Sanyo SPW-UMR94EXH56, SPW-UMR74EXH56, SPW-UMR184EXH56, SPW-UMR224EXH56, SPW-UMR124EXH56 User Manual 2

...
0 (0)

TECHNICAL DATA & SERVICE MANUAL

SPLIT SYSTEM AIR CONDITIONER

Model No.

Product Code No.

SPW-UMR74EXH56

854.0.2263

SPW-UMR94EXH56

854.0.2264

SPW-UMR124EXH56

854.0.2265

SPW-UMR164EXH56

854.0.2301

SPW-UMR184EXH56

854.0.2266

SPW-UMR224EXH56

854.0.2267

 

 

 

 

 

 

 

 

SM940046

0.8180.439.0 June 2005

IMPORTANT!

Please read before installation

This air conditioning system meets strict safety and operating standards.

For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

Observe all local, state and national electrical codes.

Pay close attention to all warning and caution notices given in this manual.

•The unit must be supplied with a dedicated electrical line.

WARNING

This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.

CAUTION

This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and maintenance conditions.

If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

SPECIAL PRECAUTIONS

During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.

WARNING

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.

Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.

Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring.

Improper connections and inadequate grounding can cause accidental injury and death.

Ground the unit following local electrical codes.

The Yellow/Green wire cannot be used for any connection different from the ground connection.

Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.

Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.

When installing...

… In a ceiling

Make sure the ceiling is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.

… In a room

Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher then drifting snow. Provide snow vents.

When connecting refrigerant tubing

Keep all tubing runs as short as possible.

Use the flare method for connecting tubing.

Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.

Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.

When servicing

Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.

Keep your fingers and clothing away from any moving parts.

Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.

Ventilate the room during the installation or testing the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.

2

Table of Contents

 

Page

1. SPECIFICATIONS

4

1-1 Unit specifications

4

1-2 Major Component specifications

7

1-3 Other Component specifications

10

2. DIMENSIONAL DATA

11

3. ELECTRICAL DATA

13

3-1 Electric Wiring Diagram

13

3-2 Control PCB switches and functions

14

4. FUNCTION

15

4-1 Room Temperature Control

15

4-2 Automatic control for heating and cooling

16

5. REPLACING PCB

17

5-1 Replacing PCB

17

5-2 How to replace PCB

18

5-3 How to replace EEPROM with EEPROM included in PCB service pack

19

5-4 Table of setting

21

6. SERVICING AND MAINTENANCE FUNCTIONS

22

6-1 Indoor unit refrigerant noise countermeasures

22

6-2 Outdoor unit noise countermeasures: EEPROM 05

22

7. TROUBLE DIAGNOSIS

23

7-1 Contents of remote controller switch alarm display

23

7-2 Outdoor unit control panel led display

25

7-3 Trouble indications and inspection points

26

7-4 Remote controller servicing functions

28

7-5 Super W-Multi alarm codes

29

7-6 Inspection of parts

35

3

1. SPECIFICATIONS

1-1 Unit Specifications

SPW-UMR74/94/124EXH56

Power source

 

 

 

220 - 240V ~ 50Hz

 

 

 

 

 

Voltage rating

 

 

 

230V

 

 

 

 

 

 

Performance

 

 

Cooling

 

Heating

 

Capacity

 

 

See catalogue with

the requested matching

 

Air circulation (High/Med./Low)

 

m³/h

 

600/510/440

 

 

 

 

 

 

Features

 

 

 

 

 

 

Controls/Temperature controls

 

 

Microprocessor/ I.C. thermostat

 

Remote Controller (Option)

 

wired

RCS-SH80AG / RCS-KR1AG

 

 

 

wireless

 

RCS-BH80AG.WL

 

Fan speed

 

 

 

3 and Auto

 

 

 

 

 

 

 

 

Air Filter

 

 

 

Washable

 

Sound pressure level (*)

high/med/low

dB(A)

 

54/52/49

 

Refrigerant tubing connections

 

 

 

Flare type

 

Refrigerant

Narrow tube

mm(in.)

 

6,35 (1/4)

 

tube diameter

Wide tube

mm(in.)

 

12,7 (1/2)

 

Refrigerant

 

 

 

R410A

 

Refrigerant control

 

 

Electronic expansion valve

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

 

Dimensions

Height

mm

 

266

 

 

Width

mm

 

571

 

 

Depth

mm

 

852

 

Package dimensions

Height

mm

 

365

 

 

Width

mm

 

745

 

 

Depth

mm

 

1086

 

 

Volume

m3

 

0,3

 

Weight

Net

kg

 

30,0

 

 

Shipping

kg

 

34

DATA SUBJECT TO CHANGE WITHOUT NOTICE

(*) Power noise level measured at operating conditions (5mmH20 external static pressure)

4

SPW-UMR164/184EXH56

Power source

 

 

 

220 - 240V ~ 50Hz

 

 

 

 

 

Voltage rating

 

 

 

230V

 

 

 

 

 

 

Performance

 

 

Cooling

 

Heating

 

Capacity

 

 

See catalogue with

the requested matching

 

Air circulation (High/Med./Low)

 

m³/h

 

875/600/400

 

 

 

 

 

 

Features

 

 

 

 

 

 

Controls/Temperature controls

 

 

Microprocessor/ I.C. thermostat

 

Remote Controller (Option)

 

wired

RCS-SH80AG / RCS-KR1AG

 

 

 

wireless

 

RCS-BH80AG.WL

 

Fan speed

 

 

 

3 and Auto

 

 

 

 

 

 

 

 

Air Filter

 

 

 

Washable

 

Sound pressure level (*)

high/med/low

dB(A)

 

54/47/42

 

Refrigerant tubing connections

 

 

 

Flare type

 

Refrigerant

Narrow tube

mm(in.)

 

6,35 (1/4)

 

tube diameter

Wide tube

mm(in.)

 

12,7 (1/2)

 

Refrigerant

 

 

 

R410A

 

Refrigerant control

 

 

Electronic expansion valve

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

 

Dimensions

Height

mm

 

266

 

 

Width

mm

 

571

 

 

Depth

mm

 

1058

 

Package dimensions

Height

mm

 

365

 

 

Width

mm

 

745

 

 

Depth

mm

 

1292

 

 

Volume

m3

 

0,35

 

Weight

Net

kg

 

35

 

 

Shipping

kg

 

39

DATA SUBJECT TO CHANGE WITHOUT NOTICE

5

SPW-UMR224EXH56

Power source

 

 

 

220 - 240V ~ 50Hz

 

 

 

 

 

Voltage rating

 

 

 

230V

 

 

 

 

 

 

Performance

 

 

Cooling

 

Heating

 

Capacity

 

 

See catalogue with

the requested matching

 

Air circulation (High/Med./Low)

 

m³/h

 

1000/700/600

 

 

 

 

 

 

Features

 

 

 

 

 

 

Controls/Temperature controls

 

 

Microprocessor/ I.C. thermostat

 

Remote Controller (Option)

 

wired

RCS-SH80AG / RCS-KR1AG

 

 

 

wireless

 

RCS-BH80AG.WL

 

Fan speed

 

 

 

3 and Auto

 

 

 

 

 

 

 

 

Air Filter

 

 

 

Washable

 

Sound pressure level (*)

high/med/low

dB(A)

 

57/49/46

 

Refrigerant tubing connections

 

 

 

Flare type

 

Refrigerant

Narrow tube

mm(in.)

 

9,52 (3/8)

 

tube diameter

Wide tube

mm(in.)

 

15,88 (5/8)

 

Refrigerant

 

 

 

R410A

 

Refrigerant control

 

 

Electronic expansion valve

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

 

Dimensions

Height

mm

 

266

 

 

Width

mm

 

571

 

 

Depth

mm

 

1058

 

Package dimensions

Height

mm

 

365

 

 

Width

mm

 

745

 

 

Depth

mm

 

1292

 

 

Volume

m3

 

0,35

 

Weight

Net

kg

 

35

 

 

Shipping

kg

 

39

DATA SUBJECT TO CHANGE WITHOUT NOTICE

6

1-2 Major Component Specifications

SPW-XMR74/94/124EXH56

Controller PCB

 

Part No.

 

 

 

CR-CRP50A-B

 

Controls

 

 

 

Microprocessor

 

 

 

 

 

 

Fan & Fan Motor

 

 

 

 

 

Type

 

 

 

Centrifugal fan

 

Q'ty ……. Dia. and lenght

 

 

mm

2…. Ø 160 / L 240

 

Fan motor model…Q'ty

 

 

 

3RGB-CO-45-30 5V/1….1

 

No. Of poles…rpm (230 V, High)

 

4 … 1060

 

Running Amps

 

 

A

0,45

 

Power input

 

 

W

110

 

Coil resistance (Ambient temp. 20 °C )

BLU-BRN: 95

 

 

 

 

 

BRN-BLK: 37

 

 

 

 

 

BLK-GRY: 15

 

 

 

 

 

GRY-VLT: 15

 

 

 

 

 

WLT-RED: 30

 

 

 

 

 

RED-YEL: 101

 

Safety devices

Type

 

Internal thermal protector - 7AM 037 A 5

 

 

Operating temp. Open

°C

150 ± 5K

 

 

 

 

 

 

 

Run capacitor

 

 

µF

1,8

 

 

 

 

VAC

450

 

 

 

 

 

 

 

 

 

 

 

Electronic expansion valve

 

 

 

 

 

Coil

 

 

 

UKV-U030E

 

Valve body

 

 

 

UKV-18D31

 

 

 

 

 

Heat Exch. Coil

 

 

 

 

 

Coil

 

 

 

Aluminium plate fin / Copper tube

 

Rows

 

 

 

2

 

Fin pitch

 

 

mm

1,6

 

face area

 

 

m2

0,126

DATA SUBJECT TO CHANGE WITHOUT NOTICE

7

SPW-XMR164/184EXH56

Controller PCB

 

Part No.

 

 

 

CR-CRP50A-B

 

Controls

 

 

 

Microprocessor

 

 

 

 

 

 

Fan & Fan Motor

 

 

 

 

 

Type

 

 

 

Centrifugal fan

 

Q'ty ……. Dia. and lenght

 

 

mm

2…. Ø 160 / L 240

 

Fan motor model…Q'ty

 

 

 

3FGB-CO-65-38 5V/1….1

 

No. Of poles…rpm (230 V, High)

 

4 … 1106

 

Running Amps

 

 

A

0,6

 

Power input

 

 

W

138

 

Coil resistance (Ambient temp. 20 °C )

BLU-BRN: 68

 

 

 

 

 

BRN-BLK: 9

 

 

 

 

 

BLK-GRY: 36

 

 

 

 

 

GRY-VLT: 18

 

 

 

 

 

VLT-RED: 18

 

 

 

 

 

BRN-YEL: 105

 

Safety devices

Type

 

Internal thermal protector - 7AM 037 A 5

 

 

Operating temp. Open

°C

150 ± 5K

 

 

 

Close

°C

 

 

Run capacitor

 

 

µF

2,0

 

 

 

 

VAC

450

 

 

 

 

 

 

 

 

 

 

 

Electronic expansion valve

 

 

 

 

 

Coil

 

 

 

UKV-U030E

 

Valve body

 

 

 

UKV-25D32

 

 

 

 

 

Heat Exch. Coil

 

 

 

 

 

Coil

 

 

 

Aluminium plate fin / Copper tube

 

Rows

 

 

 

3

 

Fin pitch

 

 

mm

1,6

 

face area

 

 

m2

0,168

DATA SUBJECT TO CHANGE WITHOUT NOTICE

8

SPW-XMR224EXH56

Controller PCB

 

Part No.

 

 

 

CR-CRP50A-B

 

Controls

 

 

 

Microprocessor

 

 

 

 

 

 

Fan & Fan Motor

 

 

 

 

 

Type

 

 

 

Centrifugal fan

 

Q'ty ……. Dia. and lenght

 

 

mm

2…. Ø 160 / L 240

 

Fan motor model…Q'ty

 

 

 

3FGB-CO-65-38 5V/1….1

 

No. Of poles…rpm (230 V, High)

 

4 … 1161

 

Running Amps

 

 

A

0,57

 

Power input

 

 

W

136

 

Coil resistance (Ambient temp. 20 °C )

BLU-BRN: 68

 

 

 

 

 

BRN-BLK: 9

 

 

 

 

 

BLK-GRY: 36

 

 

 

 

 

GRY-VLT: 18

 

 

 

 

 

VLT-RED: 18

 

 

 

 

 

BRN-YEL: 105

 

Safety devices

Type

 

Internal thermal protector - 7AM 037 A 5

 

 

Operating temp. Open

°C

150 ± 5K

 

 

 

Close

°C

 

 

Run capacitor

 

 

µF

3

 

 

 

 

VAC

450

 

 

 

 

 

 

 

 

 

 

 

Electronic expansion valve

 

 

 

 

 

Coil

 

 

 

UKV-U030E

 

Valve body

 

 

 

UKV-25D32

 

 

 

 

 

Heat Exch. Coil

 

 

 

 

 

Coil

 

 

 

Aluminium plate fin / Copper tube

 

Rows

 

 

 

3

 

Fin pitch

 

 

mm

1,6

 

face area

 

 

m2

0,168

DATA SUBJECT TO CHANGE WITHOUT NOTICE

9

1-3 Other Component Specifications

Trasformer

 

ATR-IIJ225A

 

Rating

Primary

VAC 230V, 50Hz

 

 

Secondary 1

AC 20V - 0.2A

 

 

Secondary 2

AC 14V - 0.3A

 

 

Secondary 3

AC 10,2V - 1.4A

 

 

 

 

 

Thermal cut-off temp.

 

136°C

Thermistor ( Coil sensor E1, E2)

 

 

PBC-41E-S26

 

Resistance

 

kΩ

0 °C 15,0 ± 5%

 

 

 

 

Thermistor ( Coil sensor E3)

 

 

PBC-41E-S42-2

 

Resistance

 

kΩ

0 °C 15,0 ± 4,42%

 

 

 

Thermistor ( Room sensor TA, TF/BL)

 

DHKTEC-35-S85N

 

Resistance

 

kΩ

25 °C 5,0 ± 4%

 

 

 

 

Drain pump

 

 

 

 

Model

 

 

PC 309564003

 

Rating

Voltage

 

220/240V - 50Hz

 

 

Input

 

14W

 

Flow rate

 

 

0,4 l/min

 

 

 

 

Safety float switch

 

 

 

 

Model

 

 

BI 1300 2725

 

 

 

 

 

 

Contact rating

 

 

230V AC/DC - 0,5A

10

2. DIMENSIONAL DATA

SPW-UMR74/94/124EXH56

11

Sanyo SPW-UMR94EXH56, SPW-UMR74EXH56, SPW-UMR184EXH56, SPW-UMR224EXH56, SPW-UMR124EXH56 User Manual 2

SPW-UMR164/184/224EXH56

12

Loading...