Sanyo SHA-KC64UG, RCS-SH80UA, RCS-SH80UG, TM-SH80UG User Manual

0 (0)
Save These Instructions!
(
1. RCS-SH80UG
2. RCS-SH80UA.WL RCS-BH80UA.WL
4. SHA-KC64UG
Indoor Units
SEMI-CONCEALED CEILING-MOUNTED WALL-MOUNTED CONCEALED DUCT
(4-WAY)
XH1242 KH1242 UH1242 XH1842 KH1842 UH1842 XH2442 TH2442 KH2442 UH2442 XH3642 TH3642 KH3632 UH3642 XH4242 TH4242
Split System Air Conditioner
Wired type: for all indoor units
(
Wireless type: for X and T type indoor units
(
Wireless type: for K and U type indoor units
(
Weekly Timer
(
System Remote Controller
)
)
INSTRUCTION MANUAL
)
)
)
1
2
3
4
Pub. OI-85464189432000
©SANYO 2001
SANYO Electric Co., Ltd.
Osaka, Japan
N
Save These Instructions!
RCS-SH80UG
SEMI-CONCEALED CEILING-MOUNTED WALL-MOUNTED CONCEALED DUCT
(4-WAY)
XH1242 KH1242 UH1242 XH1842 KH1842 UH1842 XH2442 TH2442 KH2442 UH2442 XH3642 TH3642 KH3632 UH3642 XH4242 TH4242
Split System Air Conditioner
INSTRUCTION MANUAL
1
Contents
Page
Product Information .......................................................................................... 2
Alert Symbols ................................................................................................... 2
Installation Location .......................................................................................... 3
Electrical Requirements.................................................................................... 3
Safety Instructions ............................................................................................ 3
Names of Parts................................................................................................. 4
Remote Control Unit ..........................................................................................5
Operation ...........................................................................................................9
Adjusting the Airflow Direction ........................................................................10
Special Remarks .............................................................................................12
Setting the Timer ............................................................................................13
Care and Cleaning ..........................................................................................15
Troubleshooting ...............................................................................................17
Tips for Energy Saving ...................................................................................17
Product Information
If you have problems or questions concerning your Air Conditioner, you will need the following information. Model and serial numbers are on the nameplate on the bottom of the cabinet.
Model No. Serial No.
Date of purchase
1
Dealer’s address
Phone number
Alert Symbols
The following symbols used in this manual, alert you to potentially dangerous conditions to users, service personnel or the appliance:
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
1 - 2
OI-432-01 - 2EG
Installation Location
We recommend that this air conditioner be installed properly by
qualified installation technicians in accordance with the Installation Instructions provided with the unit.
Before installation, check that the voltage of the electric supply in
your home or office is the same as the voltage shown on the nameplate.
• Do not install this air conditioner where there are fumes or flammable gases, or in an extremely humid space such as a greenhouse.
• Do not install the air conditioner where excessively high heat­generating objects are placed.
Avoid: To protect the air conditioner from heavy corrosion, avoid installing the
outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa.
Electrical Requirements
1. All wiring must conform to the local electrical codes. Consult your dealer
or a qualified electrician for details.
2. Each unit must be properly grounded with a ground (or earth) wire
or through the supply wiring.
3. Wiring must be done by a qualified electrician.
To warm up the system, the power mains must be turned on at least five (5) hours before operation. Leave the power mains ON unless you will not be using this appliance for an extended period.
Power mains
ON
Safety Instructions
Read this Instruction Manual carefully before using this air conditioner. If you still have any difficulties or problems, consult your dealer for help.
The air conditioner is designed to give you comfortable room conditions. Use this only for its intended purpose as described in this Instruction Manual.
• Never touch the unit with wet hands.
• Never use or store gasoline or other flammable vapor or liquid near the air conditioner — it is very dangerous.
• This air conditioner has no ventilator for intaking fresh air from outdoors. You must open doors or windows frequently when you use gas or oil heating appliances in the same room, which consume a lot of oxygen from the air. Otherwise there is a risk of suffocation in an extreme case.
1
OI-432-01 - 3EG
• Do not turn the air conditioner on and off from the power mains switch. Use the ON/OFF operation button.
• Do not stick anything into the air outlet of the outdoor unit. This is dangerous because the fan is rotating at high speed.
• Do not let children play with the air conditioner.
• Do not cool or heat the room too much if babies or invalids are present.
1 - 3
Names of Parts
INDOOR UNIT
X type (4-WAY)
Celling panel (optional)
T type
Air outlet
SEMI-CONCEALED
Air outlet Air intake
CEILING-MOUNTED
Air intake
K type
U type
Air outlet (optional)
WALL-MOUNTED
Air intake
Air outlet
CONCEALED DUCT
Ceiling
Air intake (optional)
1
REMOTE CONTROL UNITS
(optional)
(Wired type: (Wireless type: available for all available for indoor units) X and T)
System Remote Controller
Weeky Timer
(Wireless type: available for K and U)
NOTE
This illustration is based on the external appearance of a standard model. Consequently, the appearance may differ from that of the air conditioner you have selected.
1 - 4
OI-432-01 - 4EG
Remote Cotrol Unit
With this remote controller, you can operate indoor units up to 8 units.
Once you set your operation conditions, you can operate the units only by pressing the ON/OFF operation button.
For the U type, the flap position is not shown on the display.
N: SENSER
J: TIMER
SET button
B: OPERATION lamp
K: TIME
setting buttons
G: CHECK
button
A: ON/OFF operation
button
O: VENTILATION
button
F: FILTER reset
button
A: ON/OFF operation button This button is for turning the air conditioner on and off. B: Operation lamp This lamp lights when the air conditioner is turned on.
C: MODE button Use this button to select one of the following five operations:
D: Temperature : Press this button to increase the temperature setting.
setting buttons : Press this button to decrease the temperature setting.
L: SET button
M: CL button
(AUTO) : Used to automatically set cooling or heating operation.
(HEAT) : Used for normal heating operation.
(DRY) : Used for dehumidifying without changing the room temperature.
(COOL) : Used for normal cooling operation.
(FAN) : Used to run the fan only, without heating or cooling operation.
I: FLAP button
H: UNIT button
Only for heat pump type (temperature range: 62 ~ 80 °F)
Only for heat pump type (temperature range: 60 ~ 78 °F)
E: FAN SPEED
selector button
(temperature range: 64 ~ 86 °F)
(temperature range: 64 ~ 86 °F)
C: MODE button
D: Temperature
setting buttons
1
E: FAN SPEED selector
button (AUTO) : The air conditioner automatically decides the fan speed.
(HI.) : High fan speed.
(MED.) : Medium fan speed.
(LO.) : Low fan speed.
NOTE
OI-432-01 - 5EG
When low fan speed is selected and the air conditioner is in cooling operation at a low outdoor temperature of less than 50°F, the air conditioner may automatically switch to medium fan speed.
1 - 5
Remote Control Unit (continued)
F: FILTER reset button Use this button to reset the filter sign . The air conditioner has a timer
for the filter and informs you when the filter needs cleaning.
G: CHECK button This button is used only when servicing the air conditioner.
Do not use the CHECK button for normal operation.
H: UNIT button When more than one indoor unit is connected, this button is used to
select a unit when adjusting the airflow direction. If no unit is selected, the airflow direction of all units can be adjusted concurrently using the FLAP button.
I: FLAP button ( ) 1. Use this button to set the airflow direction to a specific angle.
The airflow direction ( ) is displayed on the remote control unit.
Operation mode
Number of airflow direction settings
1
(COOL) or (DRY) (HEAT) or (FAN) (AUTO)
Cooling mode: Heating mode:
In the cool mode and dry mode, when the flaps are set in a
downward position, condensation may form and drip around the vent.
Do not move the flap with your hands.
NOTE
()2. Use this button to make the airflow direction sweep up and down
NOTE
.
J: TIMER SET button Use this button while the unit is operating to switch between timer
(OFF Timer) :The air conditioner stops after the length of time set.
(OFF Cycle Timer) :The air conditioner after the same set time every time.
(ON Timer) :The air conditioner starts after the length of time set.
This function is available only for models X and T.
automatically.
Press this button several times until the ( ) symbol appears on
the display.
This function is available only for models X, T and K.
settings:
3 5
3 5
K: Time setting buttons :Press this button to increase the time.
:Press this button to decrease the time.
L: SET button Use this button to set the timer.
M: CL button Use this button to clear the timer setting.
N: Temperature sensor of the While the temperature sensor of the indoor unit usually detects ambient
remote controller temperatures, it is also possible to detect temperatures around the
remote controller. For the detail of this functionality, consult your dealer. (Do not use this functionality for group operation.)
O: VENTILATION button Use this button when you installed a fan available in the market.
Pressing this button turns on and off the fan. When turning off the air conditioner, the fan will be also turned off.
While the fan is operating, will appear in the display. If is displayed when pressing the ventilation button, no fans are installed.
1 - 6
OI-432-01 - 6EG
Remote Control Unit (continued)
NOTE
1) When two remote control units are being used in one group control* system, a) the most recent button that is pressed on any remote control unit
is effective.
b) either a main-remote control unit or a sub-remote control can set
the timer. *Group control means that maximum up to 8 indoor units can be
concurrently controlled with a remote control unit.
2) If a power failure occurs in timer mode, the time counted up to that point will be stored in memory. After power is restored, the timer starts again counting up to the set time.
1
OI-432-01 - 7EG
1 - 7
Display (Remote Control Unit)
When you first turn on the ON/OFF operation button, will blink on the display of the remote controller. During this blinking, the remote controller is verifying units connected. Use the remote controller, after stops blinking.
B
G
L
K
D
P
H
C
F I J M
N
A O
E
1
Description
A: When the unit is in the heating standby mode, the indicator appears. (Refer to the description of the
Special Remarks on page 12.)
B: The currently selected operation mode is displayed. C: This is displayed when a different operation mode was already selected by another remote control unit and
indicates that the mode cannot be changed.
D: When the TIMER SET button is pressed to set the timer, the indicator flashes. E: The currently selected FAN SPEED is displayed. F: The currently selected Airflow Direction and SWEEP status are displayed. G: This is displayed only when an abnormality occurs within a unit. H: When the CHECK button is pressed, the TEST indicator appears. I: This is displayed to indicate that the system controller is being used for control.
When is flashing on the display, the operation is not accepted by the system controller.
J: This indicates the indoor unit address in case of group control.
Unit No.
1 — 2
Indoor unit No.
Refrigerant circuit No.
K: This is displayed when it is time to clean the filter. L: When setting the timer, the selected timer mode is displayed. M: This indication appears when the temperature is set. N: This indication appears when the remote control sensor is used. O: This indication appears when the ventilation fan does not operate even if the ventilation button has been
pressed.
P: This indication appears when the ventilation fan is operating.
1 - 8
OI-432-01 - 8EG
STEP 5
Operation
STEP 1, 6
STEP 3
STEP 2
STEP 4
NOTE
To warm up the system, the power mains must be turned on at least five (5) hours before operation.
STEP 1 To start the air conditioner
Press the operation button (ON/OFF button).
STEP 2 Setting the mode
Press the MODE button to select the mode of your choice.
[ (AUTO), (HEAT), (DRY), (COOL) or (FAN)]
STEP 3 Setting the fan speed
Press the FAN SPEED selector button to select the fan speed of your choice. [ (AUTO), (HI.), (MED.) or (LO.)]
If AUTO is selected, the fan speed switches automatically.
STEP 4 Setting the temperature
Use the or button as appropriate to change the temperature setting as desired. ( reduces the temperature, and increases the temperature.)
STEP 5 Setting the airflow direction
When more than one indoor unit is connected, the UNIT button is used first to select a unit. Then use the FLAP button to set the airflow direction to a specific angle or to sweep. (Refer to the description of the remote control unit.)
STEP 6 To stop the air conditioner
Press the operation button (ON/OFF button) again.
1
OI-432-01 - 9EG
1 - 9
Adjusting the Airflow Direction
Semi-concealed type
4-way type (X)
This air conditioner is equipped with auto flaps. You can set the airflow direction to a specific angle or to the sweep mode using the remote control unit. (Refer to the description of the remote control unit.)
Do not move the flap with your hands.
Ceiling mounted type (T)
1
Auto flap
A. Vertical directions (automatic)
This air conditioner is equipped with an auto flap.You can set the airflow direction to a specific angle or to the sweep mode using the remote control unit. (Refer to the description of the remote control unit.)
Do not move the flap with your hands.
B. Horizontal directions (manual)
The horizontal airflow direction can be adjusted manually by moving the vertical vanes to the left or right.
Vertical vane
1 - 10
OI-432-01 - 10EG
Adjusting the Airflow Direction (continued)
Left
Vertical vanes
Right
Air outlet grille
Flap
Down
Up
Indoor unit
Zone A for cooling
Zone “B” for heating
30˚
60˚
Wall mounted type (K)
A. Vertical directions (automatic)
Confirm that the remote control unit has been turned on. Press the FLAP button to start the flap moving up and down. If you want to stop the flap movement and to direct the air in the desired direction, press the FLAP button again. In the cool mode, don’t direct the flap down more than 30°, otherwise, condensation may drip on to the floor. Zone “A” is the recommended flap position for cooling.
Do not move the flap with your hands.
B. Horizontal directions (manual)
The horizontal airflow can be adjusted manually by moving the vertical vanes to the left or right.
Concealed duct type (U)
This air conditioner is not equipped with air outlet parts. These must be obtained locally. Please refer to the manual of the locally adopted air outlet parts.
1
OI-432-01 - 11EG
1 - 11
DRYOperation
Special Remarks
1
How it works
Heating Operation
Heating performance
Defrosting
(STANDBY) on
the display
Once the room temperature reaches the level that was set, the unit repeats the cycle of turning on and off automatically.
In order to prevent the humidity in the room from rising again, the indoor fan also turns off when the unit stops operating.
The fan speed is set to “LO.” automatically, and cannot be adjusted.
“DRY” operation is not possible if the outdoor temperature is 59 °F or less.
Because this appliance heats a room by utilizing the heat of the outside air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this heat pump, use another heating appliance in conjunction with this unit.
When the outdoor temperature is low, frost or ice may form on the outdoor heat exchanger coil, reducing the heating performance. When this happens, a microcomputer-controlled defrosting system operates. At the same time, the fan on the indoor unit stops (or runs at very low speed in some cases) and the (STANDBY) indicator appears on the display until defrosting is completed. Heating operation then restarts after several minutes. (This interval will vary slightly depending upon the outdoor temperature and the way in which frost forms.)
For several minutes after the start of heating operation, the indoor fan will not start running (or it will run at very low speed in some cases) until the indoor heat exchanger coil has warmed up sufficiently. This is because a cold draft prevention system is operating. During this period, the (STANDBY) indicator remains displayed.
The indicator remains displayed during defrosting or when the compressor has been turned off (or when the unit is running at very low speed) by the thermostat when the system is in the heating mode.
Upon completion of defrosting and when the compressor is turned on again, (STANDBY) will turn off automatically as heating operation resumes.
1 - 12
NOTE
Should the power fail while the unit is running
If the power supply for this unit is temporarily interrupted, the unit will automatically resume operation (once the power is restored) with the same settings that were in effect before the power was interrupted.
OI-432-01 - 12EG
OFF
ON
Set time
OFF
ON
Set time
OFF
ON
Set time
OFF
ON
Set time
OFF timer
OFF cycle timer
ON timer
Setting the Timer
Use this mode to turn off the appliance automatically after the length of time set.
Use this mode to turn the appliance off automatically after the same set time every time.
Use this mode to start the appliance automatically after the length of time set.
NOTE
When two remote control units are being used, either a main-remote control unit or a sub-remote control unit can be used for timer operations. (Refer to the description of the remote control unit.)
1
OI-432-01 - 13EG
1 - 13
How to set the OFF timer ( )
Operation Indication
1. Press the ON/OFF button to start
the air conditioner.
2. Press the TIMER SET button once to
select the mode.
3. Press the button until 3.5 is displayed. Press the button if the set time is exceeded.
4. Press the SET button to set the OFF timer.
How to set the OFF cycle timer ( )
(Example) To stop the air conditioner after 3.5 hours every time
Operation Indication
1. Press the ON/OFF button to start the air conditioner.
2. Press the TIMER SET button twice to select the mode.
3. Set the time using the or button.
4. Press the SET button to set the OFF cycle timer ( ) .
(Example) To stop the air conditioner after 3.5 hours
$
$
$
$
The and time indications (hour) flash.
The indication disappears and time indications (hour) flash.
The and time indications (hour) flash.
The indication disappears and time indications (hour) flash.
1
NOTE
When the OFF cycle timer is set, the unit will stop after 3.5 hours every operation.
How to set the ON timer ( )
Operation Indication
1. Press the ON/OFF button to start the air conditioner.
2. Press the TIMER SET button three times to select the mode.
3. Press the button until 10.5 is displayed. Press the button if the set time is exceeded.
4. Press the SET button to set the ON timer.
NOTE
When the ON timer is set, the unit enters the paused state.
How to stop the timer operation
Operation Indication
Push the CL button.
(Example) To start the air conditioner after 10.5 hours
$
$
$
The and time indications (hour) flash.
The and indications shown in the display disappear and time indications (hour) flash.
The indication disappears.
To adjust the timer
1 - 14
Each press of the button increases the timer operation period with half an hour (30 minutes) step, up to 72.0 hours.
Each press of the button decreases the timer operation period with half an hour (30 minutes) step, down to half an hour.
OI-432-01 - 14EG
Care and Cleaning
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
Air Intake and outlet side
(Indoor Unit)
Air filter
Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them with a clean soft cloth.
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning the air outlet side, be careful not to force the vanes out of place.
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic parts using very hot water.
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be cleaned every year. Consult your dealer or service center.
The air filter collects dust and other particles from the air and should be cleaned at regular intervals as indicated in the table below or when the
filter indication ( ) on the display of the remote control unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air conditioner drops greatly.
Type X T K U
Period Six months Six months Two weeks (depending on
filter specifications)
*Concealed duct type (U):
An air filter is not provided with this air conditioner at the time of shipment. To get clean air and to extend the service life of the air conditioner, an air filter must be installed in the air intake. For installation and cleaning the air filter, consult your dealer or service center.
1
How to clean the filter
How to remove the filter
4-way semi-concealed type
OI-432-01 - 15EG
NOTE
(X):
The frequency with which the filter should be cleaned depends on the environment in which the unit is used.
1. Remove the air filter from the air intake grille.
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the
filter, wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.
1. Remove the bolt screw on each side out of the latch using a screwdriver.
(After cleaning, be sure to reattach the two bolt screws.)
2. Slide the two latches of the air intake grille to the direction of the arrow to
open the grille.
3. Open the air intake grille downward.
When cleaning the air filter, never remove the safety chain. If it is necessary to remove it for servicing and maintenance inside, be sure to reinstall the safety chain securely (hook on the grille side) after the work.
1 - 15
How to remove the filter
(continued)
Care and Cleaning (continued)
4. Remove the air filter attached to the air intake grille.
Latch
Safety chain
1
Air intake grille
How to remove the filter
(continued)
Ceiling-mounted type (T):
Wall-mounted type (K):
Air filter
Bolt screw
1. Remove the bolt screws on the finger-hold using a screw driver. (After
cleaning, be sure to attach the two bolt screws.)
2. Take hold of the finger-hold on the air intake grille and slide it to the rear,
and the grille will open downward.
3. Take hold of the finger-hold on the air filter, first lift it and then pull it
toward you to release it from the catch.
Finger-hold
Air filter
Air filter finger-hold
1. Move the flap on the air outlet grille to its lowest position with the remote
control unit.
2. The filter is disengaged by pushing the tab up gently. Hold the air filter by
the tab at the bottom, and pull downward.
Catch
Air intake grille
1 - 16
1 Push up
then
2 Pull down
Air filter
When replacing the filter, make sure that the FRONT mark is facing you. Push it up until you hear it click back into position.
$
OI-432-01 - 16EG
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center.
Trouble Possible Cause Remedy
Air conditioner does not 1. Power failure 1. Restore power. run at all.
Compressor runs but 1. Obstruction in front of condenser coil 1. Remove obstruction. soon stops.
Poor cooling (or heating) 1. Dirty or clogged air filter 1. Clean the air filter to improve the performance airflow.
CHECKis displayed. 1. Trouble in the system 1. Contact service center.
2. Leakage circuit breaker has tripped. 2. Contact service center.
3. Line voltage is too low. 3. Consult your electrician or dealer.
4. Operation button is turned off. 4. Press the button again.
5. The remote control unit or heat 5. Consult your dealer. pump is malfunctioning. (ERROR and characters such as E, F, H, L, P, etc., appear on the display.)
2. Heat source or many people in room 2. Eliminate heat source if possible.
3. Doors and/or windows are open. 3. Shut them to keep the heat (or cold)
out.
4. Obstacle near air intake or air 4. Remove it to ensure good airflow. discharge port
5. Thermostat is set too high for cooling 5. Set the temperature lower (or higher). (or too low for heating).
6. (Outdoor temperature is too low). 6. (Try to use a back-up heater.)
7. (Defrosting system does not work.) 7. (Consult your dealer.)
Tips for Energy Saving
Avoid Do not block the air intake and outlet of the unit. If either is
obstructed, the unit will not work well, and may be damaged.
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls and ceiling of the room are warmed by the sun, it will take longer to cool the room.
Do Always try to keep the air filter clean. (Refer to “Care and Cleaning.)
A clogged filter will impair the performance of the unit.
To prevent conditioned air from escaping, keep windows, doors and any other openings closed.
NOTE
Should the power fail while the unit is running
If the power supply for this unit is temporarily interrupted the unit will automatically resume operation (once the power is restored) with the same settings that were in effect before the power was interrupted.
1
OI-432-01 - 17EG
1 - 17