Sanyo C2472, CL2472, ks2472, CL1872, C1872 User Manual

4 (1)

TECHNICAL & SERVICE MANUAL

KS1872 + C1872 + CL1872

KS2472 + C2472 + CL2472

FILE NO.

Destination: North America

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

Indoor Model No.

Product Code No.

 

 

KS1872

1 852 099 83

 

 

KS2472

1 852 099 84

Outdoor Model No.

Product Code No.

 

 

C1872

1 852 330 36

 

 

C2472

1 852 330 37

CL1872

1 852 330 40

CL2472

1 852 330 41

Indoor Unit

 

Outdoor Unit

 

 

 

KS1872

C1872

KS2472

CL1872

IMPORTANT

These air conditioners employ new refrigerant R410A.

Pay special attention when servicing the unit.

C2472

CL2472

REFERENCE NO. SM700663

Important!

Please Read Before Starting

This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

Observe all local, state, and national electrical codes.

Pay close attention to all warning and caution notices given in this manual.

This symbol refers to a hazard

WARNING or unsafe practice which can result in severe personal

injury or death.

This symbol refers to a hazard

or unsafe practice which can

CAUTION

result in personal injury or product or property damage.

If Necessary, Get Help

These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

SPECIAL PRECAUTIONS

WARNING When Wiring

ELECTRICAL SHOCK CAN CAUSE

SEVERE PERSONAL INJURY OR DEATH.

ONLY A QUALIFIED, EXPERIENCED

ELECTRICIAN SHOULD ATTEMPT TO

WIRE THIS SYSTEM.

Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.

Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.

Ground the unit following local electrical codes.

Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.

When Transporting

Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.

When Installing

In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.

In a Room

Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors.

In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.

In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.

In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing

Use the flare method for connecting tubing.

Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.

Check carefully for leaks before starting the test run.

When Servicing

Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.

Keep your fingers and clothing away from any moving parts.

Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.

Others

CAUTION

Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.

Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.

2

Table of Contents

 

 

 

Page

1.

OPERATING RANGE ...................................................................................................................

5

2.

SPECIFICATIONS

 

 

2-1.

Unit Specifications .............................................................................................................

6

 

2-2.

Major Component Specifications .......................................................................................

14

 

2-3.

Other Component Specifications .......................................................................................

20

3. DIMENSIONAL DATA .....................................................................................................................

21

4. REFRIGERANT FLOW DIAGRAM

 

 

4-1.

Refrigerant Flow Diagram ...................................................................................................

24

5. PERFORMANCE DATA

 

 

5-1.

Temperature Charts ............................................................................................................

25

 

5-2.

Air Throw Distance Charts .................................................................................................

29

6. ELECTRICAL DATA

 

 

6-1.

Electrical Characteristics ....................................................................................................

31

 

6-2.

Electric Wiring Diagrams ....................................................................................................

33

7. INSTALLATION INSTRUCTIONS

 

 

7-1.

Installation Site Selection ...................................................................................................

37

 

7-2. Recommended Wire Length and Diameter ........................................................................

39

 

7-3. Remote Control Unit Installation Position ...........................................................................

40

 

7-4. How to Test Run the Air Conditioner ...................................................................................

41

 

7-5. Remove the Grille to Install the Indoor Unit ........................................................................

42

8. MAINTENANCE

 

 

8-1. Address Setting of the Remote Control Unit .......................................................................

43

 

8-2. Disconnecting and Connecting Positive Connector for Outdoor Unit ..................................

44

9. FUNCTIONS

 

 

9-1.

Operation Functions ...........................................................................................................

45

 

9-2.

Protective Functions ...........................................................................................................

47

3

 

 

Page

10. TROUBLESHOOTING

 

10-1. Precautions before Performing Inspection or Repair ...........................................................

48

10-2.

Method of Self-Diagnostics .................................................................................................

48

10-3. Checking the Indoor and Outdoor Units ..............................................................................

51

10-4. Trouble Diagnosis of Fan Motor ..........................................................................................

52

10-5.

Noise Malfunction and Electromagnetic Interference ..........................................................

54

11. CHECKING ELECTRICAL COMPONENTS

 

11-1.

Measurement of Insulation Resistance ...............................................................................

55

11-2.

Checking Continuity of Fuse on PCB Ass'y .........................................................................

56

12.REFRIGERANT R410A:

SPECIAL PRECAUTIONS WHEN SERVICING UNIT

12-1. Characteristics of New Refrigerant R410A .........................................................................

57

12-2.

Checklist before Servicing ...................................................................................................

58

12-3. Tools Specifically for R410A ................................................................................................

59

12-4.

Tubing Installation Procedures ............................................................................................

59

12-5. In Case of Compressor Malfunction ....................................................................................

60

12-6. In Case Refrigerant is Leaking ............................................................................................

62

12-7.

Charging Additional Refrigerant ..........................................................................................

63

12-8.

Retro-Fitting Existing Systems ............................................................................................

63

 

 

 

APPENDIX

INSTRUCTION MANUAL ............................................................................................

64

4

1. OPERATING RANGE

Models : KS1872 + C1872

 

 

KS2472 + C2472

 

 

 

 

 

 

 

Temperature

Indoor Air Intake Temp.

Outdoor Air Intake Temp.

 

 

 

 

Cooling

Maximum

95 °F D.B. / 71 °F W.B.

115 °F D.B.

 

 

 

Minimum

67 °F D.B. / 57 °F W.B.

67 °F D.B.

 

 

 

 

 

Models : KS1872 + CL1872

 

 

KS2472 + CL2472

 

 

 

 

 

 

 

Temperature

Indoor Air Intake Temp.

Outdoor Air Intake Temp.

 

 

 

 

Cooling

Maximum

95 °F D.B. / 71 °F W.B.

115 °F D.B.

 

 

 

Minimum

67 °F D.B. / 57 °F W.B.

0 °F D.B.

 

 

 

 

 

5

2. SPECIFICATIONS

2-1. Unit Specifications

Indoor Unit

KS1872

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

C1872

 

 

 

 

 

 

 

 

 

< 230V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

230V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

17,600

( 4,100 to 17,700 )

 

 

 

 

 

 

kW

 

 

5.15

( 1.2 to 5.2 )

 

 

 

 

 

 

 

 

 

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

524 (890)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

7.0 ( 1.2 to 7.0 )

 

 

Power Input

 

 

 

 

W

 

 

1,500 ( 250 to 1,500 )

 

 

Power Factor

 

 

 

%

 

 

 

93

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi,Me,Lo)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Twin Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 2.87 (1.3)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

42 / 38 / 30 / 28

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

51

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

25 (7.5)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

1/2 (12.7)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

26-3/8

(670)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

34-21/32

(880)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

11-7/32

(285)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

29-1/8 (740)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

39-27/32

(1,012)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

14-31/32

(380)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

90.4

(41.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

99.2

(45.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

9.89

(0.28)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

6

Indoor Unit

KS1872

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

C1872

 

 

 

 

 

 

 

 

 

< 208V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

208V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

17,600

( 4,100 to 17,700 )

 

 

 

 

 

 

kW

 

 

5.15

( 1.2 to 5.2 )

 

 

 

 

 

 

 

 

 

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

524 (890)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

7.7 ( 1.2 to 7.7 )

 

 

Power Input

 

 

 

 

W

 

 

1,500 ( 250 to 1,500 )

 

 

Power Factor

 

 

 

%

 

 

 

94

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi,Me,Lo)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 2.87 (1.3)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

42 / 38 / 30 / 28

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

51

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

25 (7.5)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

1/2 (12.7)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

26-3/8

(670)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

34-21/32

(880)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

11-7/32

(285)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

29-1/8 (740)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

39-27/32

(1,012)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

14-31/32

(380)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

90.4

(41.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

99.2

(45.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

9.89

(0.28)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

7

Indoor Unit

KS2472

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

C2472

 

 

 

 

 

 

 

 

 

< 230V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

230V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

24,200

( 4,100 to 24,200 )

 

 

 

 

 

 

kW

 

 

7.1

( 1.2 to 7.1 )

 

 

 

 

 

 

 

 

 

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

600 (1,020)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

10.8 ( 1.3 to 10.8 )

 

 

Power Input

 

 

 

 

W

 

 

2,355 ( 280 to 2,355 )

 

 

Power Factor

 

 

 

%

 

 

 

95

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi,Me,Lo)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Twin Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 4.30 (1.95)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

47 / 44 / 41 / 30

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

55

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

33 (10)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

5/8 (15.88)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

29-1/8

(740)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

35-7/16

(900)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

12-19/32

(320)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

33-27/32 (860)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

40-5/8

(1,032)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

16-1/4

(413)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

119.0

(54.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

127.9

(58.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

12.71

(0.36)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

8

Indoor Unit

KS2472

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

C2472

 

 

 

 

 

 

 

 

 

< 208V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

208V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

24,200

( 4,100 to 24,200 )

 

 

 

 

 

 

kW

 

 

7.1

( 1.2 to 7.1 )

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

600 (1,020)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

12.1 ( 1.3 to 12.1 )

 

 

Power Input

 

 

 

 

W

 

 

2,355 ( 280 to 2,350 )

 

 

Power Factor

 

 

 

%

 

 

 

94

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi,Me,Lo)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Twin Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 4.30 (1.95)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

47 / 44 / 41 / 30

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

55

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

33 (10)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

5/8 (15.88)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

29-1/8

(740)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

35-7/16

(900)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

12-19/32

(320)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

33-27/32 (860)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

40-5/8

(1,032)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

16-1/4

(413)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

119.0

(54.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

127.9

(58.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

12.71

(0.36)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

9

Indoor Unit

KS1872

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

CL1872

 

 

 

 

 

 

 

 

 

< 230V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

230V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

17,600

( 4,100 to 17,700 )

 

 

 

 

 

 

kW

 

 

5.15

( 1.2 to 5.2 )

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

524 (890)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

7.0 ( 1.2 to 7.0 )

 

 

Power Input

 

 

 

 

W

 

 

1,500 ( 250 to 1,500 )

 

 

Power Factor

 

 

 

%

 

 

 

93

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi and multi steps)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Twin Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 2.87 (1.3)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

42 / 38 / 30 / 28

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

51

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

33 (10)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

1/2 (12.7)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

26-3/8

(670)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

34-21/32

(880)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

11-7/32

(285)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

29-1/8 (740)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

39-27/32

(1,012)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

14-31/32

(380)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

90.4

(41.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

99.2

(45.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

9.89

(0.28)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

10

Indoor Unit

KS1872

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

CL1872

 

 

 

 

 

 

 

 

 

< 208V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

208V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

17,600

( 4,100 to 17,700 )

 

 

 

 

 

 

kW

 

 

5.15

( 1.2 to 5.2 )

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

524 (890)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

7.7 ( 1.2 to 7.7 )

 

 

Power Input

 

 

 

 

W

 

 

1,500 ( 250 to 1,500 )

 

 

Power Factor

 

 

 

%

 

 

 

94

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi and multi steps)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Twin Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 2.87 (1.3)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

42 / 38 / 30 / 28

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

51

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

33 (10)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

1/2 (12.7)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

26-3/8

(670)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

34-21/32

(880)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

11-7/32

(285)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

29-1/8 (740)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

39-27/32

(1,012)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

14-31/32

(380)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

90.4

(41.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

99.2

(45.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

9.89

(0.28)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

11

Indoor Unit

KS2472

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

CL2472

 

 

 

 

 

 

 

 

 

< 230V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

230V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

24,200

( 4,100 to 24,200 )

 

 

 

 

 

 

kW

 

 

7.1

( 1.2 to 7.1 )

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

600 (1,020)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

10.8 ( 1.3 to 10.8 )

 

 

Power Input

 

 

 

 

W

 

 

2,355 ( 280 to 2,355 )

 

 

Power Factor

 

 

 

%

 

 

 

95

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi and multi steps)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Twin Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 4.30 (1.95)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

47 / 44 / 41 / 30

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

55

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

33 (10)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

5/8 (15.88)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

29-1/8

(740)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

35-7/16

(900)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

12-19/32

(320)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

33-27/32 (860)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

40-5/8

(1,032)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

16-1/4

(413)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

119.0

(54.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

127.9

(58.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

12.71

(0.36)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

12

Indoor Unit

KS2472

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

CL2472

 

 

 

 

 

 

 

 

 

< 208V >

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

208V Single-Phase 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

BTU/h

 

 

24,200

( 4,100 to 24,200 )

 

 

 

 

 

 

kW

 

 

7.1

( 1.2 to 7.1 )

 

 

Air Circulation (High)

 

ft3/min (m3/h)

 

 

600 (1,020)

 

 

Moisture Removal (High)

 

 

Pints/h

 

 

 

4.89

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Available Voltage Range

 

 

V

 

 

187 to 253

 

 

Running Amperes

 

 

 

A

 

 

12.1 ( 1.3 to 12.1 )

 

 

Power Input

 

 

 

 

W

 

 

2,355 ( 280 to 2,355 )

 

 

Power Factor

 

 

 

%

 

 

 

94

 

 

SEER

 

 

 

 

BTU/W

 

 

 

16

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

 

17.5

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls / Temperature Control

 

 

 

 

 

Microprocessor / I.C. Thermister

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi and multi steps)

 

Airflow Direction (Indoor)

 

 

Horizontal

 

 

 

Manual

 

 

 

 

 

 

 

Vertical

 

 

 

Auto

 

 

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

 

 

Compressor

 

 

 

 

 

 

DC Twin Rotary (Inverter)

 

 

Refrigerant / Amount charged at shipment

lb. (kg)

 

 

R410A / 4.30 (1.95)

 

 

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

Operation Sound

Indoor : Hi/Me/Lo/Qt*

dB-A

 

 

47 / 44 / 41 / 30

 

 

(*Qt = Quiet mode)

Outdoor : Hi

 

 

dB-A

 

 

 

55

 

 

Refrigerant Tubing Connections

 

 

 

 

 

Flare Type

 

 

Max. allowable tubing length at shipment

ft. (m)

 

 

 

33 (10)

 

 

Refrigerant

 

Narrow tube

 

 

inch (mm)

 

 

1/4 (6.35)

 

 

Tube Diameter

Wide tube

 

 

inch (mm)

 

 

5/8 (15.88)

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

 

Optional / Air Clean Filter

 

 

 

 

 

 

 

 

 

 

Dimensions & Weight

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Height

 

 

inch (mm)

 

11-23/32

(298)

 

29-1/8

(740)

 

 

 

Width

 

 

inch (mm)

 

41-15/16

(1,065)

 

35-7/16

(900)

 

 

 

Depth

 

 

inch (mm)

 

8-19/32

(218)

 

12-19/32

(320)

 

Package Dimensions

Height

 

 

inch (mm)

 

11-3/8 (289)

 

33-27/32 (860)

 

 

 

Width

 

 

inch (mm)

 

44-7/8

(1,140)

 

40-5/8

(1,032)

 

 

 

Depth

 

 

inch (mm)

 

14-29/32

(379)

 

16-1/4

(413)

 

Weight

 

Net

 

 

lb. (kg)

 

26.5

(12.0)

 

119.0

(54.0)

 

 

 

Shipping

 

 

lb. (kg)

 

33.1

(15.0)

 

127.9

(58.0)

 

Shipping Volume

 

 

 

cu.ft (m3)

 

4.24

(0.12)

 

12.71

(0.36)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

 

 

 

 

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

 

 

 

 

 

 

 

Outdoor air temperature

95°F D.B. / 75°F W.B.

 

 

 

 

 

13

2-2. Major Component Specifications

2-2-1. Indoor Unit

Indoor Unit

KS1872

 

 

 

 

 

 

 

 

 

Control PCB

 

 

 

 

 

 

 

 

 

 

 

Part No.

 

 

 

CB-KS1872

 

Controls

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

250V 3A

 

 

 

 

 

Remote Control Unit

 

 

RCS-4VPIS4U

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Cross-Flow

 

Q'ty ... Dia. and Length

inch (mm)

1 ... D3-11/16 / L33-9/32 (D94/L845)

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Motor

 

Model ... Q'ty

 

 

SIC-39CVL-D847-2-A ... 1

 

No. of Poles

 

 

8

 

Rough Measure RPM (Cool)

 

 

1,250

 

Nominal Output

 

W

30

 

Coil Resistance

 

Ohm

-

 

(Ambient Temp. 68 oF (20 oC))

 

 

 

 

Safety Device

 

 

 

 

 

Type

 

 

Internal Controller

 

 

Over-Current Protection

 

 

Yes

 

 

Over-Heat Protection

 

 

Yes

 

Run Capacitor

 

Micro F

-

 

 

 

 

VAC

-

 

 

 

 

 

Flap Motor

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Stepping Motor

 

Model

 

 

 

MP24Z3

 

Rating

 

 

 

DC 12V

 

Coil Resistance

 

Ohm

Each Pair of Terminal : 400 +/- 7%

 

(Ambient Temp. 77 oF (25 oC ))

 

 

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

2

 

Fins per inch

 

 

19.5

 

Face Area

 

ft2 (m2)

3.07 (0.285)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

14

Indoor Unit

KS2472

 

 

 

 

 

 

 

 

 

Control PCB

 

 

 

 

 

 

 

 

 

 

 

Part No.

 

 

 

CB-KS2472

 

Controls

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

250V 3A

 

 

 

 

 

Remote Control Unit

 

 

RCS-4VPIS4U

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Cross-Flow

 

Q'ty ... Dia. and Length

inch (mm)

1 ... D3-11/16 / L33-9/32 (D94/L845)

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Motor

 

Model ... Q'ty

 

 

SIC-39CVL-D847-2-A ... 1

 

No. of Poles

 

 

8

 

Rough Measure RPM (Cool)

 

 

1,500

 

Nominal Output

 

W

30

 

Coil Resistance

 

Ohm

-

 

(Ambient Temp. 68 oF (20 oC))

 

 

 

 

Safety Device

 

 

 

 

 

Type

 

 

Internal Controller

 

 

Over-Current Protection

 

 

Yes

 

 

Over-Heat Protection

 

 

Yes

 

Run Capacitor

 

Micro F

-

 

 

 

 

VAC

-

 

 

 

 

 

Flap Motor

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Stepping Motor

 

Model

 

 

 

MP24Z3

 

Rating

 

 

 

DC 12V

 

Coil Resistance

 

Ohm

Each Pair of Terminal : 400 +/- 7%

 

(Ambient Temp. 77 oF (25 oC ))

 

 

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

2

 

Fins per inch

 

 

19.5

 

Face Area

 

ft2 (m2)

3.07 (0.285)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

15

2-2-2. Outdoor Unit

Outdoor Unit C1872

Control PCB

 

 

 

 

 

 

 

 

 

 

 

 

Part No.

 

 

 

CB-C1872

 

Controls

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

 

250V 25A

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Twin Rotary (Hermetic)

 

Compressor Model / Nominal Output

C-6RVN93H0M / 1,050W

 

Compressor Oil ... Amount

 

Pints (cc)

FV50S ... 0.74 (350)

 

Coil Resistance (Ambient Temp. 68 oF (20 oC)) Ohm

R - S : 0.482

 

 

 

 

 

 

S - T : 0.482

 

 

 

 

 

 

T - R : 0.482

 

Safety Device

 

 

 

 

 

 

CT (Peak current cut-off control)

Yes

 

 

Compressor Discharge

Temp. Control

Yes

 

 

Operation cut-off control in abnormal ambient Temp.

Yes

 

 

Overload Relay

 

 

Model

CS-7L115

 

 

 

 

Operation Temp.

Open : 239 oF(115 oC), Close : 203 oF(95 oC)

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

Crankcase Heater

 

 

 

-

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Propeller

 

Q'ty ... Dia.

 

inch (mm)

1 ... D16 -17/32 (D420)

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Motor

 

Model ... Q'ty

 

 

 

DAJ12-55J71A-CU ... 1

 

No. of Poles

 

 

 

8

 

Rough Measure RPM (Cool)

 

 

 

820

 

Nominal Output

 

 

W

50

 

Coil Resistance

 

 

Ohm

RED - WHT : 77.5

 

(Ambient Temp. 68 oF (20 oC))

WHT - BLU : 77.5

 

 

 

 

 

 

BLU - RED : 77.5

 

 

 

 

 

 

 

Safety Device

 

 

 

 

 

 

Type

 

 

 

Internal Controller

 

 

OverCurrent Protection

Yes

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

2

 

Fins per inch

 

 

 

21.2

 

Face Area

 

 

ft2 (m2)

5.49 (0.510)

 

 

 

 

 

 

External Finish

 

 

 

Acrylic baked-on enamel finish

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

16

Outdoor Unit C2472

Control PCB

 

 

 

 

 

 

 

 

 

 

 

 

Part No.

 

 

 

CB-C2472

 

Controls

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

 

250V 25A

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Twin Rotary (Hermetic)

 

Compressor Model / Nominal Output

G8T265FU1JW / 2,410W

 

Compressor Oil ... Amount

 

Pints (cc)

FV50S ... 1.49 (700)

 

Coil Resistance (Ambient Temp. 77 oF (25 oC)) Ohm

U - V : 0.36

 

 

 

 

 

 

V - W : 0.36

 

 

 

 

 

 

W - U : 0.36

 

 

 

 

 

 

 

 

Safety Device

 

 

 

 

 

 

CT (Peak current cut-off control)

Yes

 

 

Compressor Discharge

Temp. Control

Yes

 

 

Operation cut-off control in abnormal ambient Temp.

Yes

 

 

Overload Relay

 

 

Model

CS-7L115

 

 

 

 

Operation Temp.

Open : 239 oF(115 oC), Close : 203 oF(95 oC)

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

Crankcase Heater

 

 

 

-

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Propeller

 

Q'ty ... Dia.

 

inch (mm)

1 ... D18-1/8 (D460)

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Motor

 

Model ... Q'ty

 

 

 

SIC-71FW-D490-1 ... 1

 

No. of Poles

 

 

 

8

 

Rough Measure RPM (Cool)

 

 

 

850

 

Nominal Output

 

 

W

90

 

Coil Resistance

 

 

Ohm

 

 

(Ambient Temp. 68 oF (20 oC))

-

 

 

 

 

 

 

 

Safety Device

 

 

 

 

 

 

Type

 

 

 

Internal Controller

 

 

OverCurrent Protection

Yes

 

 

OverHeat Protection

 

 

 

Yes

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

2

 

Fins per inch

 

 

 

18.1

 

Face Area

 

 

ft2 (m2)

6.40 (0.595)

 

 

 

 

 

 

External Finish

 

 

 

Acrylic baked-on enamel finish

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

17

Outdoor Unit CL1872

Control PCB

 

 

 

 

 

 

 

 

 

 

 

 

Part No.

 

 

 

CB-CL1842

 

Controls

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

 

250V 25A

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Twin Rotary (Hermetic)

 

Compressor Model / Nominal Output

C-6RVN93H0M / 1,050W

 

Compressor Oil ... Amount

 

Pints (cc)

FV50S ... 0.74 (350)

 

Coil Resistance (Ambient Temp. 68 oF (20 oC)) Ohm

R - S : 0.482

 

 

 

 

 

 

S - T : 0.482

 

 

 

 

 

 

T - R : 0.482

 

 

 

 

 

 

 

 

Safety Device

 

 

 

 

 

 

CT (Peak current cut-off control)

Yes

 

 

Compressor Discharge

Temp. Control

Yes

 

 

Operation cut-off control in abnormal ambient Temp.

Yes

 

 

Overload Relay

 

 

Model

CS-7L115

 

 

 

 

Operation Temp.

Open : 239 oF(115 oC), Close : 203 oF(95 oC)

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

Crankcase Heater

 

 

 

-

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Propeller

 

Q'ty ... Dia.

 

inch (mm)

1 ... D16 -17/32 (D420)

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Motor

 

Model ... Q'ty

 

 

 

DAJ12-55J71A-CU ... 1

 

No. of Poles

 

 

 

8

 

Rough Measure RPM (Cool)

 

 

 

820

 

Nominal Output

 

 

W

50

 

Coil Resistance

 

 

Ohm

RED - WHT : 77.5

 

(Ambient Temp. 68 oF (20 oC))

WHT - BLU : 77.5

 

 

 

 

 

 

BLU - RED : 77.5

 

Safety Device

 

 

 

 

 

 

Type

 

 

 

Internal Controller

 

 

OverCurrent Protection

Yes

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

2

 

Fins per inch

 

 

 

21.2

 

Face Area

 

 

ft2 (m2)

5.49 (0.510)

 

 

 

 

 

 

External Finish

 

 

 

Acrylic baked-on enamel finish

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

18

Outdoor Unit CL2472

Control PCB

 

 

 

 

 

 

 

 

 

 

 

 

Part No.

 

 

 

CB-CL2472

 

Controls

 

 

 

Microprocessor

 

Control Circuit Fuse

 

 

 

250V 25A

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Twin Rotary (Hermetic)

 

Compressor Model / Nominal Output

G8T265FU1JW / 2,410W

 

Compressor Oil ... Amount

 

Pints (cc)

FV50S ... 1.49 (700)

 

Coil Resistance (Ambient Temp. 77 oF (25 oC)) Ohm

U - V : 0.36

 

 

 

 

 

 

V - W : 0.36

 

 

 

 

 

 

W - U : 0.36

 

 

 

 

 

 

 

 

Safety Device

 

 

 

 

 

 

CT (Peak current cut-off control)

Yes

 

 

Compressor Discharge

Temp. Control

Yes

 

 

Operation cut-off control in abnormal ambient Temp.

Yes

 

 

Overload Relay

 

 

Model

CS-7L115

 

 

 

 

Operation Temp.

Open : 239 oF(115 oC), Close : 203 oF(95 oC)

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

Crankcase Heater

 

 

 

230V 30W

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

Propeller

 

Q'ty ... Dia.

 

inch (mm)

1 ... D18-1/8 (D460)

 

 

 

 

 

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

DC Motor

 

Model ... Q'ty

 

 

 

SIC-71FW-D490-1 ... 1

 

No. of Poles

 

 

 

8

 

Rough Measure RPM (Cool)

 

 

 

850

 

Nominal Output

 

 

W

90

 

Coil Resistance

 

 

Ohm

 

 

(Ambient Temp. 68 oF (20 oC))

-

 

 

 

 

 

 

 

Safety Device

 

 

 

 

 

 

Type

 

 

 

Internal Controller

 

 

OverCurrent Protection

Yes

 

 

OverHeat Protection

 

 

 

Yes

 

Run Capacitor

 

 

Micro F

-

 

 

 

 

 

VAC

-

 

 

 

 

 

Heat Exchanger Coil

 

 

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

 

 

2

 

Fins per inch

 

 

 

18.1

 

Face Area

 

 

ft2 (m2)

6.40 (0.595)

 

 

 

 

 

 

External Finish

 

 

 

Acrylic baked-on enamel finish

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

19

2-3. Other Component Specifications

Indoor Unit

KS1872

 

 

KS2472

 

Outdoor Unit

C1872

C2472

 

CL1872

CL2472

Indoor air temp sensor

(Model:PTM-D51H-S3 TH2)

 

10

 

 

 

 

 

 

 

ohm)(k

9

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

Resistance

8

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

0

50

59

68

77

86

95

104

 

 

 

 

(10)

(15)

(20)

(25)

(30)

(35)

(40)

 

 

 

Temperature °F (°C)

 

Indoor heat exchanger sensor

(Model:PTM-D51H-S3 TH1)

Compressor temp sensor

(Model:TKS 293B)

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ohm)(k

180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

68

86

104 122 140 158 176 194

 

32

 

(0)

(10) (20) (30) (40) (50) (60) (70) (80) (90)

 

 

 

 

 

 

 

 

 

Temperature °F (°C)

Outdoor air temp sensor

(Model:TKS295B)

Outdoor heat exchanger sensor

(Model:TKS292B)

ohm)

40

 

 

 

 

 

 

 

 

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(k

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

0

-4

5

14

23

32

41

50

59

68

 

 

 

 

(-20)(-15)(-10) (-5)

(0)

(5)

(10) (15) (20)

 

 

 

 

Temperature °F (°C)

 

 

20

Sanyo C2472, CL2472, ks2472, CL1872, C1872 User Manual

3. DIMENSIONAL DATA

Indoor Unit KS1872

KS2472

Unit: inch(mm)

21

Outdoor Unit C1872

CL1872

11-17/32

1-3/8

23-15/16

 

5-11/32

 

 

15/32

ID:23/32

 

ID:15/16

-

 

2

 

-7/32 (285)

12-7/32

13-5/32

11

 

 

34-21/32 (880)

2-17/32

26-3/8 (670)

23/32

1-13/16

2-13/32

22

Wide tube service valve dia.1/2" (12.70)

Narrow tube service valve dia.1/4" (6.35)

2-5/32

 

4-3/8

6-17/32

3/32

5-23/32

Unit: inch(mm)

Outdoor Unit C2472

CL2472

11-17/32

1-3/8

23-15/16

ID:23/32

 

ID:15/16

2

-

 

5-11/32

15/32

-19/32(320)

13-19/32

14-17/32

12

 

 

Narrow tube service valve dia.1/4" (6.35)

35-7/16(900)

2-15/16

Wide tube service valve

 

 

dia.5/8" (15.88)

29-1/8 (740)

23/32

5-29/32

4-7/16

1-21/32

2-1/32

4-1/2

 

 

2-7/8

 

 

Unit: inch(mm)

23

4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram

Indoor Unit KS1872

Outdoor Unit C1872

C2472

KS2472

CL1872

CL2472

Indoor unit Outdoor unit

 

Wide tube

 

 

 

Wide tube

service

 

 

Compressor

valve

 

Accumulator

 

 

*1

 

Muffler

 

 

 

 

 

High pressure

 

 

 

 

switch

 

 

 

 

H.P.

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Narrow

 

Electric

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

expansion

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

service

 

 

 

 

 

 

 

 

 

 

 

 

Narrow tube

 

 

M

 

 

 

 

 

 

 

 

 

 

 

valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O.D.

1/4" Cooling cycle (6.35 mm)

*1 O.D.1/2"(12.7mm) ... 1872 class O.D.5/8"(15.88mm) ... 2472 class

Insulation of Refrigerant Tubing

IMPORTANT

Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 5/16"(8 mm).

Thickness:

Min. 5/16"(8 mm)

After a tube has been insulated,

Wide tube

never try to bend it into a narrow

CAUTION

curve because it can cause the tube to break or crack.

Insulation

Thickness:

Min. 5/16"(8 mm)

Narrow tube

24

5. PERFORMANCE DATA

5-1. Temperature Charts

Indoor Unit KS1872

Outdoor Unit C1872

Cooling Characteristics (230V)

service valve

psig (MPaG)

159

 

 

 

 

 

 

 

 

(1.1)

 

 

 

 

 

 

 

 

Low

High

 

 

 

 

 

 

 

145

 

 

 

 

 

 

°C)

 

 

 

 

 

 

°F

(30

 

(1.0)

 

 

.86

 

 

 

 

 

 

 

 

tube

 

 

 

temp

 

 

 

 

 

 

 

 

air

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wide

 

 

 

 

 

 

 

°C)

 

 

131

 

 

 

 

27

 

 

 

 

 

°F

(

 

 

 

 

(0.9)

 

 

80

 

 

 

 

 

at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

°C)

 

 

 

 

 

°F

(24

 

 

 

117

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0.8)

 

 

 

 

 

 

 

 

Low

 

 

 

 

 

 

 

 

 

 

77

86

 

95

 

 

 

104

 

 

 

 

 

 

 

 

(25)

(30)

 

(35)

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

 

9

 

 

 

 

 

 

 

 

 

 

Low

 

High

 

 

 

 

 

 

 

(A)

8

 

 

 

 

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

 

°

 

 

 

 

 

 

 

F

(30

 

 

 

 

 

 

°

 

 

 

 

 

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

°

 

 

 

 

air

 

 

 

27

 

 

 

 

 

 

 

(

 

 

 

 

 

 

 

 

F

 

 

 

Operating

 

 

 

 

°

 

 

 

 

7

 

Indoor

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

77

86

 

95

 

 

 

 

 

104

 

(25)

(30)

 

(35)

 

 

 

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

°C)

 

Low

 

High

 

 

 

 

 

°F(

68.0(20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

64.4(18)

 

 

 

 

 

 

 

 

60.8(16)

 

 

 

 

 

 

 

°C)

 

 

 

 

.86°F

(30

 

 

 

Indoor

air

temp

 

 

 

 

 

 

 

 

 

 

air

 

 

 

 

 

 

 

 

57.2(14)

 

 

 

 

 

 

 

 

discharge

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80°F

(27°

 

 

 

 

 

 

 

 

 

53.6(12)

 

 

 

 

 

°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

°F

(24

 

 

50.0(10)

 

 

 

 

75

 

 

 

Indoor

 

 

 

 

 

 

 

 

77

 

86

 

 

95

 

 

104

 

 

 

 

 

 

 

(25)

 

(30)

 

 

(35)

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

NOTE

Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.

Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "9-2. Overload prevention during heating.")

:Points of rating condition

Black dots in above charts indicate the following rating conditions. Cooling: Indoor air temperature 80 °F D.B. / 67 °F W.B.

Outdoor air temperature 95 °F D.B.

25

Indoor Unit KS1872

Outdoor Unit CL1872

Cooling Characteristics (230V)

service valve

psig (MPaG)

159

 

 

 

 

 

 

 

 

(1.1)

 

 

 

 

 

 

 

 

Low

High

 

 

 

 

 

 

 

145

 

 

 

 

 

 

°C)

 

 

 

 

 

 

°F

(30

 

(1.0)

 

 

.86

 

 

 

 

 

 

 

 

tube

 

 

 

temp

 

 

 

 

 

 

 

 

air

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wide

 

 

 

 

 

 

 

°C)

 

 

131

 

 

 

 

27

 

 

 

 

 

°F

(

 

 

 

 

(0.9)

 

 

80

 

 

 

 

 

at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

°C)

 

 

 

 

 

°F

(24

 

 

 

117

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0.8)

 

 

 

 

 

 

 

 

Low

 

 

 

 

 

 

 

 

 

 

77

86

 

95

 

 

 

104

 

 

 

 

 

 

 

 

(25)

(30)

 

(35)

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

 

9

 

 

 

 

 

 

 

 

 

 

Low

 

High

 

 

 

 

 

 

 

(A)

8

 

 

 

 

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

 

°

 

 

 

 

 

 

 

F

(30

 

 

 

 

 

 

°

 

 

 

 

 

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

°

 

 

 

 

air

 

 

 

27

 

 

 

 

 

 

 

(

 

 

 

 

 

 

 

 

F

 

 

 

Operating

 

 

 

 

°

 

 

 

 

7

 

Indoor

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

77

86

 

95

 

 

 

 

 

104

 

(25)

(30)

 

(35)

 

 

 

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

°C)

 

Low

 

High

 

 

 

 

 

°F(

68.0(20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

64.4(18)

 

 

 

 

 

 

 

 

60.8(16)

 

 

 

 

 

 

 

°C)

 

 

 

 

.86°F

(30

 

 

 

Indoor

air

temp

 

 

 

 

 

 

 

 

 

 

air

 

 

 

 

 

 

 

 

57.2(14)

 

 

 

 

 

 

 

 

discharge

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80°F

(27°

 

 

 

 

 

 

 

 

 

53.6(12)

 

 

 

 

 

°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

°F

(24

 

 

50.0(10)

 

 

 

 

75

 

 

 

Indoor

 

 

 

 

 

 

 

 

77

 

86

 

 

95

 

 

104

 

 

 

 

 

 

 

(25)

 

(30)

 

 

(35)

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

NOTE

Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.

Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "9-2. Overload prevention during heating.")

:Points of rating condition

Black dots in above charts indicate the following rating conditions. Cooling: Indoor air temperature 80 °F D.B. / 67 °F W.B.

Outdoor air temperature 95 °F D.B.

26

Indoor Unit KS2472

Outdoor Unit C2472

Cooling Characteristics (230V)

service valve

psig (MPaG)

159

 

 

 

 

 

 

(1.1)

 

 

 

 

 

 

Low

High

 

 

 

 

 

145

 

 

 

 

°C)

 

 

 

 

°F

(30

 

(1.0)

 

 

.86

 

 

 

 

 

 

 

 

tube

 

 

 

temp

 

 

 

 

 

 

air

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

wide

 

131

 

 

 

°C)

 

 

 

 

°F

(27

 

 

 

(0.9)

 

 

80

 

 

 

at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

°C)

 

 

 

 

 

°F

(24

 

 

 

117

 

 

75

 

 

 

 

 

 

 

 

 

 

 

(0.8)

 

 

 

 

 

 

Low

 

 

 

 

 

 

 

 

77

86

 

95

 

104

 

 

 

 

 

 

(25)

(30)

 

(35)

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

 

15

 

 

 

 

 

 

 

 

 

14

Low

High

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

13

 

 

 

 

 

 

 

 

current

12

 

 

 

 

 

 

°C)

 

 

 

 

 

 

 

°C)

 

 

 

 

 

.86

 

 

Operating

 

 

 

 

 

(27

 

11

 

 

 

temp

 

 

 

 

 

 

 

F

 

 

 

 

 

°

 

 

 

 

air

80

 

 

 

 

Indoor

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

77

 

86

 

 

95

 

 

104

 

(25)

 

(30)

 

(35)

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

°C)

 

Low

 

High

 

 

 

 

 

 

°F(

68.0(20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

64.4(18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

°C)

60.8(16)

 

 

 

 

 

F (30

 

 

 

Indoor

air

temp.86°

 

 

 

air

 

 

 

 

 

 

 

 

 

57.2(14)

 

 

 

 

 

 

 

 

 

discharge

 

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80°F (27°

 

53.6(12)

 

 

 

 

 

 

 

C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24°

 

 

 

 

 

 

F (

 

 

 

 

 

 

 

75°

 

 

 

 

Indoor

50.0(10)

 

 

 

 

 

 

 

 

 

77

 

86

 

 

95

 

 

 

104

 

 

 

 

 

 

 

 

(25)

 

(30)

 

 

(35)

 

 

 

(40)

Outdoor inlet air D.B. temp. °F(°C)

NOTE

Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.

Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "9-2. Overload prevention during heating.")

:Points of rating condition

Black dots in above charts indicate the following rating conditions. Cooling: Indoor air temperature 80 °F D.B. / 67 °F W.B.

Outdoor air temperature 95 °F D.B.

27