Siemens 125-1957 User Manual

0 (0)

APOGEE Unit Vent Controller

0 to 10V Output Owner’s Manual

125-1957

Rev. CA, July 2007

Siemens Building Technologies, Inc.

Rev. CA, July 2007

NOTICE

The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document.

All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license.

WARNING

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case users at their own expense will be required to take whatever measures may be required to correct the interference.

SERVICE STATEMENT

Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. All Siemens Building Technologies branch offices and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system performance.

For further information, contact your nearest Siemens Building Technologies, Inc. representative.

Copyright 2006 by Siemens Building Technologies, Inc.

TO THE READER

Your feedback is important to us. If you have comments about this manual, please submit them to SBT_technical.editor.us.sbt@siemens.com

CREDITS

APOGEE is a registered trademark of Siemens Building Technologies, Inc.

Insight for Minicomputers is a registered trademark of Siemens Building Technologies, Inc. Insight for Personal Computers is a registered trademark of Siemens Building Technologies, Inc.

Country of Origin: US

Table of Contents

 

How To Use This Manual.................................................................................................

iv

Manual Organization......................................................................................................

iv

Manual Conventions ...................................................................................................

v

Manual Symbols..........................................................................................................

v

Datamate Software .....................................................................................................

v

Getting Help ................................................................................................................

vi

Where To Send Comments.........................................................................................

vi

Product Overview .............................................................................................................

1

Introduction ....................................................................................................................

1

Ordering Notes............................................................................................................

1

Hardware Inputs..........................................................................................................

2

Hardware Outputs .......................................................................................................

3

Controller LED Indicators ............................................................................................

4

Temperature Sensors .................................................................................................

4

Actuators .....................................................................................................................

5

Applications.......................................................................................................................

6

Basic Operation .............................................................................................................

6

Control Temperature Setpoints...................................................................................

6

Day/Night Mode...........................................................................................................

6

Valve Configuration.....................................................................................................

7

Heating and Cooling Switchover.................................................................................

7

Control Loops..............................................................................................................

7

Morning Warm-up/Cool-down .....................................................................................

8

ON/OFF Coil Valve Control.........................................................................................

8

Electric Heat ................................................................................................................

8

Fan Operation .............................................................................................................

8

Fail-safe Operation......................................................................................................

8

Application 2281 – Heating and/or Chilled Water Cooling, ASHRAE Cycles I and II . 10

Application 2283 – Heating and/or Chilled Water Cooling, ASHRAE Cycle III ..........

13

Application 2284 – Heating and DX Cooling, ASHRAE Cycles I and II .....................

16

Application 2286 - Heating and DX Cooling, ASHRAE Cycle III .................................

18

Application 2287 – Heating and Cooling, Nesbitt Cycle W.........................................

20

Overview ...................................................................................................................

20

Application 2299 – Slave Mode ...................................................................................

22

Overview ...................................................................................................................

22

I

APOGEE Unit Vent Controller 0 to 10V Output Owner’s Manual

Point Database ................................................................................................................

23

Troubleshooting..............................................................................................................

33

Overview ......................................................................................................................

33

Basic Service Information .........................................................................................

33

Ordering Replacement Parts.....................................................................................

34

Preventive Maintenance............................................................................................

34

Safety Features .........................................................................................................

34

Controller LEDs.........................................................................................................

34

Glossary...........................................................................................................................

35

Overview ......................................................................................................................

35

ii

Table of Contents

iii

How To Use This Manual

This manual is written for the owner and user of the Siemens Building Technologies, Inc. Unit Vent Controller – 0 to 10V, often referred to as controller for the remainder of this manual. This manual is designed to help you become familiar with the controller and its applications.

This chapter covers manual organization, manual symbols and conventions used and how to access help.

Manual Organization

This manual contains the following chapters:

Chapter 1 Product Overview, describes the hardware components and accessories used with the controller.

Chapter 2 Applications, describes the control applications available in the controller.

Chapter 3 Point Database, defines the point database descriptors and includes addresses and applications.

Chapter 4 Troubleshooting, describes basic corrective measures to take should you encounter a problem when using this controller. For issues not covered in this chapter, contact your local Siemens Building Technologies representative.

A Glossary describes the terms and acronyms used in this manual.

An Index is provided to assist you in finding information.

Siemens Building Technologies,Inc.

iv

Manual Organization

Manual Conventions

The following table lists conventions used in this manual.

Convention

Example

 

 

Actions that you should

Type F for Field panels.

perform are specified in

Click OK to save changes and close the dialog box.

boldface font.

 

Error and system

The message Report Definition successfully renamed

messages are displayed

appears in the status bar.

in Courier New font.

 

New terms appearing for

The Open Processor continuously executes a user-defined set of

the first time are

instructions called the control program.

italicized.

 

 

 

Manual Symbols

The following table lists symbols that used to draw your attention to important information.

Notation

Symbol

Meaning

 

 

 

CAUTION:

 

Indicates that equipment damage or loss of data may

 

 

occur, if a procedure is not performed as specified.

 

 

 

WARNING:

 

Indicates that personal injury or loss of life may occur to the

 

 

user, if a procedure is not performed as specified.

 

 

 

Datamate Software

Datamate is a customer software tool for all controller communications. There are two versions: Datamate Base, and Datamate Advanced. Datamate Base works on an IBMcompatible Personal Computer (PC), or a Handheld PC or Pocket PC™ running Windows CE. Datamate Advanced works only on an IBM-compatible Personal Computer.

With Datamate, you can back up, restore and edit any APOGEE® database (but only Datamate Advanced allows you to edit points offline). Backing up and restoring a database is accomplished while connected to any APOGEE® field panel, or to the Automation Level Network (ALN) or Field Level Network (FLN) device in question. A modem and telephone lines can also be used. Databases can be saved for permanent storage or used as backup.

For more information on Datamate software, refer to the appropriate user guide for the version of Datamate you are using (Base or Advanced), or contact your local Siemens Building Technologies, Inc. representative.

Siemens Building Technologies,

v

APOGEE Unit Vent Controller 0 to 10 V Output Owner’s Manual

Getting Help

For more information about the Unit Vent Controller, contact your local Siemens Building Technologies representative.

Where To Send Comments

Your feedback is important to us. If you have comments about this manual, please submit them to SBT_technical.editor.us.sbt@siemens.com

vi

Siemens Building Technologies. Inc.

1

Product Overview

Introduction

The Unit Vent Controller—0 to 10V Output is the Siemens Building Technologies, Inc. Terminal Equipment Controller (TEC) used in unit ventilator applications. See Figure 1. It provides Direct Digital Control (DDC) for five applications. The controller can operate as an independent, stand-alone, DDC room controller or be networked with an APOGEE field panel.

The controller provides all termination, input/output, system and local communication connections. See Figure 1. The controller hardware consists of the controller with cover and mounting bracket.

Table 1. Unit Vent Controller – 0 to 10 V Output Applications.

Standard Applications

2281 Heating and/or Chilled Water Cooling, ASHRAE Cycles l and II

2283 Heating and/or Chilled Water Cooling, ASHRAE Cycle III

2284 Heating and DX Cooling, ASHRAE Cycles I and II

2286 Heating and DX Cooling, ASHRAE Cycle III

2287 Nesbitt Cycle W

2299Slave Mode (no control; available for set up, and point extension device)

Ordering Notes

Unit Vent Controller – 0 to 10 Volt Output

540-509

Siemens Building Technologies, Inc.

1

Siemens 125-1957 User Manual

APOGEE Unit Vent Controller 0 to 10V Output Owner’s Manual

TEC0197R3

COVER

CONTROLLER BOARD

MOUNTING

HOLE

(2)

24 V-AC

 

 

 

DO 1

DO 2

 

DO 3 DO 4

 

DO 5 DO 6 DO 7 DO 8

DI 3

 

DI 2

 

DI 4 AO 1

AO 2

AO 3

 

 

 

 

 

LAN

MOUNTING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRUNK

 

 

 

NO C NO C NO C NO C NO C NO C NO C NO C

AI 3

 

 

+ -

 

+ -

 

+ -

 

 

 

C H

 

 

 

1 2

 

3 4

 

5 6 7 8

 

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

 

TX RX + - S BST RTS

RAIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C H

2

3

4

5

6

7

8

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

 

 

 

1

+

-

S

DO LEDS

POWER

 

 

 

TRUNK

INPUT / OUTPUT TERMINATIONS

LAN

 

TERMINATIONS

 

 

TRANSMIT LED

TRUNK

ROOM TEMPERATURE

 

 

TERMINATIONS

SENSOR / MMI PORT

 

 

 

RECEIVE LED

 

BST LED

Figure 1. Unit Vent Controller - 0 to 10V Output.

Hardware Inputs

Analog

Averaging air temperature sensor

Room temperature sensor

Room temperature setpoint dial (optional)

Digital

Low Temperature Detection Thermostat (LTDT)

Night mode override (optional)

Wall switch (optional)

2

Siemens Building Technologies, Inc.

Introduction

Hardware Outputs

Analog (0 to 10V)

Application

Cooling valve actuator

2281, 2283, 2287

Face-bypass damper actuator

2281, 2283, 2284, 2286

Heating valve actuator

2281, 2283, 2284, 2286, 2287

• Outdoor air damper actuator

2281, 2283, 2284, 2286

Digital

Application

• Auxiliary radiation electric coil contact; or,

2281, 2283, 2284, 2286

 

auxiliary radiation two-position valve actuator

 

Unit fan

2281, 2283, 2284, 2286, 2287

• First stage electric heat

2281, 2283, 2284, 2286

• Second stage electric heat

2281, 2283, 2284, 2286

• Third stage electric heat

2281, 2283, 2284, 2286

• Two-position cooling valve actuator

2281, 2283, 2284, 2286

• Two-position heating valve actuator

2281, 2283, 2284, 2286

DX coil

2284, 2286, 2287

Power Wiring

The controller is powered by 24 Vac and connects to the two screw terminals on the controller. Labeled “C” (Common) and “H” (Hot) on the terminal block labeled “24 VAC”. No earth-ground connection is required (Figure 2).

Communication Wiring

The controller connects to the field panel by means of a Floor Level Network (FLN) trunk. Communication wiring connects to the three screw terminals on the controller labeled “+” (positive), “-“ (negative), and “S” (Shield) (Figure 3).

Siemens Building Technologies, Inc.

3

APOGEE Unit Vent Controller 0 to 10V Output Owner’s Manual

TEC0253R2

24 V-AC

DO 1 DO 2

DO 3 DO 4

DO 5

E C H

NO C NO C NO C NO C NO C NO

1 2 3 4 5 6 7 8 9 10 11 1

 

1

2

3

4

5

6

7

8

9 10 11 12

COMMON 24 VAC HOT

CONTROLLER POWER WIRING

NOTE: NO EARTH GROUND CONNECTION

Figure 2. Power Wiring.

TEC0470R1

FLN TRUNK

+ - S

(SHIELD)

(SHIELD)

(-) (-)

(+)(+)

Figure 3. Communication Wiring.

Controller LED Indicators

The controller has eleven Light Emitting Diode (LED) indicators. See Figure 1. Table 2 lists the type, the abbreviation on the controller, and the indication of each LED.

 

 

Table 2.

Controller LEDS.

LED Type

Label

LED

 

Indication

 

(if present)*

Number

 

 

DO

LED 1 to

1 to 8

 

Indicates the ON/OFF status of the

 

LED 8

 

 

DO associated with it. A glowing LED

 

 

 

 

indicates that the DO is energized.

 

 

 

 

 

Receive

RX

9

 

Indicates, when flashing, that the controller is

 

 

 

 

receiving information from the field panel.

 

 

 

 

 

Transmit

TX

10

 

Indicates, when flashing, that the controller is

 

 

 

 

transmitting information to the field panel.

Basic Sanity Test

BST

11

 

Indicates, when flashing ON and OFF once

 

 

 

 

per second, that the controller is functioning

 

 

 

 

property.

 

 

 

 

 

*Some LED labels and numerals may be hidden by the controller cover.

Temperature Sensors

Temperature sensors used with the Unit Vent Controller—0 to 10V Output include an electronic room, mixed air or discharge air temperature sensor.

Room Temperature Sensor

The Terminal Equipment Controller room temperature sensor connects to the controller by means of a cable pre-terminated at both ends with a 6-conductor RJ-11 plug-in connector. See Figure 1 for the location of the room temperature sensor/Man-Machine Interface (MMI) port.

4

Siemens Building Technologies, Inc.

Introduction

Mixed Air/Discharge Air Temperature Sensor

The mixed air/discharge air temperature sensor is a 100K ohm thermistor that connects to the controller at the screw terminals for Al 3.

For more information about Siemens Building Technologies, Inc. temperature sensors, contact your local Siemens Building Technologies, Inc. representative.

Actuators

Damper Actuators

The damper actuator used with the Unit Vent Controller—0 to 10V Output is a 0 to 10V spring return electronic damper motor that positions an outside air damper. A 0 to 10V electronic damper motor can be used to position a face-and-bypass damper.

Valve Actuators

The valve actuators used with the Unit Vent Controller—0 to 10V Output are modulating spring return and non-spring return electronic valve motors that position the valves.

Related Equipment

Relay Module

Damper Actuator(s)

Valve Actuator(s)

Mixed Air/Discharge Air Temperature Sensor (optional)

TEC Room Temperature Sensor

Contact your local Siemens Building Technologies, Inc. representative for product numbers and more information.

Siemens Building Technologies, Inc.

5