Samsung BACnet Gateway MIM-B17N Installation Manual

NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 68 2013-04-25 오전 10:14:42
BACnet® Gateway
MIM-B17N
Air Conditioner
imagine the possibilities
Thank you for purchasing this Samsung product.
EN
DB68-03719A(1)
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 69 2013-04-25 오전 10:14:43
E-2
Safety Precautions
Read carefully this installation manual before
installation and check if the BACnet Gateway is installed
correctly after installation.
Do not attempt to install or repair this BACnet Gateway
by yourself.
This BACnet Gateway contains no user-serviceable parts.
Always consult authorized service personnel for repairs.
When moving, consult authorized service personnel for
disconnection and installation of the BACnet Gateway.
Ensure that the wall is strong enough to support the
weight of the BACnet Gateway.
Must install the BACnet Gateway with rated power
supply.
The BACnet Gateway must be installed according to
the national electrical rules by an installation specialist.
If you wish to uninstall the BACnet Gateway, consult an
authorized installation center.
WARNING
CAUTION
Do not use inflammable gases near the BACnet
Gateway.
Do not install the BACnet Gateway in a location where
it will come into contact with combustible gases, machine oil, sulphide gas, etc.
Avoid locations where acid/alkali solution or special
spray is used.
Choose a location that is dry and sunny, but not exposed
to direct sunlight. Suitable temperature is between 0°C(32°F) and 39°C(102.2°F).
Do not spill water into the BACnet Gateway.Do not apply tensile strength to the cable to avoid cable
damage.
Do not press the buttons with a sharp object.Do not connect the power cable to the control terminal.If the BACnet Gateway is installed in a hospital or other
special places, it should not affect other electronic devices.
This installation manual describes how to install the BACnet Gateway. For installation of other optional accessories, refer to the appropriate installation manual.
BACnet® is a registered trademark of American Society of Heating,
Refrigerating and Air-Conditioning Engineers (ASHRAE).
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 2 2013-04-25 오전 10:14:31
E-3
Contents
Safety PrecautionS
.......................................................... 2
Before inStalling the Bacnet gateway
............................. 4
acceSSorieS
...................................................................... 5
Viewing the PartS
............................................................ 6
Product dimenSionS
......................................................... 8
SyStem architecture
........................................................ 9
comPatiBle deViceS
....................................................... 10
inStalling the Bacnet gateway
..................................... 12
Setting the comPuter enVironment
.................................15
Setting the Bacnet gateway
......................................... 17
reading ehP watt-hour meter
..................................... 22
SyStem Setting initialization
.......................................... 27
SyStem SettingS
............................................................ 28
tracking
....................................................................... 42
deVice configuration
.................................................... 48
Bacnet Protocol imPlementation conformance Statement
... 56
Standard oBject tyPeS SuPPorted
................................. 60
detail deScriPtion of oBject
.......................................... 61
Bacnet Point liSt
......................................................... 62
other information
....................................................... 67
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 3 2013-04-25 오전 10:14:31
E-4
Checks before installation
1
BACnet Gateway IP A public IP is needed to access the BACnet Gateway
over the internet. (One public IP is needed for each BACnet Gateway)
A private IP may be used if the BACnet Gateway need
not be accessed over the internet.
2
Network related equipments
3 Installation connection wire
The LAN cable and the communication cables from
centralized controllers/interface modules must be installed in such a way that the wires can be connected to the BACnet Gateway with ease.
Note  The BACnet Gateway is a server and supports static IP.
To access the BACnet Gateway through the internet or with BMS System, the BACnet Gateway address, which is the IP address, must be known.
 A static IP service from an internet service provider
must be used if xDSL (ADSL, VDSL) is being used for internet connection. (Static IP costs more than dynamic IP.)
BACnet Gateway should be situated in the same sub- net as BMS system.
Before Installing the BACnet Gateway
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 4 2013-04-25 오전 10:14:31
E-5
Item
BACnet
Gateway
Quantity 1
Shape
Adapter Power cable M4x16 Screw
1
1 6
User’s manual
Installation
manual
Cable tie
1 1 1
Make sure you have each item. Supplied items may vary depending on your country or service provider.
Accessories
The BACnet Gateway must be installed by a trained
installer.
Ensure the main power is turned o before installing
the BACnet Gateway.
Be sure to use adapter and power cable we provide.
The power cable and the communication cable must
be installed according to the national electrical wiring regulations.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 5 2013-04-25 오전 10:14:32
E-6
BACnet Gateway Exterior
LCD Display
Shows current time and IP address. Various messages will be displayed depending on button input.
LCD operation button
There are 4 buttons(Menu, (Down), (Up), Set) and you can access to menu and move, check the menu.
LED Indicator
Check 15 LED status such as Power, CPU-Alive, Ethernet-Linked/Active, COM1~5-TX/RX and Check
BACnet Gateway Bottom cover
Unfasten 2 screws on the bottom and separate the bottom cover from BACnet Gateway. Then check cable connection part.
Item Name Status
Power Power indicator
Turns blue when the power is supplied.
CPU Alive CPU operation indicator
Blinks in orange with 1 second intervals during normal operation.
Ethernet–Linked Internet connection indicator
Turns green during normal connection.
Ethernet–Active Internet data transmission/reception indicator
Blinks in orange during normal transmission/ reception.
COM1~5 – TX
Channel 1~5 OnO controller/Outdoor unit Data transmission Indicator
Blinks in green during normal transmission.
COM1~5 – RX
Channel 1~5 OnO controller/Outdoor unit Data reception Indicator
Blinks in green during normal reception,
Check Indoor/Outdoor unit/Communication check Indicator
Turns green when notice occurs.
LED Indicator
Viewing the Parts
Main Parts
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 6 2013-04-25 오전 10:14:32
E-7
Name Description
DI Terminal1 Digital Input connection terminal, Channel1~Channel5
DI Terminal2 Digital Input connection terminal, Channel6~Channel10
DO Terminal3 Digital Output connection terminal, Channel1~Channel5
DO Terminal4 Digital Output connection terminal, Channel6~Channel10
Reset Button
Reset BACnet Gateway
Power Terminal
Connect BACnet Gateway
adapter
Serial Terminal Service agent checks BACnet Gateway error status using this terminal
SD card socket
Sub memory (for program update and set information saving) socket
RS485
Communication
Terminal
Connect for RS485 communication with devices such as OnO controller/Outdoor unit
-COM1 ~ COM5
Ethernet Terminal Connect LAN cable
Cable tie groove Groove for arranging cables
Cable tie groove
SD Card Socket
Serial Terminal
Power Terminal
Reset Button
DI Terminal1
DI Terminal2
DO Terminal3
DO Terminal4
Ethernet Terminal
RS485 Communication Terminal
BACnet Gateway Cable Connection Part
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 7 2013-04-25 오전 10:14:32
E-8
240
255
64.80
(Unit : mm)
Display Board
40-pin Cable
20-pin Cable
Main Board
Sub Board
BACnet Gateway Interior
Main Parts
Viewing the Parts (Continued)
Note If you need external circuit configuration, consult with the manufacturer.
Product Dimensions
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 8 2013-04-25 오전 10:14:33
E-9
System Architecture
Connecting outdoor units and BACnet Gateway
- You can control up to 80 outdoor units and 256 indoor units using BACnet Gateway. *Each communication channel of BACnet Gateway can be connected with 16 outdoor units.
- The more outdoor units are connected, the longer time takes for tracking.
OnOff
controller
Outdoor
Unit
RS 485
BACnet Gateway
Internet
BMS system
BMS Engineering TRANE Engineering
Max 256 Indoor units
(DVM Series)
For the devices which support new communication, set the communication channel mode on '[System setting]-[Tracking]' menu as 'NEW' and for SIM/PIM which conventional communication is applied, set the communication channel mode as 'IM'. You cannot connect indoor & outdoor unit SET which conventional communication is applied to new communication BACnet Gateway.
When setting communication channel mode as 'NEW', the address of virtual centralized control will be assigned.
Channel 0: Virtual OnO controller 11, Channel 1: Virtual OnO controller 12, Channel 2: Virtual OnO controller 13, Channel 4: Virtual OnO controller 14, Channel 5: Virtual OnO controller 15
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 9 2013-04-25 오전 10:14:34
E-10
Compatible Devices
 Products with ‘* ’ are not Samsung products and must be purchased separately.
(Only selected power meters may be used for protocol compatibility issues.)
 Samsung is not responsible for BMS engineering which creates each device and objects.
For further directions regarding on BMS engineering, consult with specialized BMS related vendor.
No Devices Model Note
1
Indoor Unit
Outdoor Unit
DVM S HR/DVM S HP/DVM MINI outdoor unit and indoor units which can be connected to DVM S HR/ DVM S HP/DVM MINI outdoor unit.
-
2
OnOff controller MCM-A202DN
-
3
SIM MIM-B12 Needed for EHP power distribution
4
PIM MIM-B16 Needed for EHP power distribution
5
*
Watt-hour
Meter
RS485 comm. type
Connected with SIM Needed for power distribution ( Please consult Samsung for compatible
power meters)
Pulse type
Connected with PIM Pulse Width: 20~400(ms) Pulse: 1~10000(Wh/Pulse)
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 10 2013-04-25 오전 10:14:34
E-11
Maximum Devices Attachable
Devices Max. Note
Indoor Unit 256 Tracking error occurs if exceeded
OnOff
controller
75
Must not exceed 15 units per each RS485 communication terminal
Outdoor unit 80
Must not exceed 16 units per each RS485 communication terminal
SIM/PIM 8 Communication mode : IM
Watt-hour
Meter
64 Maximum 8 units can be connected to 1 SIM/PIM.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 11 2013-04-25 오전 10:14:34
E-12
Assistant hole
Installation plate
Installing the BACnet Gateway
1
Separate the installation plate on the rear side of BACnet Gateway.
2 Fix the installation plate on the wall using 4 screws.
3
Hang the BACnet Gateway on the groove which is on the top of the installation plate.
4 Fix the installation plate and BACnet Gateway using 2 screws.
Depending on the installation environment, fix BACnet
Gateway using assistant holes. ( Screws for assistant hole are not provided by our
company.)
5
If you install BACnet Gateway inside of the wall or wiring from the rear side is needed, use wiring groove on the bottom of BACnet Gateway.
To prevent breakdown and damage of BACnet Gateway, and for safe usage, it is recommended to install BACnet Gateway on the wall.
wiring groove
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 12 2013-04-25 오전 10:14:34
E-13
Cable tie
LAN cable
Connect communication cable
Adapter
Connecting Outdoor Unit
1
Unfasten the 2 screws on the bottom of the BACnet Gateway front cover. Hold the bottom 2 sides of the BACnet Gateway and push downwards to slide open the cover.
2 Connect the adapter to the power terminal.
Arrange the adapter as the right figure.
3
Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal. Then, connect outdoor unit communication cable(SOL_ COM(R1,R2)) to the terminal block.(R1A, R2B)
4
Connect LAN cable to the Ethernet terminal of BACnet Gateway. Then arrange it using cable tie.
5
Fasten the bottom cover of BACnet Gateway and fix it using 2 screws.
Maximum 80 outdoor units can be connected to one BACnet Gateway.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 13 2013-04-25 오전 10:14:35
E-14
Cable tie
LAN cable
Connect communication cable
Adapter
Connecting SIM/PIM
1
Unfasten the 2 screws on the bottom of the BACnet Gateway front cover. Hold the bottom 2 sides of the BACnet Gateway and push downwards to slide open the cover.
2 Connect the adapter to the power terminal.
Arrange the adapter as the left figure.
3
Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal. Then, connect SIM/PIM communication cable (C1, C2) to the terminal block. (C1A, C2B)
4
Connect LAN cable to the Ethernet terminal of BACnet Gateway. Then arrange it using cable tie.
5
Fasten the bottom cover of BACnet Gateway and fix it using 2 screws.
Maximum 8 SIM/PIM units can be connected to one BACnet Gateway.
Installing the BACnet Gateway (Continued)
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 14 2013-04-25 오전 10:14:36
E-15
Cross cable
BACnet Gateway
S-NET3
LAN cable
BACnet Gateway
S-NET3
HUB
Setting the Computer Environment
1
Device related to network (Purchase separately)
Computer with a LAN Card HUB or network cable(Cross·Direct cable)
2
Computer web browser specification Internet Explorer 7.0 or later version
* You can use Internet Explorer 6.0 but it is not
recommended.
Note
 A cross cable is used when connecting to PC directly.
It is produced as transmission and reception cables are crossed. Cable 1, 2, 3, and 6 are crossed each other.
 Visit internet homepage (http://www.microsoft.
com/silverlight/) to download Silverlight. Or you can download it through the download link which is noticed automatically when you access to BACnet Gateway for the first time.
Connect BACnet Gateway and Computer directly
Connect BACnet Gateway and Computer
Connect BACnet Gateway and Computer using HUB
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 15 2013-04-25 오전 10:14:36
E-16
IP address : 192.168.0.1(~253)
Except 100
Subnet mask : 255.255.255.0
Default gateway : 192.168.0.1
Setting the Computer Environment (Continued)
IP Setting (Recommended)
Computer Settings for BACnet Gateway Connection
All settings of BACnet Gateway will be arranged in web
page which built in BACnet Gateway. You should access to BACnet Gateway IP to use BACnet Gateway web page. Set your computer settings as follows.
BACnet Gateway Factory default setting
BACnet Gateway IP : 192.168.0.100
To access to BACnet Gateway IP, set the network information
of BACnet Gateway connected computer as follows.
1
Select [My network Settings] icon and click [Properties] using right button.
2 Select [Local area connection] icon and click [Properties]
using right button from the network connection folder.
3
[Internet protocol(TCP/IP)] and click [Properties] using right button from the local area connection property window.
4
Enter “192,168,0,1” in IP address field, “255,255,255,0” for subnet mask address, and “192,168,0,1” for default gateway.
5
Click [OK] after setting.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 16 2013-04-25 오전 10:14:36
E-17
Address bar
Setting the BACnet Gateway
BACnet Gateway Connection and Login
1
Click internet explorer icon( ) twice on your computer.
2 When internet explorer window appears, enter IP address
(http://192.168.0.100) on the address bar then press
[ENTER].
3
If it is the first time to access BACnet Gateway, “ Install Microsoft Silverlight” message will appear.
If Microsoft Silverlight have already installed, the screen
will not appear.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 17 2013-04-25 오전 10:14:37
E-18
Setting the BACnet Gateway (Continued)
4 Click [Run] button and continue installation.
After installation, access to BACnet Gateway again.
Silverlight operates normally with Windows XP SP2 or later version. It may not operate normally with previous version of Windows.
4
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 18 2013-04-25 오전 10:14:37
E-19
5
5
Enter ID and password when BACnet Gateway main web page appears, Then click [LOGIN].
If you use accounts with general authorization level to login, you cannot use
the BACnet Gateway settings.
Depending on authorization level set by the administrator, access to some
functions may be restricted.
You can change authorization level settings from System settings 
User authorization management.
To use the BACnet Gateway functions, you must login with the ID that is
included in administration group. Factory default BACnet Gateway ID is ‘admin’ and password is ‘ac0530’.
Note  Only authorized users can access to web page.
 Connection speed may slow down. Fewer than 5 concurrent users are
recommended.
 BACnet Gateway manager should change ID and password for security and
management.
 Logout: If you want to logout, click [LOGOUT] on the top of the menu. BACnet
Gateway will be ended.
If you use accounts with authorization level lower than management group or accounts
with general authorization level, you cannot access BACnet Gateway settings.
If you cannot access BACnet Gateway, consult the manager.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 19 2013-04-25 오전 10:14:37
E-20
Setting the BACnet Gateway (Continued)
6 If you login successfully, 'Control and Monitoring' screen
will appear. Click [System Setting][BACnet configuration] menu to switch to BACnet Gateway.
If you use accounts with authorization level lower
than management group or accounts with general authorization level, BACnet conguration will not be displayed on the menu.
If the BACnet conguration menu does not appear,
consult the manager.