Sanyo PNR-XS1872, XMS1272, XMS0972, XS1872 User Manual

0 (0)

TECHNICAL & SERVICE MANUAL

INDOOR UNIT : XMS0972 & PNR-XS1872 XMS1272 & PNR-XS1872 XS1872 & PNR-XS1872

FILE NO.

Destination: North America

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

Capacity

Indoor Model No.

Product Code No.

Body (Panel)

Body (Panel)

 

9,000BTU / h

XMS0972 (PNR-XS1872)

1 852 353 72 (1 852 352 11)

11,900BTU / h

XMS1272 (PNR-XS1872)

1 852 353 71 (1 852 352 11)

17,500BTU / h

XS1872 (PNR-XS1872)

1 852 352 09 (1 852 352 11)

Semi-Concealed Type Indoor Unit

Body

Panel

XMS0972 (Body) & PNR-XS1872 (Panel)

XMS1272 (Body) & PNR-XS1872 (Panel)

XS1872 (Body) & PNR-XS1872 (Panel)

< Applicable Multi-Outdoor Units >

CM1972 (3-room multi unit) CM2472 (4-room multi unit) CM3172 (4-room multi unit)

NOTE

For details about the combinations, refer to "Unit Combination Table" in the T. Service Manual for the Multi Outdoor Units.

Wireless Remote Controller

Wired Remote Controller

 

(Option)

REFERENCE NO. SM700815

SAFETY PRECAUTIONS

Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them.

The precautionary items here are divided into "Warning" and "Caution" items.

Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the " Warning" table.

However, even precautionary items identified as "Caution" also have the potential for serious consequences if not performed correctly.

Important safety precautions are described for all items in both categories. Be sure to carefully follow all of them.

Symbol Indication

:This symbol indicates items to which we need to pay attention. In this triangle, a definite precautionary item is described.

:This symbol indicates the item to be prohibited.

In or close to this circle, a prohibited item is described.

:This symbol indicates the items requiring special attention or instruction. In or close to this circle, a prohibited item is described.

After doing repair work, perform a test run to confirm that there are no abnormalities. At the same time, explain the precautions in use to the user.

Warning

Before performing an overhaul, disconnect the power plug or power cable from the unit.

Performing the work with the power supplied to the unit, may cause an electric shock.

When repair work or circuit inspection that requires power supply for the air conditioner, is to be performed,

 

do not touch the charging section.

 

Doing so may cause an electric shock.

Prohibit

For the step-up capacitor attached to the electric section, perform the repair work after sufficiently discharging it. Insufficient capacitor discharge may cause an electric shock.

Do not perform repair work on the electric sections with wet hands. Doing so may cause an electric shock.

Prohibit

Do not start or stop the air conditioner by means of connecting or disconnecting the power plug. Doing so may cause an electric shock or fire.

Prohibit

When conducting repair work only use components included in the parts list for the corresponding unit and perform the work with the appropriate tools.

Incorrect or poor repair work may cause an electric shock or fire.

Never modify the unit.

Doing so may cause an electric shock or fire.

Prohibit

Perform all electric work according to local applicable regulations related to electrical equipment or interior wiring regulation and make sure to use the exclusive circuit.

Insufficient capacity to the electric circuit or defective arrangement results may cause an electric shock or fire.

Make sure to replace any power cable or lead wire showing any signs of scratch or deterioration.

Failure to do so may cause an electric shock, overheating or fire.

Make sure that there is no dust on or slack in the power plug and insert fully into the socket.

Dust or incomplete connections may cause an electric shock or fire.

Do not damage or process the power cord, as it may cause an electric shock or fire.

Prohibit

For the wiring between the indoor unit and outdoor unit, securely fix the specified cable onto the terminal plate. Poorly fixed wiring may cause a heat or fire.

After connecting the wiring between the indoor unit and outdoor unit, attach the terminal cover securely.

Incomplete attachment of the terminal cover may cause overheating or fire.

2

Warning

If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite.

Prohibit

If refrigerant gas leaks during the work, ventilate the room.

If refrigerant gas catches fire, harmful gas may be generated.

Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle.

 

If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle,

 

which may cause a unit breakdown."

Prohibit

When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in a well-ventilated place after sufficiently recovering the refrigerant gas.

Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury.

When the work is to be performed in a high place (About 2 meters or more), make sure to wear a safety helmet, gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall.

When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit. Insufficient strength of the installation location and incomplete installation work may cause an injury due to

the unit falling.

When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children. If a child swallows a battery, make sure that the child gets immediate medical attention.

Caution

Do not wash the air conditioner with water, as this may cause an electric shock or fire.

Prohibit

For the repair work in places with high humidity or moisture, make sure to ground the unit. Failure to do so may cause an electric shock.

Confirm that the component attachment position, wiring condition, soldering condition and connector connection are normal.

If not, it may cause overheating or fire.

Confirm that the temperature around the compressor is not too high, and then perform the repair work. Failure to do so may cause a burn.

Perform welding work in a place with good ventilation.

If the work is performed in a poorly ventilated area, it might cause a lack of oxygen.

If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it.

Failure to do so may cause an injury due to the unit falling.

When the cleaning is to be performed, make sure to turn off the power and pull out the plug.

Touching the fan that is rotating at high speed may result in an injury.

When the indoor unit is to be removed, do not place it on an incline.

Doing so may cause wet furniture because water left inside may trickle down.

Prohibit

Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger.

Prohibit

After repairs, make sure to measure the insulation resistance and confirm that the value is 1 Mohm or more. Any insulation error may cause an electric shock.

After repairs, make sure to check the drainage of the indoor unit.

Inappropriate drainage may cause wet furniture and floors due to water leakage.

3

TABLE OF CONTENTS

 

 

 

 

 

 

Page

 

 

SAFETY PRECAUTIONS ..............................................................................................................

2

 

TABLE OF CONTENTS ...................................................................................................................

4

 

 

APPLICABLE MULTI-OUTDOOR UNITS ....................................................................................

6

 

 

 

 

 

1. OPERATING RANGE ...................................................................................................................

7

 

2. SPECIFICATIONS

 

 

8

2-1.

Unit Specifications .............................................................................................................

2-2.

Major Component Specifications .......................................................................................

14

2-3.

Other Component Specifications .......................................................................................

17

 

3. DIMENSIONAL DATA ....................................................................................................................

18

 

4. REFRIGERANT FLOW DIAGRAM

 

 

19

4-1.

Refrigerant Flow Diagram ..................................................................................................

 

5. ELECTRICAL DATA

 

 

20

5-1.

Electric Wiring Diagrams ....................................................................................................

 

6. MAINTENANCE

 

 

21

6-1.

Disassembly Procedure .....................................................................................................

 

7. FUNCTIONS

 

 

28

7-1.

Operation Functions ...........................................................................................................

7-2.

Protective Functions ...........................................................................................................

30

 

8. TROUBLESHOOTING

 

 

31

8-1.

Precautions before Performing Inspection or Repair ..........................................................

8-2.

Method of Self-Diagnostics .................................................................................................

31

8-3.

Checking the Indoor and Outdoor Units ..............................................................................

33

8-4.

Trouble Diagnosis of Fan Motor ..........................................................................................

37

 

 

8-5. Noise Malfunction and Electromagnetic Interference ..........................................................

38

 

 

 

INSTRUCTION MANUAL

.........................................................................................A-1

 

APPENDIX A

 

 

 

 

(XMS0972 & PNR-XS1872, XMS1272 & PNR-XS1872)

 

 

 

 

 

INSTRUCTION MANUAL

.........................................................................................A-2

 

APPENDIX B

 

 

 

 

(XS1872 & PNR-XS1872)

 

 

 

 

 

 

INSTALLATION INSTRUCTIONS .............................................................................A-3

 

APPENDIX C

 

 

 

 

XMS0972 & PNR-XS1872, XMS1272 & PNR-XS1872,

)

 

 

 

 

 

 

 

 

 

 

(XS1872 & PNR-XS1872

 

 

4

Page

APPENDIX D INSTRUCTION MANUAL .........................................................................................A-4

(STK-RCS-7TWSUA)

APPENDIX E INSTALLATION INSTRUCTIONS ............................................................................A-5

(STK-RCS-7TWSUA)

5

APPLICABLE MULTI-OUTDOOR UNITS

Multi-Outdoor Unit

3-Room

4-Room

4-Room

Indoor Unit

CM1972

CM2472

CM3172

XMS0972 & PNR-XS1872

YES

YES

YES

XMS1272 & PNR-XS1872

YES

YES

YES

XS1872 & PNR-XS1872

YES

YES

YES

6

1. OPERATING RANGE

 

Temperature

Indoor Air Intake Temp.

Outdoor Air Intake Temp.

Cooling

Maximum

95 °F D.B. / 71 °F W.B.

115 °F D.B.

Minimum

67 °F D.B. / 57 °F W.B.

67 °F D.B.

 

7

2. SPECIFICATIONS

2-1. Unit Specifications

2-1-1. Indoor Unit XMS0972 & PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<230V>

Type

 

 

 

 

 

 

Semi-Concealed Type Indoor Unit

Voltage Rating

 

 

 

 

 

 

230V Single-Phase 60Hz

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

Total Capacity

 

 

 

 

BTU/h

 

 

9,000

 

 

 

 

 

 

 

 

 

kW

 

 

2.65

 

 

 

 

Air Circulation (High)

 

 

 

ft3/min (m3/h)

 

 

221 (375)

 

 

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

3.4

 

 

Rating

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running Amperes

 

 

 

 

A

 

 

 

0.1

 

 

Electrical

Power Input

 

 

 

 

W

 

 

 

16

 

 

 

-

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

Microprocessor / I.C. Thermister

 

 

 

Control Unit

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

 

Fan Speeds

 

 

 

 

Indoor

 

 

Auto and 3 steps

 

 

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

-

 

 

Features

 

 

 

 

 

Vertical

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

 

 

 

 

 

Washable, Anti-Mold

 

 

 

Refrigerant

 

 

 

 

 

 

 

R410A

 

 

 

Operation Sound

 

Indoor : Hi/Me/Lo

 

dB-A

 

 

33 / 32 / 31

 

 

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

 

 

Tube Diameter

 

Wide tube

 

 

inch (mm)

 

 

3/8 (9.52)

 

 

 

 

Accessories

 

 

 

 

 

 

 

Air Clean Filter

 

 

 

Wired Remote Controller (Option)

 

 

 

 

STK-RCS-7TWSUA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight (Indoor Unit)

 

 

 

 

Indoor Unit

 

 

Individual Unit

 

 

 

 

 

 

Body

 

Panel

 

 

 

(XMS0972 & PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

(XMS0972)

 

(PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

 

Height

 

 

inch (mm)

 

12-5/16 (313)

 

 

11-5/32 (283)

 

1-9/16 (40)

 

 

 

 

Width

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

 

 

Depth

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

Package Dimensions

 

Height

 

 

inch (mm)

 

-

 

 

11-13/32 (290)

 

4-1/8 (105)

 

 

 

 

Width

 

 

inch (mm)

 

-

 

 

24-13/16 (630)

 

26-3/16 (665)

 

 

 

 

Depth

 

 

inch (mm)

 

-

 

 

28-1/8 (714)

 

26-11/16 (678)

 

 

Weight

 

Net

 

 

Ib. (kg)

 

41.3 (18.7)

 

 

35.3 (16)

 

6.0 (2.7)

 

 

 

 

Shipping

 

 

Ib. (kg)

 

-

 

 

41.9 (19)

 

7.7 (3.5)

 

 

Shipping Volume

 

 

 

 

cu.ft (m3)

 

-

 

 

4.59 (0.13)

 

1.65 (0.04)

Remarks: Rating conditions are:

 

 

 

 

DATA SUBJECT TO

CHANGE WITHOUT NOTICE.

 

 

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

 

8

Indoor Unit

XMS0972 & PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<208V>

Type

 

 

 

 

 

 

 

Semi-Concealed Type Indoor Unit

Voltage Rating

 

 

 

 

 

 

208V Single-Phase 60Hz

 

Performance

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

Total Capacity

 

 

 

 

BTU/h

 

 

9,000

 

 

 

 

 

 

 

 

 

 

kW

 

 

2.65

 

 

 

 

Air Circulation (High)

 

 

 

ft3/min (m3/h)

 

 

221 (375)

 

 

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

3.4

 

 

Rating

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running Amperes

 

 

 

 

A

 

 

0.11

 

 

Electrical

Power Input

 

 

 

 

 

W

 

 

 

15

 

 

 

 

-

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

Microprocessor / I.C. Thermister

 

 

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

 

Timer

 

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

 

Fan Speeds

 

 

 

 

 

Indoor

 

 

Auto and 3 steps

 

 

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

-

 

 

Features

 

 

 

 

 

 

Vertical

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

 

Refrigerant

 

 

 

 

 

 

 

 

R410A

 

 

 

Operation Sound

 

Indoor : Hi/Me/Lo

 

dB-A

 

 

33 / 32 / 31

 

 

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

 

Refrigerant

 

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

 

 

Tube Diameter

 

Wide tube

 

 

inch (mm)

 

 

3/8 (9.52)

 

 

 

 

Accessories

 

 

 

 

 

 

 

 

Air Clean Filter

 

 

 

Wired Remote Controller (Option)

 

 

 

 

STK-RCS-7TWSUA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight (Indoor Unit)

 

 

 

 

Indoor Unit

 

 

Individual Unit

 

 

 

 

 

 

Body

 

Panel

 

 

 

(XMS0972 & PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

(XMS0972)

 

(PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

 

Height

 

 

inch (mm)

 

12-5/16 (313)

 

 

11-5/32 (283)

 

1-9/16 (40)

 

 

 

 

 

Width

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

 

 

 

Depth

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

Package Dimensions

 

Height

 

 

inch (mm)

 

-

 

 

11-13/32 (290)

 

4-1/8 (105)

 

 

 

 

 

Width

 

 

inch (mm)

 

-

 

 

24-13/16 (630)

 

26-3/16 (665)

 

 

 

 

 

Depth

 

 

inch (mm)

 

-

 

 

28-1/8 (714)

 

26-11/16 (678)

 

 

Weight

 

 

Net

 

 

Ib. (kg)

 

41.3 (18.7)

 

 

35.3 (16)

 

6.0 (2.7)

 

 

 

 

 

Shipping

 

 

Ib. (kg)

 

-

 

 

41.9 (19)

 

7.7 (3.5)

 

 

Shipping Volume

 

 

 

 

cu.ft (m3)

 

-

 

 

4.59 (0.13)

 

1.65 (0.04)

Remarks: Rating conditions are:

 

 

 

 

DATA SUBJECT TO

CHANGE WITHOUT NOTICE.

 

 

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

 

9

Indoor Unit

XMS1272 & PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<230V>

Type

 

 

 

 

 

 

 

Semi-Concealed Type Indoor Unit

Voltage Rating

 

 

 

 

 

 

230V Single-Phase 60Hz

 

Performance

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

Total Capacity

 

 

 

 

BTU/h

 

 

11,900

 

 

 

 

 

 

 

 

 

 

kW

 

 

 

3.5

 

 

 

 

Air Circulation (High)

 

 

 

ft3/min (m3/h)

 

 

235 (400)

 

 

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

4.26

 

 

Rating

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running Amperes

 

 

 

 

A

 

 

0.11

 

 

Electrical

Power Input

 

 

 

 

 

W

 

 

 

17

 

 

 

 

-

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

Microprocessor / I.C. Thermister

 

 

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

 

Timer

 

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

 

Fan Speeds

 

 

 

 

 

Indoor

 

 

Auto and 3 steps

 

 

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

-

 

 

Features

 

 

 

 

 

 

Vertical

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

 

Refrigerant

 

 

 

 

 

 

 

 

R410A

 

 

 

Operation Sound

 

Indoor : Hi/Me/Lo

 

dB-A

 

 

34 / 32 / 31

 

 

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

 

Refrigerant

 

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

 

 

Tube Diameter

 

Wide tube

 

 

inch (mm)

 

 

3/8 (9.52)

 

 

 

 

Accessories

 

 

 

 

 

 

 

 

Air Clean Filter

 

 

 

Wired Remote Controller (Option)

 

 

 

 

STK-RCS-7TWSUA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight (Indoor Unit)

 

 

 

 

Indoor Unit

 

 

Individual Unit

 

 

 

 

 

 

Body

 

Panel

 

 

 

(XMS1272 & PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

(XMS1272)

 

(PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

 

Height

 

 

inch (mm)

 

12-5/16 (313)

 

 

11-5/32 (283)

 

1-9/16 (40)

 

 

 

 

 

Width

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

 

 

 

Depth

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

Package Dimensions

 

Height

 

 

inch (mm)

 

-

 

 

11-13/32 (290)

 

4-1/8 (105)

 

 

 

 

 

Width

 

 

inch (mm)

 

-

 

 

24-13/16 (630)

 

26-3/16 (665)

 

 

 

 

 

Depth

 

 

inch (mm)

 

-

 

 

28-1/8 (714)

 

26-11/16 (678)

 

 

Weight

 

 

Net

 

 

Ib. (kg)

 

41.3 (18.7)

 

 

35.3 (16)

 

6.0 (2.7)

 

 

 

 

 

Shipping

 

 

Ib. (kg)

 

-

 

 

41.9 (19)

 

7.7 (3.5)

 

 

Shipping Volume

 

 

 

 

cu.ft (m3)

 

-

 

 

4.59 (0.13)

 

1.65 (0.04)

Remarks: Rating conditions are:

 

 

 

 

DATA SUBJECT TO

CHANGE WITHOUT NOTICE.

 

 

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

 

10

Indoor Unit

XMS1272 & PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<208V>

Type

 

 

 

 

 

 

 

Semi-Concealed Type Indoor Unit

Voltage Rating

 

 

 

 

 

 

208V Single-Phase 60Hz

 

Performance

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

Total Capacity

 

 

 

 

BTU/h

 

 

11,900

 

 

 

 

 

 

 

 

 

 

kW

 

 

 

3.5

 

 

 

 

Air Circulation (High)

 

 

 

ft3/min (m3/h)

 

 

235 (400)

 

 

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

4.26

 

 

Rating

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running Amperes

 

 

 

 

A

 

 

0.12

 

 

Electrical

Power Input

 

 

 

 

 

W

 

 

 

16

 

 

 

 

-

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

Microprocessor / I.C. Thermister

 

 

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

 

Timer

 

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

 

Fan Speeds

 

 

 

 

 

Indoor

 

 

Auto and 3 steps

 

 

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

-

 

 

Features

 

 

 

 

 

 

Vertical

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

 

Refrigerant

 

 

 

 

 

 

 

 

R410A

 

 

 

Operation Sound

 

Indoor : Hi/Me/Lo

 

dB-A

 

 

34 / 32 / 31

 

 

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

 

Refrigerant

 

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

 

 

Tube Diameter

 

Wide tube

 

 

inch (mm)

 

 

3/8 (9.52)

 

 

 

 

Accessories

 

 

 

 

 

 

 

 

Air Clean Filter

 

 

 

Wired Remote Controller (Option)

 

 

 

 

STK-RCS-7TWSUA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight (Indoor Unit)

 

 

 

 

Indoor Unit

 

 

Individual Unit

 

 

 

 

 

 

Body

 

Panel

 

 

 

(XMS1272 & PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

(XMS1272)

 

(PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

 

Height

 

 

inch (mm)

 

12-5/16 (313)

 

 

11-5/32 (283)

 

1-9/16 (40)

 

 

 

 

 

Width

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

 

 

 

Depth

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

Package Dimensions

 

Height

 

 

inch (mm)

 

-

 

 

11-13/32 (290)

 

4-1/8 (105)

 

 

 

 

 

Width

 

 

inch (mm)

 

-

 

 

24-13/16 (630)

 

26-3/16 (665)

 

 

 

 

 

Depth

 

 

inch (mm)

 

-

 

 

28-1/8 (714)

 

26-11/16 (678)

 

 

Weight

 

 

Net

 

 

Ib. (kg)

 

41.3 (18.7)

 

 

35.3 (16)

 

6.0 (2.7)

 

 

 

 

 

Shipping

 

 

Ib. (kg)

 

-

 

 

41.9 (19)

 

7.7 (3.5)

 

 

Shipping Volume

 

 

 

 

cu.ft (m3)

 

-

 

 

4.59 (0.13)

 

1.65 (0.04)

Remarks: Rating conditions are:

 

 

 

 

DATA SUBJECT TO

CHANGE WITHOUT NOTICE.

 

 

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

 

11

Indoor Unit

XS1872 & PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<230V>

Type

 

 

 

 

 

 

 

Semi-Concealed Type Indoor Unit

Voltage Rating

 

 

 

 

 

 

230V Single-Phase 60Hz

 

Performance

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

Total Capacity

 

 

 

 

BTU/h

 

 

17,500

 

 

 

 

 

 

 

 

 

 

kW

 

 

 

5.15

 

 

 

 

Air Circulation (High)

 

 

 

ft3/min (m3/h)

 

 

341 (580)

 

 

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

Rating

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running Amperes

 

 

 

 

A

 

 

 

0.15

 

 

Electrical

Power Input

 

 

 

 

 

W

 

 

 

22

 

 

 

 

-

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

Microprocessor / I.C. Thermister

 

 

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

 

Timer

 

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

 

Fan Speeds

 

 

 

 

 

Indoor

 

 

Auto and 3 steps

 

 

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

-

 

 

Features

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

 

Refrigerant

 

 

 

 

 

 

 

 

R410A

 

 

 

Operation Sound

 

Indoor : Hi/Me/Lo

 

dB-A

 

 

44 / 40 / 36

 

 

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

 

Refrigerant

 

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

 

 

Tube Diameter

 

Wide tube

 

 

inch (mm)

 

 

1/2 (12.7)

 

 

 

 

Accessories

 

 

 

 

 

 

 

 

Air Clean Filter

 

 

 

Wired Remote Controller (Option)

 

 

 

 

STK-RCS-7TWSUA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight (Indoor Unit)

 

 

 

 

Indoor Unit

 

 

Individual Unit

 

 

 

 

 

 

Body

 

Panel

 

 

 

(XS1872 & PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

(XS1872)

 

(PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

 

Height

 

 

inch (mm)

 

12-5/16 (313)

 

 

11-5/32 (283)

 

1-9/16 (40)

 

 

 

 

 

Width

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

 

 

 

Depth

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

Package Dimensions

 

Height

 

 

inch (mm)

 

-

 

 

11-13/32 (290)

 

4-1/8 (105)

 

 

 

 

 

Width

 

 

inch (mm)

 

-

 

 

24-13/16 (630)

 

26-3/16 (665)

 

 

 

 

 

Depth

 

 

inch (mm)

 

-

 

 

28-1/8 (714)

 

26-11/16 (678)

 

 

Weight

 

 

Net

 

 

Ib. (kg)

 

41.3 (18.7)

 

 

35.3 (16)

 

6.0 (2.7)

 

 

 

 

 

Shipping

 

 

Ib. (kg)

 

-

 

 

41.9 (19)

 

7.7 (3.5)

 

 

Shipping Volume

 

 

 

 

cu.ft (m3)

 

-

 

 

4.59 (0.13)

 

1.65 (0.04)

Remarks: Rating conditions are:

 

 

 

 

DATA SUBJECT TO

CHANGE WITHOUT NOTICE.

 

 

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

 

12

Indoor Unit

XS1872 & PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<208V>

Type

 

 

 

 

 

 

 

Semi-Concealed Type Indoor Unit

Voltage Rating

 

 

 

 

 

 

208V Single-Phase 60Hz

 

Performance

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

Total Capacity

 

 

 

 

BTU/h

 

 

17,500

 

 

 

 

 

 

 

 

 

 

kW

 

 

 

5.15

 

 

 

 

Air Circulation (High)

 

 

 

ft3/min (m3/h)

 

 

341 (580)

 

 

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

Rating

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running Amperes

 

 

 

 

A

 

 

 

0.16

 

 

Electrical

Power Input

 

 

 

 

 

W

 

 

 

22

 

 

 

 

-

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

Microprocessor / I.C. Thermister

 

 

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

 

Timer

 

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

 

Fan Speeds

 

 

 

 

 

Indoor

 

 

Auto and 3 steps

 

 

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

-

 

 

Features

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

 

Refrigerant

 

 

 

 

 

 

 

 

R410A

 

 

 

Operation Sound

 

Indoor : Hi/Me/Lo

 

dB-A

 

 

44 / 40 / 36

 

 

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

 

Refrigerant

 

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

 

 

Tube Diameter

 

Wide tube

 

 

inch (mm)

 

 

1/2 (12.7)

 

 

 

 

Accessories

 

 

 

 

 

 

 

 

Air Clean Filter

 

 

 

Wired Remote Controller (Option)

 

 

 

 

STK-RCS-7TWSUA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight (Indoor Unit)

 

 

 

 

Indoor Unit

 

 

Individual Unit

 

 

 

 

 

 

Body

 

Panel

 

 

 

(XS1872 & PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

(XS1872)

 

(PNR-XS1872)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

 

Height

 

 

inch (mm)

 

12-5/16 (313)

 

 

11-5/32 (283)

 

1-9/16 (40)

 

 

 

 

 

Width

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

 

 

 

Depth

 

 

inch (mm)

 

24-19/32 (625)

 

 

22-5/8 (575)

 

24-19/32 (625)

 

 

Package Dimensions

 

Height

 

 

inch (mm)

 

-

 

 

11-13/32 (290)

 

4-1/8 (105)

 

 

 

 

 

Width

 

 

inch (mm)

 

-

 

 

24-13/16 (630)

 

26-3/16 (665)

 

 

 

 

 

Depth

 

 

inch (mm)

 

-

 

 

28-1/8 (714)

 

26-11/16 (678)

 

 

Weight

 

 

Net

 

 

Ib. (kg)

 

41.3 (18.7)

 

 

35.3 (16)

 

6.0 (2.7)

 

 

 

 

 

Shipping

 

 

Ib. (kg)

 

-

 

 

41.9 (19)

 

7.7 (3.5)

 

 

Shipping Volume

 

 

 

 

cu.ft (m3)

 

-

 

 

4.59 (0.13)

 

1.65 (0.04)

Remarks: Rating conditions are:

 

 

 

 

DATA SUBJECT TO

CHANGE WITHOUT NOTICE.

 

 

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

 

13

2-2. Major Component Specifications

2-2-1. Indoor Unit

Indoor Unit (Body)

XMS0972

 

 

 

 

 

 

 

 

 

 

 

Control PCB

 

 

 

 

 

 

Part No.

 

 

 

 

CB-XMS0972

 

Controls

 

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

250V 3A

 

 

 

 

 

Remote Control Unit

 

 

RCS-7MHVPSW4U

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Type

 

 

 

 

Turbo

 

Q'ty ... Dia. and Length

inch (mm)

1 ... D12-5/8 / L5-3/4 (D322/L147)

 

 

 

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

Type

 

 

 

 

DC Motor

 

Model ... Q'ty

 

 

 

 

SIC-69FV-D866-1 ... 1

 

No. of Poles

 

 

 

 

8

 

Rough Measure RPM (Cool)

 

 

440

 

Rating

Voltage / Nominal Output

DC280V / 23W

 

Coil Resistance

 

 

 

Ohm

-

 

(Ambient Temp. 68 °F (20 °C))

 

 

 

 

Safety Device

 

 

 

 

 

 

 

Type

 

 

 

 

Internal Controller

 

 

OverCurrent Protection

 

 

Yes

 

 

OverHeat Protection

 

 

Yes

 

Run Capacitor

 

 

 

Micro F

-

 

 

 

 

 

 

VAC

-

 

 

 

 

 

 

 

 

Drain Pump

 

 

 

 

 

 

Model ... Q'ty

 

 

 

 

PLD-12230ST-1 ... 1

 

Rating

 

Voltage, Hz

 

 

AC208 to 240V, 60Hz

 

 

 

 

Input

 

W

10.8

 

Coil Resistance

 

 

 

Ohm

333 +/- 10%

 

(Ambient Temp. 68 °F (20 °C))

 

 

 

 

Safety Device

 

Type

 

 

Thermal Fuse

 

 

 

 

Open

 

°F (°C)

293 (145)

 

 

 

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

Coil

 

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

 

2

 

Fins per inch

 

 

 

 

18.1

 

Face Area

 

 

 

ft2 (m2)

2.94 (0.273)

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Indoor Unit (Panel)

PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

Flap Motor

 

 

 

 

 

 

Type

 

 

 

 

Stepping Motor

 

Model ... Q'ty

 

 

 

 

MP24ZN-12V ... 2

 

Rating

 

 

 

 

DC 12V

 

Coil Resistance

 

 

 

Ohm

Each Pair of Terminal : 380 +/- 7%

 

(Ambient Temp. 77 °F (25 °C))

 

 

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

14

Indoor Unit (Body)

XMS1272

 

 

 

 

 

 

 

 

 

 

 

Control PCB

 

 

 

 

 

 

Part No.

 

 

 

 

CB-XMS1272

 

Controls

 

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

250V 3A

 

 

 

 

 

Remote Control Unit

 

 

RCS-7MHVPSW4U

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Type

 

 

 

 

Turbo

 

Q'ty ... Dia. and Length

inch (mm)

1 ... D12-5/8 / L5-3/4 (D322/L147)

 

 

 

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

Type

 

 

 

 

DC Motor

 

Model ... Q'ty

 

 

 

 

SIC-69FV-D866-1 ... 1

 

No. of Poles

 

 

 

 

8

 

Rough Measure RPM (Cool)

 

 

470

 

Rating

Voltage / Nominal Output

DC280V / 23W

 

Coil Resistance

 

 

 

Ohm

-

 

(Ambient Temp. 68 °F (20 °C))

 

 

 

 

Safety Device

 

 

 

 

 

 

 

Type

 

 

 

 

Thermal Fuse

 

 

OverCurrent Protection

 

 

Yes

 

 

OverHeat Protection

 

 

Yes

 

Run Capacitor

 

 

 

Micro F

-

 

 

 

 

 

 

VAC

-

 

 

 

 

 

 

Drain Pump

 

 

 

 

 

 

Model ... Q'ty

 

 

 

 

PLD-12230ST-1 ... 1

 

Rating

 

Voltage, Hz

 

 

AC208 to 240V, 60Hz

 

 

 

 

Input

 

W

10.8

 

Coil Resistance

 

 

 

Ohm

333 +/- 10%

 

(Ambient Temp. 68 °F (20 °C))

 

 

 

 

Safety Device

 

Type

 

 

Thermal Fuse

 

 

 

 

Open

 

°F (°C)

293 (145)

 

 

 

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

Coil

 

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

 

2

 

Fins per inch

 

 

 

 

18.1

 

Face Area

 

 

 

ft2 (m2)

2.94 (0.273)

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Indoor Unit (Panel)

PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

Flap Motor

 

 

 

 

 

 

Type

 

 

 

 

Stepping Motor

 

Model ... Q'ty

 

 

 

 

MP24ZN-12V ... 2

 

Rating

 

 

 

 

DC 12V

 

Coil Resistance

 

 

 

Ohm

Each Pair of Terminal : 380 +/- 7%

 

(Ambient Temp. 77 °F (25 °C))

 

 

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

15

Indoor Unit (Body)

XS1872

 

 

 

 

 

 

 

 

 

 

 

Control PCB

 

 

 

 

 

 

Part No.

 

 

 

 

CB-XS1872

 

Controls

 

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

250V 3A

 

 

 

 

 

Remote Control Unit

 

 

RCS-7MHVPSW4U

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Type

 

 

 

 

Turbo

 

Q'ty ... Dia. and Length

inch (mm)

1 ... D12-5/8 / L5-3/4 (D322/L147)

 

 

 

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

Type

 

 

 

 

DC Motor

 

Model ... Q'ty

 

 

 

 

SIC-72FV-D866-1B ... 1

 

No. of Poles

 

 

 

 

8

 

Rough Measure RPM (Cool)

 

 

650

 

Rating

Voltage / Nominal Output

DC340V / 20W

 

Coil Resistance

 

 

 

Ohm

-

 

(Ambient Temp. 68 °F (20 °C))

 

 

 

 

Safety Device

 

 

 

 

 

 

 

Type

 

 

 

 

Internal Controller

 

 

OverCurrent Protection

 

 

Yes

 

 

OverHeat Protection

 

 

Yes

 

Run Capacitor

 

 

 

Micro F

-

 

 

 

 

 

 

VAC

-

 

 

 

 

 

 

Drain Pump

 

 

 

 

 

 

Model ... Q'ty

 

 

 

 

PLD-12230ST-1 ... 1

 

Rating

 

Voltage, Hz

 

 

AC208 to 240V, 60Hz

 

 

 

 

Input

 

W

10.8

 

Coil Resistance

 

 

 

Ohm

333 +/- 10%

 

(Ambient Temp. 68 °F (20 °C))

 

 

 

 

Safety Device

 

Type

 

 

Thermal Fuse

 

 

 

 

Open

 

°F (°C)

293 (145)

 

 

 

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

Coil

 

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

 

2

 

Fins per inch

 

 

 

 

18.1

 

Face Area

 

 

 

ft2 (m2)

2.94 (0.273)

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Indoor Unit (Panel)

PNR-XS1872

 

 

 

 

 

 

 

 

 

 

 

Flap Motor

 

 

 

 

 

 

Type

 

 

 

 

Stepping Motor

 

Model ... Q'ty

 

 

 

 

MP24ZN-12V ... 2

 

Rating

 

 

 

 

DC 12V

 

Coil Resistance

 

 

 

Ohm

Each Pair of Terminal : 380 +/- 7%

 

(Ambient Temp. 77 °F (25 °C))

 

 

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

16

2-3. Other Component Specifications

Indoor Unit XMS0972 & PNR-XS1872

XMS1272 & PNR-XS1872

XS1872 & PNR-XS1872

Indoor air temp sensor

(Model:KTEC-35-S98)

 

10

 

 

 

 

 

 

 

ohm)(k

9

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

Resistance

8

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

0

50

59

68

77

86

95

104

 

 

 

 

(10)

(15)

(20)

(25)

(30)

(35)

(40)

Temperature °F (°C)

Indoor heat exchanger sensor

(Model:PT2M-51H-S3)

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ohm)(k

180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

50

68

86

104 122 140 158 176 194

 

 

 

 

(0)

(10) (20) (30) (40) (50) (60) (70) (80) (90)

Temperature °F (°C)

17

Sanyo PNR-XS1872, XMS1272, XMS0972, XS1872 User Manual

3. DIMENSIONAL DATA

Indoor Unit XMS0972 & PNR-XS1872

XMS1272 & PNR-XS1872

XS1872 & PNR-XS1872

7-11/16

8

 

4-29/32 A View

 

 

 

Ceilingopeningdimensions

 

 

 

 

23-5/8(600)

 

 

 

 

Suspensionboltpitch

 

 

 

 

21-1/32(534)

5

 

 

 

12-7/16

 

dimensions

pitch

of

5/8-22(575) 3/32-2

A

Ceiling

Suspension

Center panel

 

opening

(534)

 

11/16 - 6

 

(600)

bolt

 

5/16-6

 

23

1/32-21

 

 

5/8-

 

 

 

11-5/32(283)

1-3/16(30)

8-15/32

 

6 3

24-19/32 (625) 14-3/32 (358) 2

 

 

 

 

1-3/16

 

 

 

 

21/32

 

 

 

 

3-1/8

so that

 

 

 

suspension the

or3/16"

 

or

theof

unit

 

more

inthe contact

suspension -1

surface

willit

selected

 

the and

the of

 

shownas long,

should

 

lowerthe

is installed.be

be

(21/32"

 

right. panel

of gap

 

 

If

 

 

too

lengthThe bolts there ceilingthe below unit),main figure bolts ceilingthe cannot

isa

 

 

at

(625)19/32-24

(334)52-13

7

1 Air intake 2 Discharge outlet 3 Refrigerant tubing (liquid tube) dia. 1/4" (flared)

12-7/8

(575)5/8-22

1-25/32

tube)(gastubingRefrigerantdia. 1/2" (flared) VP20portconnectiontubeDrain(outer dia. 1") portsupplyPower 1/2"-(4holeboltSuspensionx 1-1/8" hole) connectionductintakeairFreshport (dia. 3-7/8")

31/32thanLess Less than31/32

 

1-25/32

4-19/32

4 5 6 7 8

 

3-5/8

 

 

2

2 1

2

25/32

 

 

 

5-9/16

 

1-9/32

2-3/4

 

2-3/32

 

3/32

 

 

1-

7-23/32

1-27/32

 

Unit : inch (mm)

18

4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram

Indoor Unit XMS0972 & PNR-XS1872

XMS1272 & PNR-XS1872 Indoor unit

exchangerHeat

Strainer

Indoor Unit XS1872 & PNR-XS1872

Indoor unit

Heat exchanger

Strainer

O.D. 3/8" (9.52 mm)

O.D. 1/4" (6.35 mm)

O.D. 1/2" (12.7 mm)

O.D. 1/4" (6.35 mm)

Cooling cycle

Cooling cycle

19

5. ELECTRICAL DATA

5-1. Electric Wiring Diagrams

Indoor Unit XMS0972 & PNR-XS1872

XMS1272 & PNR-XS1872

XS1872 & PNR-XS1872

 

 

THERMISTOR

 

 

 

 

 

 

21 1

2P

-2

 

 

 

 

 

 

 

 

46900-5250

 

 

 

 

COIL - 1

 

 

 

2

(RED)

 

 

 

 

 

 

 

 

BLK

2 1 1 COIL

 

 

 

 

 

 

 

 

BLK

 

2P

 

 

 

 

 

ROOM

 

 

 

 

(YEL)

 

 

 

 

 

 

BLK

2 ROOM

 

 

 

 

 

 

 

 

BLK

 

(RED)3P

8FA2-

 

 

 

 

 

 

 

BLK

13 1

 

 

 

 

 

 

 

3 FS

 

 

 

 

 

 

 

 

BLK

 

 

 

FLOATSWITCH

 

 

 

 

 

 

 

 

 

 

 

(R)

5

ORG

 

 

 

 

 

 

 

 

 

45 4

BLU

 

 

 

 

 

 

 

 

 

FLAP

23 2

 

 

 

 

 

 

 

 

 

WHT

 

 

 

 

 

 

 

 

 

 

3

BRN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1

BLK

 

 

 

 

 

 

 

 

 

 

 

WHT

 

6 6

WHT

 

 

 

 

FLAP (W)

5 5

 

5 5

5 5

(WHT)

CONTROLLER

 

3 4

BLU

 

3 4

 

 

BLU

3 4

 

109 9

BLU

1 2 1

BRN

54 4 IND (WHT)5P

 

 

4

BRN

 

 

4

4

 

 

 

 

3 2 2

ORG

 

 

3 2

ORG

3 2 2 FLAP

 

 

 

1 1

BLK

 

 

 

 

BLK

1 1

 

 

 

 

 

 

 

 

 

 

 

7 7

 

 

 

 

10

 

 

 

 

 

 

6 6

 

 

 

 

VLT

 

 

 

 

5

 

 

 

ASSY

78 7

 

 

 

 

23 2

7P

 

 

YEL

 

 

 

 

 

 

 

8

PNK

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

LAMPIND

32 2

ORG

 

 

 

 

32 2 RC (WHT)

 

 

 

6 6

RED

 

 

 

 

1 1

 

 

 

 

5 5

 

 

 

 

 

 

 

 

 

4 4

BRN

 

 

 

 

4 4

 

 

 

 

3

GRN

 

 

 

 

3

 

 

 

 

1 1

BLK

 

 

 

 

1 1

4P

 

 

 

WHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7 7

(RED)

 

 

 

 

 

 

 

 

 

 

6 6

7P (WHT)

 

 

 

 

 

 

 

 

 

 

3 43

 

 

 

 

 

 

 

 

 

 

5 5

 

BOX

 

 

 

 

 

 

 

 

 

21 1 PWM/POW 1SERIAL 2

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

2

2P

 

 

 

 

 

 

 

 

 

 

 

1 2

 

 

 

 

 

BRN RED ORG YEL PNK BLU VLT

 

RED WHT GRN

 

 

 

 

 

 

 

 

 

 

1 2

BOX

 

 

 

 

 

 

 

 

 

21 1 PWM/POW7P (RED) 2P

 

 

 

 

 

 

 

 

 

7 7

1 2

 

 

 

 

 

 

 

 

 

 

6 5

(WHT)

 

 

 

 

 

 

 

 

 

 

5 4 4

SERIAL

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

3 3

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

BASETERMINAL

DRAIN PUMP

MOTORFAN

GRN/YEL

 

21 1

6P

CONTROLLER

 

FM

 

 

 

 

 

 

 

DP

 

 

 

 

3

DP (BLU) (RED)

 

 

 

 

 

 

YEL/(RED)

 

 

 

 

 

 

 

 

YEL/(RED)

 

 

 

 

 

 

 

 

 

 

 

BLU

6 6

DCM (WHT)

 

 

 

 

 

 

 

 

 

YEL

43

 

 

 

 

 

 

 

 

 

 

5 4

(BLU)

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

WHT

2 3

 

 

 

 

 

 

 

 

 

 

BLK

6P

 

UNIT

3

 

 

 

 

 

 

RED

SI

 

 

GND

FERRITE

 

RED

 

OUTDOORTO

12

 

 

WHT

AC1AC2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

 

 

 

 

 

 

CORE

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

6. MAINTENANCE

6-1. Disassembly Procedure

 

To avoid electrical shock hazard, be sure to disconnect power before

 

Warning

attempting to disassemble the unit.

 

When a footstool, etc. is used for disassembling the indoor unit,

 

 

be careful not to fall down. If you fall down, you might be injured seriously.

 

6-1-1. Remove the air intake grill.

(1)Slide the 2 latches each to the corresponding arrow direction. (Fig. 1 and Fig. 2) Open downward the air intake grill located on the latch side.

(2)Undo the air intake grill drop preventive hook. (Fig. 3)

Undo the 2 hinges for the grill and remove the air intake grill.

Latch

Hinge

 

 

Hook

 

 

Latch

Air intake grill

Hinge

 

Fig.1

Fig.2

Fig.3

6-1-2. Disconnect the connectors in the control box.

(1)Remove the 2 screws and remove the control box cover. (Fig. 4)

(2)Disconnect the connectors CN04 (FLAP 5P), CN12 (RC 4P) and CN13 (IND 7P). (Fig. 5)

CN04

 

Control PCboard

CN13

CN12

Screw

Control box cover

 

 

Fig.4

 

Fig.5

 

21

6-1-3. Remove the ceiling panel.

(1)Open the clamp (4 locations) and remove the 2 lead wires from the clamps. (Fig. 6)

(2)Remove the 4 screws fixing the corner cover (at 3 locations) and indicator cover (at 1 location). (Fig. 6)

(3)Press the center 1 of the cover and remove the cover with the section 2 pulled down. (Fig. 7)

(4)Remove the strap (3 locations) from the hook on the ceiling panel. (Fig. 8)

NOTE There is no strap on the indicator cover.

(5) Remove the bolt (4 locations) with a washer and remove the ceiling panel. (Fig. 9)

Screw

Clamp

Corner cover

 

Indicator

 

 

 

 

 

cover

 

 

 

 

 

Lead wire

Pull down

 

 

 

section 2.

Cover

Clamp

Center 1

Corner cover

 

Corner cover

Screw

Fig.6

Fig.7

 

 

Bolt

Strap

 

Remove the strap

 

from the hook.

 

Bolt

Fig.8

Fig.9

22

6-1-4. Remove the indoor air temperature sensor.

(1)Disconnect the connector CN08 (ROOM 2P) in the control box and remove the indoor air temperature sensor. (Fig. 10)

Indoor air temperature sensor

CN08

Fig.10

6-1-5. Remove the power box and control box.

(1)Remove a screw and remove the terminal cover. (Fig. 11)

(2)Remove the 2 screws and remove the power box cover. (Fig. 11)

(3)Disconnect the power lines (No. 1 and No. 2) / signal line (No. 3) and ground cable from the terminals in the power box. (Fig. 12)

Terminal cover

Screw

Screw

Power box cover

Fig.11

Terminal

1

2 3

Ground cable

Power lines / Signal line

Fig.12

23

(4)Disconnect the connector CN07 (DP 2P) in the power box. (Fig. 13) Remove a screw and disconnect the ground cable. (Fig. 13)

(5)Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 14)

(6)Remove the 4 screws and remove the power box. (Fig. 14)

(7)Disconnect the connectors CN06 (FS 3P) and CN09 (COIL-1 2P) in the control box. (Fig. 15)

(8)Remove the 2 screws and remove the control box. (Fig. 15)

Screw

Ground cable

1 2 3

CN07

Fig.13

Screw

Screw

Screw

Screw

CN03

Fig.14

CN09

Screw

Screw

CN06

Fig.15

24

NOTE For the removal of the following components, perform any work after removing the indoor

unit (main body) from the ceiling.

 

 

Main body lower section

Heat exchanger sensor

Drain pump

Float switch

Turbo fan

Fan motor

Heat exchanger

 

 

1.Perform the work after draining the water to prevent the water leakage from the drain pan.

Put a bucket, etc., under the drain cap and remove the drain cap to drain the water. (Fig. 16)

2.Refer to the installation instructions for recovery of refrigerant or removal of the power cable or tubing.

6-1-6. Remove the main body lower section.

(1)Remove the 4 screws. (Fig. 16)

(2)Remove the 2 screws. (Fig. 17)

(3)Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 18)

(4)Lift the main body lower section and remove it from the main body upper section.

Screw

Screw

 

 

Drain cap

Main body lower section

Main body lower section

Screw

Screw

Fig.16

Main body lower section

Main body upper section

Screw

CN03

Fig.17

Fig.18

25

6-1-7. Remove the heat exchanger sensor.

(1) Remove the heat exchanger sensor from the sensor holder. (Fig. 19)

Heat exchanger sensor

Holder

Fig.19

6-1-8. Remove the drain pump and float switch.

(1)Remove the 2 screws (Fig. 20)

(2)Loosen the clamp and disconnect the drain hose from the drain pump. (Fig. 20)

(3)Remove the drain pump from the main body upper section. (Fig. 20)

(4)Remove a nut and remove the float switch. (Fig. 21)

Drain pump

Screw

Float switch

 

Nut

Drain hose

Clamp

Fig.20

Fig.21

26

6-1-9. Remove the turbo fan and fan motor.

(1)Remove a nut and remove the turbo fan. (Fig. 22)

(2)Remove the 2 screws and 3 nuts, and remove the fan motor. (Fig. 23)

Turbo fan

Screw

Nut

Nut

Fan motor

Fig.22

Fig.23

6-1-10. Remove the heat exchanger.

(1)Remove the 3 screws. (Fig. 24)

(2)Remove the 3 screws. (Fig. 25)

(3)Remove the heat exchanger from the main body upper section with the heat exchanger lifted.

Heat exchanger

Screw

Screw

Main body upper section

Screw

Fig.24

Fig.25

27

7. FUNCTIONS

7-1. Operation Functions

Emergency operation

Emergency operation is available when the remote controller malfunctions, has been lost, or otherwise cannot be used.

To operate the system, press the OPERATION button, which is also used as the receiver, below the unit display. Each time this button is pressed, the OPERATION lamp changes color to indicate the type of operation. Select the desired type of operation.

COOL

 

STOP

 

(GREEN)

 

(Lamp Off)

The set temperature is 4°F(2°C) below the detected room temperature in the case of cooling operation. The flap and fan speed settings are AUTO.

SENSOR DRY

During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment.

SENSOR DRY operation

• DRY operation is as shown in the figure below.

Load

COOL zone

Azone

Bzone

Conditions are monitored at all times when the room temperature is below 59°F(15°C).

DRY A

The compressor operation frequency varies. The indoor fan operates with 1/f fluctuation.

DRY B

The compressor operates at a low operating frequency. The indoor fan operates with 1/f fluctuation.

Monitor

Monitoring operation takes place when the room temperature is below 59°F(15°C), or more than 5°F(3°C) below the set temperature.

When the monitoring range is entered, the compressor stops, and the indoor fan operates with 1/f fluctuation.

PAMcontrol

In order to further improve inverter performance, control is switched between PWM control at low operation speeds, and PAM control at high operation speeds, making the most effective use of power.

28

HIGH POWER

This function acts to raise the power but keeps the AC system in the same operating mode.

This function is set with the HIGH POWER button on the remote controller.

(It can be set regardless of the temperature and fan speed settings.)

HIGH POWER operation from remote controller

The unit operates at maximum output for 30 minutes, regardless of the desired temperature.

The fan speed is 1 step above "High."

Frequency

MAX

0

Time

30 min. 5 min.

Start End

NOTE

When HIGH POWER operation ends, the unit operates at low Hz for 5 minutes, regardless of the thermostat OFF conditions.

When in DRY mode, operation is in the cooling zone.

Lamp colors

OPERATION lamp

 

DRY operation

Orange

COOL operation

Green

FAN operation

Green

DEFROSTING operation

Red and Orange

 

alternately

OPERATION lamp

Green

TIMER lamp

Green

HIGH POWER lamp

Green

Timer backup

Operation stops if there are no operator controls for 25 hours or longer after unit operation switched from OFF to ON by use of ON timer operation.

NIGHT SETBACK

When NIGHT SETBACK operation is set, the temperature and fan speed settings will be adjusted automatically to allow comfortable sleep.

When NIGHT SETBACK operation is set, " mark" appears on the remote controller. The main unit display lamp also becomes dimmer.

COOL and DRY modes

When the night setback mode is selected, the air conditioner automatically raises the temperature setting 2°F(1°C) when 30 minutes have passed after the selection was made, and then another 2°F(1°C) after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed.

Setting temperature

Press the NIGHT SETBACK button

2°F(1°C)

 

 

2°F(1°C)

 

 

30 min.

30 min.

Time

29

7-2. Protective Functions

Freeze prevention

During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below.

1.Freeze-prevention operation is engaged when the temperature of the indoor heat exchanger is below 43°F(6°C).

2.Restart after freeze-prevention operation occurs when the temperature of the indoor heat exchanger reaches 46°F(8°C) or above.

exchanger

46

 

 

 

C

 

 

 

 

 

°F(°C)

(8)

 

A

B

 

 

 

 

temperature

43

 

 

(6)

 

 

 

 

heat

36

 

 

 

 

Indoor

*

 

 

 

(2)

 

 

 

 

 

 

 

 

 

 

a

b

c

d

a.Area: Automatic capacity control

b.When the temperature drops below Point A, the operation frequency is reduced by a certain proportion.

c.Area: Frequency increase is prohibited.

d.When the temperature reaches Point C or above, freezing prevention is ended and control is the same as in the a area.

*When the temperature drops to below 36°F(2°C) (continuously for 2 minutes or longer), the compressor stops. Once the freeze condition is detected, the air conditioner will work less than the maximum frequency until it is turned off.

30

Loading...