maximum number of control zones with 16 criteria is limited by 200.

To optimize the performance of your system minimize the number of CPU-overlapping controls as much as possible.

A maximum of 40 CPU-overlapping controls (zone control 6) are admissible per C-Bus.

8.1.4Maximum number of ZONE time channel

Max. 16 ZONES time channel are permitted per station.

20

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Limitations of C-Bus participants

8.1.5Maximum number of I-Bus-modules

Table 'Maximum number of I-Bus-modules'

Station type

FC700A

I-Bus modules

... 16 1) ... 8 2) 3)

1)Limited by software

2)Value based on experience (depends on cabinet size and/or 5V current consumption)

3)Battery charging unit E3C011 counts as one I-Bus module

8.1.6Limits of 5V supply

All I-Bus modules are supplied with 24V and 5V. The available current for the 5V, supplied from main CPU is limited:

'Main CPU'

Available current

B3Q700 / E3C011

250mA

Table '5V-Current consumption of I-Bus modules'

I-Bus module

Current consumption

I-Bus module

Current consumption

from 'Main CPU'

from 'Main CPU'

 

 

E3M080

55mA

E3G060

10mA

E3M111

25mA

E3G070

10mA

E3L020

10mA

E3C011

12mA

E3L030

35mA

E3I020*

100mA

E3G050

8mA

E3I040

70mA

*Not an I-Bus module, but supplied via the 'Main CPU'

8.2Control terminal limits (FC/FT)

8.2.1Limitation of visible texts on a FC700A

The number of texts of other stations (i.e. AREAS) that can be displayed on one control terminal is limited by 14'000 texts.

To evaluate how many control panels FC700A can be displayed to one FC700A,

the following calculation must be used:

Twice the number of visible sections (worst case 1000)

+The number of visible ZONES (worst case 1000)

+The number of visible ELEMENTS with element text (worst case 1000)

= Number of texts per FC/FT (worst case 4000)

Example (worst case)

14'000 : 4000 (e.g.) = 3 fully configured FC can be displayed to one FC

8.2.2Limitation of visible texts on a FT700A

The number of texts of other stations (FC700A) that can be displayed on one control terminal is limited by 14'000 texts.

To evaluate how many control panels FC700A can be displayed to one FT700A,

the following calculation must be used:

Twice the number of visible sections (worst case 1000)

+The number of visible ZONES (worst case 1000)

+The number of visible ELEMENTS with element text (worst case 1000)

= Number of texts per FC/FT (worst case 4000)

Example (worst case)

30'000 : 4000 (e.g.) = 7 fully configured FC can be displayed to one FT

 

21

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004