Samsung AS180UE, AS181UE, AS-2408BR, AS18A1UD, AS18A1UE Service Manual

SERVICE
Manual
AS180UE AS181UE AS18A1UD AS18A1UE AS-2408BR
CONTENTSAIR CONDITIONER
2. Product Specifications
3. Operating Instructions and I n s t a l l a t i o n
4. Disassembly and Reassembly
5. Tro u b l e s h o o t i n g
6. Exploded Views and Parts List
7. Block Diagrams
8. PCB Diagrams
9. Wiring Diagrams
10. Schematic Diagrams
ROOM AIR CONDITIONER
© Samsung Electronics Co., Ltd. FEB. 1999.
Printed in Korea. Code No. DB81-10161A(3)
1) Remove power cable from power outlet. Remove power cable from an outlet prior to disassembly for repair. When the power cable is removed wait for at least 1 minute and measure the voltage between the + and - terminal of the large capacity electrolyti capacitor using a tester. Make sure that the voltage is less than DC 10V, then starts repairing.
2) Warning about electrical shock If you cannot avoid checking the circuits with power not disconnected pay special attention not to touch live parts to avoid electric shock.
3) Use proper parts Use genuine parts of a model if parts need to be replaced. (It is recommended that parts are replaced rather than repaired, to avoid electrical contact. Customers should refrain from repairing parts themselves as this can be extremely dangerous.)
4) Use proper tools Use proper tools for repair and be familiarized with handling test equipment. Using worn out tools may result in problems such as intermittent contact, etc.
5) Lead wire or power cable damaged Check if lead wire or power cord is damaged prior to repair, and replace if damaged.
6) Avoid tapping a power cord Tapping a power cable or using an extension cord from a power outlet is dangerous and should be avoided. It may result is malfunctioning or fire.
7) Checking insulation Be sure to check insulation resistance when assembly is completed. (Check insulation resistance between the power cord plug and ground terminal using an ohm meter and check if it is greater than 30M prior to applying the power.)
8) Check grounding Check grounding status and fix it if not sufficient.
9) Check installation condition Check installation condition and fix insufficient conditions. If it is still not satisfactory find another area for installation.
10) Child care It is recommended to have children stay away the units when the repair is being done to avoid accidents.
Samsung Electronics
1-1
1. Precautions
dangerous
No inter connection
Clean the unit and the area arount it. Let the customer know that the unit has been repaired.
Brilliantly
Cleaning
1-2
Samsung Electronics
M E M O
Samsung Electronics
2-1
2. Product Specifications
2-1 AS180UE/AS181UE/AS18A1UE/AS18A1UD/AS-2408BR
M o d e l
I t e m
Ty p e ­C o o l i n g B T U / h D e h u m i d i t y i n g l/ h Low temp. heating B T U / h Air volume C o o l i n g m3/ m i n N o i s e C o o l i n g d B E n e rgy efficiency ratio C o o l i n g B T U / h . W Power V- H z Power Consumption C o o l i n g W Operating Curre n t C o o l i n g A Power factor C o o l i n g % S t a rting curre n t A Power cable L e n g t h m
Number of core wire Fuse capacity A Outer Width x Height m m dimension x Depth i n c h We i g h t k g Coolant pipe L i q u i d OD(mm) x L(m)
C o o l a n t OD(mm) x L(m) Drain hose ID(mm)x L(m) C o m p ressor Ty p e
M o t o r Ty p e
Rated input W Blower Ty p e
M o t o r Ty p e
Rated input W
Heat exchanger Coolant control unit F reezer oil capacity c c Coolant to charg e ( R - 2 2 ) g Cooling test Condition
Maximum operation Condition
A S 1 8 0 U E / A S 1 8 1 U E / A S 1 8 A 1 U E
Indoor unit Outdoor unit
Wa l l - m o u n t i n g
1 7 , 5 0 0 ( * 1 7 , 0 0 0 )
1 . 6
-
1 3 . 8
4 5 5 5
9 . 7 ( * 9 . 4 )
1-220 / 240-50
1 8 0 0
8 . 0
93.8 (at 240V) 4 0
6 . 2
3G x 2.5mm2/ A re a
3 . 1 5 ­1 0 5 0 x 2 9 8 x 1 8 0 7 8 7 x 6 2 0 x 3 2 0 4 1 . 3 4 x 1 1 . 7 3 x 7 . 0 9 3 0 . 9 8 x 2 4 . 4 x 1 2 . 6
1 3 4 6
ø6.35 x 5 ø12.7 x 5
ø17 x 2
- R o t a ry
- -
- 1 8 5 5
C ro s s - f a n P ro p e l l e r
R e s i n S t e e l
3 0 6 0
2Row 12Step 2Row 24Step
C A P I L L A RY TUBE
6 0 0
1 , 5 8 0
P e rf o r­m a n c e
P o w e r E l e c t r i ­c a l C h a r a ­c t e r i s­t i c s
P ro d u c t
INDOOR UNIT : DB 27°C W B 1 9 ° C OUTDOOR UNIT : DB35°C W B 2 4 ° C INDOOR UNIT : DB 32°C W B 2 3 ° C OUTDOOR UNIT : DB 43°C W B 2 6 ° C
INDOOR UNIT : DB 27°C W B 1 9 . 5 ° C OUTDOOR UNIT : DB35°C W B 2 4 ° C INDOOR UNIT : DB 32°C W B 2 2 . 5 ° C OUTDOOR UNIT: DB 43°C W B 2 5 . 5 ° C
AS18A1UD
Indoor unit Outdoor unit
Wa l l - m o u n t i n g
17,000 (5,000W)
1 . 6
-
1 3 . 8
4 5 5 5
9 . 2
1-200 / 220-50
1 8 5 0
9 . 3
90.9 (at 220V) 4 0
6 . 2
3G x 2.5mm2/ A re a
3 . 1 5 ­1 0 5 0 x 2 9 8 x 1 8 0 7 8 7 x 6 2 0 x 3 2 0 4 1 . 3 4 x 1 1 . 7 3 x 7 . 0 9 3 0 . 9 8 x 2 4 . 4 x 1 2 . 6
1 3 4 6
ø6.35 x 5 ø12.7 x 5
ø17 x 2
- R o t a ry
- -
- 1 8 5 5
C ro s s - f a n P ro p e l l e r
R e s i n S t e e l
3 0 6 0
2Row 12Step 2Row 24Step
C A P I L L A RY TUBE
6 0 0
1 , 1 8 0
AS-2408BR
Indoor unit Outdoor unit
Wa l l - m o u n t i n g
2 2 , 0 0 0
2 . 8
-
1 4 . 3
4 6 5 6
1 0 . 5
1 - 2 2 0 - 6 0
2 1 0 0
1 0 . 0 9 5 . 4
5 0 6 . 2
3G, AW G 1 4
3 . 1 5 ­1 0 5 0 x 2 9 8 x 1 8 0 7 8 7 x 6 2 0 x 3 2 0 4 1 . 3 4 x 1 1 . 7 3 x 7 . 0 9 3 0 . 9 8 x 2 4 . 4 x 1 2 . 6
1 3 4 6
ø6.35 x 5 ø15.8 x 5
ø17 x 2
- R o t a ry
- -
- 2 1 5 7
C ro s s - f a n P ro p e l l e r
R e s i n S t e e l
3 0 6 0
2Row 12Step 2Row 24Step
C A P I L L A RY TUBE
6 0 0
1 , 6 5 0
“*” : Tailand Only
2-2
Samsung Electronics
2-2 Dimensions
2-2-1 Indoor Unit
2-2-1 Outdoor Unit
Air in
(Front view)
(Remote control unit)
(Rear view)
(Front view) (Rear view)
Air out
1050
787
582 340
180 63
21
(Installation plate)
250 145
260 200 100
outer edge of indoor unit
unit : mm
Samsung Electronics
3-1
NO
1 2
3
4
5
6
7
8
9
10
11
12
13
NAMED OF KEY
ON/OFF
MODE
TURBO
MILD
Q. TIMER
FAN SPEED
SET
SWING
AUTO
TIME
TIMER/CANCEL
ON
TIMER
OFF
(UP)
TIME
(DOWN)
(UP)
TEMP
(DOWN)
SLEEP
ONE SHOT KEY ONE SHOT KEY
OR
CONTINUOUS KEY
ONE SHOT KEY
ONE SHOT KEY
ONE SHOT KEY
OR
CONTINUOUS KEY
ONE SHOT KEY
OR
CONTINUOUS KEY
ONE SHOT KEY
OR
CONTINUOUS KEY
ONE SHOT KEY
ONE SHOT KEY
ONE SHOT KEY
ONE SHOT KEY
ONE SHOT KEY
OR
CONTINUOUS KEY
ONE SHOT KEY
OR
CONTINUOUS KEY
ONE SHOT KEY
OR
CONTINUOUS KEY
ONE SHOT KEY
FUNCTION OF KEY Use this button to start and stop air conditioner. Each time you press this button,
MODE is changed in the following order.
"AUTO" "COOL" "DRY" "FAN"
Use this button to provide heavy duty cooling for 30 minutes.
Use this button to provide pleasant cooling
for 3 hours.
Set up the reserve or cancel the timer on and timer off quickly.
Each time you press this button, FAN SPEED is changed in the following order. "AUTO" " (L)" " (ME)" " (HI)" NATURAL
Adjusts air flow vertically. Each time you press this button, BLADE-H rotates by 8° (Changable range 50°).
Each time you press this button, BLADE-H rotates within 35° and stop.
Without regard to ON/OFF condition in remote controller, use this button to set current time. Adjust the current time using TIME button. (Data can be transmitted after setting up the time)
Use this button to reserve or cancel the timer on and timer off. Set up the time that operation start. Set up the time that operation stop. If the TIME button is pressed once, the time increase by one
minute during the time set mode, and ten minutes during the timer set mode.
If the TIME button is pressed once, the time decrease by one minute during the time set mode, and ten minutes during the timer set mode.
If the button is pressed once, the setting temperature is increased by 1°C.
If the button is pressed once, the setting temperature is decreased by 1°C.
Use this button for sleep operation. (The SLEEP mode can be selected at COOL mode.
3-1-1 Name & Function of Key in remote controller
3. Operating Instructions and Installation
3-1 Operating Instructions
Operating Instructions and Installation
3-2
Samsung Electronics
1. A U TO MODE: In this mode, operation mode (COOL) is selected automatically by the room temperature of initial operation.
T= -1°, -2°C, 0°C, +1°C, +2°CT is controlled by setting temperature
up/down key of remote contro l l e r
2. C O O L MODE: The unit operates accord i n g to the diff e rence between the setting and room temperature . The setting temperature range is 1 8 ° C t h rough 30°C.
3. D RY MODE: The unit is operated at com­p ressor on state re g a rdless of room temper­a t u re for an initial 30 minutes of dehumidi­fication operation, and the indoor fan motor is automatically operated due to the temper­a t u re diff e rence between the room tempera­t u re and set temperature . The compressor is automatically contro l l e d due to the temperature diff e rence between room temperature and set temperature after operation of 30 minutes. * Set temperature: 18°C~30°C * Protective function: Low temperature release. (Prevention against fre e z e )
4. TURBO MODE: This mode is available only in A U TO, COOL m o d e . When this button is pressed at first, the air conditioner is operated “powerful” state for 30 minutes re g a rdless of the set tempera­t u re, room temperature . When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode.
5 . MILD MODE: This mode is available only
in A U TO, COOL m o d e . When this button is pressed at first, the air conditioner is operated in its current state for 3 hours. The setting temperature is automatically raised by 3°C. When this button is pressed again or when the operating time is 3 hours, mild opera­tion mode is canceled and returned to the p revious mode.
6 . S L E E P MODE: Sleep mode is available only
in COOL m o d e . The operation will stop after 6 hours. * In COOL mode : The setting temperature is automatically raised by 1°C each 1hour When the temperature has been raised by total of 2°C, that temperature is main­t a i n e d .
7. FAN SPEED: Manual (3 step), Auto (4 step), N a t u r a l Fan speed automatically varies depending on both the diff e rence between setting and the room temperature .
8 . C O M P U L S O RY O P E R ATION:
For operating the air conditioner without the remote contro l l e r. The operating is the same function that A U TO MODE in the remote contro l l e r. * Set temperature: 22°C
Operation Type
Cool Operation (Set Temp:24°C + T)
3-1-2 Main controller function.
Operating Instructions and Installation
3-3
Samsung Electronics
9 . SWING: BLADE-H is rotated vertically by
the stepping motor. * Memory louve: When ON/OFF button is p ressed at stop state, the BLADE-H re t u r n s to its original location which is operating state before stop. * Swing auto: The BLADE-H can ro t a t e within about 35° in the original position set by the SWING SET button. * Swing set: Press the SWING SET button, then the blade rotates vertically by 8° The BLADE-H location is dispalyed on REMOTE CONTROL. (total 7 steps)
1 0 . Q.TIMER: Q. timer (quick timer) allows
reservation or cancel the timer on and timer o ff quickly. When Q.timer button is pressed at operat­ing state, LCD displays the polling state s e q u e n t i a l l y. The LCD also displays the time re m a i n i n g .
11 . TIMER: The air conditioner is turned
ON/OFF at a specified time using TIMER O N / O F F.
* Timer LED lights on.
1 2 . SELF TEST
* Interruption of electric power and Power o n . * Abnormal condition of the room sensor. * Indoor unit fan motor lock. * Abnormal condition of the indoor unit's heat exchanger sensor.
1 3 . TIME SHORTENING: If the "Time short"
connector pin is shorted on the main P. C. B, the compressor's three minutes delay func­tion is cancelled, and each operation time is shortened to one fiftieth of its original time.
1 4 . BUZZER SOUND: Whenever the ON/OFF
button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep".
3-4
Samsung Electronics
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable to the customer's needs.
3-2-1(a) Indoor Unit
1 . Make sure that you install the indoor unit in
an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet.
2 . Make sure that you install the indoor unit in
an area allowing good air handling and endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in an area where there is no source of heat or vapor nearby.
4 . Make sure that you install the indoor unit in
an area from which hot or cool air is spre a d evenly in a ro o m .
5 . Make sure that you install the indoor unit in
an area away from TVs, audio units, cord­less phones, fluorescent lighting fixture s and other electrical appliances (at least 1 m e t e r ) .
6 . Make sure that you install the indoor unit in
an area which provides easy pipe connec­tion with the outdoor unit, and easy drainage for condensed water.
7. Make sure that you install the indoor unit in an area which is large enough to accomo­date the measurements shown in figure on the next page.
3-2-1(b) Outdoor Unit
1 . Make sure that you install the outdoor unit
in area not exposed to the rain or direct sun l i g h t .
(Install a separate sunblind if exposed to
d i rect sun light.)
2 . Make sure that you install the outdoor unit
in area allowing good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbours.
(Fix the unit firmly if it is mounted in a
high place.)
3 . Make sure that you install the outdoor unit
in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet.
4 . Make sure that you install the outdoor unit
in area free from animals or plants.
5 . Make sure that you install the outdoor unit
in area not blocking the traff i c .
6. Make sure that you install the outdoor unit in area easy to drain condensed water fro m the indoor unit.
7. Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe (10 meters).
Note
1. Add 10 grams of refrigerant (R-22) for
every 1 meter if the pipe length exceeds the standard pipe length of 5 meters.
2. Maintain a height between the indoor and
outdoor units of less than 3 meters.
8 . Make sure that you install the outdoor unit
in an area which is large enough to accom­modate the measurements
shown in figure on the next page.
3-2-1(c) Remote Control Unit
1 . Make sure that you install the remote con-
t rol unit in an area free from obstacles such as curtains etc, which may block signals f rom the remote control unit.
2. Make sure that you install the remote con­t rol unit in an area not exposed to d i rect sunlight, and where there is no sourc e of heat.
3. Make sure that you install the remote con­t rol unit in an area away from TVs, audio units, cordless phones, fluorescent lighting f i x t u res and other electrical appliances (at least 1 meter).
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
Operating Instructions and
3-5
Samsung Electronics
3-2-2 Installation diagram of indoor unit and outdoor unit
Indoor unit check points
Avoid up slopes
Outdoor unit check points
* Check for gas leak from the flare nut
connections with leak detector.
Right
Rear
Down
250mm
m i n i m u m
350mm or more
Left rear
Left
GAS LEAK TEST Slope of drain hose * Piping may be laid to the rear, left, right or down.
Insulation of pipe connection area
* Perform gas leakage test first, and insulate the pipe
connection area. Use an insulation tube for insulation as shown in figure.
The insulation tube shall be properly finished not to allow any gap.
Vinyl tape (purchase locally)
Insulation tube
Hole dimension of bolts for the outdoor unit
Fix firmly if installed in an area affected by typhoons.
Tighten the flare nut by hand first, and tighten firmly with a spanner
582
ø12
Remote control
Remote control holder
10
4
5 6
C o n n e c t i o n
pipe lengh
5m max
5 ~ 1 0 m
A i r- p u rg e
m e t h o d
Refer to the
detailed
a i r- p u rg e
p ro c e d u re .
C o o l a n t a d j u s t m e n t u n n e c e s s a ry
Add 10g of c o o l a n t <R-22> for e v e ry 1m. (Refer to the detailed c o o l a n t c h a rg e p ro c e d u re . )
Air purg e
m e t h o d
P u rge air using a vacuum pump or an
a d d i t i o n a l c o o l a n t c y l i n d e r.
R e f r i g e r a n t q u a n t i t y
See table r i g h t .
Add 10g of c o o l a n t <R-22> for e v e ry 1m. (Refer to the detailed c o o l a n t c h a rg e p ro c e d u re . )
C l a s s
Coolant adjustment pro c e d u re
Coolant adjustment pro c e d u re
kg .cmAt installation At installation
Outer diameter Fixing torque Final torque
ø6.35mm 160 200 ø12.7mm 500 550 ø15.8mm 700 750
Operating Instructions and Installation
3-6
Samsung Electronics
3-2-2(a) Fixing the Installation Plate
Installation plate
Pipe hole (ø65mm)
260mm
250mm 145mm
Indoor unit
Installation plate
Weight
200mm 100mm
250mm350mm
Pipe hole
(ø65mm)
Determine the pipe hole position for installation and drill the pipe hole (65mm inner diameter) so that it slants slightly downward.
1. Install the installation plate horizontally on structural members (studs, etc.) in the wall.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the left figure.
3. When the anchor bolts are already driven in the wall, also utilize the anchor bolts holes to secure the installation plate. (If an anchor bolt is too long, adjust the projecting length to 20mm or less.)
1. As the left Fig. Fix the wood pillar at the wood frame and install installation plate with screw tap.
2. Fix the wood pillar with enough strength to bear the weight of the indoor unit.
CUTTING A HOLE
MOUNTING THE INSTALLATION PLATE
When the refrigerant piping are hooked up from the rear.
When the installation plate is directly mounted on the wall.
Wood pillarScrew wood
Mounting at the window frame.
Operating Instructions and Installation
3-7
Samsung Electronics
3-2-2(c) Piping and drain hose installation
1 . Fix the drain hose right the refrigerant piping.
2. Be careful not to form a slack of the drain hose.
3. Do not allow the piping to jut out from the back of the indoor unit.
4. Insulate both of the refrigerant pipings so that dewing and troubles may not happen.
5. Be careful in bending the pipes. The bending radius must be 100mm or larg e r.
A.Right-hand connection with piping C.Under-side connection with pipingB.Left-hand connection with piping
1. Cut out the knock-out piece from the
rightside of the rear body with a knife, etc. Smooth the cut edges.
2. Cut out the Holder-pipe slit part.
3. Support the above section to be bent with your hand and bend the pipes there.
1. Cut out the knock-out piece from the leftside of the rear body with a knife,
etc. Smooth the cut edges.
1. Cut out the knock-out piece from the underside of the rear body with a knife, etc. Smooth the cut edges.
2. Cut out the Holder-pipe on its slit part.
Set the drain hose in the inner part of the indoor unit and the assembly cable in lower part of it. Wind tape round them.
Piping
Assembly cable
Drain hose
Tape
Piping
B
C
A
Assembly cable
Installation plate
Drain hose
3-2-2(b) Wiring connection(Indoor unit)
1. Open the Grille and remove the screw securing the cover.
2. AS-18**: Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals 1~3. *Each wire is labelled with the corresponding terminal number. AS-24**: Firmly connet the cable connector with connector.(6pin, 4-cable)
3. Assembly every parts by contrary order to disassembly.
Screw
Indoor unit
Conneitor
AS-18**
AS-24**
Outdoor unit
Operating Instructions and Installation
3-8
Samsung Electronics
AUXILIARY POWER S/W WIRING CONNECTION
A u x i l i a ry power S/W should be installed near indoor unit so that each access is p o s s i b l e . Main/Outdoor unit power cords are connected to upper/lower terminal of a u x i l i a ry power S/W.
Indoor unit connector wire should be connected to both indoor unit connector ( t e rminal board) and outdoor unit term i n a l b o a rd as shown in the figure below.
distributind board
Auxiliary
power S/W
EARTH WIRE
EARTH WIRE
EARTH WIRE
AS-18**
AS-24**
(POWER CABLE)
(ASSEMBLY CABLE)
EARTH WIRE
<Indoor unit> <Outdoor unit>
(POWER CABLE)
(ASSEMBLY CABLE)
<Indoor unit>
<Outdoor unit>
3-2-2(e) Wiring connection(outdoor unit)
3-2-2(d) Indoor unit installation
1. Pass the pipes t h rough the hole in the wall and hook the indoor unit to the i n s t a l l a t i o n plate at the upper and lower hooks.
2. Move the indoor unit to the right and left to make sure that the unit is s e c u rely hooked on to the installation p l a t e .
DRAINAGE
1. Run the drain hose sloped downward .
2. Do not install the drain hose as illustrated below.
Do not form a rise
Do not put the drain hose end into water
Do not wave the hose
Keep a distance
at least 5cm
or more
Do not put the drain hose end in the ditch
Ditch
3. Put water in the drain pan and make sure that the water is drained outdoor.
4. When connecting the extension drain hose, insulate the inside part of the extension drain hose with shield.
Hook here
Operating Instructions and Installation
3-9
Samsung Electronics
No. JOB EXPLANATION PRECAUTIONS
1 Determine the • Suitable location • Avoid sandy or gravelly soil as its grounding
grounding position. a) Place that is always dank. resistance is high.
b) Hard soil rather than loose sandy soil. • The grounding wire for the telephone line cannot
be used for the grounding of the air conditioner.
• Unsuitable location • When the grounding electrode is to be installed a) Where there are underground structures or under a place with heavy traffic, its wire must be
facilites such as gas pipes, water pipes, connected firmly with the utmost care. telephone lines, underground cables, etc.
b) A place 2m or less from the lightning arrester
grounding electrode and its cable.
2 Drive the grounding a) Dig a hole to the size illustrated,
electrode into position. and drive in the grounding electrode.
b) Cover the top of the grounding
electrode with excavated soil.
3 Put the grounding a) If the grounding wire is too short, connect an • The grounding wire should be a green
wire in order. extention lead to it. Solder the joint and insulated wire of ø1.6mm or 2mm2or larger.
wrap it with tape. • The soldered joint should not be buried
b) Fasten the grounding wire with staples. underground.
4 Check the a) After grounding work, measure the grounding
workmanship, resistance with a grounding resistance tester. and provide
corrective b) If the resistance is above a specified level, measures if drive the grounding electrode in deeper necessary. or increase the number of grounding
electrodes.
5 Connect the Secure the grounding wire to the
grounding grounding terminal of the air conditioner wire to the air conditioner.
3-2-2(f) Grounding
(The Parts for this work are optional.)
• A g rounding terminal can be found on the outdoor unit as illustrated.
1. When an existing grounding terminal is avilable. ( G rounding wire of ø1.6mm or larger<solid w i re > o r
2 m m2or larger <standard wire > )
2. Use of a grounding electro d e .
• Specifications of grounding electro d e .
Terminal used exclusively for grounding.
Steel coreCarbon plastic
PVC-Insulated(2mm2x3.5m), green Terminal, M4
Grounding resistance ; Less than 100 ohms (existing grounding electrode)
Operating Instructions and Installation
3-10
Samsung Electronics
• Flare modification procedure
3-2-2(g) Flare modification
• Tools used
Tightening
knob
Cutting wheel
Clamp handle
Bar
Cone
Roller
Yoke
1) Cut the pipe using a pipe cutter.
3) Insert a flare nut into the pipe and modifty flare.
• Unproper flaring
2) Remove burrs at the tip of the pipe cut. Caution : Burrs not removed may result
in leakage of gas.
Outer diameter A(mm)
ø6.35mm 1.3 ø12.7mm 2.0 ø15.8mm 2.2
Oblique Raughness Burr
Point down
D
A
Inclined Surface
damaged
Cracked Uneven
thickness
Pipe
Reamer
Operating Instructions and Installation
3-11
Samsung Electronics
3-2-2(h) Air-Purge Procedure
1. Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
3 Open the valve of the low pressure side of manifold gauge
counter-clockwise.
6. Mount the valve stem nuts to the 2-way and 3-way valve.
And mount the service port cap to 3-way valve.
4. Purge the air from the system using vacuum pump for about 10 minutes.
- Close the valve of the low pressure side of manifold gauge
clockwise.
- Remove the hose of the low pressure side of manifold
gauge.
7. Check for gas leakage.
- At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap.
5. Set valve cork of both liquid side and gas side of packed valve to the open position.
2 Connect the charging hose of low pressure side of manifold
gauge to the packed valve having a service port (3/8” or 1/2” Packed valve) as shown at the figure.
Outdoor unit
Indoor unit
Gas pipe side
Liquid pipe side
Vacuum Pump
B
(liquid)
Valve stem
Stem cap
A
(gas)