Samsung MH18AP2-09, MH19AP2-07, MH19AP2-12, MH24AP2-12, MH26AP2-07 Service Manual

...
MULTI AIR CONDITIONER
INDOOR UNIT
MH18AP1(P2)-09 MH19AP1(P2)-07 MH19AP1(P2)-12 MH24AP1(P2)-12 MH26AP1(P2)-07 MH26AP1(P2)-12
SERVICE
OUTDOOR UNIT
MH18AP1(P2)X MH19AP1(P2)X
MH24AP1(P2)X MH26AP1(P2)X
Manual
CONTENTSAIR CONDITIONER
11.Product Specifications
Technical Document
13. Disassembly and Reassembly
14. Refrigerating Cycle Diagram
15. Set Up the Model Option
16. Troubleshooting
17. Exploded Views and Parts List
18. PCB Diagram
19.Wiring Diagram
10.Schematic Diagram
1. Product Specifications
1-1 Table
Item
Type
Cooling/Heating 1 Unit(A)
1 Unit(B/C) 2 Unit(A+B/C) kW
Perfor­mance
Dehumidifying(A+B/C) \ /h Noise Cooling / Heating dB Power ø/V/Hz
Power Consumption 1 Unit(A) (Cooling/Heating) 1 Unit(B/C)
Power
Operating Current 1 Unit(A) (Cooling/Heating) 1 Unit(B/C)
Starting Current(Cooling/Heating) A
Outer Dimension WxHxD
Weight kg Refrigerant Pipe Drain Hose ID(mm)
Size
Compressor
Blower Motor Type
Heat Exchanger
2 Unit(B+C) 3 Unit(A+B+C)
2 Unit(A+B/C) W 2 Unit(B+C) 3 Unit(A+B+C)
2 Unit(A+B/C) A 2 Unit(B+C) 3 Unit(A+B+C)
Liquid Gas
Type Model Name Capacitor
Motor Type(Model)
Rated Output(A+B/C)
Type
Rated Input W
Model
mm
inch
OD(mm)xL(m)
W
MH18AP1(P2)
INDOOR UNIT OUTDOOR UNIT
MH18AP1(P2)-09 MH18AP1(P2)X
WALL-MOUNTING MULTISPLIT
2.65 / 2.78
2.65 / 2.78
5.30 / 5.56
-
-
1.1+1.1 ­39 / 39 57 / 57
1 / 220-240V~ / 50
1,020 / 980 1,020 / 980
1,940 / 1,900
-
-
4.5 / 4.4
4.5 / 4.4
8.6 / 8.4
-
-
30
795 x 258 x 179 880 x 638 x 310
31 x 10 x 7 35 x 25 x 12
7.5 59.5 ø6.35 x 7.5 ø9.52 x 7.5
ø17
- ROTARY
-
- 35 / 35
-
-
CROSS-FAN PROPELLER
RESIN STEEL
30 100
2ROW 10STEP 2ROW 28STEP
G4A097JU1EP
INDUCTION MOTOR
925+925
MH19AP1(P2)
INDOOR UNIT OUTDOOR UNIT
MH19AP1(P2)-07 MH19AP1(P2)-12
WALL-MOUNTING MULTISPLIT
1.0+1.4 -
(–07):36 / 36,
(–12):43 / 43
1 / 220-240V~ / 50
795 x 258 x 179 890 x 285 x 179
31 x 10 x 7 35 x 11 x 7
7.5 / 8.5 60
- ROTARY
-
- 30 / 35
-
-
CROSS-FAN PROPELLER
RESIN STEEL
30 100
2ROW 10STEP 2ROW 10STEP 2ROW 12STEP 2ROW 18STEP
MH19AP1(P2)X
2.05 / 2.25
3.51 / 3.60
5.56 / 5.85
-
-
57 / 57
870 / 780 1,270 / 1,420 2,100 / 2,120
-
-
3.9 / 3.5
5.7 / 6.3
9.3 / 9.4
-
-
30
880 x 638 x 310
35 x 25 x 12
ø6.35 x 7.5 ø9.52 x 7.5
ø17
G4A080JU1EP G8C124JU1EL
INDUCTION MOTOR
820+1,060
Refrigerant Control Unit Refrigerant to Change(R410A)
Additional Refrigerant (Refrigerant must be added if the piping)
Protection Device Standard Conditions
g/m
A,B-UNIT:CAPILLARY TUBE
A-UNIT:770g / B-UNIT:770g
20(A,B-UNIT) -
- RAC12131-9622
ISO R5151 STANDARD
A,B-UNIT:CAPILLARY TUBE A-UNIT:620g / B-UNIT:1,080g
18(A-UNIT) 25(B-UNIT)
-
ISO R5151 STANDARD
RAC12126-9622 RAC12128-9622
-
1Samsung Electronics
Table(cont.)
Item
Type
Cooling/Heating 1 Unit(A)
1 Unit(B/C) 2 Unit(A+B/C) kW
Perfor­mance
Power
Dehumidifying(A+B/C) \ /h Noise Cooling / Heating dB Power ø/V/Hz
Power Consumption 1 Unit(A) (Cooling/Heating) 1 Unit(B/C)
Operating Current 1 Unit(A) (Cooling/Heating) 1 Unit(B/C)
Starting Current(Cooling/Heating) A
Outer Dimension WxHxD
Weight kg Refrigerant Pipe Drain Hose ID(mm)
Size
Compressor
Blower Motor Type
Heat Exchanger
Refrigerant Control Unit Refrigerant to Change(R410A)
Additional Refrigerant (Refrigerant must be added if the piping)
Protection Device Standard Conditions
2 Unit(B+C) 3 Unit(A+B+C)
2 Unit(A+B/C) W 2 Unit(B+C) 3 Unit(A+B+C)
2 Unit(A+B/C) A 2 Unit(B+C) 3 Unit(A+B+C)
Liquid Gas
Type Model Name Capacitor
Motor Type(Model)
Rated Output(A+B/C)
Type
Rated Input W
Model
mm
inch
OD(mm)xL(m)
W
g/m
MH24AP1(P2)
INDOOR UNIT OUTDOOR UNIT
MH24AP1(P2)-12 MH24AP1(P2)X
WALL-MOUNTING MULTISPLIT
3.51 / 3.8
3.51 / 3.8
7.02 / 7.6
-
-
1.4+1.4 ­43 / 43 60 / 60
1 / 220-240V~ / 50
1,280 / 1,280 1,280 / 1,280
2, 560 / 2, 560
-
-
5.7 / 5.7
5.7 / 5.7
11.4 / 11.4
-
-
35
890 x 285 x 179 1,000 x 790 x 310
35 x 11 x 7 39 x 31 x 12
8.5 69 ø6.35 x 7.5 ø9.52 x 7.5
ø17
-ROTARY
-
- 35 / 35
-
-
CROSS-FAN PROPELLER
RESIN STEEL
30 150
2ROW 12STEP 2ROW 36STEP
A,B-UNIT:CAPILLARY TUBE
A-UNIT:1,000g / B-UNIT:1,000g
16(A,B-UNIT) -
- RAC12128-9622
ISO R5151 STANDARD
G8C124JU1EL
INDUCTION MOTOR
1,060+1,060
MH26AP1(P2)
INDOOR UNIT OUTDOOR UNIT
MH26AP1(P2)-12 MH26AP1(P2)-07
WALL-MOUNTING MULTISPLIT
1.4+1.0 / 1.0 -
(–12):43 / 43,
(–07):36 / 36
1 / 220-240V~ / 50
890 x 285 x 179 795 x 258 x 179
35 x 11 x 7 31 x 10 x 7
8.5 / 7.5 71
-ROTARY
-
- 35 / 35
-
-
CROSS-FAN PROPELLER
RESIN STEEL
30 150
2ROW 12STEP 2ROW 16STEP 2ROW 10STEP 2ROW 20STEP
A-UNIT:CAPILLARY TUBE
B,C-UNIT:ELEC.EXPANSION V/V
A-UNIT:910g / B-UNIT:1,290g
16(A-UNIT)
21(B+C-UNIT)
-
ISO R5151 STANDARD
MH26AP1(P2)X
3.51 / 3.65
2.05 / 2.06
5.56 / 5.71
4.1 / 4.12
7.61 / 7.77
60 / 60
1,370 / 1,310 1,590 / 1,720 2,780 / 2,840 1,640 / 1,490 2,900 / 2,630
6.0 / 5.8
7.2 / 7.8
12.4 / 12.7
7.5 / 6.9
13.0 / 11.7 40
1,000 x 790 x 310
39 x 31 x 12
ø6.35 x 7.5 ø9.52 x 7.5
ø17
G8C124JU1EL
G8C150JU1EH
INDUCTION MOTOR
1,060+1,250
-
RAC12128-9622 RAC12122-9622
Samsung Electronics2
MEMO
3Samsung Electronics
Low Medium High
Automatic(rotated : )
2. Operating Instructions & Technical Document
2-1 Operating Instructions
2-1-1 The Feature of Key in remote control
NAMED OF KEYNo
1
2
3
(On/Off)
(UP)
(DOWN)
On/Off button. Press the button to stop or run the air conditioner.
Temperature adjustment button(UP). To increase the temperature by the pressing the temperature button.
Temperature adjustment button(DOWN). To decrease the temperature by the pressing the temperature button.
Mode selection button. Each time you press this button Mode is changed in the following order
Fan speed adjustment button. Each time you press this button, FAN SPEED is changed in the following order.
FUNCTION OF KEY
: Auto Mode : Fan Only : Cool Mode : Heat Mode : Dry Mode
4
5
6
7
Swing button. It adjusts the airflow to upward and downward.
Turbo button. The air conditioner cools or heats the room as quickly as possible. After 30minutes, the air conditioner is reset automatically to the previous mode.
Sleep button. The sleep timer can be used when you are cooling or heating your room to switch the air conditioner off automatically after a period of 6 hours.
Samsung Electronics4
The Feature of Key in remote control(cont.)
On Timer button. The On Timer enables you to switch on the air conditioner automatically after
8
9
10
a given period of time that is from 30 minutes to 24 hours. To set the operating time, press the button one or more times until the required
time display.
Off Timer button. The Off Timer enables you to switch off the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours.
To set the operating time, press the button one or more times until the required time display.
Timer Set/Cancel button. After setting On Timer or Off Timer, press the button to set it completely.
And press the button again to cancel On Timer or Off Timer set.
FUNCTION OF KEYNAMED OF KEYNo
11
Digital On/Off button. If you want to turn off the display during operation press the button.
5Samsung Electronics
Operating Instructions & Technical Document
2-1-2 Name & Function of Key in remote control
1. AUTO MODE : In this mode, operation mode(COOL, HEAT) is selected automatically by the room temperature of initial operation.
Room Temp
Tr21°C+∆T 21°C +∆T>Tr
Cool Operation (Set Temp:24˚C+∆T) Heat Operation (Set Temp:22˚C+T)
Operation Type
T= -1°C, -2°C, 0°C, +1°C, +2°CT is controlled by setting temperature up/down key of
remote control
2. COOL MODE : The unit operates according to the difference between the setting and room temperature. (18°C~30°C)
3. HEAT MODE : The unit operates according to the difference between the setting and room tempera­ture.(16°C~30°C) *Prevention against cold wind : In order to prevent the
cool air from flowing out at the heat mode, the indoor fan does not operate or operates very slowly in the following cases. At this time, the indoor heat exchanger will be preheating.
- For 3~5 minutes after the initial operation
- For deicing operation
- The operation of an indoor fan in accordance with the temperature of an indoor heat exchanger
The temperature of
indoor heat exchanger
below 28˚C
28˚C~below 34˚C
34˚C~below 40˚C
above 40˚C
Indoor fan speed
off
LL Speed
L Speed
Setting Speed
*High temperature release function : It is a function to
detect an outdoor overload by the sensor of an indoor heat exchanger and to turn the outdoor fan or the compressor ON/OFF for safety.
*Deice : Deicing operation is controlled by indoor unit's
heat exchanger temperature and accumulating time of compressor's operation. Deice ends by sensing of the processing time by deice condition.
4. DRY MODE : Has 3 states, each determined by room temperature. The unit operates in DRY mode. *Compressor ON/OFF Time is controlled compulsorily
(can not set up the fan speed, always breeze).
*Protective function : Low temperature release.
(Prevention against freeze)
5. TURBO MODE : This mode is available in AUTO, COOL, HEAT, DRY, FAN MODE. When this button is pressed at first, the air conditioner is operated "powerful" state for 30 minutes regardless of the set temperature, room temperature. When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode. *But, if you press the TURBO button in DRY or FAN
mode that is changed with AUTO mode automatically.
6. SLEEP MODE : Sleep mode is available only in COOL or HEAT mode. The operation will stop after 6 hours. *In COOL mode : The setting temperature is automatical-
ly raised by 1°C each 1hour When the temperature has been raised by total of 2°C, that temperature is maintained.
*In HEAT mode : The setting temperature is automatically
dropped by 1°C each 1hour. When the temperature has been dropped by total of 2°C, that temperature is maintained.
7. FAN SPEED : Manual (3 step), Auto (4 step) Fan speed automatically varies depending on both the difference between setting and the room temperature.
8. COMPULSORY OPERATION : For operating the air conditioner without the remote control. *The air conditioner starts up in the most suitable mode
for the room temperature:
Room Temperature
Less than 21˚C
21˚C or above
Operating Mode
Heat
Cool
Temperature Setting
24˚C approx. 22˚C approx.
Samsung Electronics6
Operating Instructions & Technical Document
9. SWING : BLADE-H is rotated vertically by the stepping motor. *Swing Set : Press the button under the remote
control is displayed on LCD the and the blades move up and down. If the one more time press the
button, blades location is stop.
10. SETTING THE ON/OFF TIMER. : *ON TIMER : The On Timer enables you to switch on the
air conditioner automatically after a given period of time. You can set the period of time from 30 minutes to 24 hours.
*OFF TIMER : The Off Timer enables you to switch off
the air conditioner automatically after a given period of time. You can set the period of time from 30 minutes to 24 hours.
11. SELF DIAGNOSIS
Error Mode
Indoor unit room temperature sensor error (open or short)
Indoor unit heat exchanger temperature sensor error(open or short)
Indoor FAN MOTOR error : Keep the RPM value 450 below for 15 seconds
EEPROM error
Error in option In case of No option set-up In case of option data error
DISPLAY 7-SEGMENT
Operation Off Operation On
OFF E1
OFF E2
OFF E3
OFF E6
All lamp
blinking
All lamp
blinking
Remark
12. BUZZER SOUND : Whenever the On/Off button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep".
7Samsung Electronics
2-2 Technical Document (Pressure Graph)
20
27.2
26.5
31.6
30.4
38.8
38.5
25 30
Outdoor Temperature (ßC)
High Pressure (kgf/cm
2
G)
35 40 45
43
39
35
31
27
23
19
15
A-unit B-unit
25.225.225.2
28.828.828.8
20 25 30
Outdoor Temperature (ßC)
Low Pressure (kgf/cm
2
G)
35 40 45
9.8
9.6
9.4
9.2 9
8.8
8.6
8.4
8.2 8
8.2
8.2
8.3
9.4
A-unit B-unit
8.518.51
8.288.28
8.5
8.3
8.738.738.7
9.529.529.5
2-2-1 MH18AP1(P2)
Cooling(7.5m–Piping)
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/15 28.8 27.2 8.2 8.2 27/19 27/20 26.5 25.2 8.3 8.3 27/19 35/24 31.6 30.4 8.7 8.5 27/19 43/26 38.5 38.8 9.5 9.4
Samsung Electronics8
2-1-1 MH18AP1(P2)
20 25 30
Outdoor Temperature (ßC)
35 40 45
High Pressure (kgf/cm
2
G)
43
39
35
31
27
23
19
15
27.8
26.8
32.3
31.3
38.2
37.9
A-unit B-unit
2525
24.424.4
25.025.025.0
24.4
20 25 30
Outdoor Temperature (ßC)
35 40 45
Low Pressure (kgf/cm
2
G)
9
8.8
8.6
8.4
8.2
8
7.8
8.0
8.0
8.0
8.4
8.8
8.8
8.2
8.0
A-unit B-unit
Cooling(15m–Piping)
Operating Instructions & Technical Document
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/15 27.8 25.0 8.0 8.0 27/19 27/20 26.8 24.4 8.0 8.0 27/19 35/24 32.3 31.3 8.4 8.2 27/19 43/26 38.2 37.9 8.8 8.8
9Samsung Electronics
Operating Instructions & Technical Document
-15 -10 -5
Outdoor Temperature (ßC)
0510
High Pressure (kgf/cm
2
G)
29.5
27.5
25.5
23.5
21.5
19.5
17.5
15.5
13.5
11.5
23.8
28.6
20.2
A-unit B-unit
23.8523.85
(27.8)(27.8)
25.6925.69
23.9
27.8
25.7
-15 -10 -5
Outdoor Temperature (ßC)
0510
Low Pressure (kgf/cm
2
G)
7.5 7
6.5 6
5.5 5
4.5 4
3.5 3
6.0
6.8
A-unit B-unit
(5.9)(5.9)
6.846.84
3.683.68
3.723.72
5.9
6.8
3.7
3.7
Heating(7.5m–Piping)
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
20/15 –10 23.9 20.2 3.7 3.7
20/15 7 28.6 25.7 6.8 6.8
Samsung Electronics10
Heating(15m–Piping)
-15 -10 -5
Outdoor Temperature (ßC)
0510
High Pressure (kgf/cm
2
G)
31.5
29.5
27.5
25.5
23.5
21.5
19.5
17.5
15.5
13.5
11.5
29.0
25.7
19.6
27.4
23.8
A-unit B-unit
23.9323.9323.9
-15 -10 -5
Outdoor Temperature (ßC)
0510
Low Pressure (kgf/cm
2
G)
7
6.5 6
5.5 5
4.5 4
3.5 3
3.5
3.4
A-unit B-unit
(5.9)(5.9)
(27.4)(27.4)
5.9
6.7
6.7
5.8
Operating Instructions & Technical Document
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
20/15 –10 23.9 19.6 3.5 3.4
20/15 7 29.0 25.7 6.7 6.7
11Samsung Electronics
Operating Instructions & Technical Document
20 25 30
Outdoor Temperature (ßC)
35 40 45
High Pressure (kgf/cm
2
G)
43
39
35
31
27
23
19
15
27.2
27.0
26.8
26.6
31.8
31.6
38.4
37.6
A-unit B-unit
20 25 30
Outdoor Temperature (ßC)
35 40 45
Low Pressure (kgf/cm
2
G)
9.4
9.2 9
8.8
8.6
8.4
8.2 8
8.8
9.2
A-unit B-unit
8.58.5
8.58.5
8.38.3
8.38.3
8.98.9
9.39.3
8.5
8.5
8.3
8.9
9.3
8.3
2-2-2 MH19AP1(P2)
Cooling(7.5m–Piping)
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/15 27.2 27.0 8.5 8.5 27/19 27/20 26.8 26.6 8.3 8.3 27/19 35/24 31.8 31.6 8.9 8.8 27/19 43/26 38.4 37.6 9.3 9.2
Samsung Electronics12
2-1-1 MH18AP1(P2)
20 25 30
Outdoor Temperature (ßC)
35 40 45
High Pressure (kgf/cm
2
G)
43
39
35
31
27
23
19
15
27.4
27.2
27.0
26.8
32.0
31.8
38.6
37.8
A-unit B-unit
20 25 30
Outdoor Temperature (ßC)
35 40 45
Low Pressure (kgf/cm
2
G)
9.4
9.2 9
8.8
8.6
8.4
8.2 8
8.4
8.2
8.4
9.2
8.8
8.2
8.1
A-unit B-unit
8.78.78.7
Cooling(15m–Piping)
Operating Instructions & Technical Document
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/15 27.4 27.2 8.4 8.2 27/19 27/20 27.0 26.8 8.2 8.1 27/19 35/24 32.0 31.8 8.7 8.4 27/19 43/26 38.6 37.8 9.2 8.8
13Samsung Electronics
Operating Instructions & Technical Document
-15 -10 -5
Outdoor Temperature (ßC)
0510
High Pressure (kgf/cm
2
G)
35
32
29
26
23
20
27.5
22.7
33.1
27.7
A-unit B-unit
-15 -10 -5
Outdoor Temperature (ßC)
0510
Low Pressure (kgf/cm
2
G)
7
6.5 6
5.5 5
4.5 4
3.5 3
3.5
6.8
6.7
3.4
A-unit B-unit
Heating(7.5m–Piping)
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
20/15 –10 22.7 27.5 3.5 3.4
20/15 7 27.7 33.1 6.8 6.7
Samsung Electronics14
Heating(15m–Piping)
-15 -10 -5
Outdoor Temperature (ßC)
0510
High Pressure (kgf/cm
2
G)
36.5
31.5
26.5
21.5
16.5
11.5
26.7
21.3
32.3
26.3
A-unit B-unit
-15 -10 -5
Outdoor Temperature (ßC)
0510
Low Pressure (kgf/cm
2
G)
7
6.5 6
5.5 5
4.5 4
3.5 3
3.4
6.7
3.1
A-unit B-unit
6.46.46.4
Operating Instructions & Technical Document
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit (7.5m) B-unit (32.5m)
20/15 –10 21.3 26.7 3.4 3.1
20/15 7 26.3 32.3 6.7 6.4
15Samsung Electronics
Operating Instructions & Technical Document
20 25 30
Outdoor Temperature (ßC)
35 40 45
High Pressure (kgf/cm
2
G)
43
39
35
31
27
23
19
15
27.9
31.1
38.0
38.0
30.1
28.7528.75
25.425.4
28.8
26.0
25.4
A-unit B-unit
20 25 30
Outdoor Temperature (ßC)
35 40 45
Low Pressure (kgf/cm
2
G)
9.5
9.4
9.3
9.2
9.1 9
8.9
8.8
8.7
8.6
8.5
9.0
8.9
9.1
9.2
9.2
9.0
8.8
8.9
A-unit B-unit
2-2-3 MH24AP1(P2)
Cooling(7.5m–Piping)
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/15 28.8 26.0 8.9 9.0 27/19 27/20 27.9 25.4 8.8 8.9 27/19 35/24 31.1 30.1 9.0 9.1 27/19 43/26 38.0 38.0 9.2 9.2
Samsung Electronics16
2-1-1 MH18AP1(P2)
20 25 30
Outdoor Temperature (ßC)
35 40 45
High Pressure (kgf/cm
2
G)
39
35
31
27
23
19
15
27.8
26.9
29.1
37.3
26.0
A-unit B-unit
24.424.4
30.130.1
3737
24.4
30.1
37.0
20 25 30
Outdoor Temperature (ßC)
35 40 45
Low Pressure (kgf/cm
2
G)
9.5
9.4
9.3
9.2
9.1 9
8.9
8.8
8.7
8.6
8.5
8.8
8.7
8.7
8.6
8.9
8.8
9.0
A-unit B-unit
9.0
Cooling(15m–Piping)
Operating Instructions & Technical Document
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/15 27.8 26.0 8.7 8.8 27/19 27/20 26.9 24.4 8.6 8.7 27/19 35/24 30.1 29.1 8.8 8.9 27/19 43/26 37.3 37.0 9.0 9.0
17Samsung Electronics
Operating Instructions & Technical Document
-15 -10 -5
Outdoor Temperature (ßC)
0510
High Pressure (kgf/cm
2
G)
31.5
29.5
27.5
25.5
23.5
21.5
19.5
17.5
15.5
13.5
11.5
24.9
30.0
26.7
A-unit B-unit
20.6120.61
(28.4)(28.4)
(24.8)(24.8)
20.6
28.4
24.8
-15 -10 -5
Outdoor Temperature (ßC)
0510
Low Pressure (kgf/cm
2
G)
7.5 7
6.5 6
5.5 5
4.5 4
3.5 3
A-unit B-unit
6.0
7.0
3.7
6.856.85
3.73.7
(5.9)(5.9)
6.9
3.7
5.9
Heating(7.5m–Piping)
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
20/15 –10 24.9 20.6 3.7 3.7
20/15 7 30.0 26.7 7.0 6.9
Samsung Electronics18
Heating(15m–Piping)
-15 -10 -5
Outdoor Temperature (ßC)
0510
High Pressure (kgf/cm
2
G)
31.5
29.5
27.5
25.5
23.5
21.5
19.5
17.5
15.5
13.5
11.5
A-unit B-unit
19.6
29.0
25.7
27.4
23.8
23.9123.9123.9
-15 -10 -5
Outdoor Temperature (ßC)
0510
Low Pressure (kgf/cm
2
G)
7
6.5 6
5.5 5
4.5 4
3.5 3
A-unit B-unit
3.5
3.5
5.9
6.8
5.8
6.7
Operating Instructions & Technical Document
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
20/15 –10 23.9 19.6 3.5 3.5
20/15 7 29.0 25.7 6.8 6.7
19Samsung Electronics
Operating Instructions & Technical Document
High Pressure (kgf/cm
2
G)
43.0
39.0
35.0
31.0
27.0
23.0
19.0
15.0
27.3
27.1
32.2
31.3
39.5
38.0
20 25 30
Outdoor Temperature (ßC)
35 40 45
A-unit B-unit
25.4625.46
25.0625.06
25.5
25.1
Low Pressure (kgf/cm
2
G)
10.0
9.5
9.0
8.5
8.0
7.5
7.0
6.5
6.0 20 25 30 35 40 45
6.9
6.8
8.8
8.6
9.6
A-unit B-unit
9.319.319.3
6.646.646.6
6.776.776.8
Outdoor Temperature (ßC)
2-2-4 MH26AP1(P2)
Cooling(7.5m–Piping)
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/10 27.3 25.5 6.8 6.9 27/19 27/19 27.1 25.1 6.6 6.8 27/19 35/24 32.2 31.3 8.6 8.8 27/19 45/26 39.5 38.0 9.3 9.6
Samsung Electronics20
2-1-1 MH18AP1(P2)
High Pressure (kgf/cm
2
G)
43.0
39.0
35.0
31.0
27.0
23.0
19.0
15.0 20 25 30
Outdoor Temperature (ßC)
35 40 45
39.5
28.1
38.0
A-unit B-unit
28.6
29.5729.57
32.8732.87
32.4032.40
29.3229.32
29.6
32.9
32.4
29.3
Low Pressure (kgf/cm
2
G)
10.0
9.5
9.0
8.5
8.0
7.5
7.0 20 25 30
Outdoor Temperature (ßC)
35 40 45
A-unit B-unit
8.9
7.67.67.6
9.8
8.33
9.129.12
8.148.14
8.338.33
9.1
8.1
7.62
8.3
7.627.627.6
8.48.48.4
Cooling(15m–Piping)
Operating Instructions & Technical Document
Cooing
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
27/19 21/10 29.6 29.3 7.6 8.4 27/19 27/19 28.1 28.6 7.6 8.3 27/19 35/24 32.4 32.9 8.1 9.1 27/19 45/26 39.5 38.0 8.9 9.8
21Samsung Electronics
Operating Instructions & Technical Document
High Pressure (kgf/cm
2
G)
29
27
25
23
21
19
-12 -7 -2
Outdoor Temperature (ßC)
38
A-unit B-unit
19.3
20.0
24.8
24.7
28.0
27.2
High Pressure (kgf/cm
2
G)
7
6.5 6
5.5 5
4.5 4
3.5 3
2.5
-11 -6 -1
Outdoor Temperature (ßC)
49
A-unit B-unit
3.0
3.273.27
(5.22)(5.22)
4.9
6.386.38
6.0
3.3
5.2
6.4
Heating(7.5m–Piping)
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
20/15 –10 20.0 19.3 3.3 3.0 20/15 2 24.8 24.7 5.2 4.9 20/15 7 28.0 27.2 6.4 6.0
Samsung Electronics22
Heating(15m–Piping)
High Pressure (kgf/cm
2
G)
29
27
25
23
21
19
17
-12 -7 -2
Outdoor Temperature (ßC)
38
A-unit B-unit
19.0
25.5
27.7
24.4
24.3
19.7
Low Pressure (kgf/cm
2
G)
6.5
6
5.5
5
4.5
4
3.5
3
2.5
-11 -6 -1
Outdoor Temperature (ßC)
49
A-unit B-unit
2.8
4.5
5.4
6.2
3.1
5.0
Operating Instructions & Technical Document
Heating
Indoor
(DB/WB)
Outdoor
(DB)
High Pressure Low Pressure
A-unit B-unit A-unit B-unit
20/15 –10 19.7 19.0 3.1 2.8 20/15 2 24.4 24.3 5.0 4.5 20/15 7 27.7 25.5 6.2 5.4
23Samsung Electronics
3. Disassembly and Reassembly
Stop operation of the air conditioner and remove the power cord before repairing the unit.
3-1 Indoor Unit
No Parts Procedure Remark
1 Front Panel
1) Stop the air conditioner operation and block the main power.
2) Detach tape of Front Panel upper.
3) Slide the lower Front Grille down, then disassemble it by pulling it forwards.
4) Open the upper Front Grille by pulling right and left sides of the Grille.
5) Take the left and right Filter out.
6) Loosen one of the right screw and detach the Terminal Cover.
7) Detach the thermistor from the Front Grille.
8) Loosen 5 fixing screws of Front Grille.
9) Pull the lower left and right of discharge softly for the outside cover to be pulled out.