Andover Continuum Power Supplies
with or without UPS Features (continued)
03
A connector located on the bottom of the power
supply is provided for an optional Main Power
indicator LED. This option is ideal if you mount your
Andover Continuum system within a larger control
panel or enclosure and wish to verify power to the
system from a separate location.
The power supply module features a sleek,
lightweight casing designed for natural convection
cooling. Built-in quick-release fasteners at the back
of the module are provided for DIN rail mounting —
no tools required. These fasteners also snap into
a locked position for panel mounting. The power
supply is designed for mounting in an optional
NEMA 1-style Andover Continuum enclosure.
Other Available Models
PS 120/240 AC 85
A non-UPS version, the PS 120/240 AC 85, is also
available. This power supply can also be used as
an extended power source to power additional
I/O modules directly, extending the capabilities
of a typical Andover Continuum system, even to
remote locations. Because there is no built-in
battery charger in this model, a full 85 watts of
power is available.
PS 120/240 AC 65
A non-UPS version, the PS 120/240 AC 65, is also
available. This power supply can also be used as
an extended power source to power additional
I/O modules directly, extending the capabilities
of a typical Andover Continuum system, even
to remote locations. Because there is no built-in
battery charger in this model, a full 65 watts of
power is available.
Dimensional Drawing
PS 120/240 AC 50
A non-UPS version, the PS 120/240 AC 50, is also
available. This power supply can also be used as
an extended power source to power additional
I/O modules directly, extending the capabilities
of a typical Andover Continuum system, even
to remote locations. Because there is no built-in
battery charger in this model, a full 50 watts of
power is available.
PS –48 DC 50
A PS –48 DC 50 model is available. This model
accepts power from –41 to –53 VDC and allows
industries such as telecommunications to provide
uninterrupted power to critical environmental
monitoring and control equipment using their own
battery-backed power systems.
SDS-C-POWERSUP-A4.BU.N.EN.5.2010.0.01.CC

Andover Continuum Power Supplies
with or without UPS Specifications
Andover Continuum Power Supplies
04
Electrical
Input Voltages
100 to 240 VAC, 50/60 Hz
-41 to -53 VDC
(PS –48 DC 50 model only)
Output Voltages
24 VDC, ±5% (all models)
Output Power Available
70 watts (PS 120/240 AC 85-U model)
85 watts (PS 120/240 AC 85 model)
50 watts (PS 120/240 AC 65-U, PS 120/240
AC 50 and PS -48 DC 50 models)
65 watts (PS 120/240 AC 65 model)
35 watts (PS 120/240 AC 50-U model)
Overload Protection
Short circuit protection
Overvoltage protection
Fuse protection on inputs
MOV protection on inputs
Mechanical
Operating Environment
32 to 120°F, (0 to 49°C),
10 to 95%RH (non-condensing)
Size
9.0˝ W (228.7mm)
7.2˝ H (182.88mm)
(with mounting clips extended)
6.2˝ H (157.48mm)
(with mounting clips closed)
2.5˝ D (96.5 x 170.2 x 63.5mm)
Weight
1.75 lbs (0.79kg)
Enclosure Type
UL open class, flammability rating of UL94-
5V, IP 10
Mounting
Mount on DIN rail or wall-mount using at-
tached fasteners. Andover Continuum NEMA
1-style enclosure available.
Battery
(PS 120/240 AC 50-U, PS 120/240 AC
65-U and PS 120/240 AC 85-U models only)
Battery Backup
Battery backup UPS circuit with built-in
battery charger provides automatic battery
backup UPS power in event of AC line
failure. Two 12V 7.0 AHr sealed
rechargeable batteries (not included),
connected with 5 amp pico fuse, provide
a 24 VDC battery source.
Battery Backup Duration
60 minutes @ 35 watts power consumption
full UPS to CPU plus I/O power
(PS 120/240 AC 50-U model),
60 minutes @ 50 watts power consumption
full UPS to CPU plus I/O power
(PS 120/240 AC 65-U model) and
30 minutes @ 70 watts (PS 120/240 AC
85-U model); 4 hours CPU module only (in-
cluding modem and network interface) with
no I/O; or 72 hours DRAM and real-time
clock. Expandable by use of greater amp
hour batteries. For example, for a 4-hour
full backup time, minimum of 2-12V 28 AHr
batteries must be provided.
Battery Charging Time
48 hours maximum for built-in 15 watt
battery charger to fully charge battery from
lowest system battery discharge point.
Connections
AC Input
(PS 120/240 AC 50-U, PS 120/240 AC 50,
PS 120/240 AC 65-U, PS 120/240 AC 65,
PS 120/240 AC 85, and PS 120/240 AC
85-U models only)
Three-position screw connector
DC Input
(PS –48 DC 50 model only)
Three-position screw connector
Battery, 24 VDC
(PS 120/240 AC 50-U, PS 120/240 AC
65-U and PS 120/240 AC 85-U models only)
Two-position plug-in screw connector
External Power Indicator
Two-position connector for
optional power indicator LED
(optional cable assembly available).
User LEDs/Switches
Status Indicator LEDs
MAIN POWER
AC (or DC) Power ON/OFF Status Indicator
UPS POWER
(PS 120/240 AC 50-U, PS 120/240 AC
65-U and PS 120/240 AC 85-U models only)
UPS Power ON/OFF Status Indicator
SDS-C-POWERSUP-A4.BU.N.EN.5.2010.0.01.CC

Andover Continuum Power Supplies
with or without UPS Specifications (continued)
Andover Continuum Power Supplies
05
Switches
ON/OFF
Turns AC (or DC) power ON and OFF.
Located on top left side of module.
Indicated by MAIN POWER LED.
Agency Listings
UL/CUL 916, FCC CLASS A, CE,
UL 864 (PS 120/240 AC 65-U and
PS 120/240 AC 65 only)
UL 294 (PS 120/240 AC 50-U, PS 120/240
AC 50, PS 120/240 AC 65-U, PS 120/240
AC 65, PS 120/240 AC 85-U, PS 120/240 85)
UL1076 (PS 120/240 AC 50-U, PS 120/240
AC 65-U and PS 120/240 AC 85-U only)
Options
External Power Indicator LED Cable
Assembly—Approximately 2 ft. in length.
(P/N: 01-0100-422)
Two 12V 7.0 AHr Sealed Rechargeable
Batteries Only (P/N: 01-2100-423)
Battery Bracket & Cable Only
(P/N: 01-0010-868)
Two 12V 7.0 AHr Sealed Rechargeable
Batteries plus Battery Bracket & Cable
(P/N: 01-0010-842)
All brand names, trademarks and re gistered trademarks are the property of their respective ow ners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
SDS-C-POWERSUP-A4.BU.N.EN.5.2010.0.01.CC
May 2010
© 2010 Schneider Electric. All rights reserved.