TECHNICAL DATA & SERVICE MANUAL
SPLIT SYSTEM AIR CONDITIONER
Model No. |
Product Code No. |
||
SPW-UMR74EXH56 |
854.0.2263 |
||
SPW-UMR94EXH56 |
854.0.2264 |
||
SPW-UMR124EXH56 |
854.0.2265 |
||
SPW-UMR164EXH56 |
854.0.2301 |
||
SPW-UMR184EXH56 |
854.0.2266 |
||
SPW-UMR224EXH56 |
854.0.2267 |
||
|
|
|
|
|
|
|
|
SM940046
0.8180.439.0 June 2005
IMPORTANT!
Please read before installation
This air conditioning system meets strict safety and operating standards.
For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
•Carefully read this instruction booklet before beginning.
•Follow each installation or repair step exactly as shown.
•Observe all local, state and national electrical codes.
•Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions.
If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
•During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
WARNING |
When wiring |
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.
•Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
•Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring.
Improper connections and inadequate grounding can cause accidental injury and death.
•Ground the unit following local electrical codes.
•The Yellow/Green wire cannot be used for any connection different from the ground connection.
•Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
•Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
•Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing...
… In a ceiling
Make sure the ceiling is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.
… In a room
Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher then drifting snow. Provide snow vents.
When connecting refrigerant tubing
•Keep all tubing runs as short as possible.
•Use the flare method for connecting tubing.
•Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
•Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
When servicing
•Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
•Keep your fingers and clothing away from any moving parts.
•Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
•Ventilate the room during the installation or testing the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
2
Table of Contents
|
Page |
1. SPECIFICATIONS |
4 |
1-1 Unit specifications |
4 |
1-2 Major Component specifications |
7 |
1-3 Other Component specifications |
10 |
2. DIMENSIONAL DATA |
11 |
3. ELECTRICAL DATA |
13 |
3-1 Electric Wiring Diagram |
13 |
3-2 Control PCB switches and functions |
14 |
4. FUNCTION |
15 |
4-1 Room Temperature Control |
15 |
4-2 Automatic control for heating and cooling |
16 |
5. REPLACING PCB |
17 |
5-1 Replacing PCB |
17 |
5-2 How to replace PCB |
18 |
5-3 How to replace EEPROM with EEPROM included in PCB service pack |
19 |
5-4 Table of setting |
21 |
6. SERVICING AND MAINTENANCE FUNCTIONS |
22 |
6-1 Indoor unit refrigerant noise countermeasures |
22 |
6-2 Outdoor unit noise countermeasures: EEPROM 05 |
22 |
7. TROUBLE DIAGNOSIS |
23 |
7-1 Contents of remote controller switch alarm display |
23 |
7-2 Outdoor unit control panel led display |
25 |
7-3 Trouble indications and inspection points |
26 |
7-4 Remote controller servicing functions |
28 |
7-5 Super W-Multi alarm codes |
29 |
7-6 Inspection of parts |
35 |
3
1. SPECIFICATIONS
1-1 Unit Specifications
SPW-UMR74/94/124EXH56
Power source |
|
|
|
220 - 240V ~ 50Hz |
||
|
|
|
|
|
||
Voltage rating |
|
|
|
230V |
||
|
|
|
|
|
|
|
Performance |
|
|
Cooling |
|
Heating |
|
|
Capacity |
|
|
See catalogue with |
the requested matching |
|
|
Air circulation (High/Med./Low) |
|
m³/h |
|
600/510/440 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
Controls/Temperature controls |
|
|
Microprocessor/ I.C. thermostat |
||
|
Remote Controller (Option) |
|
wired |
RCS-SH80AG / RCS-KR1AG |
||
|
|
|
wireless |
|
RCS-BH80AG.WL |
|
|
Fan speed |
|
|
|
3 and Auto |
|
|
|
|
|
|
|
|
|
Air Filter |
|
|
|
Washable |
|
|
Sound pressure level (*) |
high/med/low |
dB(A) |
|
54/52/49 |
|
|
Refrigerant tubing connections |
|
|
|
Flare type |
|
|
Refrigerant |
Narrow tube |
mm(in.) |
|
6,35 (1/4) |
|
|
tube diameter |
Wide tube |
mm(in.) |
|
12,7 (1/2) |
|
|
Refrigerant |
|
|
|
R410A |
|
|
Refrigerant control |
|
|
Electronic expansion valve |
||
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
|
|
Dimensions |
Height |
mm |
|
266 |
|
|
|
Width |
mm |
|
571 |
|
|
|
Depth |
mm |
|
852 |
|
|
Package dimensions |
Height |
mm |
|
365 |
|
|
|
Width |
mm |
|
745 |
|
|
|
Depth |
mm |
|
1086 |
|
|
|
Volume |
m3 |
|
0,3 |
|
|
Weight |
Net |
kg |
|
30,0 |
|
|
|
Shipping |
kg |
|
34 |
DATA SUBJECT TO CHANGE WITHOUT NOTICE
(*) Power noise level measured at operating conditions (5mmH20 external static pressure)
4
SPW-UMR164/184EXH56
Power source |
|
|
|
220 - 240V ~ 50Hz |
||
|
|
|
|
|
||
Voltage rating |
|
|
|
230V |
||
|
|
|
|
|
|
|
Performance |
|
|
Cooling |
|
Heating |
|
|
Capacity |
|
|
See catalogue with |
the requested matching |
|
|
Air circulation (High/Med./Low) |
|
m³/h |
|
875/600/400 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
Controls/Temperature controls |
|
|
Microprocessor/ I.C. thermostat |
||
|
Remote Controller (Option) |
|
wired |
RCS-SH80AG / RCS-KR1AG |
||
|
|
|
wireless |
|
RCS-BH80AG.WL |
|
|
Fan speed |
|
|
|
3 and Auto |
|
|
|
|
|
|
|
|
|
Air Filter |
|
|
|
Washable |
|
|
Sound pressure level (*) |
high/med/low |
dB(A) |
|
54/47/42 |
|
|
Refrigerant tubing connections |
|
|
|
Flare type |
|
|
Refrigerant |
Narrow tube |
mm(in.) |
|
6,35 (1/4) |
|
|
tube diameter |
Wide tube |
mm(in.) |
|
12,7 (1/2) |
|
|
Refrigerant |
|
|
|
R410A |
|
|
Refrigerant control |
|
|
Electronic expansion valve |
||
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
|
|
Dimensions |
Height |
mm |
|
266 |
|
|
|
Width |
mm |
|
571 |
|
|
|
Depth |
mm |
|
1058 |
|
|
Package dimensions |
Height |
mm |
|
365 |
|
|
|
Width |
mm |
|
745 |
|
|
|
Depth |
mm |
|
1292 |
|
|
|
Volume |
m3 |
|
0,35 |
|
|
Weight |
Net |
kg |
|
35 |
|
|
|
Shipping |
kg |
|
39 |
DATA SUBJECT TO CHANGE WITHOUT NOTICE
5
SPW-UMR224EXH56
Power source |
|
|
|
220 - 240V ~ 50Hz |
||
|
|
|
|
|
||
Voltage rating |
|
|
|
230V |
||
|
|
|
|
|
|
|
Performance |
|
|
Cooling |
|
Heating |
|
|
Capacity |
|
|
See catalogue with |
the requested matching |
|
|
Air circulation (High/Med./Low) |
|
m³/h |
|
1000/700/600 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
Controls/Temperature controls |
|
|
Microprocessor/ I.C. thermostat |
||
|
Remote Controller (Option) |
|
wired |
RCS-SH80AG / RCS-KR1AG |
||
|
|
|
wireless |
|
RCS-BH80AG.WL |
|
|
Fan speed |
|
|
|
3 and Auto |
|
|
|
|
|
|
|
|
|
Air Filter |
|
|
|
Washable |
|
|
Sound pressure level (*) |
high/med/low |
dB(A) |
|
57/49/46 |
|
|
Refrigerant tubing connections |
|
|
|
Flare type |
|
|
Refrigerant |
Narrow tube |
mm(in.) |
|
9,52 (3/8) |
|
|
tube diameter |
Wide tube |
mm(in.) |
|
15,88 (5/8) |
|
|
Refrigerant |
|
|
|
R410A |
|
|
Refrigerant control |
|
|
Electronic expansion valve |
||
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
|
|
Dimensions |
Height |
mm |
|
266 |
|
|
|
Width |
mm |
|
571 |
|
|
|
Depth |
mm |
|
1058 |
|
|
Package dimensions |
Height |
mm |
|
365 |
|
|
|
Width |
mm |
|
745 |
|
|
|
Depth |
mm |
|
1292 |
|
|
|
Volume |
m3 |
|
0,35 |
|
|
Weight |
Net |
kg |
|
35 |
|
|
|
Shipping |
kg |
|
39 |
DATA SUBJECT TO CHANGE WITHOUT NOTICE
6
1-2 Major Component Specifications
SPW-XMR74/94/124EXH56
Controller PCB
|
Part No. |
|
|
|
CR-CRP50A-B |
|
Controls |
|
|
|
Microprocessor |
|
|
|
|
|
|
Fan & Fan Motor |
|
|
|
|
|
|
Type |
|
|
|
Centrifugal fan |
|
Q'ty ……. Dia. and lenght |
|
|
mm |
2…. Ø 160 / L 240 |
|
Fan motor model…Q'ty |
|
|
|
3RGB-CO-45-30 5V/1….1 |
|
No. Of poles…rpm (230 V, High) |
|
4 … 1060 |
||
|
Running Amps |
|
|
A |
0,45 |
|
Power input |
|
|
W |
110 |
|
Coil resistance (Ambient temp. 20 °C ) |
Ω |
BLU-BRN: 95 |
||
|
|
|
|
|
BRN-BLK: 37 |
|
|
|
|
|
BLK-GRY: 15 |
|
|
|
|
|
GRY-VLT: 15 |
|
|
|
|
|
WLT-RED: 30 |
|
|
|
|
|
RED-YEL: 101 |
|
Safety devices |
Type |
|
Internal thermal protector - 7AM 037 A 5 |
|
|
|
Operating temp. Open |
°C |
150 ± 5K |
|
|
|
|
|
|
|
|
Run capacitor |
|
|
µF |
1,8 |
|
|
|
|
VAC |
450 |
|
|
|
|
|
|
|
|
|
|
|
|
Electronic expansion valve |
|
|
|
|
|
|
Coil |
|
|
|
UKV-U030E |
|
Valve body |
|
|
|
UKV-18D31 |
|
|
|
|
|
|
Heat Exch. Coil |
|
|
|
|
|
|
Coil |
|
|
|
Aluminium plate fin / Copper tube |
|
Rows |
|
|
|
2 |
|
Fin pitch |
|
|
mm |
1,6 |
|
face area |
|
|
m2 |
0,126 |
DATA SUBJECT TO CHANGE WITHOUT NOTICE
7
SPW-XMR164/184EXH56
Controller PCB
|
Part No. |
|
|
|
CR-CRP50A-B |
|
Controls |
|
|
|
Microprocessor |
|
|
|
|
|
|
Fan & Fan Motor |
|
|
|
|
|
|
Type |
|
|
|
Centrifugal fan |
|
Q'ty ……. Dia. and lenght |
|
|
mm |
2…. Ø 160 / L 240 |
|
Fan motor model…Q'ty |
|
|
|
3FGB-CO-65-38 5V/1….1 |
|
No. Of poles…rpm (230 V, High) |
|
4 … 1106 |
||
|
Running Amps |
|
|
A |
0,6 |
|
Power input |
|
|
W |
138 |
|
Coil resistance (Ambient temp. 20 °C ) |
Ω |
BLU-BRN: 68 |
||
|
|
|
|
|
BRN-BLK: 9 |
|
|
|
|
|
BLK-GRY: 36 |
|
|
|
|
|
GRY-VLT: 18 |
|
|
|
|
|
VLT-RED: 18 |
|
|
|
|
|
BRN-YEL: 105 |
|
Safety devices |
Type |
|
Internal thermal protector - 7AM 037 A 5 |
|
|
|
Operating temp. Open |
°C |
150 ± 5K |
|
|
|
|
Close |
°C |
|
|
Run capacitor |
|
|
µF |
2,0 |
|
|
|
|
VAC |
450 |
|
|
|
|
|
|
|
|
|
|
|
|
Electronic expansion valve |
|
|
|
|
|
|
Coil |
|
|
|
UKV-U030E |
|
Valve body |
|
|
|
UKV-25D32 |
|
|
|
|
|
|
Heat Exch. Coil |
|
|
|
|
|
|
Coil |
|
|
|
Aluminium plate fin / Copper tube |
|
Rows |
|
|
|
3 |
|
Fin pitch |
|
|
mm |
1,6 |
|
face area |
|
|
m2 |
0,168 |
DATA SUBJECT TO CHANGE WITHOUT NOTICE
8
SPW-XMR224EXH56
Controller PCB
|
Part No. |
|
|
|
CR-CRP50A-B |
|
Controls |
|
|
|
Microprocessor |
|
|
|
|
|
|
Fan & Fan Motor |
|
|
|
|
|
|
Type |
|
|
|
Centrifugal fan |
|
Q'ty ……. Dia. and lenght |
|
|
mm |
2…. Ø 160 / L 240 |
|
Fan motor model…Q'ty |
|
|
|
3FGB-CO-65-38 5V/1….1 |
|
No. Of poles…rpm (230 V, High) |
|
4 … 1161 |
||
|
Running Amps |
|
|
A |
0,57 |
|
Power input |
|
|
W |
136 |
|
Coil resistance (Ambient temp. 20 °C ) |
Ω |
BLU-BRN: 68 |
||
|
|
|
|
|
BRN-BLK: 9 |
|
|
|
|
|
BLK-GRY: 36 |
|
|
|
|
|
GRY-VLT: 18 |
|
|
|
|
|
VLT-RED: 18 |
|
|
|
|
|
BRN-YEL: 105 |
|
Safety devices |
Type |
|
Internal thermal protector - 7AM 037 A 5 |
|
|
|
Operating temp. Open |
°C |
150 ± 5K |
|
|
|
|
Close |
°C |
|
|
Run capacitor |
|
|
µF |
3 |
|
|
|
|
VAC |
450 |
|
|
|
|
|
|
|
|
|
|
|
|
Electronic expansion valve |
|
|
|
|
|
|
Coil |
|
|
|
UKV-U030E |
|
Valve body |
|
|
|
UKV-25D32 |
|
|
|
|
|
|
Heat Exch. Coil |
|
|
|
|
|
|
Coil |
|
|
|
Aluminium plate fin / Copper tube |
|
Rows |
|
|
|
3 |
|
Fin pitch |
|
|
mm |
1,6 |
|
face area |
|
|
m2 |
0,168 |
DATA SUBJECT TO CHANGE WITHOUT NOTICE
9
1-3 Other Component Specifications
Trasformer |
|
ATR-IIJ225A |
|
|
Rating |
Primary |
VAC 230V, 50Hz |
|
|
Secondary 1 |
AC 20V - 0.2A |
|
|
Secondary 2 |
AC 14V - 0.3A |
|
|
Secondary 3 |
AC 10,2V - 1.4A |
|
|
|
|
|
Thermal cut-off temp. |
|
136°C |
Thermistor ( Coil sensor E1, E2) |
|
|
PBC-41E-S26 |
|
|
Resistance |
|
kΩ |
0 °C 15,0 ± 5% |
|
|
|
|
|
Thermistor ( Coil sensor E3) |
|
|
PBC-41E-S42-2 |
|
|
Resistance |
|
kΩ |
0 °C 15,0 ± 4,42% |
|
|
|
||
Thermistor ( Room sensor TA, TF/BL) |
|
DHKTEC-35-S85N |
||
|
Resistance |
|
kΩ |
25 °C 5,0 ± 4% |
|
|
|
|
|
Drain pump |
|
|
|
|
|
Model |
|
|
PC 309564003 |
|
Rating |
Voltage |
|
220/240V - 50Hz |
|
|
Input |
|
14W |
|
Flow rate |
|
|
0,4 l/min |
|
|
|
|
|
Safety float switch |
|
|
|
|
|
Model |
|
|
BI 1300 2725 |
|
|
|
|
|
|
Contact rating |
|
|
230V AC/DC - 0,5A |
10
2. DIMENSIONAL DATA
SPW-UMR74/94/124EXH56
11
SPW-UMR164/184/224EXH56
12