Samsung AC024JXADCH, AC030JXADCH, AC042JXADCH, AC048JXADCH, AC030JXSCCH Installation Manual

...
AC024JXADCH AC030JXADCH AC036JXADCH AC042JXADCH AC048JXADCH AC030JXSCCH AC036JXSCCH AC054KXADCH
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
2
Contents
PREPARATION
Safety precautions ....................................................................................................... 3
Preparation for outdoor unit installation ................................................................................. 5
Deciding on where to install the outdoor unit ............................................................................ 7
Outdoor unit installation ................................................................................................ 13
INSTALLATION
Connecting the cable ................................................................................................... 15
Connecting the refrigerant pipe ......................................................................................... 23
Adding refrigerant (R-410A) ............................................................................................. 24
Connecting to the system and removing air in the circuit ................................................................ 25
Connecting the drain hose to the outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Cutting/Flaring the pipes ............................................................................................... 28
Performing leak tests ................................................................................................... 29
Refrigerant pipe work ................................................................................................... 29
Using stop valve ........................................................................................................ 30
Interface module Installation (Optional) ................................................................................. 31
Pump down Procedure ................................................................................................. 32
Checking correct grounding ............................................................................................ 33
Testing operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Installing the wind bae ............................................................................................... 37
Troubleshooting ........................................................................................................ 38
OTHERS
IMPORTANT – This product has been designed and manufactured to meet ENERGY STAR criteria for energy eciency when matched with appropriate coil components.
However, proper refrigerant charge and proper air ow are critical to achieve rated capacity and eciency. Installation of this product should follow the manufacturer’s refrigerant charging and air ow instructions. Failure to conrm proper charge and airow may reduce energy eciency and shorten equipment life.
3
ENGLISH
Safety precautions
WARNING
State of California Proposition 65 Warning (US only) This product contains chemicals known to the State of California to cause cancer and birth defects or
other reproductive harm.
Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.
WARNING
• Always disconnect the air conditioner from the power supply before servicing it or accessing its internal components.
• Verify that installation and testing operations are performed by qualied personnel.
• Verify that the air conditioner is not installed in an easily accessible area.
General information
f Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order
to be able to use it as reference after installation.
f For maximum safety, installers should always carefully read the following warnings.f Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air
conditioner is sold or transferred.
f This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types
of units with dierent control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for damages arising from the use of non compliant units.
f The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper
connection of electric and requirements set forth in the “Operating limits” table, included in the manual, shall immediately invalidate the warranty.
f The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable
to be installed in areas used for laundry.
f Do not use the units if damaged. If problems occur, switch the unit o and disconnect it from the power supply.f In order to prevent electric shocks, res or injuries, always stop the unit, disable the protection switch and contact
SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
f Always remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These operations
should be performed by qualied personnel only.
f The unit contains moving parts, which should always be kept out of the reach of children.f Do not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations may
cause electric shocks or res.
f Do not disassemble and alter the heater at your own discretion. * (Applicable model : AC030JXSCCH, AC036JXSCCH)f Do not place containers with liquids or other objects on the unit.f All the materials used for the manufacture and packaging of the air conditioner are recyclable.f The packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with
current laws.
f The air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air
conditioner must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly and safely.
f This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
4
Installing the unit
f IMPORTANT: When installing the unit, always remember to connect rst the refrigerant tubes, then the electrical lines.
Always disassemble the electric lines before the refrigerant tubes.
f Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears
damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the material from the retailer.)
f After completing the installation, always carry out a functional test and provide the instructions on how to operate the air
conditioner to the user.
f Do not use the air conditioner in environments with hazardous substances or close to equipment that release free ames
to avoid the occurrence of res, explosions or injuries.
f Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from
both sides and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible and easy to disassemble without endangering people and objects.
f For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair
the units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaolding or any other elevation system will NOT be considered part of the warranty and will be charged to the end customer.
f If you operate the cooling operation of air conditioner in the condition where ambient temperature is lower than 23 °F
DB(Dry bulb), a wind bae should be installed to protect the compressor of the outdoor unit.
Power supply line, fuse or circuit breaker
f Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in
compliance with current local safety standards.
f Always verify that a suitable grounding connection is available.f Verify that the voltage and frequency of the power supply comply with the specications and that the installed power is
sucient to ensure the operation of any other domestic appliance connected to the same electric lines.
f Always verify that the cut-o and protection switches are suitably dimensioned.f Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the
wiring diagram included in the manual.
f Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric
specications and with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable to the installation of air conditioners.
f Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage
category.
f Be sure not to perform power cable modication, extension wiring, and multiple wire connection.
- It may cause electric shock or re due to poor connection, poor insulation, or current limit override.
- When extension wiring is required due to power line damage, refer to “How to connect your extended power cables” in the installation manual.
Safety precautions
5
ENGLISH
Preparation for outdoor unit installation
The air conditioner uses R-410A refrigerant.
Outdoor unit dimension
A Type AC024JXADCH / AC030JXADCH
(Unit : inch)
24.4
37.0
13.038.3
39.3
26.6
20.8
21.1
14.2
15.1
B Type
AC036JXADCH / AC042JXADCH / AC048JXADCH
24.4
37.0
13.046.7
47.6
34.8
22.0
22.3
14.2
15.1
C Type
AC030JXSCCH / AC036JXSCCH / AC054KXADCH
37.0
54.9
55.9
43.1
22.0
22.3
24.4
13.0
14.2
15.1
6
Preparation for outdoor unit installation
Moving the Outdoor Unit by Wire Rope
Fasten the outdoor unit by two wire ropes (26.3 ft or longer) as shown in the gure. To prevent from damage or scratches, insert a piece of cloth between the outdoor unit and rope, then move the unit.
The appearance of the unit may be dierent from the picture depending
on the model.
Plate protection cloth
Wire rope
When moving an outdoor unit by hand
f Moving the outdoor unit by lifting up and carrying due to the short travel distance.
- Two people should carry the outdoor unit.
- Be careful not to damage the heat exchanger of the rear side of the outdoor unit during transportation.
- Be careful not to get hurt by the sharp surface of the heat exchanger.
7
ENGLISH
Deciding on where to install the outdoor unit
Outdoor Unit
f The outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run into the cooling
circuit and seriously damage the unit.
f Choose a location that is dry and sunny, but not exposed to direct sunlight or strong winds.f Do not block any passageways or thoroughfares.f Choose a location where the noise of the air conditioner when running and the discharged air do not disturb any neighbours.f Choose a position that enables the pipes and cables to be easily connected to the indoor unit.f Install the outdoor unit on a at, stable surface that can support its weight and does not generate any unnecessary noise
and vibration.
f Position the outdoor unit so that the air ow is directed towards the open area. f Maintain sucient clearance around the outdoor unit, especially from a radio, computer, stereo system, etc.
Fuse
Outdoor Unit
Stereo
5 ft or more
Indoor Unit
Control
Air Guide Duct (This product is not
provided by Samsung)
3.3 ft or more
3.3 ft or more
5 ft or more
5 ft or more
5 ft or more
Fuse
8 inch
12 inch
f If the outdoor unit is installed at a height, ensure that its base is rmly xed in position. f When you install the outdoor unit at wayside, you should install it above 6.6 ft height or make sure that the heat from the
outdoor unit shouldn't be in direct contact with passersby.
• You have just purchased a system air conditioner and it has been installed by your installation specialist.
• This device must be installed according to the national electrical rules.
CAUTION
8
Deciding on where to install the outdoor unit
f When installing the outdoor unit near seashore, make sure it is not directly exposed to sea breeze. If you can not nd a
adequate place without direct see breeze, protection wall should be constructed.
- Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can damage the outdoor unit.
Outdoor unit
Outdoor unit
Sea breeze Sea breeze
Sea
Sea
- If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to block the sea breeze.
Protection wall should be constructed with a solid material such as concrete to block the sea breeze and the height and the width of the wall should be 1.5 times larger than the size of the outdoor unit. Also, secure over 27.6 inch between the protection wall and the outdoor unit for exhausted air to ventilate.
Protection wall
Outdoor unit
Sea breeze
Sea
- Install the outdoor unit in a place where water can drain smoothly.
• If you cannot nd a place satisfying above conditions, please contact manufacturer. Make sure to clean the sea water and the dust on the outdoor unit heat exchanger and spread corrosion inhibitor on heat exchanger. (At least one time per one year.)
• In areas with heavy snow fall, piled snow could block the air intake. To avoid this incident, install a frame that is higher than estimated snow fall. In addition, install a snow-proof hood to avoid snow from piling on the outdoor unit.
CAUTION
Frame
Ground
Estimated
snow fall
Snow-proof hood
9
ENGLISH
Space Requirements for Outdoor Unit
When installing 1 outdoor unit
(Unit : inch)
11.81 or more
59.06 or more
❋ When the air outlet is opposite the wall ❋ When the air outlet is towards the wall
11.81 or more
5.91 or more
23.62 or more
59.06 or more
78.74 or more
❋ When 3 sides of the outdoor unit are blocked by a wall ❋ The upper part of the outdoor unit and the air outlet is
towards the wall
19.69 or more
11.81 or more
11.81 or more59.06 or more
The upper part of the outdoor unit and the air outlet is
opposite the wall
When front and rear side of the outdoor unit is towards
the wall
10
Deciding on where to install the outdoor unit
When installing 1 outdoor unit (with wind bae)
f Wind bae is not supplied with the product.
(Unit : inch)
11.81 or more
59.06 or more
❋ When the air outlet is opposite the wall ❋ When the air outlet is towards the wall
11.81 or more
5.91 or more
23.62 or more
59.06 or more
78.74 or more
❋ When 3 sides of the outdoor unit are blocked by a wall ❋ The upper part of the outdoor unit and the air outlet is
towards the wall
19.69 or more
11.81 or more
11.81 or more59.06 or more
The upper part of the outdoor unit and the air outlet is
opposite the wall
When front and rear side of the outdoor unit is towards
the wall
11
ENGLISH
When installing more than 1 outdoor unit
(Unit : inch)
59.06 or more
When the air outlet is towards the wall
11.81 or
more
11.81 or more 23.62 or more 23.62 or more 23.62 or more
When 3 sides of the outdoor unit are blocked by a wall
11.81 or
more
59.06 or more
23.62 or more
23.62 or more
When front and rear side of the outdoor unit is towards a wall
59.06 or more 23.62 or more 118.11 or more 7.87 or more118.11 or more
When 3 sides of the outdoor unit are blocked by a wall
• The units must be installed according to the distances specied above in order to permit accessibility from each side to guarantee correct operation and for future maintenance or repair. The unit’s parts must be safely accessible and completely removable.
CAUTION
When installing more than 1 outdoor unit (with wind bae)
f Wind bae is not supplied with the product.
(Unit : inch)
59.06 or more
When the air outlet is towards a wall
12
Deciding on where to install the outdoor unit
11.81 or more
11.81 or more 23.62 or more 23.62 or more 23.62 or more
When 3 sides of the outdoor unit are blocked by a wall
11.81 or
more
59.06 or more
23.62 or more
23.62 or more
When front and rear side of the outdoor unit is towards a wall
59.06 or more 23.62 or more 118.11 or more 7.87 or more118.11 or more
When 3 sides of the outdoor unit are blocked by a wall
• Should adopt bar type louver. Don’t use a type of rain resistance louver.
[Bar type louver]
[Rain resistance louver]
• Louver specications.
- Angle criteria : less than 20˚
- Opening ratio criteria : greater than 80%
WARNING